HIGH VOLTAGE ELECTRICAL APPARATUS

ARYAM AUSTRALIA GROUPwww.aryamenergy.com | Email: [email protected] | Phone: 1300 347 922

Page 2: HIGH VOLTAGE ELECTRICAL APPARATUS

ContentsZW6-12 Series Outdoor Column Voltage Vacuum Circuit Breaker

ZW8-12 Series Outdoor Column Voltage Vacuum Circuit Breaker

ZW10-12, ZW27-12 series outdoor high voltage vacuum circuit breaker

ZW20G-12 Type Outdoor Column Vacuum Circuit Breaker

ZW32-12 Series Outdoor High Voltage Pole Vacuum Circuit Breaker

ZW32-12/M Series Outdoor Column Permanent Vacuum Breaker

ZW7(A)-40.5,ZW17-40.5 Series Outdoor High-Voltage Vacuum Circuit Breaker

ZN28-12 Series Indoor High Voltage Vacuum Circuit Breaker

ZN28A-12 Series Indoor High Voltage Vacuum Circuit Breaker

ZN63A(VS1)-12 Series Indoor High Voltage Vacuum Circuit Breaker

ZN63G-24(VS1-24)Series Indoor High Voltage Vacuum Circuit Breaker

ZN23-40.5C Series Indoor Handcart Vacuum Circuit Breaker

ZN39-40.5C Series Indoor High Voltage Vacuum Circuit Breaker

ZN85-40.5 Series Indoor High Voltage Vacuum Circuit Breaker

LW3-12(D) I II III Series Outdoor High Voltage SF6 Circuit Breaker

LW8-40.5 Series Of Sulfur Hexafluoride Circuit Breaker

LW36 □ -126 Series Of Sulfur Hexafluoride Circuit Breaker

FN12-12 Series Indoor High Voltage Load Switch And Fuse combination units

FZN21-12(D)/T630-20·FZRN21-12(D)/T125-31.5Type Indoor High Voltage Vacuum Load Switch-Fuse Combinations

FZN25-12(D)/T630-20·FZRN25-12(D)/T200-31.5Series Indoor High Voltage Vacuum Load Switch-Fuse Combinations

FZW20-12 Series Outdoor Ac High Voltage Isolation Vacuum Load Switch

FZN36-40.5/D630,1250-20 Series Outdoor High Voltage Disconnect Vacuum Load Switch

GW4 Series Outdoor AC High Voltage Disconnectors

GW5 Series Outdoor AC High Voltage Disconnectors

02

04

06

08

09

10

12

14

15

16

18

19

20

22

23

24

26

28

29

31

33

35

38

40

Page 3: HIGH VOLTAGE ELECTRICAL APPARATUS

-02-

ZW6-12 Series Outdoor Voltage Vacuum Circuit Breaker

ZW6-12 type Outdoor high-voltage vacuum circuit breaker is rated voltage 12kV, three-phase AC 50Hz high voltage outdoor switch equipment. Mainly used for breaking and closing ru-ral network, city network and small power system load current, overload current and short-circuit current. The three phase of this circuit breaker are hold in one box, three-phase vacuum

Description

main Technical Data

Number Item UnitParameter

16KA 20KA

1 Rated voltage KV 12

2 Rated Current A 630

3 Frequency withstand voltageDry test KV 42

Wet test KV 30

4 Lightning impulse withstand voltage (peak) KV 75

5 Rated short-circuit breaking current KA 16 20

6 Rated short-circuit current (peak) KA 40 50

7 Rated peak withstand current KA 40 50

8 4s short-time withstand current KA 16 20

9 Rated operating sequence O-0.3s-CO-180s-CO

10 Rated short-circuit current breaking times Times 30

11 Mechanical life Times 10000

12 Energy storage motor rated voltage V AC/DC 110/220

13 Rated operating voltageTripping coil

V AC/DC 110/220Closing coil

14 Static and dynamic contact permissible wear thickness mm 3

15 Contact a distance mm 9±1

16 Contact overtravel mm 3+1 3.5±0.5

17 Average m/s 0.6±0.2

18 Average opening speed m/s 1.0±0.2 1.1±0.2

19 Bounce time ms ≤ 0.2

20 Three-phase gates and different points ms ≤ 2 ≤ 2

21 Closing time (with CT type spring operating mechanism) s ≤ 0.1

22Opening time (with CT typespring operating mechanism)

s≤ 0.06

≤ 0.1

23 DC resistance of each phase loop μΩ ≤ 200

24 White center distance (interrupter end) mm 193

interrupter is placed in the epoxy resin cast, the body shell is a metal box, this structure not only solve the condensation prob-lem, and is easy to get the insulation of interphase and to ground. The product served with reclosing controller to get recloser, be equipped with the subsection controller to sectionalizer,it is ideal distribution automation switch.

Page 4: HIGH VOLTAGE ELECTRICAL APPARATUS

-03-

ZW6-12 Series Outdoor Voltage Vacuum Circuit Breaker

Page 5: HIGH VOLTAGE ELECTRICAL APPARATUS

-04-

ZW8-12 Series Outdoor Voltage Vacuum Circuit Breaker

ZW8-12 series outdoor pole vacuum circuit breaker is rated voltage 12kV, three-phase AC 50Hz high voltage outdoor switch equipment, mainly for breaking and closing rural network, city network and small power system load current, overload current and short-circuit current. The three phase of this circuit breaker are hold in one box,The three-phase vacuum interrupter placed in a metal box, Use SMC insulation material, and insulation of

Description

main Technical Data

Number Item UnitParameter

6.3KA 12.5KA 20KA

1 Rated voltage KV 12

2 Maximum operating voltage KV 12

3 Rated Current A 630/1250

4 Rated short-circuit breaking current KA 6.3 12.5 20

5 Rated short-circuit current (peak) KA 16 31.5 50

6 Rated peak withstand current KA 16 31.5 50

7 4s short-time withstand current KA 6.3 12.5 20

8 Rated insulation levelPower frequency voltage rating

KV42

Impulse withstand voltage 75

9 Rated operating sequence O-0.3s-CO-180s-CO

10 Mechanical life Times 10000

11 Rated short circuit breaking current breaking times Times 30

12 Operating mechanism rated switch-on voltage V AC/DC 110/220

13 Operating mechanism rated gate voltage. V AC/DC 110/220

14 Contact a distance mm 11±1

15 Overtravel mm 3

16 The three-phase points, together different period ms ≤ 2

17 Contact closing bounce time ms ≤ 2

18 Average opening speed M/s 1.2±0.2

19 The average closing speed M/s 0.7±0.15

20 Opening timeMaximum operating voltage

s0.015-0.05

Minimum operating voltage 0.03-0.05

21 Closing time s 0.025-0.05

22 Each phase main circuit resistance μΩ ≤ 150

23Static and dynamic contact the permissible wear cumulative thickness

mm 3

interphase and to ground have reliable performance, have high dielectric strength. ZW8A-12 is a ZW8-12 circuit breaker com-bined with isolation touch knife, called the combination circuit breaker.

The actuator of the series circuit breaker is the CT23 type spring energy-storage operating mechanism, has electric type and manual type.

Page 6: HIGH VOLTAGE ELECTRICAL APPARATUS

-05-

ZW8-12 Series Outdoor Voltage Vacuum Circuit Breaker

Page 7: HIGH VOLTAGE ELECTRICAL APPARATUS

-06-

ZW10-12, ZW27-12 series outdoor high voltage vacuum circuit breaker

ZW10-12 ZW27-12 series outdoor AC high voltage vacuum circuit breaker is three-phase AC 50Hz outdoor high voltage switchgear, mainly used for electric power system of 10kV rural network and urban network for closing and breaking the load current, overload current and short-circuit current, can also be used in other similar Places. The circuit breaker can be equipped with isolation switch to be combination breaker.

Equipped with Controller to become reclosers.

To be distribution automation switches with FTU, RTU, can auto-matically clear and isolate fault, can automatically transfer power

■ The inside use the special anti-condensation measures toensure insulation of inside of box.

■ Transmission using patented technology, easy to install, reli-able action,avoid affecting the performance of the circuit

Description

Featuresbreaker due to mechanical failure;

■ No Oil-filled, no gas-filled, small size, light weight, CT pro-tection;

■ Breaking current, no pollution, free maintenance;

■ Operated by electric power or manual.

supply, automatically restore power. By telecontrol device, com-municating with DMS system of distribution management Center, has four remote control function. And combining with the power electronics PT to become circuit breaker with its own power supply, can achieve the nearest remote operation, surge delay, overcurrent delay and short circuit quick break protection.

Configured with Smart IC card prepaid distribution control box, can achieve no fee automatically power off, automatically restore electric power after payment, it can meet the demand of energy management reform of the power supply department.

main Technical DataNumber Item Unit Parameter

1 Rated voltage KV 12

2 Rated Current A 630/1250

3 Rated frequency Hz 50

4 Frequency withstand voltage KV 42/48

5 Lightning impulse voltage (peak) KV 75/85

6 Rated short-circuit breaking current KA 12.5 16 20/20 25

7 Rated short-circuit current (peak) KA 31.5 40 50/50 63

8 Rated short-time withstand current KA 12.5 16 20/20 25

9 Rated peak withstand current KA 31.5 40 50/50 63

10 Rated operating sequence O-0.3s-CO-180s-CO

11 Rated short-circuit current breaking times Times 30

12 Mechanical life Times 10000

13 Contact allow wear thickness mm 3

14Rated operating voltage(With CT type spring actuator)

Switch-on voltageV DC or AC 220V, 110V

Sub-gate voltage

15 Overcurrent tripping coil rated operating current A 5

16 Current transformer Times current ratio 5~1000/5

17Electrical energy storage

Rated voltage V DC or AC 220V, 110V

Power W ≤ 200

18 Weight Kg 150

Page 8: HIGH VOLTAGE ELECTRICAL APPARATUS

-07-

ZW10-12, ZW27-12 series outdoor high voltage vacuum circuit breaker

Page 9: HIGH VOLTAGE ELECTRICAL APPARATUS

-08-

ZW20G-12 Type Outdoor Vacuum Circuit Breaker

ZW20G-12 type outdoor pole vacuum circuit breaker (hereinaf-ter referred to as breaker) series is three-phase AC 50Hz, rated voltage 12kV outdoor switchgear, suitable for the urban and rural power grids, industrial and mining enterprises 10kV distribution system for breaking and closing load current and short circuit Current. Fully sealed box-type structure, SF6 gas is insulating medium, with excellent anti-condensation performance, espe-cially for frequent operation, the harsh environment of the place. The product can be used as pole breaker independently with function such as avoiding surge current, the over current delay, short-circuit quick break.

At the same time, this circuit breaker can be accompanied by related components to become products with other function:

■ Simple recloser: together with the simple reclosing controller,have the current three stage protection, three time reclosing,small current grounding protection, local remote control andother functions;

■ Easy sectionalizer: with simple segment controller to composesectionalizer, can be used in conjunction with the recloserto eliminate the impact of transient faults on the line, but alsoisolate permanent faults, and it can be self-powered.

Description■ Automatical Recloser: with automatic reclosing controller,

forming auto-recloser. “Commonly known as the watchdog,In addition to easy recloser function, it also has four remotefunctions, by means of wired, fiber-optic, microwave, carrier,radio and wireless communications to achieve, to meet therequirements of the automatical distribution. Self-powered orexternal power.

■ Multifunction recloser: together with the current-voltage com-posite controller to form multi-function recloser. In additionto the auto-recloser function, has a looped network powerdistribution, power measurement, the unilateral voltage delayclosing, after loss of voltage automatically breaking, bilateralvoltage, no closing, automatically restore the power supply ofnon-fault segment, automatically isolate fault segment.

■ Automatical electric power management device: with pre-paid energy meter metering equipments, to be composed toautomatic energy management device, to achieve automaticpower-off when arrearage.electric power is restored auto-matically after payment, it can meet the needs of the energymanagement of power supply department.

main Technical DataNumber Item Unit Numerical

1 Rated voltage KV 12

2 Rated frequency Hz 50

3 Rated Current A 630、1250

4 Rated short-circuit breaking current KA 12.5、16、20、25

5 Rated short-circuit current (peak) KA 31.5、40、50、63

6 Rated short-time withstand current (4s) KA 12.5、16、20、25

7 Rated short-circuit current (peak) KA 31.5、40、50、63

8 Mechanical life Times 10000

9 Rated short circuit breaking current breaking times Times 30

10Power frequency withstand voltage(1min): And phase to phase,to earth/across open contacts

KV 42/49

11Lightning impulse withstand voltage (peak) And phase to phase,to earth/across open contacts

KV 75/85

12 Times circuit 1min frequency voltage KV 2

13 Net weight kg 140

Page 10: HIGH VOLTAGE ELECTRICAL APPARATUS

-09-

ZW32-12 type outdoor high-voltage pole vacuum circuit breaker applies to the three-phase AC 50Hz, rated voltage 12kV and below the power transformer and distribution system. Widely applicable to the urban and rural power grid construction and renovation projects, industrial and mining enterprises and other

Descriptionpublic facilities, can be used as a power supply unit of the looped network and terminal equipment, can achieve the distribution of electrical energy, the control and protection of electrical equip-ment.

The product is small, light weight (less than 100kg), long life, safe and reliable. The operation, maintenance and installation is easy.

main Technical DataNumber Item Unit Parameter

1 Rated voltage KV 12

2 Rated Current A 630/1250

3 Rated frequency Hz 50

4 Rated short-time withstand current (4s) KA 20/25

5 Rated peak withstand current KA 50/63

6 Rated short-circuit current KA 50/63

7 Rated short-circuit breaking current KA 20/25/

8 Rated short-circuit current breaking times Times 30

9 1 min Power frequency withstand voltage KV 42/48

10 Lightning impulse withstand voltage KV 75/85

11 Mechanical life Times 10000

12 Rated operating voltage V DC(AC)220 110

ZW32-12 Series Outdoor High Voltage Vacuum Circuit Breaker

Page 11: HIGH VOLTAGE ELECTRICAL APPARATUS

-10-

ZW32-12/m Series Outdoor Pole Permanent Vacuum Breaker

ZW32-12/M-type outdoor high-voltage permanent vacuum cir-cuit breaker is rated voltage 12kV, three-phase AC 50Hz outdoor distribution equipment. Mainly used for breaking and closing power system load current, overload current and short-circuit current, applicable for the purposes of protection and control substation and industrial and mining enterprises in the power

■ Fully sealed structure: good sealing performance, help to im-prove the moisture-proof, anti-condensation performance,suitable for hot and humid regions, effectively avoid the me-chanical rust caused by the switch due to long-term outdoorenvironment. The overall structure is compact and reasonable,small size, light weight (less than 70kg).

■ Vacuum interrupter: breaking performance is stable and reli-able, contact wearing small, no flammable and no explosion

■ Technical parameters

Description

Structure and characteristics

distribution system, more suitable for rural power grids and fre-quent operation. Breakers comply with GB1984-2003 “AC high-voltage circuit breakers, the JB/T3855-2008 high-voltage AC vacuum circuit breaker DL/T403-2000 12-40.5KV high volt-age vacuum circuit breaker ordering technology standards, also in line with IEC56 requirements.

hazards, safe and reliable, maintenance-free.

■ Outdoor special epoxy alicyclic: enhanced the insulation sta-bility under wet conditions, anti-] erosion caused by ultravioletradiation and applicable to high, harsh operating conditionsand environment.

■ The breaker using permanent magnet operating mechanism,fewer parts, maintenance-free, mechanical life can reachmore than 30,000 times, high reliability.

The main Technical Parameters And mechanical Properties

Number Item Unit Parameter

1 Rated voltage KV 12

2 Rated Current A 630/1250

3 Rated short-circuit breaking current KA 20/25

4 Rated peak withstand current KA 50/63

5 4s thermal stability current KA 20/25

6 Rated short-circuit current (peak) KA 50/63

7 Rated short-circuit current breaking times Times 34

8 Mechanical life Times 20000

9 Rated operating sequence O-0.3s-CO-180s-CO

10Frequency withstand voltage (1 min)

Interphase and to ground KV 30(Wet)/42(Dry)

Across open contacts KV 42

11 Lightning impulse withstand voltage (peak)

Interphase and to ground KV 75

Across open contacts KV 75

12 Rated operating voltage V 220(AC、DC)

13 Net weight kg 70

Page 12: HIGH VOLTAGE ELECTRICAL APPARATUS

-11-

■ Mechanical properties

Number Item Unit Parameter

1 Distance between open contacts mm 9±1

2 Contacting over travel mm 3±0.5

3 Center distance of phase mm 240

4 Average opening speed M/s 1±0.2

5 The average closing speed M/s 0.6±0.2

6 Opening time ms 25~45

7 Closing time ms 35~55

8 Bounce time when closing ms ≤ 2

9 The rebound amplitude when opening mm ≤ 2

10 Asynchronous time when three phase opening/closing ms ≤ 2

11 Main circuit resistance μΩ ≤ 60

ZW32-12/m Series Outdoor Pole Permanent Vacuum Breaker

Page 13: HIGH VOLTAGE ELECTRICAL APPARATUS

-12-

ZW7(A)-40.5, ZW17-40.5 Series Outdoor High-Voltage Vacuum Circuit Breaker

ZW7(A)-40.5 series outdoor high-voltage vacuum circuit Breaker is an outdoor three-phase switch equipment with 40.5KV voltage and 50Hz AC. The breaker is mainly used to control the loading current, overloading current and short circuit current. The 40.5KV power system can be used as power plants, substations, power

Descriptionequipment and power lines to control and protect equipments. In each box, there is a LZZBJ4 type current transformer(CT). Every CT has four windings to measure and protect. The breaker has good seismic capacity, small size, simple structure, easy opera-tion, good breaking performance and high reliability.

main Technical DataNumber Item Unit Parameter

1 Rated voltage KV 40.5

2

Rated insulation level

1min power frequency withstand

Dry testKV

95

Wet test 80

Lightning impulse voltage (peak) KV 185

3 Rated Current A 630 1250 1600 2000

4 Rated short-circuit breaking current KA 20 25 31.5

5 Rated short-circuit current breaking times Times 20

6 Rated operating sequence Times O-0.3s-CO-180s-CO

7 Rated short-circuit current (peak) KA50 63 80

8 Rated peak withstand current KA

9 Rated short-time withstand current KA 20 25 31.5

10 Rated short duration s 4

11 Rated operating voltage V 220(DC、AC)

12 Closing time ms 60 ≤ t ≤ 120

13 Opening time ms 35 ≤ t ≤ 80

14 The average closing speed M/s 0.6±0.2

15 Average opening speed M/s 1.6±0.2

16 Opening asynchronous time ms ≤ 2

17 Contact closing bounce time ms ≤ 3

18 Mechanical life Times 10000

19 Loop resistance of each pole μΩ ≤ 150

20 White center distance mm 710 ±1

Page 14: HIGH VOLTAGE ELECTRICAL APPARATUS

-13-

ZW7(A)-40.5, ZW17-40.5 Series Outdoor High-Voltage Vacuum Circuit Breaker

Page 15: HIGH VOLTAGE ELECTRICAL APPARATUS

-14-

ZN28-12 Series Indoor High Voltage Vacuum Circuit Breaker

ZN28-12 series indoor high voltage vacuum circuit breaker is an indoor three-phase switch equipment with 10KV voltage and 50Hz AC. The breaker is mainly installed in closed metal box. The breaker can be operated frequently and used in industrial and mining enterprises, power plants and substations to control and

Descriptionprotect the equipments.

This model of vacuum circuit breaker is standardized with the GB1984 “AC high voltage circuit breaker”, the JB3855 “high voltage AC vacuum circuit breaker” And the DL/T403 “12-40.5KV high voltage circuit breaker”.

main Technical DataNumber Item Unit Parameter

1 Rated voltage KV 12 12 12 12

2 Rated Current A630,1000

1250630,1250

16001250,1600

20002000,2500

3150

3 Rated short-circuit breaking current KA 20 25 31.5 40

4 Rated short-circuit current KA 50 63 80 100

5 Rated dynamic current KA 50 63 80 100

6 Rated thermal current KA 20 25 31.5 40

7 The rated thermal stability time s 4 4 4 4

8Rated short circuit breakingCurrent breaking times

Times 50 50 50 50

9 Rated operating sequence O-0.3s-CO-180s-CO

10 1minl frequency withstand voltage (rms) KV 42 42 42 42

11 Lightning impulse voltage KV 75 75 75 75

12 Mechanical life Times 10000 10000 10000 10000

Page 16: HIGH VOLTAGE ELECTRICAL APPARATUS

-15-

ZN28A-12 series indoor high voltage vacuum circuit breaker is an indoor three-phase switch equipment with 10KV voltage and 50Hz AC. The breaker is mainly installed in closed metal box. The breaker can be operated frequently and used in industrial and mining enterprises, power plants and substations to control and

Descriptionprotect the equipments.

This model of vacuum circuit breaker is standardized with the GB1984 “AC high voltage circuit breaker”, the JB3855 “3.5-40.5KV high voltage AC vacuum circuit breaker” And the DL/T403 “10-35KV high voltage circuit breaker”.

ZN28A-12 Series Indoor High Voltage Vacuum Circuit Breaker

main Technical DataNumber Item Unit Parameter

1 Rated voltage KV 12 12 12 12

2 Rated Current A 630,1000,1250 630,1250,1600 1250,1600,2000 2000,2500,3150

3 Rated short-circuit breaking current KA 20 25 31.5 40

4 Rated short-circuit current KA 50 63 80 100

5 Rated dynamic current KA 50 63 80 100

6 Rated thermal current KA 20 25 31.5 40

7 The rated thermal stability time s 4 4 4 4

8Rated short circuit breakingCurrent breaking times

Times 50 50 50 50

9 Rated operating sequence O-0.3s-CO-180s-CO

10 1minl power frequency withstand voltage (rms) KV 42 42 42 42

11 Lightning impulse voltage KV 75 75 75 75

12 Mechanical life Times 10000 10000 10000 10000

Page 17: HIGH VOLTAGE ELECTRICAL APPARATUS

-16-

ZN63A(VS1)-12 Series Indoor High Voltage Vacuum Circuit Breaker

ZN63A(VS1)-12 series indoor high voltage vacuum circuit breaker is an indoor three-phase switch equipment with 12KV voltage and 50Hz AC. The breaker can be operated frequently and used in industrial and mining enterprises, power plants and substations to control and protect the equipments. This model of

Descriptionvacuum circuit breaker is standardized with the GB1984 “AC high voltage circuit breaker”.

The breaker can work with the spring operation mechanism or permanent operating mechanism as the permanent vacuum cir-cuit breaker.

main Technical DataNumber Item Unit Parameter

1 Rated voltage KV 12

2 Rated insulation level

1min power frequency withstandKV

42

Rated lightning impulse withstand voltage 75

3 Rated Current A 630,1250,1600,2000

4 Rated short-circuit breaking current KA 20,25,31.5,40

5 Rated short-circuit current KA 50,63,80,100

6 Rated peak withstand current KA 50,63,80,100

7 Rated short-time withstand current (rms) KA 20、25、31.5、40

8 Rated short-circuit current breaking times Times 50

9 Rated short duration s 4

10 Rated operating sequence A O-0.3s-CO-180s-CO

11 Mechanical life Times 20000

12 Rated single capacitor bank breaking current 630

13 Rated back-to-back capacitor bank breaking current 400

Number Item Unit Parameter

1 Distance between open contactsmm

11±1

2 Contacting over travel 3 ± 0.5

3 Asynchronous time when three phase opening/closingms

≤ 2

4 Bounce time when closing ≤ 2

5 Center distance of phase mm 210±1.5(275±1.5)

6 The closing contact pressure N 3200±100

7 Average opening speed M/s 0.9~1.2

8 The average closing speed m/s 0.55 ~0.8

9 Opening time ms 20~50

10 Closing time ms 35~70

11Static and dynamic contact cumulative permissible wear thickness

mm 3

Page 18: HIGH VOLTAGE ELECTRICAL APPARATUS

-17-

ZN63A(VS1)-12 Series Indoor High Voltage Vacuum Circuit Breaker

Page 19: HIGH VOLTAGE ELECTRICAL APPARATUS

-18-

ZN63G-24(VS1-24)Series Indoor High Voltage Vacuum Circuit Breaker

ZN63G-24(VS1-24) series indoor high voltage vacuum circuit breaker is an indoor high voltage switch equipment with 24KV voltage and 50Hz AC. The breaker can be used in industrial and mining enterprises, power plants and substations to control and protect the equipments. The breaker is especially suitable in the places which need frequent operation and repeated important loading breaking under rated operating current.

The breaker has an integrated design of the actuator and breaker body. It has a bomb operating agency so that the breaker can work with AC and DC current to store energy or work by hand. The reliable interlock function of breaker not only can be the unit

Descriptionof a fixed installation, but also can be the mid-mounted handcart unit equipped with chassis. The fixed circuit breaker can add a special interlock to meet the XGN2. GG1A fixed cabinet’s need. What’s more, when the breaker works with a permanent magnet actuator, the mechanical life can be 1 million times. The breaker can be used with the 24KV system in the altitude less than 1000m, and with 12KV system in the altitude less than 4000m.

This model of vacuum circuit breaker is standardized with the GB1984 “AC high voltage circuit breaker”, the JB3855 “high voltage AC vacuum circuit breaker”, the DL/T403 “12-40.5KV high voltage circuit breaker” And IEC60056.

main Technical DataNumber Item Unit Parameter

1 Rated voltage

KV

24

2 Rated insulation level

Power frequency withstand voltage (1min) 65

Lightning impulse withstand voltage (peak) 125

3 Rated frequency Hz 50

4 Rated Current A 6301250

6301250

63012501600200025003150

125016002000250031504000*

125016002000250031504000*

5 Rated short-circuit breaking currentKA

20 25 31.5 40 50

6 Rated short-time withstand current 20 25 31.5 40 50

7 Rated short duration s 4

8 Rated peak withstand currentKA

50 63 80 100 125

9 Rated short-circuit current 50 63 80 100 125

10 Rated current breaking timesTimes

20000(50KA 10000 times)

11 Rated short-circuit breaking times 50(40KA 30 times,50KA 20 times)

12 Times circuit frequency withstand voltage (1min) V 2000

13 Leading electrical circuit resistance μΩ≤ 80(630A) ≤ 60(1250A) ≤ 40(1600~2000A

≤ 25(2500A above)

14 Rated single/back-to-back capacitor bank breaking current A 630/400(40KA 800/400)

15 The nominal capacitor bank closing surge KA 12.5(Frequency no greater than 1000Hz)

Page 20: HIGH VOLTAGE ELECTRICAL APPARATUS

-19-

ZN23-40.5C series indoor handcart vacuum circuit breaker is an indoor high voltage equipment with 40.5KV voltage and 50Hz AC. The breaker can be used in industrial and mining enterprises to control and protect the switch. The breaker is specialized in

Descriptioncontrolling and protecting the equipments in frequent operation metallurgy and arc steelmaking.

This model of vacuum circuit breaker is standardized with the GB1984 “AC high voltage circuit breaker”.

main Technical DataNumber Item Unit Parameter

1 Rated voltage KV 40.5

2 Lightning impulse withstand voltage (peak) KV 185

3 1min power frequency withstand voltage KV 95

4 Rated frequency Hz 50

5 Rated Current A 630,1250,1600,2000

6 Rated short-circuit breaking current KA 25

7 Rated short-time withstand current KA 25

8 Rated peak withstand current KA 80

9 Rated short duration S 4

10 Rated short-circuit current KA 80

11 Rated operating sequence O-0.3s-CO-180s-CO

12 Closing time ms 50-85

13 Opening time ms 40-85

14 Rated short circuit breaking current breaking times Times 20

15 Mechanical life Times 12000

16 The nominal capacitor bank breaking current A 630

17 Energy storage motor rated power W 275

18 Rated voltage of the energy storage motor V 220,110

19 Storage time S 15

20 Opening and closing electromagnets rated voltage V 220,110(AC,DC)

21 Rated voltage of under-votage trip V 220,110(AC,DC)

22 Rated voltage of the over-current trip A 5

23 Auxiliary switch rated current A 10

ZN23-40.5C Series Indoor Handcart Vacuum Circuit Breaker

ZN23-40.5C/1600-25 series of indoor

handcart Overall schematic diagram

of the vacuum circuit breaker

Page 21: HIGH VOLTAGE ELECTRICAL APPARATUS

-20-

ZN39-40.5C Series Indoor High Voltage Vacuum Circuit Breaker

ZN39-40.5C series indoor high voltage vacuum circuit breaker is an indoor high voltage equipment with 40.5KV voltage and 50Hz AC. The breaker can work with the JYN1-35/GBC-35 switch cabinet. It can be operated frequently and used in power plants and substations to control and protect the equipments.

■ Altitude: ≤ 1000m;

■ The ambient temperature: -10~ +40 ℃ ,

■ Relative humidity (daily average): ≤ 95%, (monthly average)≤ 90%;

Description

Normal Conditions Of Use

This handcart type vacuum circuit breaker has reasonable struc-ture, easy maintenance and high reliability. The breaker can be used with the CD10-11 permanent operating mechanism or CT19-11 spring operating mechanism.

■ Water vapor pressure(daily average): ≤ 2.2kpa, (monthly av-erage) ≤ 1.8kpa;

■ Place without Fire, explosion, heavy pollution, chemical corro-sion and violent Vibration.

main Technical DataNumber Item Unit Parameter

1 Rated voltage KV 40.5

2 Rated frequency Hz 50

3 Rated power frequency withstand voltage (1min)KV

95

4 Rated lightning impulse withstand voltage (peak) 185

5 Rated Current

KA

1250/1600

6 Rated short-circuit breaking current 20 25

7 Rated short-circuit current (peak) 50 63

8 Rated short-time withstand current 20 25

9 Rated peak withstand current 50 63

10 Rated short duration S 4

11 Rated short circuit breaking current breaking timesTimes

8

12 Mechanical life 10000

13 Closing timems

≤ 100

14 Opening time ≤ 60

15 Dimensions (W × D × H) mm 1180×1414×1728

16 Weight kg 500

Page 22: HIGH VOLTAGE ELECTRICAL APPARATUS

-21-

ZN39-40.5C Series Indoor High Voltage Vacuum Circuit Breaker

Page 23: HIGH VOLTAGE ELECTRICAL APPARATUS

-22-

ZN85-40.5 Series Indoor High Voltage Vacuum Circuit Breaker

ZN85-40.5 type indoor high voltage vacuum circuit breaker is appropriate to 40.5kv, 50Hz three phase indoor system, equipped with 3AV3 spring mechanism circuit breaker which can be used for KYN1-40.5 withdraw metal enclosed switch cabinet and KYN61-40.5 armored metal enclosed switch cabinet. Now ZN85-40.5 is current optimal product for 40.5 system.

As this series product with the strength of high technical pa-rameters, strong breaking capacity, reliable action, stable per-formance, long life, convenient maintain, and being free from explosion and pollution, apply to the power plant, substation and

■ The ambient temperature: -10 ~ +40 ℃

■ Altitude: ≤ 1000m;

■ Relative humidity (daily average): ≤ 95%, (monthly average)≤ 90%; (+25℃ )

Z N 85 - 40.5(Z) / □ - □

Description

Environmental Functions And Conditions

model meaning

other power supply and distribution equipment as the electri-cal protective and control device, and frequently operation, also adaptable for the special occasions, such as on-off switching operation capacitor bank.

Circuit breaker using integration and modular design, the whole structure is simple and reasonable. Taking up and down layout, parts of interrupter on the top, and interlock and operation mech-anism in the bottom. It uses dedicated 3AV3 spring mechanism, no need to adjust, action stable and reliable. Interrupter is ar-ranged in a closed insulated barrel, which improve the insulation performance and reduced the overall size.

■ Saturated vapor pressure (daily average): ≤ 2.2×10-3MPa,(monthly average) ≤ 1.8×10-3MPa;

■ The seismic intensity ≤ 8 ;

■ Place without Fire, explosion, heavy pollution, chemical corro-sion and violent Vibration.

Rated short-circuit breaking current(kA)

Rated Current(A)

Rated voltage(kV)

Design number

Indoor

Vacuum breaker

Page 24: HIGH VOLTAGE ELECTRICAL APPARATUS

-23-

■ Updating conductive rod design to ensure that the porcelainwithout crack

■ Improve protection function: over-current delay protection,short-circuit instantaneous trip protection, under-voltageprotection;

■ Increase the types of transformers, single protect the trans-

Descriptionformer which can make Times transformer either measure or protect,which can save power station investment cost

■ Increase the apparent fracture operation with anti mistakenlyinterlock;

■ Using Pressure-sensitive components, the data of pressurecan be read remotely

LW3-12(D) I II III Series Outdoor High Voltage SF6 Circuit Breaker

main Technical DataNumber Item Unit Parameter

1 Rated voltage KV 122 Max working voltage KV 12

3Rated insulation level (when the breaker charge SF6 gas with pressure of 0.2MPa, 20 ℃ )

Lightning impulse withstand voltage (full-wave)KV

751min power frequency withstand voltage 42Withstand voltage during raining 34

4 Insulation level under zero gauge pressure (maximum phase voltage 5min) KV 95 Rated Current A 400 6306 Rated short-circuit breaking current KA 6.3 8 12.5 7 Breaking current under zero gauge pressure A 400 6308 Rated short-circuit current breaking times Times 20

9Rated operating sequence

I Type O-180S-CO-180S-COII Type O-0.5S-CO-180S-CO

10 Rated making current (peak) KA 16 20 31.511 Rated dynamic current (peak) given KA 16 20 31.512 The rated thermal stability time S 413 Rated thermal current KA 6.3 20 12.514 Inherent closing time I Type S ≤ 0.06

15 Inherent opening timeII Type

S≤ 0.06

III Type ≤ 0.0416 Rated working pressure MPa 0.3517 Minimum working pressure MPa 0.2518 Annual leakage rate % ≤ 119 Mechanical life Times 2000

20 WeightI Type

Kg122

II Type 130

Page 25: HIGH VOLTAGE ELECTRICAL APPARATUS

-24-

LW8-40.5 Series Of Sulfur Hexafluoride Circuit Breaker

LW8-40.5 series is a kind of three-phase AC 50HZ OUTDOOR HV electrical equipments. It is used for controlling and protect-ing 40.5kv transmission and distribution systems. It can also be used for network interconnecting breaker and switching capaci-tor bank. The breaker has an excellent break performance, air-pressure explosion chamber and long electricity life. On the rated voltage, after continuously break 40kv short circuit current up to 21 times, it will not have to be overhauled and exchange its sulfur hexafluoride gas. High mechanical reliability makes its

■ Altitude: ≤ 1000m; 2000m;3000m;

■ Ambient temperature: -30℃ ~+40℃ ;

■ Pollution level: II、III、IV.

Description

Environmental Conditions

mechanical life longer more than 3000 times. So, it can frequently operate. Each can install 12 current transformer to be choices for user. Using new MKZ SF6 pointer density meter, pressure meter reading will not be influenced by temperature variation. It is convenient to use. This product also match with CT14 spring mechanism.

Circuit breaker is divided into ground tank and porcelain column type. porcelain column is also divided into parallel layout and high frame T type(Centrally-mounted type).

main Technical DataNumber Item Unit Parameter

1 Rated voltage KV 40.5

2 Rated Current A 1600/2000

3 Rated short-circuit breaking current KA 20/25

4 Rated out breaking current KA 5/6.3

5 Rated single capacitor bank breaking current A 400

6 Rated operating sequence O- 0.3S-CO-180S-CO

7 Rated pressure of SF6 gas MPa 0.45

8 Opening time ms 55 ≤ t 分≤ 65

9 Closing time ms 60 ≤ t 分≤ 100

10 Closing speed m/s 3.2± 0.2

11 Opening speed m/s 3.4±0.2

12 Weight kg 1000

Page 26: HIGH VOLTAGE ELECTRICAL APPARATUS

-25-

LW8-40.5 Series Of Sulfur Hexafluoride Circuit Breaker

Page 27: HIGH VOLTAGE ELECTRICAL APPARATUS

-26-

LW36 □ -126 Series Of Sulfur Hexafluoride Circuit Breaker

LW36 □ -126 intelligent high-pressure sulfur hexafluoride cir-cuit Breaker is a kind of outdoor products. Applied to the altitude not more than 3000m, the ambient temperature is not lower than -30 ℃ , Pollution level no higher than Class IV regional AC 50Hzmaximum voltage is 126kV grid to cut the rated current, fault cur-rent, or convert lines, so that can realize power system controland protection, Also can be used as a tie circuit breaker

■ The circuit breaker is an outdoor three phase live tank Singlefracture structure, three phases use one classi together, andmatch with a spring operating mechanism, three-phase ismechanical linkage. Inside Three-phase Porcelain column,there is SF6 gas connected, the adoption of temperaturecompensation of SF6 gas density control condition monitoring

■ Arc extinguish chamber adopts thermal expansion and auxil-iary compressor intelligent arcing technology, excellent breakperformance, and long electricity life. Rated short-breakingcurrent 40KA, total breaking times more than 20.

■ Circuit breaker in the sports system optimization design, there-fore, effectively improve the efficiency of movement, maximumlimit reduces the operators, and improve the reliability of themovement, match with new spring Operating mechanism withthe characteristic of low operating power, low noise, reliablemechanical behavior, it is suit for frequent operation.

■ High insulation lever, external insulation for large creepage

Description

Characteristic

The product as the arc and insulation medium SF6 gas, using the most advanced intelligent interrupter technology with new spring mechanism, with electric long life operation of small power, low noise, high reliability,competitive price, In the present electric power equipment tend to no oil change, large capacity in the process, which can fully replace imported products of the same type

distance design, specific creepage distance ≥ 31mm/KV, excellent resistance to impurity excellently, strong aseismatic ability, it is suit for bad environment of home and abroad and altitude not more than 3000m

■ Strong current-Carrying Capability: according to rated current1.2 time 3150A(3780A temperature rise test), there are still largemargin in each point temperature rise there are still large margin.

■ Installation classi and brace made of Thick steel plate overallbending, the surface treatment adopts hot galvanizing, all fas-teners uses the material of high stength stainless steel,Three-phase rotation connecting rod also use high strength stainlesssteel. Dacromet process the surface of the main parts of thehouse and soft ammonia treatment process, the institutionsmechanism made of stainless steel, to improve the corrosionresistance.

■ Product overall appearance bright and neat, structure com-pact, light and handy, field installation debugs conveniently

Page 28: HIGH VOLTAGE ELECTRICAL APPARATUS

-27-

LW36 □ -126 Series Of Sulfur Hexafluoride Circuit Breaker

main Technical DataNumber Item Unit Parameter

1 Rated voltage KV 126

2Rated power frequency withstand voltage (1min)

To earthKV

230

Across open contacts 230+73

3Rated lightning impulse withstand voltage

To earthKV

550

Across open contacts 550+103

4Frequency withstand voltage at SF6 zero gauge pressure (5min)

KV 95

5 Rated frequency Hz 50

6 Rated Current A 3150

7 First pole-to-clear factor 1.5

8 Rated short-circuit breaking current KA 40

9 Rated short circuit making current KA 100

10 Rated short - time withstand current KA 40

11 Rated peak withstand current KA 100

12 Rated Short-circuit Continuing Time S 4

13 Rated out of phase breaking current KA 10

14 Short-line fault breaking current KA 90%1k, 75%1K

15 Rated line-charging making current A 31.5

16 Rated operating sequence O-0.3S-CO-180-CO

17 Main circuit resistance μΩ ≤ 35

18 Rated SF6 pressure (20℃ gage pressure) MPa 0 6

19 Alarm/lock pressure(20℃ gage pressure) MPa 0 55±0.015/0.50±0 015

20 Annual leakage rate of SF6 gas ≤ 1

21 Gas moisture content ppm ≤ 150×10-6

22 Machinery life time 3000

23 Radio interference level μV v ≤ 500

24 Creepage distanceAcross the isolating distance mm ≥ 3150(3910)

To earthing mm ≥ 3150(3910)

25 Filling SF6 Gas quality for each kg 10

26 CB quality for each kg 1500

Page 29: HIGH VOLTAGE ELECTRICAL APPARATUS

-28-

FN12-12 Series Indoor High Voltage Load Switch And Fuse combination units

The composite apparatus of FN12-12(D) and FN12-12(RD) is three-phase high-voltage switchgear with rated voltage 12kv,rated frequency 50HZ,applying to separate and close load current,closed-loop current,charging current of noload trans-

Descriptionformer and cable,to close the short circuit current and assem-bling equip load switch of grounding switch.It can bear short circuit current.It is mainly applied as loading control and short circuit protection in downtown distribution station of three-phase rig net or terminal power supply and industrial consumer.

FN 12 - 12 / 630 - 20 - □ □ FRN 12 - 12 / 125 - 315 - □ □

model meaning

Earthing switch

Mechanical form: S by hand, D Motors

Rated thermal current (kA)

Rated active load current (A)

Rated voltage (kV)

Design number

Indoor AC HV load switch

Earthing switch

Mechanical form: S by hand, D Motors

Rated short circuit breaking current (kA)

Rated Current (A)

Rated voltage (kV)

Design number

Indoor AC HV load switch and fuse-combination

Technical ParametersNumber Item Unit FN12-12/630 FN12-12/125-31.5

1 Rated voltage KV 12

2 Rated frequency Hz 50

3 Rated Current A 630 125

4 Lightning impulse withstand voltage KV To earth and phase to phase75 across open contact 85

5 1min power frequency withstand voltage KV To earth and phase to phase42 across open contact 48

6 Rated thermal current KA 20(4S)

7 Rated dynamic current KA 50

8 Rated closed current (peak) KA 50

9 Rated short-circuit breaking current (predictive value) KA 31.5

10 Rated transfer current KA 1.5

11 Breaking no-load transformer capacity KVA 1250

12 Rated cable charging current A 10

13 Rated active load current breaking times Times 10000

14 reaking times of striker with load-switch S <0.06

15 Earth switch thermostabilization current KA 20(2S)

16 Earth switch thermostabilization current (peak) KA 50

17 Source voltage AC and DC100、220

Page 30: HIGH VOLTAGE ELECTRICAL APPARATUS

-29-

FZN25-12D/T630-20 indoors a.c. high voltage vacuum load switch applicate to three phase ac 50Hz, the 12kV electrical power distribution system, as the achievement opens breaks us-ing of the load current , the product does not have the oil, non-toxic, does not have and the explosion hazard, widespread use to industry and mining enterprise and city building Power plant and so on.

DescriptionFZ(R)N21-12 (D of of) the /T125-31.5 indoors a.c. high volt-age vacuum load switch - fuse combination electric appliance (abbreviation “combines electric appliance”) to be suitable to exchanges 50Hz, in the rated voltage 12kV electrical power sys-tem, the achievement opens breaks using of the load current, the excess current and the short-circuit current, specially is suitable to does not have the oiling, does not overhaul and the frequent operation and the ring net power supply unit and the terminal power supply transformer controls and protects the place.

FZN21-12(D)/T630-20·FZRN21-12(D)/T125-31.5 Type Indoor High Voltage Vacuum Load Switch-Fuse Combinations

main Technical Data

Number Item Unit Parameter

1 Rated voltage KV 12

2 Rated frequency Hz 50

3 The fuse maximum rated current A 125

4 Rated transfer current A 3150

5 Rated short circuit breaking current (expected current effective value) KA 31.5

6 Rated short-circuit current (expected peak current) KA 80

7 1min power frequency withstand voltage; to earth and phase to phase/across open contacts KV 42 48

8 Lightning impulse withstand voltage; to earth and phase to phase/across open contacts KV 75 85

9 Fuse impactor output energy J 2~5

Number Item Unit Parameter

1 Rated voltage KV 12

2 Rated Current A 630

3 Rated frequency Hz 50

4 Rated active load breaking current A 630

5 Breaking current Rated closed A 630

6 5% of rated power load breaking current A 31.5

7 Rated current charging breaking current A 10

8 Rated load transformer breaking current A 1250kVA transformer no-load current

9 1min power frequency withstand voltage;to earth and phase to phase/across open contacts KV 42

10 Lightning impulse withstand voltage;to earth and phase to phase/across open contacts KV 75

11 Rated short-time withstand current / time KA/S 20/4

12 Rated peak withstand current KA 50

13 Rated short-circuit current (peak) KA 50

14 Mechanical life Times 10000

15 Contact permissible wear cumulative thickness mm 2

16 The OC operation torque N-mm ≤ 200

■ Combination of electrical technology parameters

■ Technical parameters of the vacuum load switch

Page 31: HIGH VOLTAGE ELECTRICAL APPARATUS

-30-

Number Item Unit Parameter

1 Rated distance between open contact mm 10±1

2 Connection stroke contacting over travel mm 4±1

3 Closing speed m/s 0.6±0.2

4 Opening speed m/s 1.1±0.2

5 Simultaneity ms ≤ 2

6 Bounce ms ≤ 2

7 Distance between phases mm ≥ 125

8 Main circuit resistance μΩ ≤ 70

■ Technical parameters of the mechanical properties

FZN21-12(D)/T630-20·FZRN21-12(D)/T125-31.5 Type Indoor High Voltage Vacuum Load Switch-Fuse Combinations

Page 32: HIGH VOLTAGE ELECTRICAL APPARATUS

-31-

FZN25-12(D)/T630-20·FZRN25-12(D)/T200-31.5 Series Indoor High Voltage Vacuum Load Switch-Fuse Combinations

FZN25-12D/T630-20 AC high voltage load switch is indoor de-vice with three-phase AC 50Hz, rated voltage 12kV. Can be ap-plied to as protection and control of the electrical facilities in such occasions as industrial and mining enterprises and distribution substations, for breaking and closing load current, closed-loop current, no-load transformer and cable charging current.

With manual and motor operating mechanism to facilitate the realization of the three remote control requirements of the power system.

FZRN25-12D/T125-31.5 AC high voltage vacuum load switch fuse combinations appliances with three phase AC 50Hz, rated voltage 12kV indoor unit, suitable for industrial and mining en-

Descriptionterprises distribution substations and other occasions, for load control and short-circuit protection purposes. Equipped with grounding switch can withstand short-circuit current. The oper-ating mechanism of manual and power-driven are available, to facilitate the realization of the three remote control requirements of the power system.

FZN25-12D、FZRN25-12D type load switch and combination units are suitable for city distribution and industrial equipment of three-phase ring or terminal power supply for load control and short-circuit protection. As combined appliances are more reliable and economical than circuit breakers in protecting the transformer units, it is especially suitable for the ring network, dual the radiated power supply unit and the cabinet-typed sub-station.

main Technical Data

Number Item UnitParameter

FZN25-12D/T630-20 FZN25-12D/T200-31.5

1 Rated voltage KV 12

2 Rated frequency Hz 50

3 Rated Current A 630 200

4Rated insulation level

1min power frequency withstand voltage (rms)

KVInterrupter across open contacts 30

To earth phase to phase 42 isolated across open contacts 48

Lightning impulse withstand voltage (rms) To earthphase to phase 75 isolated across open contacts 85

5 Rated current (peak) KA 50 -

6 The 4s stable current KA 20 -

7 Rated active load breaking current A 630 -

8 Rated closed loop breaking current A 630 -

9 Rated cable charging breaking current A 10 -

10 Breaking unload transformer capacity KV/A 1250 31.5

11 Rated transfer current A - 2000

12 Fuse model -SDLAJ-12SFLAJ-12

13 Impactor output energy J 2-5(Moderate)

14 Rated short-circuit current KA 50

15 Earthing switch Rated dynamic current KA 50

16 The grounding switches 2s thermal stability current KA 20

17 Rated voltage of auxiliary circuit V 220 110

18 Mechanical life Times 10000

Page 33: HIGH VOLTAGE ELECTRICAL APPARATUS

-32-

Number Item UnitParameter

FZN25-12D/T630-20 FZRN25-12D/T200-31.5

1 Charged body and the air-to-ground distance mm ≥ 125

2 Depth of electric conduction tin inserted to static contact mm ≮ 125

3 The vacuum interrupter room open distance mm 6

4 The vacuum interrupter room pressure spring shrinkage mm 2

5 The vacuum interrupter average closing speed m/s 0.6±0.1

6 The vacuum interrupter average opening speed m/s 1.0±0.1

7 Opening bounce time ms ≤ 2

8 Opening and Closing simultaneity ms ≤ 3

9 Loop resistance μΩ ≤ 150 ≤ 300

10 Maximum torque of manual operation Nm ≤ 160

11 Fuse triggered Opening time ms 30~40

12 Release triggered Opening time ms 40~50

Model Rated voltage(V) Rated Current(A) Rated power(W) Normal operating voltage range

66ZY-CJ01B DC220 0.770

85%~110%

66ZY-CJ02B DC110 1.5 Rated voltage

■ Mechanical properties parameters

■ Storage of motor parameters

FZN25-12(D)/T630-20·FZRN25-12(D)/T200-31.5 Series Indoor High Voltage Vacuum Load Switch-Fuse Combinations

Page 34: HIGH VOLTAGE ELECTRICAL APPARATUS

-33-

FZW20-12 Series Outdoor Ac High Voltage Isolation Vacuum Load Switch

FZW20-12/T630A-20 type outdoor AC high voltage vacuum iso-lation load switch with rated voltage of 12kV, rated current 630A, rated frequency of 50Hz, can break and close load current, can also break the no-load current of the transformer,the capaci-

Descriptiontance current of overhead lines of certain distance, cable lines and the condenser bank.

With segment, isolation, connection, switching and protection functions, it can be applied to overhead distribution lines of urban and rural power, railways, petrifaction, etc.

main Technical DataNumber Item Unit Parameter

1 Rated voltage KV 12

2 Rated Current A 630

3 Rated frequency Hz 50

4 Rated active load breaking current A 630

5 Rated closed loop breaking current A 630

6 Rated cable charging breaking current A 10

7Rated power frequency withstand voltage interrupter/isolation opening contact KV 42/48

Rated lighting impulse withstand voltage interrupter/isolation opening contact KV 75/85

8 Rated short-time withstand current KA 16(20)

9 Rated short circuit duration S 4

10 Rated peak withstand current KA 40(50)

11 Rated short-circuit closing current KA 40(50)

12 Mechanical life Times 10000

13 Interrupter opening distance mm 7±1

14 Interrupter over travel mm 3±0.5

15 Average closing speed (Interrupter) m/s 0.7±0.3

16 Average opening speed (Interrupter) m/s 1.1±0.3

17 Three-phase closing simultaneity ms ≤ 5

18 Interrupter rated contact pressure N 800±100

19 Interrupter contacts bounce when closing ms ≤ 3

20 Isolation fracture opening distance mm 200

21 Main circuit resistance μΩ ≤ 200

22 Power supply voltage of the electric operating mechanism V 100V、220V(DC,AC)

23 Weight kg 95

Page 35: HIGH VOLTAGE ELECTRICAL APPARATUS

-34-

FZW20-12 Series Outdoor Ac High Voltage Isolation Vacuum Load Switch

■ A new generation of outdoor pole mounted load switch ,re-cently developed by our company

■ Adopted vacuum arc extinguish chamber to extinguish arc,free from fire and explosion hazards, without repair;

■ Has obvious fracture in the state of opening. Isolation bladelinked with the three-phase vacuum arc extinguish chamber.By operating time programmed fit, vacuum arc extinguishchamber blowout, while isolation blade does not start arc inbreaking and closing process, to complete the electrical com-bination function.

■ Full-open style. Vacuum arc extinguish chamber covered with

Featurehigh insulating Silastic, without being sealed, oil filled, or in-flated;

■ Can be applied in combination with fuse;

■ Mainly vertically mounted, can be also horizontally mounted,manual and electric operation. Operating mechanism is inte-grated with switch body;

■ User friendly, single handle operation (combined breaking andclosing function);

■ In combined with the automatic controller, composed of thedistribution automation section breaker.

Page 36: HIGH VOLTAGE ELECTRICAL APPARATUS

-35-

FZW36-40.5/D1250-20 type outdoor high-voltage vacuum isolation load switch (hereinafter referred to as load switch) is a three-phase AC 50Hz, rated voltage of 40.5kV outdoor high voltage switchgear, for breaking and closing load current or fuse breaking transfer current of urban or rural distribution system. Together with the motor mechanism and controller can be used

The product is three-phase integrated pole mounted switch, with operation mechanism, being associated with the switch to a unity, mounted on the end surface of the switch base. Normally electric operating switch through cabinet, which is installed on the ce-ment pole vertically 1.5 m away from the ground. It is convenient to operate on site. The control box is connected to the mecha-nism box by cable through the air outlet. Each phase of switch has a vacuum arc extinguish chamber of ceramic shell, mounted in the insulation sleeve coated with cast resin. Separated drive mechanism mounted on the top of the insulation sleeve for each phase of vacuum arc extinguish chamber, whose terminal move-ment drives by the cam. The creeping distance between the

Description

Structural Features

as switches or automatic segmentation. With adoption of a new type of insulated design and vacuum arc extinguish chamber, the load switch has visible fracture when breaking, therefore it has the function of isolation switch. With large breaking capacity and oil-free function, it has environmental friendly, no risk of explo-sion, long mechanical lifespan and maintenance free character-istics

vacuum arc extinguish chamber and the insulating sleeve are covered by insulation silicone grease to meet the outdoor use. The vacuum arc extinguish chamber circuits the moment when switches is breaking or closing. Its normal working current is turned on by the isolation blade. When opening, the rotation of the spindle by mechanism, drives the switch tripping, the main circuit is totally separated, wherein, the main circuit has visible isolation fracture after being separated. As the adoption of vac-uum switch tube arc, the load switch has characteristics of large closing capacity, good arc extinguishing effect, high reliability and environmental friendly, no explosion danger, long mechani-cal life and free maintenance.

FZN36-40.5/D630, 1250-20 Series Outdoor High Voltage Disconnect Vacuum Load Switch

F Z W 36 - 40.5 / D 1250 - 20

model meaning

Rated short-time withstand current(KA)

Rated current(A)

Electric

Rated voltage (kV)

Design number

Outdoor

Vacuum interrupter

Load switch

■ The ambient temperature: -40~ +40 ℃ ;

■ Pollution levelL: ≤ III;

■ Altitude: ≤ 1000m;;

■ Air pressure ≤ 700Pa (equivalent to wind speed of 34m/s);

Environmental Functions And Conditions■ Condensation is allowed in high humidity during the period the

temperature dropped rapidly;

■ Place without fire, explosion, chemical corrosion;

■ The seismic intensity ≤ 8 .

Page 37: HIGH VOLTAGE ELECTRICAL APPARATUS

-36-

FZN36-40.5/D630, 1250-20 Series Outdoor High Voltage Vacuum Isolation Load Switch

main Technical Data

Number Item Unit Parameter

1 Rated voltage KV 40.5

2 Rated current A 1250

3 Rated frequency Hz 50

4 Rated active load breaking current A 1250

5 Rated closed loop breaking current A 1250

6 5% of rated active power load breaking current A 62.5

7 Rated cable charging breaking current A 21

8 Rated short-circuit closing current (peak) KA 50

9 Rated dynamic stability current (peak) KA 50

10 The 4S thermal stability current KA 20

11Insulation level

Power frequency withstand voltage(1 min)

Interrupter across open contacts

KV

70

Isolated across open contacts (Dry test / Wet test)

110/95

To the ground and interphase(Dry test / Wet test)

95/85

Lightning impulse withstand voltage (peak)

Isolated across open contactsKV

215

To ground.interphase 185

12 Mechanical life times 10000

13 Total weight Kg 300

Number Item Unit Parameter

1 Contact opening distance (Interrupter) mm 14±1

2 Contact over travel (Interrupter) mm 2±0.5

3 Three-phase breaking, closing Asynchrony ms ≤ 5

4 Average closing speed (Interrupter) m/s 0.7±0.3

5 Average opening speed (Interrupter) m/s 1.1±0.3

6 Bounce when closing (Interrupter) ms ≤ 3

7 Isolation opening contact distanrce mm ≤ 380

8 Each phase loop resistance μΩ ≤ 200

■ Technical parameters

■ Mechanical properties

Page 38: HIGH VOLTAGE ELECTRICAL APPARATUS

-37-

FZN36-40.5/D630, 1250-20 Series Outdoor HighVoltage Vacuum Isolation Load Switch

Please indicate the type, name, quantity and rated load current of the product. For ordering motors please specify the nature of the control current (AC or DC).

Ordering Information

Page 39: HIGH VOLTAGE ELECTRICAL APPARATUS

-38-

GW4 Series Outdoor AC High Voltage Disconnectors

GW4 Series Outdoor high-voltage isolation switch is widely used in power plants, transformer substations and large industrial and mining enterprises. In three-phase AC 50Hz circuit, It switches on/off circuit when having voltage and no load. The electric and mechanical properties conform to nation standards of GB1985 AC HV Disconnecting Switch and Grounding Switch and DL486 AC HV Disconnecting Switch Order Technical Condition and IEC standard.

GW4 series disconnecting switch is a kind of double-post isola-tion switch. It is a monopole type. When using triple pole, connect interelectrode by the zone axis and synchronize triple pole. GW4 series disconnecting switch is composed of base, post insulator and conduction part. Each pole of the GW4 series disconnecting

■ Altitude: ≤ 2000m;

■ Ambient temperature: -50℃ ~+50℃ ;

■ Partial pressure: ≤ 700Pa;

■ Earthquake intensity: ≤ IX;

Description

Normal Working Environment

swith has two knob insulators installed on the bearing, connected with connecting-rod (GW4-10 series disconnecting switch has only one knob insulator installed on the bearing, and the other one fixed on the other side). It can circumgyrate horizon-tally. GW4 series disconnecting switch conduction switch blade separated to two parts is fixed on two knob insulators, and make switch on/off horizontally. The contacting position of contact is on the middle between two knob insulators. When using operating mechanism and tum electric conductor 91o, the other knob insu-lator and electric conductor will also turn 91° (when the operat-ing mechanism of the GW4-10 series disconnecting switch work, only the knob insulator installed on base bearing and electric conductor turn 91o, the other will be fixed). So the switch blade will switch on/off alone to the same direction.

■ Ice coating thickness: ≤ 20mm;

■ No burning or explosion hazard, chemical corrosion and se-vere vibration.

main Technical DataNumber Item GW4-40.5 GW4-40.5 GW4-126 GW4-126G GW4-145

1 Rated voltage 40.5 72.5 126 126 145

2 Rated Current630,1250,2000,2500

630,1250,2000,2500,

4000

630,1250,2000,2500

630,12501250,2000,

2500

3Rated short-time withstand current (effective value) (kA)

20 31.540(46)

20 31.540(46)

20 31.540(46)

20 31.520 31.5 40(46)

4 Rated peak withstand current (peak) (kA)50 80

100(104)50 80

100(104)50 80

100(104)50 80

50 80

100(104)

5Rated short-time power frequency withstand voltage (rms) (kV)

earth 80 140 185(230) 185 375

across open contacts

110 160 210(265) 210 315

6Rated lightning impulse withstand voltage (peak) (kV)

earth 185 325 450(550) 450 650

across open contacts

215 375 520(630) 550 750

7 Rated horizontal pull of the terminal 490(735) 735 735 735 960

8 Unipolar weight(Kg) 80 200 240 300 300

Page 40: HIGH VOLTAGE ELECTRICAL APPARATUS

-39-

GW4 Series Outdoor AC High Voltage Disconnectors

Page 41: HIGH VOLTAGE ELECTRICAL APPARATUS

-40-

GW5 Series Outdoor AC High Voltage Disconnectors

■ Altitude: 1000~3000m;

■ Ambient temperature: +40 ℃ ~-30 ℃ , ≤ -40 ℃ for alpineregion;

■ The wind pressure ≤ 35m/s

Environmental Conditions■ The seismic intensity ≤ 8

■ Icing thickness ≤ 10mm;

■ Place without fire, explosion, chemical corrosion;

■ Post Insulator pollution level: common type is 0 , and anti-pollution type is II;

main Technical Data

Classification ModelRated

voltage(KV)

Rated Current

(A)

Isolation switch Earthing switch

Earthing switch

Rated peak withstand current

(KA)

Rated short-time withstand current

(KA)

Rated peak withstand

current (KA)

Rated short-time withstand current

(KA)

General (pollution

prevention)GW5

40.5126

63050

20(4S)

50 80

Not grounded,Single

grounded,Double ground

1000 31.5(4s)

1250

80 31.5(4s)1600

2000

Page 42: HIGH VOLTAGE ELECTRICAL APPARATUS

-41-

GW5 Series Outdoor AC High Voltage Disconnectors