Upload
others
View
3
Download
0
Embed Size (px)
Citation preview
tsdos.org
Market Variability Trends Among Copper Grounding Products
Lora AboulmounaJeff Jordan, PE
Copperweld
tsdos.org
Is there variability in the copper market?
If so, what does that mean for performanceversus the expected standard?
tsdos.org
What is the Problem?• CDEGS published a paper by Jeffrey Jordan, PE
SHORT CIRCUIT (ISC) PERFORMANCE CONSIDERATIONS FOR CCS
• Copperweld 19 No 9 (4/0 copper equivalent)
tsdos.org
Assessment Overview• 5 Manufacturers:
CME, Nehring, Southwire, Republic, Cerro and Encore
• 42 total Samples:4/0, 2/0, #4, #6 wire
• Standards Referenced:IEEE Standard 80 (substation grounding and short-circuit rating) ASTM B-3 (Soft or Annealed Copper Wire)ASTM B-8 (Concentric-Lay Stranded Copper)ASTM B-787 (19 Wire Combination Unilay-Stranded)
tsdos.org
Testing & Measurement Overview
1. Sample – cut at approximately 2 ft lengths 2. Wire diameter – measured by a laser micrometer 3. Resistance – measured using a resistance bridge 4. Break load – measured by taking the sum of the
individual strands
tsdos.org
Standard IEEE 80 simplified formula:
𝐴𝐴𝑘𝑘𝑘𝑘𝑘𝑘𝑘𝑘𝑘𝑘 = 𝐼𝐼 ∗ 𝑘𝑘𝑓𝑓 ∗ 𝑡𝑡𝑘𝑘
Application: 4/0 Substation Grounding
tsdos.org
Standard ASTM B-787:12.1 The cross-sectional area of the completed conductor shall be not less than 98 % of the area indicated in Column 1 of Table 1.
Standard ASTM B-8-11:11.1 The area of cross section of the completed conductor shall be not less than 98 % of the area indicated in Column 1 of Table 1.
tsdos.org
Standard IEEE 80 simplified formula:
𝐴𝐴𝑘𝑘𝑘𝑘𝑘𝑘𝑘𝑘𝑘𝑘 = 𝐼𝐼 ∗ 𝑘𝑘𝑓𝑓 ∗ 𝑡𝑡𝑘𝑘
Application: 2/0 Substation Grounding
tsdos.org
Standard ASTM B-787:12.1 The cross-sectional area of the completed conductor shall be not less than 98 % of the area indicated in Column 1 of Table 1.
Standard ASTM B-8-11:11.1 The area of cross section of the completed conductor shall be not less than 98 % of the area indicated in Column 1 of Table 1.
tsdos.org
Preliminary Findings• 40% of the samples tested out of spec
2 wire samples met the upper limitthe remaining 50% met the lower limit of ASTM
• None met the ultimate short circuit rating in IEEE standard 80 table 6
4/0 had 3-8% variability range2/0 had 4-8% variability range
tsdos.org
Standard IEEE 80 :
𝐴𝐴𝑘𝑘𝑘𝑘𝑘𝑘𝑘𝑘𝑘𝑘 = 𝐼𝐼 ∗ 𝑘𝑘𝑓𝑓 ∗ 𝑡𝑡𝑘𝑘
Application: #4 Pole Grounding
tsdos.org
Standard ASTM B-8:11.1 … not less than 98 % of the area indicated in Column 1 of Table 1.
Standard ASTM B-3:5.3 …. And for diameters of 0.100 in (.254 mm) and over the wire shall not vary from the specified diameter by more than +/- 1%, expressed to the nearest 0.0001 in (or 0.001 mm).
tsdos.org
Standard IEEE 80 :
𝐴𝐴𝑘𝑘𝑘𝑘𝑘𝑘𝑘𝑘𝑘𝑘 = 𝐼𝐼 ∗ 𝑘𝑘𝑓𝑓 ∗ 𝑡𝑡𝑘𝑘
Application: #6 Pole Grounding
tsdos.org
Standard ASTM B-8:11.1 … not less than 98 % of the area indicated in Column 1 of Table 1.
Standard ASTM B-3:5.3 …. And for diameters of 0.100 in (.254 mm) and over the wire shall not vary from the specified diameter by more than +/- 1%, expressed to the nearest 0.0001 in (or 0.001 mm).
tsdos.org
Preliminary Findings• 10% of the samples tested out of spec
– 70% met or exceeded the upper limit
• None met the ultimate short circuit rating in IEEE Standard 80 Table 6
#4 had 3-9% variability range#6 had 10-13% variability range
tsdos.org
Normal Distribution Model
tsdos.org
4/0 Distribution Model
Copper Sampling
ASTMIEEE Table 6
tsdos.org
Data
0
0.1
0.2
0.3
0.4
0 2 4 6 8 10
4/0
0
0.2
0.4
0.6
0.8
1
0 2 4 6 8
2/0
0
0.5
1
1.5
2
2.5
0 5 10 15
#4
01234567
0 5 10 15
#6
tsdos.org
Key Take-Aways• Variability in the market exists
Variability of up to 13% from IEEE short circuit standardApproximately 25% of samples did not meet ASTM
• Further studies necessary Larger sample sizeExperimental replicates
tsdos.org
Questions?• Contact Info:
– Lora [email protected](P): 615-377-4172(M): 615-270-5990
– Jeff Jordan [email protected]
Market Variability Trends Among Copper Grounding ProductsSlide Number 2What is the Problem?Assessment Overview�Testing & Measurement Overview�Application: 4/0 Substation GroundingSlide Number 7Application: 2/0 Substation GroundingSlide Number 9Preliminary FindingsSlide Number 11Slide Number 12Slide Number 13Slide Number 14Preliminary FindingsNormal Distribution Model 4/0 Distribution Model DataKey Take-AwaysQuestions?