1

Click here to load reader

HMIWeb Client Browser Station Intranet and Internet Access ... · Intranet and Internet Access Connectivity options allow access from anywhere in the world via HMIWeb Client and Browser

Embed Size (px)

Citation preview

Page 1: HMIWeb Client Browser Station Intranet and Internet Access ... · Intranet and Internet Access Connectivity options allow access from anywhere in the world via HMIWeb Client and Browser

HVAC Controls Security and Access Control Fire and Life Safety Systems

CCTV & Digital Video Asset Tracking Energy Applications

Ente

rprise

Buildings Integrator

Netw

orking functions easily integrate with existing systems and devices.

Distributed System Architecture (DSA)Provides centralized monitoring for geographically distributed systems, and scalability for large enterprise systems.

PRODUCT FEATURES:• Integrate multiple servers each performing a different application: HVAC, Security, Life Safety, Industrial Control• DSA for points and DSA for cardholders allows Operator Client Stations consistent access to both local and remote points and cardholder data• Extends the capacity of a single server solution to support additional points, channels, and controllers• Utilizes Windows 2000 Server

APPLICATIONS:• The HVAC system and security system operate independently, and share data to optimize occupancy scheduling, lighting, and energy management

strategies based on information from both systems• Cardholder data may be managed from a single client on a single server in a “Traveling Card” concept allowing cardholders to move between sites

EBI DSA Server EBI DSA Server

Intranet and Internet AccessConnectivity options allow access from anywhere in the world via HMIWeb Client and Browser Stations, or web page access via Web Toolkit and Web Point Control optional interfaces.

PRODUCT FEATURES:• HMIWeb browser station utilizing Microsoft Internet Explorer (IE) provides full client access with

operator permissions and area segregation enforced• EBI systems with TCP/IP network access and the network server option may also utilize Web Toolkit

pages with Active X controls for analog and status point monitoring and control• Web Point Control utilizes Java Applets to allow status point control and allow users to define sched-

ules up to one week in advance

APPLICATIONS:• Users away from the office may access their EBI system using VPN, or through a thin client access

over the internet to check system status, issue commands, respond to alarms, or request reports

HMIWeb Client Browser Station

Internet Explorer Web Toolkit

EBI Web Point Control

Modbus

Open System Integration – EBI supports multiple industry standard communication protocols to allow enterprise-wide monitoring and control from a single client workstation.

PRODUCT FEATURES:• Client and server support for BACnet, LonWorks, OPC, Modbus, and Advanced DDE• BACnet and OPC discovery mechanisms to simplify engineering and configuration

APPLICATIONS:• Monitoring and control of third-party HVAC central plant and unitary equipment, industrial controls, and other systems utilizing Open System Communication Protocols• Monitoring third-party Life Safety systems • Integrated system sequences of operation• History collection, trending, and global scheduling of third-party open systems

BACnet, ASHRAE STD, SSPC 135-2001 • Client/Server Interface, Cimetrics BACstac • BACnet Ethernet & IP Support• RPM, WRP, COV, BBMD support

(See EBI PICs for more information)LonWorks® Network• ANSI/EIA Std. 709.1• LonWorks Network Services (LNS)• Connectivity via: PCLTA, i.LON® 600/1000• EXCEL 5000 Open LON and Excel CARE

(see 63-9026 for more information)

Advanced Dynamic Data Exchange (AdvDDE) and DDE• Point monitoring and control

Modbus: Gould, Modbus Plus, Universal Modbus• Gould Modbus to Modicon 584 and 984 PLCs• RS232 serial interface and Modbus TCP support

OLE for Process Control (OPC)• Read/write of analog and status points• Item names up to 64 characters EBI HMIWeb Client Stations

• Static and rotary station licensing• HMIWeb client and IE browser support• 40 simultaneous clients supported

– Operator area segregation and permissions enforced• Multi-Monitor support on single client license• Operator definable alarm and event summaries• Windows 2000 or Windows XP

Wide Area Network/Internet (WAN)

Local Area Network (LAN)

Redundant LAN (optional)

Network Router/Firewall-14507744 Series74-3487 Specification Data• Ethernet and T1 interfaces• AES network encryption capable

Redundant Router(Optional)

Enterprise Systems IntegrationShare information with personnel, office and financial system databases.

PRODUCT FEATURES:• PeopleSoft and SAP Integration to EBI Cardholder Management System (CMS) database for database synchronization periodically or on demand• Generic Cardholder Object Model (CHOM) database integration interface option• Open Database Connectivity (ODBC) support allows read-only access to EBI point, history, and event data for third-party system analysis and reporting

APPLICATIONS:• Changes made to personnel information in the HR database are automatically sent to the EBI CMS to update area and equipment access information• Events in the EBI CMS sends information to the HR system for time and attendance or after-hours billing reporting for energy and services

Global HRMS & PeopleTools support Interface to SAP R/3 Human Resources Module ODBC

Redundant Ethernet Network (optional)

Primary Ethernet Network

W7054A UL Listed EBI ServerSpecification Data 74-3201• Single or dual Intel Xeon processors at up to 3.2 Ghz clock speed• 12 GB SDRAM (max)• 584GB Internal HD storage (max)• 10/100/1000 Gigabit on-board Ethernet• Embedded SCSI and RAID controllers• CD/CDR/DVD and tape backup options

EBI Server and Redundancy Option• Microsoft Windows 2000, SQL (or MSDE) platform• Remote access server (RAS) supported (see EBI Compatibility Matrix for more information)Server PC Specifications (Standard Performance):• Dell, Pentium 4, 1.7 GHz, 1 GB RAM, 40 GB HD min.• Terminal services support for remote access via PDA or other handheld device• Alarm pager capability for off-site notification including e-mail and SNMP support• Diagnostics tools with remote access capabilities• Quality assurance: ISO 9001, SEI Level 3

Go to: www.honeywell.com/ebi for additional information regarding our powerful software applications.

PRODUCT FEATURES:• The complete solution for the safety and comfort of your people and the effective operation of your buildings• Provides an “enterprise view” that goes beyond traditional building automation, fire, and security systems• Fully UL listed to provide authorized operators with 2-way command/control of any subsystem from any listed station• Allows full interaction between applications to minimize risk to personnel and assets, maximize personnel productivity, and optimize system and equipment efficiency• Operator segregation allowing access only to data and information appropriate for the specific user• Fully scalable from a single application and controller, to enterprise integration with multiple applications and servers distributed across the Ethernet LAN and WAN• Migration platform for a wide range of Honeywell legacy products including Excel Building Supervisor (XBS), Excel Building Supervisor Integrated (XBSi), DeltaNet

Excel Plus, MicroCel, MacroCel, Excel Classic, FS90/FS90 Plus, Delta 1000 and Delta 2000

APPLICATIONS:• Enterprise-wide, Integrated sequences of operation allow events in one subsystem to automatically and directly trigger events in another system. Example:

– Tenant activates Fire Alarm pull station– EBI initiates digital video recording and captures the pre-recorded video leading up to the event– Doors are unlocked allowing safe egress while presenting live video to maintain facility security– HVAC initiates proper fan pressurization control for smoke control system operation– Instruction pages and system information is presented to the various operators to manage risk and follow proper emergency procedures

• Emergency and routine situations handled with maximum efficiency by bringing the right information together at the correct decision point

Honeywell Enterprise Buildings Integrator™ An integrated facility management solution.

Honeyewll EBI is approved for use in the following categories:• UL 864 – UOJZ Proprietary Protective Signaling System

– UOXX Control Unit Accessories– UUKL Smoke Control Systems– UDTZ Signal System Units

• UL 916 – PAZX Energy Management Equipment• UL 1610 – AMCX Central Station Receiving Unit• UL 294 – ALVY Access Control System Units• UL 1076 – APOU Proprietary Alarm Receiving Units• UL 2017 – QVAX Process Management Equipment• UL 60951 – NWGQ Information Technology Equipment

• Applicable for use in UL2050, DoD, DCID, and SCIF high-security applications• Approved by ULC for similar applications in Canada• Approved by the California State Fire Marshal, NYC/MEA, and additional international agencies• See individual product specification data sheets for specific approvals

NetworkFirewall

Corporate Intranet, VPN, or WAN

NetworkFirewall

NetworkFirewall

Excel 50 Controller74-3029 Specification DataI/O Point Capacity

Analog Inputs: 8 ............................. 0 to 10 Vdc........................................................ 0 to 20 mA........................................................ (w 499 Ω resistor)........................................................ NTC 20k ohmAnalog Outputs: 4 ........................... 0 to 10 VdcDigital Inputs: 4 .............................. 3 of 4 fast totalizerDigital Outputs: 6............................ Triac 800 mA

(all 6 Triacs max 2.4A)

Same Power of the Excel 500• Similar operator interface• Same software• Same bus configuration• Fully programmable using Excel CARE

Model Type• Excel 50 UPC – without operator interface; Excel 50 UMMIPC-with

operator interface

I/O Point Capacity• 22 physical points• Up to 256 pseudo points• 46 network variables supported on the LonWorks® Network

Application module: ........................ Flash–EPROMEngineering tool:............................. Excel CARE

Constant Volume AHU Controller W775074-2956 Specification Data• Proven PID space temperature control algorithm• Integral or packaged economizer control• Separate intelligent recovery rates for heating and cooling• Demand limit control temperature setpoint in energy saving direction• LonMark profile 8030

W7750A Constant Volume AHU ControllerInputs• 1 T7770 wall module• 1 resistive input• 2 dry contact digital inputs• 1 bypass button inputOutputs• 6 relay outputs• 1 LED output

W7750B/C Constant Volume AHU ControllerInputs• 1 T7770 wall module• 4 resistive inputs• 2 voltage inputs• 4 dry contact digital inputs• 1 bypass button inputOutputs• 8 triac outputs (W7750B)• 1 LED output• 5 triac and 3 analog outputs (W7750C)

VAV Box Controller W775174-2942 Specification Data74-2953 Specification Data• Pressure-independent or pressure-dependent VAV box control• Single-duct/dual-duct VAV box control solutions• Reheat and peripheral radiation control (selectable "first on" sequencing)• Series/parallel fan• Supply/return air tracking• LonMark functional profile 8010

W7751HInputs• 1T7770 wall module• 1 resistive input• 1 voltage input• 1 bypass button inputOutputs• 4 triac outputs• 1 LED output• Integrated actuator

W7751B, D, F• 1 Expanded input/output capacity actuator not includedInputs• 1 T7770 wall module• 2 resistive inputs• 1 voltage input• 3 dry contact inputs• 1 bypass button inputOutputs• 8 triac outputs• 1 LED output

Unit Ventilator Controller W7753A74-2962 Specification Data• Space or return air temperature control• ASHRAE cycles 1, 2, 3• 8 output for HVAC control• PWM or floating damper control• LonMark functional profile 8080

W7753AInputs• 1 T7770 wall module• 2 resistive inputs• 2 voltage/current inputs• 4 dry contact digital inputs• 1 bypass button inputOutputs• 8 triac outputs• 1 LED output

Fan Coil Unit Controller W775274-2959 Specification Data• 2 pipe, 4 pipe fan coil unit control• Up to 3 speed fan control• With or without electrical reheat• Space freeze protection• LonMark functional profile 8020

W7752Inputs• 1 T7770 wall module• 1 dry contact digital input• 1 bypass button inputOutputs• 3 relay outputs• 1 LED output• 1 electric heat relay (F type only)

Remote Input/Output Device W7761A74-2698 Specification Data• Generic I/O for lighting, exhaust fans, pumps, and more LonMark stan-

dard objects for sensors and actuators

W7761AInputs• 4 resistive inputs• 2 voltage inputs• 4 dry contact digital inputsOutputs• 8 triac outputs

Communicating Thermostat T7300F/Q7300H63-1281 Specification Data• One thermostat model for either heat pump or conventional RTU • Up to three stages of heat and cool• Works with T7047 Remote Temperature Sensor • Proportional plus integral control eliminates temperature fluctuations • 7 day programming - 2 occupied / 2 unoccupied periods per day • Discharge air sensing capability with C7046C Sensor• Conforms to LonMark thermostat functional profile

Hydronic Controller W7762B/7763C74-2934 Specification Data• Radiators, induction units and fan coil units with manual fan switching • High efficiency, low cost heat/cool valve application solution • Model with integrated or remote module for wall or unit mounted• LonMark functional profile 8020

W7762/3Inputs• 1 space temperature sensor (either built in or via T7770 wall module)• 1 dry contact digital inputOutputs• 1 relay output• 4 triac outputs

i.LON® 600 Router• Provides network connectivity between Ethernet

LAN and LONTalk (FTT-10A) bus

NOTE: For UUKL applications, use the i.LON® 1000

If C-Bus:

Building network adapter (BNA) Q7055A74-3445 Specification Data• TCP/IP capable, offers a wide range of

network connectivity options and online system diagnostic support

If LON:See i.LON® 600

Excel 500 Controller74-2036 Specification DataI/O Point ModulesAnalog InputXF521A Insert Card

Module Type: .................................. Analog inputNo. of Inputs:.................................. 8Type of Inputs: ................................ 0 to 10 volts........................................................ 0 to 20 mA or 4 to 20 mA........................................................ NTC

XF526 Insert CardModule Type: .................................. Analog inputNo. of Inputs:.................................. 8Type of Inputs: ................................ 0 to 10 volts........................................................ 0 to 20 mA or 4 to 20 mA........................................................ NTC........................................................ PT100, 1000, 3000, Balco

Analog OutputXF522 Insert Card

Module Type: .................................. Analog outputNo. of Outputs: ............................... 8Type of Outputs: ............................. 0 to 10 volts +/- mA eachManual OverrideSwitches: ........................................ 5No. of LEDs:.................................... 8

XF527 Insert CardModule Type: .................................. Analog outputNo. of Outputs: ............................... 8Type of Outputs .............................. 0 to 10 volts +/- mA eachManual OverrideSwitches: ........................................ 0No. of LEDs:.................................... 8

Digital InputXF523 Insert Card

Module Type: .................................. Digital inputNo. of Inputs:.................................. 12No. of LEDs:.................................... 12Inputs 1 and 2: ............................... Digital input or fast totalizerInputs 3-12: .................................... Digital input or slow totalizer

Digital OutputXF524 Insert Card

Module Type: .................................. Digital outputNo. of Outputs: ............................... 6Type of Outputs: ............................. 5 change over contacts........................................................ 1normally open contactManual OverrideSwitches: ........................................ 5No. of LEDs:.................................... 6

XF529 Insert CardModule Type: .................................. Digital outputNo. of Outputs: ............................... 6Type of Outputs: ............................. 5 change over contacts........................................................ 1 normally open contactManual OverrideSwitches: ........................................ 0No. of LEDs:.................................... 6

Three Position OutputXF525 Insert Card

Module Type: .................................. Three position outputNo. of Outputs: ............................... 3Type of Outputs: ............................. Floating controlManual OverrideSwitches: ........................................ 3No. of LEDs:.................................... 3 pairs of 2

Power ModuleXF502 Power Module

Module Type: .................................. Power supplyInput: .............................................. 24Vac + 10%/-15%Output:............................................ Class 2, 24VacSwitches: ........................................ 1No. of LEDs:.................................... 3

Smart Excel 500 Controller74-3666 Specification Data

Distributed Input/Output Modules 74-2145 Specification Data Analog Input XFL521B Module

Distributed Module Type: ................ Analog inputNo. of Inputs: ................................. 8Type of Inputs................................. 0 to 10 volts........................................................ 0 to 20 mA or 4 to 20 mA........................................................ 20k NTC........................................................ PT1000Accessories:.................................... 3 4 5

Analog OutputXFL522B Module

Distributed Module Type: ................ Analog outputNo. of Outputs: ............................... 8Type of Outputs: ............................. 0 to 10 voltsNo. of LEDs:.................................... 8Accessories:.................................... 1 3 4 5

Digital InputXFL523B Module

Distributed Module Type: ................ Digital inputNo. of Inputs:.................................. 12No. of LEDs:.................................... 12Accessories:.................................... 3 4 5

Digital OutputXFL524B Module

Distributed Module Type: ................ Digital outputNo. of Outputs: ............................... 6No. of LEDs:.................................... 6Type of Outputs: ............................. 6 Isolated changeover contactsAccessories:.................................... 2 3 4 6

Distributed Input/Output Accessories1 XFR522

Module Type: .................................. Manual override for XFL522Manual OverrideSwitches: ........................................ 8

2 XFR524 Module Type: .................................. Manual override for XFL524Manual OverrideSwitches: ........................................ 6

3 XSL511 Module Type: .................................. Connector module for XFL521,

XFL522, XFL523, XFL5244 XSL512

Module Type: .................................. Manual disconnect module between terminals and I/O modules

5 XSL513 Module Type: .................................. Terminal block for XFL521/522/523

6 XSL513 Module Type: .................................. Terminal block for XFL524

Smart I/O Module74-3671 Specification DataXFC3A06001

Terminals: ....................................... Fixed permanentDigital Inputs: ................................. 4Digital Outputs: ............................... 4Analog Inputs:................................. 4 (20K NTC)Analog Outputs: .............................. 2 (VDC)

XFC3D06001Terminals: ....................................... RemovableManual Override:............................. 6No. of LEDs:.................................... 10Digital Inputs: ................................. 4Digital Outputs: ............................... 4Analog Inputs:................................. 4 (20K NTC)Analog Outputs: .............................. 2 (VDC)

C-Bu

s or

LON

LON

LON

PRODUCT FEATURES• A family of distributed control products that are open and easy to use, the EXCEL

5000 OPEN System is a proven performer that defines versatility• Every control device in the EXCEL 5000 OPEN System family uses LonWorks®-

based open communications protocol – the worldwide standard in building control – so you can expect smooth, efficient interoperability between devices

• Third-party LonMark device support allows additional devices from multiple manu-facturers to be added to the existing LON bus

• Stand-alone operation at the field control bus level for maximum performance and reliability

• Free topology transceiver technology simplifies wiring, uses standard network tools• True Integration with fire, security, and digital video systems creates application

opportunities never before available

EXCEL 5000® OPEN™ System Architecture: Designed for unmatched DDC control versatility and true open system flexibility.

Network Device Server – 14006700 Series74-3487 Specification Data• Ethernet to RS232 or RS485 Converter, DB25 connecting via DB25 serial• 128 – 256 bit AES NIST certified encryption

NexSentry Star II Controller (board only)P/N 92410250030 Base 2-door ControllerP/N 92410000300 Star Controller Modular EnclosureP/N 92410450020 4-door Chipset P/N 92410850020 8-door ChipsetP/N 92411650030 16-door Chipset• Base two-door system can be field upgraded to a 16-door unit• On-board integrated 16 inputs and 4 outputs• Can monitor 255 inputs and control 96 outputs• Modular upgrade options for easy customization and expansion• Switch selectable baud rate and address for ease of installation• Elevator control up to 96 floors• 100,000 cardholder capacity• S-NET dual twisted-pair wire installation for readers and inputs• 2 on-board Wiegand ports expandable to 16• Ethernet, RS-232, RS-485, and dial-up host communications• Built-in automatic battery charging system

OmniProx™ OP1092995100063-B Specification DataP/N OP10HON• Lowest profile HID compatible card reader• Typical read range: 2 - 3"• Wiegand output • Genuine HID™ compatible

OmniSmart OS1092995100082-A Specification DataP/N OS10HON• Contactless smart card reader

OmniProx™ OP3092995100063-B Specification DataP/N OP30HON• Mullion size• Typical read range: 4"• Wiegand output • Genuine HID™ compatible

OmniSmart OS3092995100082-A Specification DataP/N OS30HON• Contactless smart card reader

OmniProx™ OP4092995100063-B Specification DataP/N OP40HON• Mounts on single-gang electrical box• Typical read range: 4"• Wiegand output • Genuine HID™ compatible

OmniSmart OS409299510082-A Specification DataP/N OS40HON• Contactless smart card reader

OmniProx™ OP4592995100063-B Specification DataP/N OP45HON• Switch-plate size; mounts on a UK size electrical box• Typical read range: 3 – 4.5"• Wiegand output • Genuine HID™ compatible

OmniProx™ OP9092995100063-B Specification DataP/N OP90-FWS• Switch-plate size; mounts on a US size electrical box• Vandal-resistant cast zinc-alloy design• Typical read range: 2"• Wiegand output • Genuine HID™ compatible

OmniProx™ OP95P/N OP95-FWS• Switch-plate size; mounts on a US size electrical box• Vandal-resistant cast zinc-alloy design with piezo keypad• Typical read range: 2"• Wiegand output • Genuine HID™ compatible

SNET

RS-4

85 Wie

gand

TCP/IP Network AdapterP/N 92410000020• Controller mounted Ethernet LAN module• 128 – 256 bit AES-certified encryption

SNET

RS-4

85

Lon

HandKey IIP/N HK-2• Hand geometry reader• Up to 32512 users with

memory upgrade• Direct enrollment integra-

tion to EBI• Outdoor version available

Mifare BioAccess™ Finger Print Reader92995100070-B Specification DataP/N 92030600200• High accuracy• Highly secure• Compatible with Magstripe and Wiegand 26-56 bit systems

DR420192995100012-D Specification DataP/N 92042011000• Low profile DigiReader

(HID compatible)• SNET and Wiegand connections

DR420592995100043 Specification DataP/N 92042050100• DigiReader with tamper

DR420892995100012-D Specification DataP/N 92042081000• HID compatible• SNET and Wiegand connections

DR4205K92995100012-D Specification DataP/N 92042050000• DigiReader with integrated keypad

– 24 V

DR4205K92995100012-D Specification DataP/N 92042052100• DigiReader with integrated keypad,

12 V with tamper

DR420392995100012-D Specification DataP/N 92042030000• Mullion-mount DigiReader

DR422092995100012-D Specification DataP/N 92042200000• Long-range proximity reader

WIRO 4/8/4 (board only)92995100050-D Specification Data92995100049-D Specification DataP/N 92410034840• Additional 8 inputs / 4 outputs and

4 Wiegand ports

WIRO 4/8/4 Modular Double Board EnclosureP/N 92410000400

MIRO 16/8 Board in Modular EnclosureP/N 92410020200• Additional 16 inputs / 8 outputs and 2 SNET ports

MIRO 32/0 Board in Modular EnclosureP/N 92410021200• Additional 32 inputs and 2 SNET ports

MIRO 2/24 Board in Modular EnclosureP/N 92410023200• Additional 2 inputs / 24 outputs and 2 SNET ports

*Tema Server – Proximity TerminalP/N TS_TA32, TS_TA33• CPU68EN302 bi-processor including a 68000 (32 bit archi-

tecture) and onboard Ethernet controller• Bi-directional reader with manual swiping for proximity cards • Multi-language management of the user interface• Up to 15.500 cardholder capacity with full time and

Attendance functionality• Up to 65.000 transactions stored on a removable cartridge

with Flash EPROM• Lead battery backup, with full functionality for 4 hours in

case of network failure• Tamper protection of the unit to prevent opening

*Tema Server – Magnetic TerminalP/N TS_TA31• CPU68EN302 bi-processor including a 68000 (32 bit archi-

tecture) and onboard Ethernet controller• Bi-directional reader with manual swiping for magnetic

stripe cards • Multi-language management of the user interface• Up to 15.500 cardholder capacity with full time and

attendance functionality • Up to 65.000 transactions stored on a removable cartridge

with Flash EPROM • Lead battery backup, with full functionality for 4 hours in

case of network failure• Tamper protection of the unit to prevent opening

*Tema Key – Proximity & HID ReaderP/N TK_C02, TK_C03 HID Compatible• NEURON CHIP™ 3150 (Echelon) 32 KByte EPROM

to download application firmware• LonWorks™(Echelon) connection to the TS_AC01

unit with a transfer rate of 78 kbps • Alphanumeric graphic liquid crystal display (LCD),

back-lit, with two lines of 16 characters• Reader for proximity cards, HID with TK_C03, (stan-

dard ISO/ABA 125Khz, up to 5cm reading distance)• Numeric-function keyboard with 16 keys• 1 double-colored LED signal: green LED for the cor-

rect reading and red/yellow for invalid • Variable tones for valid/invalid transactions• Management of two dry contact digital inputs to

control the door status• Management of two relay outputs (1A@30V) to

command door unlock and signal external outputs• Tamper protection of the unit to prevent opening

*Tema Key – Magnetic ReaderP/N TK_C01• NEURON CHIP™ 3150 (Echelon) 32 KByte EPROM

to download application firmware• LonWorks™(Echelon) connection to the TS_AC01

unit with a transfer rate of 78 kbps • Alphanumeric graphic liquid crystal display (LCD),

back-lit, with two lines of 16 characters • Bi-directional reader with manual swiping for mag-

netic cards (track 2, ISO/ABA 7811 standard).• Numeric-function Keyboard with 16 keys• 1 double-colored LED signal: green LED for the cor-

rect reading and red/yellow for invalid • Variable Tones for valid/invalid transactions• Management of two dry contact digital inputs to

control the door status• Management of two relay outputs (1A@30V) to

command door unlock and signal external outputs• Tamper protection of the unit to prevent opening

*Tema Key – Digital I/O ModuleP/N TK_C21• NEURON CHIP™ 3120 (Echelon)• 4 balanced inputs with a range between 0 and 12 V• 4 open collector outputs with a range between 0 and

12 V up to 100mA• LonWorks™ (Echelon) connection with a transfer

rate of 78 kbps • Tamper protection of the unit to prevent opening

*Tema Server – Control UnitP/N TS_AC01• CPU68EN302 bi-processor including a 68000 (32

bit architecture) and onboard Ethernet controller• Dialer support with LAN or as a backup to LAN• Industry standard LON architecture• Fault tolerant controllers and power supplies• Management of up to 8 doors with TemaKeys on

both directions• Management of up to 64 I/O• 1 MB FLASH EPROM to download application

firmware via FTP• Up to 60.000 cardholder capacity• Up to 40.000 transactions buffer• Peer-to-peer communication for fast front-end

independent decision making• Onboard clock/calendar chip with automatic man-

agement of DST• Onboard battery backup, with full functionality for

4 hours• Full Time and Attendance functionality

*Tema Key – Dual Wiegand InterfaceP/N TK_S014• NEURON CHIP™ 3120 (Echelon)• LonWorks™ (Echelon) connection with a transfer

rate of 78 kbps • 2 balanced inputs with a range between 0 and 12 V• 2 powered open collectors output, holding current

1.2A, peak max 5A inductive load • Tamper protection of the unit to prevent opening

*Tema Power – Power Supply UnitP/N TP_U01 (0.8A), TP_U03 (4.5A)• LonWorks™ (Echelon) connection to the

TemaServer control units, with a communication speed of 78 kbps

• Protection from power overloads• LED signal: green LED for “correct functioning,”

flashing red for “errors in the communication signal,” red for “device out of order” and yellow for “Echelon connection is active”

• Lead battery backup, with full functionality for 4 hours in case of network failure

• Tamper protection of the unit to prevent opening

Control Center 2 (CC2) KeypadsP/N 8003-277Order # HL-8003277• Maximum 4 units per system• Status display and local control• 2 line x 24 character LCD display

Area Keypad (KID) P/N 8003-220Order # HL-8003220• Maximum 8 units per system• Arm/disarm specific areas• 6 LED annunciator display

6-Input Concentrator (BIC-6)P/N 8003-238Order # HL-8003238• Supervised and tamper protected• 6 supervised inputs/outputs• 7 segmented LED point alarm/trouble display window

Multiple Output Module (MOM)P/N 8003-286Order # HL-8003286• Supervised and tamper protected• 8 opto-coupled outputs• 7 segmented LED point/alarm display window

2-Input Concentrator BIC-2P/N 8003-242; Order # HL-8003242 (White actuator buttons)

2-Input Concentrator BIC-2 HUP/N 8003-284; Order # HL-8003284 (Red actuator buttons for emergency/panic)• 2 supervised inputs• 1 output• Supervised and tamper protected• Remote reset• Distress actuator button

Hall Effect Door Switch IV (HEDS IV)P/N 8003-283Order # HL-8003283• High-security door contact detector• Supervised and tamper proof

i9000 Remote Intelligent Power Supply (RIPS)P/N 8003-217Order # HL-8003217• Maximum 7 units per controller• Powered by 16V AC transformer• Two 400mA, 12V DC switched auxiliary outputs• 1A programmable output• Status report to control unit over RS485 comm

RS-2

32

COMM 1RS-485

COMM 2RS-485

i9000 Control UnitSpecification Data 74-3035P/N 8003-332Order # HL-8003332• Monitors multiple areas (8 areas maximum)• 62 device modular architecture capacity• 512 input points with precise identification• 64 output points to various equipment and accessories• 99 user IDs• 4 authority levels limiting access to selected functions• Area access – limits access to selected areas• Language preference personalized to each user• 2 RS-485 communication lines• Power supply included

Wie

gand

Ethe

rnet

Intelliguard 9000™ Security and Intrusion Detection

PRODUCT FEATURES:The Intelliguard 9000™ (I9000) is a protection system designed to detect intrusions and other critical conditions when used with the Enterprise Building Integrator™ (EBI)• The I9000 monitors multiple areas, receiving input and providing localized report-

ing and control. A single I9000 control unit can simultaneously monitor many different buildings, areas with high-security door sensors

• Other compatible detectors and output devices can be added to the system, such as motion sensors, sound detectors, lights, sirens, and buzzers

• Multiple regulatory agency listings• Meets high-security UL Grade AA requirements• Multi drop EBI configurations (3 i9000's) using RRI and RS-485 bus wiring or

Cobox/Ethernet

TemaLine A Comprehensive Solution for Security

PRODUCT FEATURES:TemaLine is redefining the concept of integrated security solution subsystems for today and tomorrow.• Designed for unparalleled system reliability and availability using the “Shared

Load” concept• New distributed architecture and modularity reducing the management load

on the supervisory system• Multi-application/multi-functional controller provides access control, time and

attendance and intruder protection• Optional redundant TemaServer and “Shared Load TemaPower”• Single standalone application to a fully integrated EBI solution

NexSentry Star II Controller Innovative Access Control System

PRODUCT FEATURES:NexSentry® Star II controller changes access control standards by offering easy installation, modular components at an affordable price for the most demanding access control applications.• Modular architecture allows for easy upgrades to future technologies• Advanced digital technology with embedded Intel® 32 bit microprocessor

provides the fastest response in the industry• Support for multiple access technologies including Digital Proximity,

Magnetic Strip, Smart Card, Key Pad, and Biometrics

Photo ID StationLogitech® QuickCam Pro 4000Logitech P/N 961239-0403

3Com® Watchport V USB Camera3Com P/N 00371800

PhotoID MiniTower• Intel Pentium 4 processor, 1000BaseT • Integrated Ethernet adapter, online HD storage

configurable to meet customer requirements

FlashPoint 3Dx Lite Video Capture CardIntegral Technologies® P/N 3280• Allows use of any analog camera• Available in PCI or AGP

FlashBus MV Lite Video Capture CardIntegral Technologies® P/N 3047• Allows use of any analog camera• Only available in PCI

Fargo® DTC500 Series• Up to133 cards per hour

Fargo® Pro-LX• Up to120 cards per hour

Evolis Dualys Series• Up to 140 cards per hour

Evolis Pebble Series• Up to 140 cards per hour

USB

USB

Parallel

Parallel Ethe

rnet

Ethe

rnet

*Please contact your Honeywell sales representative for information on the Tema product line.

Ethe

rnet

Excel Life Safety System (XLS) – LAN Interface32004871-005 (single), 32004871-002 (dual)74-3444 Specification Data• One XLS LAN Interface serves entire XLS200/1000 subsystem:

- XLS system point display and command from any EBI workstation- Up to 40,000 points available from 64 XLS nodes- XLS points served via XLS high-speed peer network

Meets requirements of UL864 UOJZ for fire alarm control unit and UL1076 for security applications.• 24 Vdc power supplied directly from XLS1000• Redundant version with Ethernet Link Protector for Class A/Style 6 LAN connections

Excel Life Safety System (XLS) – Fire Network Adapter (FNA)– Q7055A103174-3966 Specification Data• TCP/IP network capable• Offers wide range of network connectivity options• Online system diagnostic support• Using the XLS-NCM interface, up to 100 XLS-NCA/XLS140 nodes can be connected to

the EBI through a single FNA Interface• UL864 (UOJZ) listed for full control of the XLS140 subsystem

PRODUCT FEATURES:As a stand-alone small-to-medium system, or as a network of distributed panels, Honeywell’s XLS140 intelligent fire alarm control panel meets virtually every application requirement. Designed with modularity and for ease of system planning, the XLS140 can be configured with just a few devices for small building applications, or for integrated campus and commercial installations.

High-speed/patented smoke detection technology:• FlashScan® Intelligent features• Poll 318 devices on each loop in less than one second• Activate up to 159 outputs in less than three seconds• Fully digital, high-precision protocol (U.S. Patent 5,539,389)• Advanced Warning Addressable Combustion Sensing (AWACS™) — nine levels• Multi-detector algorithm involves nearby detectors in alarm decision

(U.S. Patent 5,627,515)• Automatic detector sensitivity testing

Excel Life Safety System – XLS14085-3001 Specification Data• One, expandable to two, isolated intelligent Signaling Line Circuit (SLC) Style 4, 6, or 7• Up to 159 detectors (any mix) and 159 modules per SLC• Standard 80-character display, 640-character large display, or display-less

(a node on a network)• Network option – 103 nodes supported (XLS140, XLS-NCA Network Annunciator) using

wire or fiber-optic connections• Selectable system sensor strobe synchronization

Excel Life Safety System – XLS-NCA85-3008 Specification Data• 640 character – enhanced LCD display• Printer, CRT, and keyboard interfaces• User interface for all points in all nodes on the system• Can be used as a separate annunciator or combined in the XLS140 cabinet• Supports additional 32 remote ACS annunciator modules

Excel Life Safety System – XLS-CAB-4 Series85-3002 Specification Data• 16 gauge steel with locking doors• Right- and left-hand hinge• Trim rings for semi-flush mounting• Cabinets available in 4 sizes (C size shown) to accommodate job site requirements

Excel Life Safety System – LDM Series Graphic Annunciators85-3001 Specification Data• Modular and expandable, graphic annunciators display the information required by each

job site• LDM input/output modules communicate via RS485

Communication Interface ModulesPart Number FunctionRPT-485 Repeats EIA-485 over twisted pair or converts to fiber-optic

mediumXP5 The XP5-M and XP5-C provide FlashScan® transponder pointsXP The XP series transponder provides conventional monitor and

control points in CLIP (standard polling of each intelligent device) mode only

XPIQ The XPIQ quad intelligent voice transponder for distributed multichannel voice evacuation systems, an integrated audio amplification and distribution subsystem controlled by FACP. Capable of playing up to four simultaneous messages. Accepts up to four 25-watt amplifiers.

Annunciator/Control ModulesPart Number FunctionACS Annunciator control modules ACM-16AT, AEM-16AT, ACM-32A,

and AEM-32AAFM Annunciator fixed modules AFM-16A, AFM-16AT, and AFM-32ALDM Lamp driver modules LDM-32, LDM-E32, and LDM-R32SCS Smoke control station; eight (expandable to 16) circuits

Power SuppliesPart Number FunctionACPS-2406 6.0 amp addressable charger power supplyFCPS-24 The FCPS-24 is a remote six-amp (four-amp continuous)

repeater/power supplyFCPS-24S6/-24S8 Remote six-amp and eight-amp power supplies with battery

charger

NotificationPart Number FunctionICM-4RK NAC module, provides four style Y (Class B) or Style Z (Class

A) circuitsCRM-4RK Control relay module, four form-C relay contacts per circuitVCM-4RK Voice control module, provides four Style Y and Style Z speaker

circuits, eight manual select switches and indicatorsDCM-4RK Dual channel module provides four class B or class A speaker

circuitsXLS-VCC-1B Voice control center; provides a variety of user-selectable tones

on a single channelXLS-TCC-1B Telephone Control Center; provides a stand-alone two-way Fire

Fighters telephone (FFT-7S)FFT-7 FFT-7S Fire fighters telephone control with master handsetAA-30 Audio amplifier, 30 wattsAA-120 Audio amplifier provides up to 120 watts of audio power (25

VRMS) for the XLS140AA-100 Use the AA-100 for 70.7 VRMS systems and 100 watts of power

XLS140 Primary System ComponentsPart Number FunctionXLS140-CPU Central processing unit with integral 3.0 amp power supplyKDM-2 80-character backlit LCD display with keypadXLS-NCA Network control annunciator, 640 characters

Twis

ted

Pair

Leas

ed T

elep

hone

Lin

eFi

ber O

ptic

Cab

le

RS48

5 Au

dio

& D

ata

Twis

ted

Copp

er P

air

Shor

t Hau

l Mod

ems

24 g

a Te

leph

one

Line

sAu

dio

& D

ata

Fibe

r Opt

ic C

able

Flexible Network Communication

Topology

XLS-

NET

Twis

ted

Copp

er P

air

XLS-

NET

Fibe

r Opt

ic C

able

XLS-

NET

Tele

phon

e Li

nes

DeltaNet FS90Capability, Reliability, Expandability

PRODUCT FEATURES:The DeltaNet FS90 Fire and Security (F&S) family of real-time, microprocessor-based controllers offers conventional and intelligent fire detection and annunciation, security, and access control.

Building on the base FS90 system architecture, the family includes:• DeltaNet FS90 System for conventional zone alarm verification, cross-zoning, annun-

ciation, control, individual zone alarm, supervisory and trouble indication, zone discon-nect switches, and a local audible signal. Security functions include local and remote secure/access switching and high-security line supervision

• DeltaNet FS90 Plus System (“FS90 Plus”) for intelligent functions to monitor and con-trol individually addressable fire and security devices. FS90 Plus can have up to nine Intelligent Loop Interface Boards, each of which can have two 2-wire circuits or one fault-tolerant 4-wire circuit

• DeltaNet Access Control for monitoring and control of up to eight card readers and/or keypads per controller. The system supports multiple card technologies, multilevel antipassback, two-card access, supervisor-required access, and elevator control

DeltaNet FS90 Fire and Security Controller74-3154 Specification Data• Conventional and intelligent detection and signaling• Stand-alone operation and/or integration with higher order systems• Function boards for configuration to site requirements• Easily changeable data file in nonvolatile memory• Auto-tuning sensitivity• Communication to panels via dual twisted pair, leased telephone lines, or fiber

optic cables

DeltaNet FS90 Fire Command Center74-3154 Specification DataAny DeltaNet F&S system, whether stand-alone or connected to a higher-order system, can include an optional command center for alarm and trouble message display and optional printout, and for data display and entry from a keypad

XLS1000 F&S Bus Interface - 1450753274-2771 Specification DataFully compatible with the DeltaNet F&S bus architecture, this interface allows XLS1000 controllers to co-exist with the FS90 on the F&S bus, providing a seemless migration path for customers

DeltaNet FS90 Access Management Controller (AMC)74-2438 Specification DataFS90 functions or operate as a dedicated access system• Fully integrated with EBI• Support for major access card technologies, including magstripe, barrium ferrite,

proximity, Wiegand, and biometric readers• Complex access control applications such as elevators control, multi-level anti-pass-

back, two-card, supervisor rules, PIN support, and over 200 schedules per controller

DeltaNet FS90 Fire Management System74-3154 Specification DataSingle and dual channel audio with optional fire warden telephoneFCS function boards provide:• Audio and phone control (for fire signal and evacuation message output, all-call paging

of multiple speakers)• Speaker and phone selection (for individual selection of speaker and phone circuits,

all-talk two-way communication with multiple phones, optional phone page to address audio speakers from a fire fighter telephone)

• Heating, ventilating, and air conditioning (HVAC) override (for two and three-position control of fans, dampers, and other non-audio equipment)

AccesoriesPart Number Function3-BATS Battery shelf for XLS-RCC enclosures; space for one 65 AH or two 50

AH batteries3-BTSEN Battery sensor/distribution module3-TAMP Tamper switch for 3-CAB7, 3-CAB14 and 3-CAB21 cabinets3-TAMP5 Tamper switch for 3-CAB5; mounts to side of cabinet3-TAMPRCC Tamper switch for XLS-RCC series cabinets; mounts to side of cabinet32004129 XLS1000 high-security interface for UL 1076 Grade AA security for up

to eight zones32003193 XLS1000 panel mount printer

Modules, Amplifiers, Power Supplies and BoardsPart Number Function3-LDSM LED display support module3-24R (Y/G) 24 red LED display module (yel/grn)3-12SR (Y/G) 12 switches/12 red led display/control modules (yel/grn)3-12RY 12 red LED and 12 yellow LED display modules3-12/S2Y 12 switches, each with 2 yellow LED display/control modules3-12/S1GY 12 switches with one grn and one yel LED per switch3-12/S1RY 12 switches with one red and one yellow LED per switch3-6/3S1G2Y 6 groups of 3 switches; each switch has (1) grn, (2) yel LEDs3-6/3S1GYR Control/display module with six groups of three switches; each switch has

one grn, yel, red LED3-ZA20A/B 20W zoned amplifier; selectable for 70 or 25 Vrms operation3-ZA40A/B 40W zoned amplifier; selectable for 70 or 25 Vrms operation3-ZA90 90W zoned amplifier; selectable for 70 or 25 Vrms operation3-PPS/M Primary power supply with local rail module 120v, 50/60 hz3-IDC8/4 Initiating device circuit module3-OPS Off premises signaling module3-ASUFT Audio source unit with local microphone and firefighter’s telephone3-CPU1 Main panel processor3-LCD Main display interface with LCD3-RS485A/B/R Network communication board3-RS232 RS232 communication board3-FIB/A Fiber optic communications interface3-MODCOM(P) Modem communicator DACT with duplex V.32 bis 14.4K baud modem3-NSHM1/2 Network short haul modem communications interface with modem

connections3-SAC Security control moduleXLS-KPDISP Keypad/display module

XLS1000 Primary System ComponentsPart Number Function3-DSDC Dual SIGA data controller with one SIGA data board; mounts to local rail

3-AADC Analog addressable data loop controller; mounts to local rail

Excel Life Safety Sensors

SMOK

E

Model Type Features CompatibilityFS90 XLS1000 XLS140

TC806 Photoelectric • Low-profile design, low current draw• Tamper-resistant wiring base• Integral insect resistant screen to reduce nuisance alarms• Dual LEDs provide 360-degree viewing• Optional remote LED annunciator• Built-in test mechanism

Yes Yes Yes

TC807 Ionization

XLS-IS Ionization • Environmental compensation• Pre-alarm sensitivity capability• Continuous self-diagnosis and storage of environmental and operational data• Day/night sensitivity adjustment• One red and one green status LED• Standard, relay, and fault Isolator mounting bases• Design and manufacture per ISO 9001 standards

Yes

XLS-PS Photoelectric Yes

HEAT

TC808 Thermal135° ROR/FT190° FT

• Thermistor sensing circuit for fast response• Rate-of-rise detection model available• Dual sensor LEDs provide 360-degree viewing• Modern low-profile design• Compatible with Honeywell CLIP and FlashScan loop transmission

Yes Yes Yes

XLS-HFS Fixed Temperature135° FT

• 135°F (57°C) fixed temperature detector type• Combination 15°F (9°C) per minute minimum rate-of-rise and/or 135°F (57°C) fixed temperature detector type• Electronic addressing and device mapping• Continuous self-diagnosis and storage of environmental and operational data• Standard, relay, and fault isolator mounting bases

Yes

XLS-HRS Rate of Rise Yes

SPEC

IAL

APPL

ICAT

IONS

TC840Acclimate

Multi-CriteriaPhotoelectricThermal

• Automatically optimizes performance for each installed location• Continuous monitoring of detector sensitivity• Digital pulse-width encoded communication with noise immunity• Compatible with Honeywell CLIP and FlashScan™ intelligent

Yes Yes Yes

TC844Filtrex™

Harsh EnvironmentPhotoelectric

• High-density Filtrex™ filter eliminates the need for sensor cleanings• Filtrex™ filter self-monitors clogs and reports a trouble condition at the panel when replacement is needed• Two sensor LEDs provide status indication at the control panel• Provides rotary-decade switches to set sensor address

Yes Yes Yes

TC846Pinnacle™

Ultra-High Sensitivity Laser Smoke Detector0.02% - 2.00%/ftObscuration

• Fast response to detect very early particles of combustion• Ultra-high sensitivity capability• On-board drift compensation• Transient rejection algorithms• Environmental tracking• Wide sensitivity range

Yes Yes Yes

XLS-IPHS MultiCriteriaIon, Photo, Heat

• Environmental compensation• Wide 0.67 percent to 3.70 percent/ft. sensitivity range• Pre-alarm sensitivity capability• High ambient temperature operation (up to 100°F [38°C])

Yes

FS90 Control and Communication Function BoardsPart Number Board Function14505104-005 CA FS90 control/CPU board14506344-001 LJ RS485 communications and display board14506690-001 LJ Leased line communications and display board14506302-003 CC Audio control board14506302-004 CE Fire telephone control board14506302-002 SB/SD Two position manual switch – 4 circuits14506302-001 SH/SK Three position manual switch – 4 circuits

Fire/Security Function Boards Part Number Board Function14506106-001 AA Class “B” initiating device circuit – 4 zones14505108-001 AB Class “A” initiating device circuit – 2 zones14505106-002 AC Class “B” initiating device circuit – 4 zones – contact input only14505118-001 AD Digital input – 8 circuits, unsupervised14505132-002 AE Intelligent detection loop (slc) - 2 circuits per board14505188-001 AF Class “B” secure/access circuit – 4 zones, with local control14505188-002 AG Class “B” secure/access circuit – 4 zones, no local control14506432-001 AH Class “B” ul grade aa high-security circuits14505110-001 BF Class “B” notification appliance circuit – 2 NAC circuits, 2 N.O. Relays14505110-002 BG Class “A” notification appliance circuit – 2 NAC circuits14505116-001 DB Digital output – 8 circuits14505112-001 DC Accessory relay board - 4 SPST N.O. OR N.C. relays

*LONMARK is a trademark of Echelon Corporation

Ethe

rnet

Ethe

rnet

Ethe

rnet

FS90 LAN Interface Assy- 14006700-59810074-3487 Specification Data74-3646 Specification Data• Configurable for single or dual Ethernet networks• Converts Ethernet to RS232/RS485 with optical isolation for UL Fire/Security applications• Supports 128-bit AES encryption

PRODUCT FEATURES:Honeywell LifeSafety Manager™ provides unprecedented protection of your building’s assets and occupants. This life-safety application incorporates: • Intelligent, microprocessor-based devices, including multi-sensor detectors that provide

early warning of smoke and fire conditions, and virtual elimination of nuisance alarms• Advanced distributed, digital audio communication system facilitating safe, orderly

evacuation of occupants • Rapid and reliable fire alarm controller peer-to-peer communications network • Integral firefighters telephone communication system • Emergency paging to support storm warning and hazardous materials (HazMat) notifica-

tion • Control of the facilities’ HVAC equipment, such as fans and dampers, to contain smoke

and create safe havens • Releasing of fire doors to permit safe exit • Sprinkler supervisory status of suppression systems, sprinkler valves, and fire pumps

Excel Life Safety System – XLS100074-2073 Specification Data• Modular system designed for medium to large building and campus applications• 168-character LCD automatically displays system messages and alarms• 64 node, 160,000 points with 3-second alarm response over any size network• Total network wring over 300,000 ft (91,440m)• 250 devices per loop, 2500 devices per node• 750 ms signature loop alarm response• Every point can be viewed and controlled from any node• Digital storage and transmission of eight multiplexed channels of audio for

unmatched intelligibility• Local, proprietary and central station operations with integral alarm printer option• Modem communicator option with DACT functionality• Graphic, text/LED, and keypad/display annunciator options• Listed for suppression releasing and smoke control applications

Excel Life Safety System – Envoy Annunciator74-3481 Specification Data• High-contrast lines and text• LCD displays custom text messages in graphic annunciator enclosure

- Firefighters smoke control station options- Agency listed with Honeywell control panels- Surface or semi-flush mounting with optional trim- Field-installed modification of graphic with optional graphic transfer kit

Excel Life Safety System – Remote Annunciator74-2888 Specification Data• Backlit LCD display provides 168 characters

- Displays information important to user- Hands-free, first and last event with highest priority

• LCD display uses queues to sort events• Variety of cabinet configurations size the annunciator to the application• Programmable LED flash rates• Slide-in custom labels

Excel Life Safety System – Flexible Network CommunicationsSupports communication on:• Twisted pair copper• Single and multimode fiber optic cable• Existing dry telephone lines

Excel Life Safety System – XLS1000A High-Performance Life-Safety Solution

Excel Life Safety System – XLS140Advanced Detection and Networking Digital Video Manager (DVM) - A Flexible, Highly Integrated

CCTV Solution with Advanced Capabilities.

PRODUCT FEATURES:• Software-based digital CCTV video management platform • Uses off-the-shelf PC, storage, and networking hardware • Live viewing and playback while recording• Camera pan/tilt/zoom control from any client on the network• Continuous, scheduled, alarm, pre-alarm motion, and user-activated recording modes• Up to 30fps performance on all channels• Communicates using TCP/IP network protocol using industry-standard Ethernet technologies• Full integration with EBI including direct access to alarm recordings from EBI alarm/event

summary display• High-speed SQL-based search engine (date, time, camera, operator, point, alarm)• Digitally signed recordings and audit trail• Redundant server for complete fault tolerance (optional)

DVM Database ServerManages the DVM system. Contains recording index, audit log, and web server(1) database server per system(1) optional redundant database server per system

Uses off-the-shelf PC with the following minimum specifications:

Processor:....................................... Intel Pentium IV 1GHz or greater (Dual processors recommended).

System Memory: ............................ 1GB RAMFloppy: ............................................ 3.5”, 1.44MBCD ROM:......................................... 24X or greaterSystem Storage: ............................. 40GB RAID-1 storageInput Devices: ................................. Standard Windows keyboard, mouseMonitor: .......................................... 15” SVGA colorOperating System: .......................... Windows 2000 Server

DVM Camera ServerStores video streams and transmits video to clients. Number of database servers required dependent on application, minimum of (1) per system

Uses off-the-shelf PC with the following minimum specifications:

Processor:....................................... Intel Pentium IV 1GHz or greater (Dual processors recommended).

System Memory: ............................ 1GB RAMFloppy: ............................................ 3.5”, 1.44MBCD ROM:......................................... 24X or greaterSystem Storage: ............................. 40GB storageVideo Storage: ................................ RAID-5 fault tolerant storage, capacity dependent on appli-

cationInput Devices: ................................. Standard Windows keyboard, mouseMonitor: .......................................... 15” SVGA colorOperating System: .......................... Windows 2000 Server

Optional Video Storage Subsystem (Promise Technology or NexSan)Provides additional fault tolerant (RAID-5) video storage. Scales from 10’s to 100’s of terabytes. DVM supports any Windows 2000-compatible off-the-shelf storage device including Direct or Network Attached Storage (DAS or NAS) or Storage Area Network (SAN) systems

Use Promise, NexSan or other off-the-shelf storage subsystem with the following minimum specifications:

RAID Levels: ................................... 0, 1, 3, 4, and 5Redundancy: ................................... Hot-swappable drives, hot-sparing, redundant power sup-

plies, redundant RAID controllerDrives Supported: ........................... 4, 8, 14, or 42Drive Types: .................................... Ultra ATA/133, Ultra ATA/100, or SATAData Rebuild: .................................. 40GB storageRAID Controller:.............................. RAID-5 fault tolerant storage, capacity dependent on appli-

cationSCSI Interface:................................ SCSI Ultra160O/S Supported: ............................... Windows 2000

Network SwitchesDVM Communicates using TCP/IP network protocol using industry-standard Ethernet technologies. The network switch links the video streamers to the camera server(s) andcamera servers to clients

Use off-the-shelf storage network switches with the following minimum specifications:

• Simple Network Management Protocol (SNMP)• IEEE 802.1D bridging capability and loop detection• IEEE 802.1Q tagged VLANs• IEEE 802.1 traffic prioritization for multiple QoS levels• Support for multicast traffic• Non-blocking, wire-speed access across all ports

IP Network CamerasIP Network cameras combine the video encoding and streaming functions of the video streamer with a security camera. Digital video streams that are transmitted across a standard LAN/WAN to DVM Camera Servers for indexing and storage. Use Axis Communications

AXIS:............................................... 2100, 2110, 2120, 2130, 205 (MJPEG) and 2420

Video Encoding and StreamingVideo Streamers convert analog NSTC or PAL camera images into highly compresseddigital video streams that are transmitted across a standard LAN/WAN to DVM cameraServers for indexing and storage. Use Axis Communications, MegaChips or Sungjin

AXIS:............................................... 2400+/2400+ Blade, 2401+/2401+ Blade, 241S/241Q (MJPEG) or 2411

MegaChips: ..................................... OpennetView, MD100, MJPEG encodingSungjin:........................................... CamStation CS100, CS300-1V (MPEG-4)

Analog CamerasAnalog camera signals are input into a video streamer and converted into a digital format and transmitted across a standard LAN/WAN. DVM supports industry-standard NTSC and PAL analog cameras

Fixed Camera Support

Honeywell: ...................................... Ademco e-Series, Ademco System Series, Ultrak KC Professional Series

Other:.............................................. Any NTSC or PAL analog camera

Pan/Tilt/Zoom (PTZ) Camera Support

Honeywell: ...................................... ADEMCO RapidDome/VCL Orbiter, Ultrak UltraDomeOther:.............................................. American Dynamics Speed Dome, Bosch AutoDome G3A,

Canon VC-C3/C4/C4R, Daiwa DMP 15, Ernitec Orion, Lilin FastDome, Molynx Surcha, Panasonic WVCS850/854, Pelco SpectraDome, Sony EVI-D30/D31/G20/G21

Coax

Cab

le

Coax

Cab

le

LON

Honeywell, Enterprise Buildings Integrator (EBI), EXCEL 5000 OPEN, Excel Building Supervisor (XBS), Excel Building Supervisor Integrated (XBSi), Excel Plus, Excel Classic, Excel 500, Smart Excel 500, Excel 50, Excel Security Manager (XLS/XLS1000), Excel Life Safety, Delta 1000, Delta 2000, Intelliguard 9000 (i9000) and DeltaNet FS90 are trademarks of Honeywell International, Inc. All other brands are trademarks of their respective companies.

Asset Locator - Axcess

PRODUCT FEATURES:• Real-time location tracking and status monitoring solution• Radio-frequency (RF) based tracking for area location• Low-frequency RF (Activator) based tracking for precise door/

elevator location • Tag models include: asset, personnel, cargo, vehicle, and

prisoner/wrist tags

APPLICATIONS:• Laptop and computer theft deterrence• Staff safety (location tracking and duress alarming)• Long-range, wireless vehicle gate access control• Cargo location tracking and tamper monitoring• Prisoner/patient location tracking and perimeter alarming• Casino key and cash box location tracking and theft deterrence

RF Receiver(P/N: AT-132-NR-IP & AT-132-NR-S)Ceiling mounted device that receives coded RF transmissions from Axcess tags• Read range of 35-40 ft.• 315 MHz and 433.92 MHz versions• Ethernet/Wiegand output version (P/N: AT-132-NR-IP)• RS232/Wiegand output version (P/N: AT-132-NR-S)• FCC Part 15 and EC compliance• General area location precision• -30 to 85ºC operation

Activator (P/N: AT-132-AT & AT-132-AT-D)When used with an activator antenna, it generates a “wake-up” field for all Axcess tags and forces them to transmit• Operates at 126 KHz using 24 VDC power• Standard one antenna version (P/N: AT-132-AT)• Dual antenna version for in/out vehicle gates (P/N: AT-132-AT-D)• When used with an activator antenna it provides precise loca-

tion to a small area (door, elevator cab, gate, muster zone)• Wake-up field can be adjusted using 20-turn adjustment screw• -40 to 85ºC operation

Road Loop Activator Antenna (P/N: AT-132-VL-S & AT-132-VL-D)Provides tag wake-up field for vehicles when connected to an acti-vator and mounted in roads or non-metallic doorway floors• Single lane road loop version (P/N: AT-132-VL-S)• Dual lane road loop version (P/N: AT-132-VL-D)

Flex Activator Antenna (P/N: AT-132-A-F)Very thin activator antenna encapsulated in a Kapton sheet. Designed to go under carpet, inside of non-metallic turnstiles or inside walls• 10.5 x 21 inches in size• Range up to 8 ft. for personnel tags and 6 ft. for asset tags

Overhead Activator Antenna (P/N: AT-132-A-PO)Activator antenna constructed of plexiglas, which is made to be installed in a ceiling (replaces one ceiling tile)• 21 x 21 inches in size• Range up to 8 ft.

Plex Activator Antenna (P/N: AT-132-A-PT & AT-132-A-PW)Activator antenna constructed of plexiglas, which is made to be installed above or next to a door• Thin plex antenna is 4.5 x 37 inches in size (P/N: AT-132-A-PT)• Thick plex antenna is 9 x 52 inches in size (P/N: AT-132-A-PW)• Range up to 8 ft. for personnel tags and 3 ft. for asset tags

Picture Frame Activator Antenna (P/N: AT-132-A-F8 & AT-132-A-F10)Activator antenna that is integrated into a picture frame to provide unobtrusive monitoring• Standard size is 16 x 20 inches (P/N: AT-132-A-F8)• Large size is 20 x 26 inches (P/N: AT-132-A-F10)

Axcess Tag Styles• Standard tags only provide location change events only when

they enter activator fields• Beacon tags provide location change events when they enter

Activator fields and when they move between areas covered by Receivers. The standard beacon rate is once per hour however, through special orders this can be set from once per minute to once every 18 hours

Asset Tags (P/N: AT-132-A, AT-132-A-B, AT-132-A-T, AT-132-BT)Water-proof tags that attach directly to equipment (laptops, com-puters, etc.) to monitor location and generate perimeter alarms in conjunction with activators and RF receivers. Tags are 1.25 x 2.56 x 0.38 inches• Standard asset tag (AT-132-A) and with tamper (AT-132-A-T)• Beacon asset tag (AT-132-A-B) and with tamper (AT-132-A-BT)

Key Fob Tags (P/N: AT-132-PF-R, AT-132- PF-C, AT-132-RF)Fob style tags that are designed to be attached to key rings. Tags are 1.31 x 2.81 x 0.31 inches• Standard tag with replaceable battery – not water-proof

(AT-132-PF-R)• Standard tag with replaceable battery and duress alarm – not

water-proof (AT-132-PF-C)• Ruggedized standard tag “casino key tag”– water-proof

(AT-132-RF)

Metal Mount Tags (P/N: AT-132-M, AT-132- M-B, AT-132-M-BA)Rugged, water-proof, chemical-resistant tags designed for harsh environments and for direct mounting to metal objects (metal cases, truck bumpers). Tags are 2.19 x 4.13 x 0.56 inches• Standard metal mount tag (AT-132-M)• Beacon metal mount tag (AT-132-M-B)• Beacon metal mount tag with temperature sensor

(AT-132-M-BA)

Cargo Tag (P/N: AT-132-L)Rugged, water-proof, chemical-resistant tags designed for direct mounting to metal cargo containers. Tamper detect wire included which loops through cargo lock. Tags are 2.19 x 4.13 x 0.56 inches• Standard cargo tag (AT-132-L)

Personnel Tags (P/N: AT-132-P, AT-132-P-B)The water-proof personnel tags are standard ISO prox size and have a slot for clip or lanyard attachment. Tags are 2.19 x 3.44 x 0.25 inches• Standard personnel tag (AT-132-P)• Beacon personnel tag (AT-132-P-B)

Vehicle Tags (P/N: AT-132-V, AT-132-V-D)The water-proof vehicle tags are standard ISO prox size and are made to mount on the inside windshield of cars and trucks. Tags are 2.19 x 3.44 x 0.25 inches• Standard vehicle tag (AT-132-V)• Standard vehicle tag with tamper disable (AT-132-V-D)

Wrist Strap/Prisoner Tag (P/N: AT-132-W)Rugged, water-proof tag designed to be attached to wrists or ankles of prisoners or patients for location tracking and perimeter alarming. Attachment of tag arms the conductive tamper strap, which then generates a tamper alarm if it is ever cut. The tamper strap is disposable• Standard wrist strap tag (AT-132-W)

Asset Locator - A real-time location tracking and monitoring solution for people and equipmentHoneywell Asset Locator supports two hardware solutions, which enable it to be customized for most markets and applications

Asset Locator-Elpas – High-performance solution targeted at health-care and museum applications

Asset Locator-Axcess – Cost-effective solution targeted at com-mercial, industrial, prison, airport, education, seaport, and casino applications

Asset Locator - Elpas

PRODUCT FEATURES:• Real-time location tracking and status monitoring solution• Infra-Red (IR) based tracking for room-by-room location• Radio-Frequency (RF) based tracking for area location• Low-Frequency RF (LF) based tracking for precise door/elevator

location • Tag models include: equipment, personnel, baby, mother, pediatric/

Alzheimer and alert

APPLICATIONS:• Infant abduction deterrence and mother-baby matching• Pediatric abduction deterrence• Patient wandering deterrence and duress alarming• Medical equipment location tracking and theft deterrence• Staff safety (location tracking and duress alarming)

i.LON® 600 RouterProvides network connectivity between Ethernet LAN and LONTalk (FTT-10A) bus

Physical Layer Repeater/PLR (P/N: ERS02001)Extends reader network beyond 64 node limit• Extends free topology bus length by 500 meters• Up to 50 IR or RF readers per PLR• Up to 9 PLRs per LON channel (per iLON 1000® router)

IR Reader (P/N: RDT00001)Ceiling mounted device that receives coded IR transmissions from Elpas tags• Read range up to 40 ft.• Room-by-room location precision

External Relay Box (P/N: NXB00001)Local (reader-connected) relay to control doors, lights, and buzzers in response to InstaTrak alarms• Connects directly to IR and RF readers• 2 normally open or normally closed relays (5A/230V)

RF Reader (P/N: RDF00001)Ceiling mounted device that receives coded RF transmissions from Elpas tags• Read range up to 60 ft.• Operates at 433.92 MHz.• FCC Part 15 and EC compliance• General area location precision

LF Reader (P/N: RLF00001)Ceiling mounted device that generates a “wake-up” RF field for selected Elpas tags and forces them to transmit• Read range up to 10 ft.• Operates at 125 KHz.• Provides precise location to a small area (door, elevator cab).• Master/Slave LF readers available for larger areas• Tags with LF support: BTB00433, PTA00433, ART00433,

ETB00433, ETB00433-2, ETF00433

Junction Box (P/N: FJB00001 & EJB00001)Connects Elpas LON devices to LONTalk network• 2 reader/2 LON backbone connect version (FJB00001)• 4 reader/4 LON backbone version (EJB00001)

Elpas Tag Styles• Personal badges. Transmits periodically, duress button option

Types include combinations of IR/RF and triple technology with temperature measurement

• Alert tags. Combinations of IR/RF with various button/pull activations

• Equipment tags. Combinations of IR/RF with without inputs and triple technology with temperature measurement

• Health care baby tags. Wrist tag & pediatric tag using combina-tions of IR/RF and supervised inputs

Baby Tag (P/N: BTB00433)Water-resistant tag attaches to baby's ankle to monitor location and generates perimeter alarms in conjunction with LF and RF readers• Tamper-proof band will generate alarm if removed• New disposable cap/band used for every baby (P/N: BTB90001)

Wrist Mother/Patient Tag (P/N: PWB00901 & EWB00001)Water-resistant tag attaches to patient's wrist using standard hospital strap• IR version (P/N: EWB00001), IR/RF version (P/N: PWB00901)• When used in conjunction with baby tag and BabyMatch applica-

tion, pressing mother tag button initiates match process

Pediatric/Alzheimer’s Tag (P/N: PTA00433)Water-resistant tag attaches to patient's wrist using standard hospital strap to monitor location and generates perimeter alarms in conjunc-tion with LF and RF readers• Tamper-proof wire will generate alarm if removed.• New disposable cap/wire used for every patient (P/N: PTA90001)

Personnel Tag (P/N: ERS01201, PBE00433 & ETB00433-2)Clip-on tag is used for location tracking and duress alarming• IR version (P/N: ERS01201), IR/RF version (PBE00433), IR/RF/LF version (ETB00433-2)• Button on the back of the tag can be used to generate personal

duress/ attack alarms

Alert Tag (P/N: ALB00001, PLB00001 & ART00433)Tag with strap is designed to be worn around the neck or carried. Large button makes it easy for the elderly to initiate a duress or panic alarm• IR version (P/N: ALB00001), IR/RF version (PLB00001), RF/LF ver-

sion (ART00433)

Rectangular Equipment Tag (P/N: ETB00433 & ETF00433)Attaches to equipment to monitor location and generate perimeter alarms in conjunction with RF and LF readers• IR/RF/LF version (P/N: ETB00433) and RF/LF version (ETF00433)• Optical tamper sensor on the back of the tag will generate alarm if

the tag is ever removed• Wire inputs can be used to monitor equipment run-time or open/closed status of equipment

Oval Equipment Tag (P/N: EQB00901, EQB00903 & WSE00433)Water-resistant tag to monitor location and status of equipment. • IR version (P/N: EQB00901), IR version with wire inputs

(EQB00903) and IR/RF version with wire inputs (WSE00433)• Wire inputs can be used to monitor equipment run-time or open/

closed status of equipment

System DescriptionBase System Includes 50 metersAdder 1 10 meter adder to baseAdder 2 50 meter adder to baseAdder 3 100 meter adder to baseAdder 4 250 meter adder to baseAdder 5 1000 meter adder to baseOptionsLoad Management Adder to baseWeather Data Adder to base

Energy Manager - Understand and Control Energy

PRODUCT FEATURES:• “Out-of-the-box” solution for energy data collection, cleaning, analysis, and reporting, plus load

management and control• Flexible, hierarchical modeling of your energy system that can include circuits, equipment, meters,

tenants, weather stations, locations, and more• Automatic data cleaning removes or reduces the impact of meter failures, dropouts, and spikes• Exceptionally powerful drag-and-drop reporting using tools that you are already familiar with • Software-based solution; compatible with virtually any utility metering device that can be interfaced

to EBI. Supports electric, gas, water, fuel oil, and other meter types• Automatic load shedding based on demand limits and configurable algorithms• Automatic generator control for peak shaving, including email notifications and approvals• Electrical and gas load forecasting with wizard-based configuration• Weather data can be read from local weather stations or the internet and incorporated into reports• Thermal load forecasting• Baseline import wizard• Environmental and greenhouse gas reporting• Automatic unit conversion for data collection and reporting. Conversion of fuels to common energy

units to allow fuel comparisons

Energy Manager Foundation:Energy Manager Foundation is built upon the Energy System Model. This model describes the objects within your energy system and the relationships between them. The objects that can be included in your Energy System Model are:

• Meters (real and virtual) • Localities (geographical locations, campus, building, building area)• Equipment (lighting, boiler, chiller, general)• Circuits (grouping of loads and generators)• Tenants • Weather stations

Benefits of Energy Manager• Identify and reduce peak energy demands that are driving up costs• Implement powerful load curtailment strategies• Validate and understand utility data• Help optimize your equipment start and stop times• Provide the data to negotiate lower energy rates• Uncover employee equipment overrides that increase costs

Utilities Supported• Electric • Gas • Water• Fuel Oil • Steam• User-defined

Meter Management• LonWorks• Modbus• OPC• Pulse Accumulators/Totalizers• Data Validation and Spike Detection• Data Cleaning and Filling

Enterprise Demand Management• Load monitoring with automatic alarming and event logging• Loads can be shed according to various strategies to curtail costly spikes in demand• Load management operator displays with real-time visualization and tuning

Internationalization• Energy Builder and Operator Display content can be configured in local language

Server Requirements• 1024 MB RAM (recommended), 512 MB (minimum)• 1 GHz Pentium III Processor• 25MB per meter per year hard disk storage (approximate)• Windows 2000 Server

Client Requirements• Per EBI Release 200.2 requirements

Licensing• Energy Manager Foundation license model is based upon the number of meters

combined with a 10-pack incremental adder option• Enterprise Demand Management is sold as an option to the base system• Enterprise Load Management and Advanced Energy Modeling options are sold as

options Energy Manager Foundation

* Tailored Solutions Available for:• Rates analysis• Tenant billing• Energy (electric, gas) and thermal (heating and cooling) load forecasting• Real-time-pricing (RTP) based control• Data import and export• Equipment modeling and optimization• Measurement and Verification (M&V) and operations reports

Architecture Options• Energy Manager can either be installed on an existing EBI Server (typical) or on a dedicated

EBI server to be interfaced to your existing EBI network via EBI’s DSA capability• For large sites, the reporting engine of Energy Manager can be installed on a dedicated

Report Server to maximize reporting performance

Architecture OptionsArchitecture OptionsArchitecture Options

Meters• Veris Industries (www.veris.com)• Power Measurement Limited

(www.pwrm.com)• Square D (www.squared.com)• WattNode by Continental Controls

(www.ccontrolsys.com)

TCP/IP

LonWorksMeter

Pulse

Pulse

LON

LonWorksMeter

EXCEL 500

Ethe

rnet

i.LON® 600 RouterProvides network connectivity between Ethernet LAN and LONTalk (FTT-10A) bus

Automation and Control SolutionsHoneywell Honeywell Limited-Honeywell Limitée1985 Douglas Drive North 35 Dynamic DriveGolden Valley, MN 55422 Scarborough, Ontario M1V 4Z9

www.honeywell.com77-2148 04/04 Printed in the USA on recycled paper containing 10% post consumer waste.