Minera MP Oil immersed medium power transformer
StandardThese transformers comply with standards: IEC standards; French standards NFC 52 100 (1990);Schneider Electric guarantees that its transformers are assembled using new PCB-free components.
DescriptionThis range consists of transformers complyingwiththefollowingspecification: Three-phase transformers, 50 or 60 Hz, for indoor
oroutdooruse(installationtobespecified); Maximum ambient temperature: 40C (others
ambient temperatures 45C, 50C, 55C, etc. upon request); Mineral oil immersed (other dielectric upon re-
quest); Breathing type with conservator ; Cover bolted on tank or welded bell type as per
specification; ONAN, ONAF, ODAF or ODWF cooling type; Standard anti-corrosion surface treatment and
coating (others possibilities upon request); Final colour RAL 7033.
Standard fittingEach transformer includes: 1 off-circuit tappings switch with padlocking located
on the cover ; this switch operates on the highest rated voltage to bring the transformer to the supply voltage-actual value (generally 5%, 3 or 5 positions);
Porcelain bushings on primary and secondary sides;
2 earthing terminals; 1 conservator with level indicator tube; 1 silicagel airdryer; 1 Buchholz relay with 2 contacts
(alarm and tripping); 1 thermostat with two contact
(alarm and tripping);
1 dial type thermometer (without contact); 4directionalflatrollers; Lifting and/or untanking lugs; 1 rating plate; 1fillingplug; 1 draining device and treatment valve with sampler.
OptionsThefollowingfittingsmaybeprovidedasanoption: 1 on-load tap changer in the main tank (generally
12% - 19 positions maximum) with: -1motordriveunitfittedontank; - 1 tap changer compartment in the conservator with a level indicator; - 1 protective relay and eventually, on request: - 1 parallel operation device; - 1 voltage regulator with voltage drop equalizer; - 1 remote indicator of tap changer position.
Magnetic level indicator (with or without contact, please specify);
HVfixedplug-inconnectorsHN52S61: - 250, 400, 630 or 1250 A - 24 kV; - 400, 630 or 1250 A - 36 kV.
HV mobile plug-in connectors HN 52 S 61, straight or elbow (the cable characteristics should be speci-fied);
Condenser bushings; Increased creepage distance bushings; 1 bonnet on HV bushings:
- in the air for connection by dry cables or busducts (except rated insulation level 72.5 kV) ; - oil immersed, hermetically sealed for cable con-nection; - SF6 immersed, hermetically sealed for connec-tion by busbars on oil/SF6 bushings;
Winding temperature indicator by thermal image ; Current transformer: bushing type around termi-
nals - standard type for earth fault current detector; 1 overpressure valve (with or without contact,
please specify); 1 automatic oil retaining valve (between conserva-
tor and tank); Atmoseal oil protection system; 1 treatment valve at the upper part of the tank ; 1 insulation valve for radiators; 4 jacking lugs with hauling eyes.
Minera MPFrom 5 to 60 MVA, for 7.2 to 123 kV systems
PM
1023
10
Oil Distribution Transformers
The above options concern usual cases and are not restrictive. For other information,please consult us.
Electrical characteristics
Oil Distribution Transformers
Dimensions and weights
NRJED311273EN 11-2011
Asstandards,specificationsanddesignschangefromtime totime,pleaseaskforconfirmationoftheinformationgiven in this publication.
Design: Schneider Electric Industries SASPhotos: Schneider Electric Industries SAS
35, rue Joseph Monier CS 30323 F - 92506 Rueil Malmaison Cedex (France) Tl. : +33 (0)1 41 29 70 00RCS Nanterre 954 503 439 Capital social 896 313 776 www.schneider-electric.com
Schneider Electric Industries SAS
S
chne
ider
Ele
ctric
. All
right
s re
serv
ed.
Minera MP
ONAN Type Cooling
Typical dimensions and weights are indicated in the table below for mineral oil immersed transformers, completely set up* with a standard type cooling. They corre-spond to transformers intented for systems of 7.2 to 72.5 kV having electrical character-istics as indicated in the previous table. For other voltages, other characteristics or when the transformers are immersed in another dielectric,dimensions and weights would be different, please, consult us.
Power (MVA) 5 10 20 25 5 10 20 25 30
Insulation level - Primary- Secondary
24-36 kV7.2- 12 - 17.5 - 24
72.5 kV7.2 - 17.5
No-load losses (w)Load losses (w)
643
1071
17120
21140
743
1171
18120
22140
25160
Impedance voltage (%) 8 9 10 11 8 9 10 11 11
with off-voltage tappings switch with on-load tap changer
Rated power (MVA)
Dimensions (mm) Total weight Kg
Dimensions (mm) Total weight KgA B C E A B C E
Rated insulation level 24 kV
5102031 to 60
2700375043004000
2100245039003900
2500350036003800
1000150015001500
8500170002650035000
3400380046004100
2200250039003900
2550350036003800
1000150015001500
10000190002700037000
Rated insulation level 36 kV
5102031 to 60
3300390044004200
2400330039504300
2950360037004000
1000150015001500
11000180002700036000
3600390047004800
2400340040004300
3000360037004000
1000150015001500
13000200002900038000
Rated insulation level 72.5 kV
5102031 to 60
4100390045004400
2600340040004600
3300350040004300
1000150015001500
17000180002700041000
-400050005000
-390041004600
-360040004300
-150015001500
-220003200043000
The above options concern usual cases and are not restrictive. For other information,please consult us.
ODAF Type Cooling
C
E B
A
Transformers 5 MVA, with off-voltage tappings switch.
E
A
C
B
Transformers 5 MVA with on-load tap changer, or 10 to 25 MVA with off-voltage tappings switch or with on-load tap changer.
C
BA
Transformers 20 to 25 MVA, with off-voltage switch or on-load tap changer.
With off-voltage tappings switch With on-load tap changer
Rated power (MVA)
Dimensions (mm) Total weight Kg
Dimensions (mm) Total weight KgA B C A B C
Rated insulation level 72.5 kV
2025
35004000
27003000
40004300
2100025000
45004700
30003000
40004300
2300028000
Rated insulation level >72.5 kV