10
WWW.JEVEN.COM UV-Turbo hoods Product description, Product code 2 Parts 3 Functioning principle 4 Dimensions 5 Exhaust air, pressure loss and sound data 7 Supply air, pressure loss and sound data 8 Distribution of supply air, lights 9 Positioning Electrical and automation planning 10 We want to help you in design of ventilation by offering Jeven designer service to your disposal. Design Service helps in design and makes unique proposal solution with Jeven products. Contact us: [email protected] 010 231 2030

JSI JLI UV Turbo eng - Jeven · Sound power level Lw in each octave band is computed by ... Spigot size ø Exhaust flow Pressure loss ... JSI_JLI_UV_Turbo_eng.cdr

  • Upload
    hatuyen

  • View
    213

  • Download
    0

Embed Size (px)

Citation preview

WWW.JEVEN.COM

U V - T u r b o h o o d s

Product description, Product code 2

Parts 3

Functioning principle 4

Dimensions 5

Exhaust air, pressure loss and sound data 7

Supply air, pressure loss and sound data 8 Distribution of supply air, lights 9

Positioning Electrical and automation planning 10

We want to help you in design of ventilationby offering Jeven designer service to yourdisposal.Design Service helps in design and makesunique proposal solution with Jevenproducts.

Contact us: [email protected] 010 231 2030

WWW.JEVEN.COMAll rights reserved

PAGE 2 JEVEN Kitchen ventilation

PRODUCT DESCRIPTION

UV-Turbo canopies are equipped with TurboSwing filter unit including ozone-free UV-light.

UV-Turbo hood has been designed especially for the kitchens with heat recovery or changing air flow.

UV-TurboSwing filtering solution was developed for high efficient grease separation and odour removal in professional kitchens. Thanks to excellent filtration efficiency ducts stay clean and filtration efficiency remains high even at low airflows.

UV-Turbo hoods

UV-Turbo hood is equipped with lights IP 54 and TurboSwing filtering unit and ozone-free UV-light.

LIGHTS AND FILTERS

PRODUCT CODE

JSI - R - UV - Turbo - 3000 x 1500 x 540 - 4 x 250 - 3 x315 + 480 l/s - 550 l/s - CB - UV-SC - FP

JSI = Supply air hood JLI = Exhaust air hood

MaterialR = Stainless steelS = Glass

FilterLenghtWidthHeight

Number and size of the supply air connectionsNumber and size of the exhaust air connectionsSupply air flow, l/sExhaust air flow, l/s

ACCESSORIESCB= Covering boardUV-SC= UV-SwingControl FP = Ansul fire extinguishing system

PAGE 3

WWW.JEVEN.COM All rights reserved

JEVEN Kitchen ventilation

UV-Turbo hoods

7

10

8

9

6

1

324

1

3

2

5

6

4

5

2

6

PARTS JSI-R-UV-TURBO

1. Outer casing, stainless steel or laminated glass 2. Light fixture with cable 3. UV-TurboSwing filter unit

4. Exhaust air connection and damper plate 5. Ceiling console

6. Hanging bracket

MATERIAL

1. Outer casing, stainless steel or laminated glass 2. Direction air unit with measurement tap for the supply air 3. UV-TurboSwing filter unit

4. Personal supply air nozzle

5. Supply air connection and damper unit

6. Exhaust air connection and damper plate

7. Light fixture with cable

8. Supply air unit

9. Ceiling console

10. Hanging bracket

PARTS JLI-R-UV-TURBO

The canopy’s base material is stainless steel,AISI 304. The side panels can be made of stainless steel or laminated glass.

PAGE 4 JEVEN Kitchen ventilation

WWW.JEVEN.COMAll rights reserved

1

26

1

4

5

2

3

1

2

4

3FUNCTIONING PRINCIPLE JLI-R-UV-TURBO

UV-Turbo hoodsFUNCTIONING PRINCIPLE JSI-R-UV-TURBO

1. Dirty air rises due to temperature differences against the

ceiling of the hood.

2. Dirty air is exhausted immediately through the TurboSwing units.

3. Since TurboSwing’s air intake is placed close to the ceiling, the

warmest dirty air is always exhausted through it.

Ventilation efficiency is of the highest rate because of the correct

position of TurboSwing with respect to the kitchen equipment.

4. The purified air flows in the catalyst-coated chamber where UV-

light transforms remaining grease to carbon dioxide and water.

Clean air is exhausted into the ducts.

PAGE 5

WWW.JEVEN.COM All rights reserved

JEVEN Kitchen ventilation

UV-Turbo hoods

DIMENSIONS JSI-R-UV-TURBO

Wall hood

Island type hood

500

120

190

width

F

he

igh

t

75

M

AA

2x36W 2x36W

wid

th

A

K

length

C

B

øD

53W+24WM

UV-Turbo

315

53W+24WM

UV-Turbo

315

Module 2Module 1

A-A

A-A

wid

th

K

length

2x58W2x58W

2x58W 2x58W

E

G

A

315

53W+24WM

UV-Turbo

315

53W+24WM

UV-Turbo

315

53W+24WM

UV-Turbo

315

53W+24WM

UV-Turbo

315

53W+24WM

UV-Turbo

315

53W+24WM

UV-Turbo

315

53W+24WM

UV-Turbo

315

53W+24WM

UV-Turbo

Module 2Module 1

AA

width

M

Fh

eig

ht

75500500120

190

C F øD G E min K min M540 200 500 160 100 400 340 65330 500 290 200 125 550 350 110540 500 500 250 150 550 350 110

Size and place of supply air Height

A and B measurement must be >300mm.

UV-Turbo hoods are designed based on your drawings.The length and width can be freely selected.

Island type hood

Wall hood

UV-Turbo hoods

UV-Turbo hoods are designed based on your drawings.

The length and width can be freely selected.

DIMENSIONS JLI-R-UV-TURBO

Module 2Module 1

AA

2x36W2x36W

wid

th

(module)

length

A

B

50

0

315

53W+24W

M

UV-Turbo

315

53W+24W

M

UV-Turbo

widthh

eig

ht

75

500

190

120

500

A-A

Module 2Module 1

2x36W2x36W

2x36W2x36W

wid

th

(module)

length

A

B

315

53W+24W

M

UV-Turbo

315

53W+24W

M

UV-Turbo

315

53W+24W

M

UV-Turbo

315

53W+24W

M

UV-Turbo

315

53W+24W

M

UV-Turbo

315

53W+24W

M

UV-Turbo

315

53W+24W

M

UV-Turbo

315

53W+24W

M

UV-Turbo

BB

B - B

width

he

igh

t

75190

120

500

500

PAGE 6 JEVEN Kitchen ventilation

WWW.JEVEN.COMAll rights reserved

Factor, Kok

Hz 125 250 500 1000 2000 4000

Kok 7 -1 -5 -5 -7 -6

tol. ±3 ±3 ±2 ±2 ±3 ±4

Sound power level Lw in each octave band is computed by adding the corresponding factor, Kok to the sound power level LpA. Lw= LpA+Kok.

PRESSURE LOSS AND SOUND DATA

100

120

80

6070

40

50

30

Adjustment plate ½ closed

Pre

ssu

re

P

s(P

a)

dB(A) =40

dB(A) =38

80

6070

40

50

l/s

3m /h

dB(A) =44

dB(A) =40

dB(A) =35

open

80 100 160 240 320 400 120 200

300 500 700 1000 1400

TurboSwing 1100 rpm

100

120

80

6070

40

50

30

Adjustment plate ½ closed

Pre

ssu

re

P

s(P

a)

50

l/s

dB(A) =38

dB(A) =34

dB(A) =30

3m /h

open

80 100 160 240 320 400 120 200

300 500 700 1000 1400

TurboSwing 750 rpm

EXHAUST AIR

20

40

60

80

100

1 2 3 4 5 6 7 8 9 10 11

Particle size, micrometer (µm)

TurboSwing separation rate 90-95%

UV-light’s effect to separation rate, (ozone free UV-light)

Combined separation rate 95-99%, Kitchen equipment and manufacturing process affect separation rate

Combined filtiration efficiency of TurboSwing and UV-light

Spigot size ø Exhaust flow Pressure loss3

mm l/s m /h Pa

315 100-200 360 - 720 20 - 60

Recommended exhaust flow / spigot

UV-Turbo hoods

WWW.JEVEN.COM All rights reserved

PAGE 7JEVEN Kitchen ventilation

SUPPLY AIR

Hood height Supply air unit width

mm 200 mm 500 mm

330 - 50-90 l/s

540 40-70 l/s 100-150 l/s

Spigot ø200 mm. Unit width 500 mm. Hood height 330 mm.

Ps

(Pa

)

l/s

605040

302520

16

121087

14

25 30 40 50 60 80 100 120 160

100 200 300 500

0,5 0,8 1,4L0,2 (m)

dB(A) =45

dB(A) =40

dB(A) =35

Damper half closed

dB(A) =30

open

Ps

(Pa

)

l/s

605040

302520

16

121087

14

25 30 40 50 60 80 100 120 160

100 200 300 500

0,5 0,8 1,4L0,2 (m)

dB(A) =45

dB(A) =40

dB(A) =35

dB(A) =30

Damper half closed open

Hz 125 250 500 1000 2000 4000 Kok -2 7 4 -5 -19 -26 tol. ±6 ±4 ±2 ±2 ±3 ±5

Spigot ø160 mm. Unit width 200 mm. Hood height 540 mm.

Ps

(Pa

)

l/s3m /h

605040

302520

16

121087

14

30 40 50 60 80 100 120 160 200

100 200 300 500 700

0,5 0,8 1,4L0,2 (m)

dB(A) =40

dB(A) =35

dB(A) =30

Damper half closed open

dB(A) =45

Spigot ø250 mm. Unit width 500 mm. Hood height 540 mm.

Hz 125 250 500 1000 2000 4000 Kok -2 1 2 1 -7 -16 tol. ±3 ±3 ±2 ±2 ±3 ±4

Hz 125 250 500 1000 2000 4000 Kok 6 8 4 -5 -10 -18 tol. ±3 ±3 ±2 ±2 ±3 ±4

Spigot ø200

Spigot ø160

Spigot ø250

UV-Turbo hoods

PAGE 8 JEVEN Kitchen ventilation

WWW.JEVEN.COMAll rights reserved

The canopies are supplied from the factory with suitable air flow rates for a pressure level of 25-35 Pa.

PRESSURE LOSS, SOUND DATA & THROW LENGTH / SUPPLY AIR UNIT

LIGHTS

DISTRIBUTION OF SUPPLY AIR

1 Unidirectional thrown pattern

2 Displacement thrown pattern

3 Bidirectional throw pattern

Supply air unit, Damper open

HzSound attenuation, dB

Hood height Spigot 125 250 500 1000 2000 4000

330 mm ø 200 17 10 10 11 18 24

540 mmø 160 24 8 5 12 17 24

ø 250 16 9 7 11 16 23

1 2 3

UV-Turbo hoods

Jeven supply air columns deliver a controlled and flexible distribution of the supply air. It is possible to wash the supply air columns in a dishwasher and the inside of the supply air chambers is easy to clean. These columns allow individual adjustment of air patterns and airflows, which means better indoor climate for the kitchen staff.

1 Light fixture as standard, IP 54-67

T8:B=111mm,(1x18W, 1x36W, 1x58W)B=168mm, (2x18W, 2x36W, 2x58W)

Colour temperature 840(Cool White)

2 About 2m cable, type EKK 3x1,5

By default, every hood module comes with a light fixture.The light fixture has a cable which should be connectedto a junction box with a cable lock.The junction box is not included.

12

B60

50

WWW.JEVEN.COM All rights reserved

PAGE 9JEVEN Kitchen ventilation

UV-Turbo hoodsPOSITIONING

The size of the canopy is determined by the size of the kitchen equipment. The overhang depends on the type of equipment and the distance between the hood and the equipment.For this type of equipment, the overhang should be at least 300 mm. With ovens the overhang should be min. 400 mm.The typical distance between the hood side and the floor is 2100-2200 mm.If the equipment has any doors that open upwards, make sure there is enough distance to the canopy.

21

00

-22

00 X >0.2 X >400

ELECTRICAL AND AUTOMATION DESIGN GUIDELINES

HPAC designer defines to the plans the types and locations of the products to be wired.

Electrical designer defines to the plans the location of the safety switch, switchgear and wiring from the panelboard or kitchen switch to the safety switch.

Automation designer defines to the plans the running time of the UV-TurboSwing and it shall match to the running time of kitchen.

Safety switch is compulsory and it should be situated close to the hood and on the visible place in the kitchen.

The safety switch, appliance sockets and the cables marked with the broken line are not included in the Jeven delivery.

230VAC230VAC230VAC2m

230VAC

Connection boxUV-Turbo

Connection boxUV-Turbo 2m

Safety switch

Appliancesockets forpossible branches

TurboSwing motor

LNPe

UV-TurboInternal interface

UV-unit

Wiring diagram

PAGE 10 JEVEN Kitchen ventilation

WWW.JEVEN.COMAll rights reserved