High Voltage High Voltage Electrical Equipment Electrical Equipment Failure Diagnosis Failure Diagnosis Presented by: Spencer Tang & Terence Ng T&T Inspection & Engineering Sdn Bhd

High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Embed Size (px)

Citation preview

Page 1: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

High Voltage High Voltage Electrical Equipment Electrical Equipment

Failure DiagnosisFailure Diagnosis

Presented by:Spencer Tang & Terence Ng

T&T Inspection & Engineering Sdn Bhd

Page 2: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 22

High Voltage Electrical Equipment Failure Diagnosis

Definition of High Voltage (H.V. / H.T.)Definition of High Voltage (H.V. / H.T.)–– According to IEC standard, According to IEC standard,

High voltageHigh voltage is defined as those with more than is defined as those with more than 1000V (>1000V AC) for 1000V (>1000V AC) for alternating current alternating current low voltagelow voltage (50~1000V AC) and (50~1000V AC) and extraextra--low voltagelow voltage(<50V AC) circuits, in the context of building wiring (<50V AC) circuits, in the context of building wiring and the safety of electrical apparatus.and the safety of electrical apparatus.

–– In South East Asia, HV is ranging from In South East Asia, HV is ranging from 1kV (1000V), 3.3kV, 6.6kV, 11kV, 22kV, 1kV (1000V), 3.3kV, 6.6kV, 11kV, 22kV, 33kV, 132kV, 230kV, 275kV, 400kV & 500kV. 33kV, 132kV, 230kV, 275kV, 400kV & 500kV.

Page 3: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 33

Map of the Map of the AseanAsean

Page 4: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 44

High Voltage Electrical Equipment Failure Diagnosis

Characteristic of High VoltageCharacteristic of High Voltage–– Higher voltage required higher insulation level Higher voltage required higher insulation level –– Ability to penetrate insulation material (air, Ability to penetrate insulation material (air,

vacuum, gas, oil, XLPE, PILC, porcelain, etc) vacuum, gas, oil, XLPE, PILC, porcelain, etc) due to deterioration / aging / interruption / due to deterioration / aging / interruption / human error, etc and create short circuit / human error, etc and create short circuit / discharge between phase to phase / phase to discharge between phase to phase / phase to groundground

–– resulting severe facility damage / loss, injury / resulting severe facility damage / loss, injury / deathdeath

Page 5: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 55

High Voltage Electrical Equipment Failure Diagnosis

NDT Technology of UltrasoundNDT Technology of Ultrasound–– a method to detect HV fault symptom a method to detect HV fault symptom

(electrical partial discharge (electrical partial discharge –– E.P.D.) from a E.P.D.) from a safesafe distancedistance

–– Provide safeProvide safe accessaccess via structure borne and via structure borne and airborne method without direct expose to the airborne method without direct expose to the live part / component.live part / component.

–– HighlyHighly sensitivesensitive ultrasound instrument ultrasound instrument coupled with coupled with qualifiedqualified inspector will able to inspector will able to detect HV fault symptom (detect HV fault symptom (egeg: corona, : corona, tracking, arcing, mechanical looseness and tracking, arcing, mechanical looseness and etc)etc)

Page 6: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 66

E.P.D. at 33kV VCB E.P.D. at 33kV VCB –– Cable VOIDCable VOID

Cable insulation void at cable compartment Cable insulation void at cable compartment

Page 7: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 77

E.P.D. at 33kV VCB E.P.D. at 33kV VCB –– Cable VOIDCable VOID

Cable insulation void at cable compartmentCable insulation void at cable compartment

2007

Jul 2008

Oct 2008

Page 8: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 88

E.P.D. at 33kV VCB E.P.D. at 33kV VCB –– BusbarBusbar

BusbarBusbar insulation deterioration insulation deterioration –– corona corona partial dischargepartial discharge

Page 9: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 99

E.P.D. at 33kV VCB E.P.D. at 33kV VCB –– Breaker ContactBreaker Contact

Chemical reaction on conductor Chemical reaction on conductor

Page 10: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 1010

E.P.D. at 132kV Lightning ArresterE.P.D. at 132kV Lightning Arrester

Internal partial discharge at porcelainInternal partial discharge at porcelain

Page 11: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 1111

E.P.D. at 33kV Overhead Disc IsolatorE.P.D. at 33kV Overhead Disc Isolator

Airborne detected PD at disc isolator Airborne detected PD at disc isolator suspension clamp suspension clamp –– sharp edges/ sharp edges/ oxidization / deterioration oxidization / deterioration

Page 12: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 1212

High Voltage Electrical Equipment Failure Diagnosis

mechanical vibration / looseness in HV mechanical vibration / looseness in HV breaker causes bybreaker causes by–– the resonance of electrical frequency (50Hz / the resonance of electrical frequency (50Hz /

60Hz) or electrical harmonics60Hz) or electrical harmonics–– workmanship issue during on site installation workmanship issue during on site installation

((egeg: tightening / torque, panel and floor : tightening / torque, panel and floor leveling, greasing, etc)leveling, greasing, etc)

–– Operator ignorant or mechanism error (Operator ignorant or mechanism error (egeg: : breaker misalignment, breaker arm bent, breaker misalignment, breaker arm bent, shutter jammed, etc shutter jammed, etc

Page 13: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 1313

Mechanical vibration / looseness in HV breakerMechanical vibration / looseness in HV breaker

Looseness detected at breaker & Looseness detected at breaker & busbarbusbar

Page 14: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 1414

High Voltage Electrical Equipment Failure Diagnosis

Repair urgency on partial discharge Repair urgency on partial discharge detected:detected:–– Rate of deteriorationRate of deterioration–– Location of the PD detectedLocation of the PD detected–– Loading fluctuation Loading fluctuation -- on/off, surge start, peak on/off, surge start, peak

loadload–– Surrounding environment condition Surrounding environment condition –– seaside, seaside,

chemical industry, dusty areachemical industry, dusty area……–– External factors External factors –– animal, human erroranimal, human error……

Page 15: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 1515

Repair urgency on PD detected

11kV CT flashover during breaker surge 11kV CT flashover during breaker surge start after maintenance due to ignorantstart after maintenance due to ignorant

Page 16: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 1616

Repair urgency on PD detected

Dusty and salty environment induced Dusty and salty environment induced speedy deterioration at 33kV VCBspeedy deterioration at 33kV VCB

Page 17: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 1717

Repair urgency on PD detected

High moisture environment induced High moisture environment induced oxidization & chemical reaction oxidization & chemical reaction

Page 18: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 1818

Repair urgency on PD detected

PD chemical effect on metal panel PD chemical effect on metal panel

Before After

Page 19: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 1919

Repair urgency on PD detected

Close PD location increase rate of Close PD location increase rate of deteriorationdeterioration

Page 20: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 2020

Repair urgency on PD detected

External factorExternal factor–– Minor corona partial discharge give way in 7 days due Minor corona partial discharge give way in 7 days due

to road constructionto road construction

Page 21: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 2121

Repair urgency on PD detected

Client common question to inspector:Client common question to inspector:How long does the PD symptom can last before it How long does the PD symptom can last before it flashover??flashover??

Can we arrange shut down after our production Can we arrange shut down after our production peak time, may be about 6 months later??peak time, may be about 6 months later??

Should we shut down by tonight?? Should we shut down by tonight??

Page 22: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 2222

Perfect match of Ultrasound and Thermography

Ultrasound (US) Ultrasound (US) –– hear what we cannot hear what we cannot hear; hear; ThermographyThermography (IR) (IR) –– see what we see what we cannot see.cannot see.–– Technology limitation but not weakness.Technology limitation but not weakness.

Integration of US & IR will supplement the Integration of US & IR will supplement the survey findings and produce a better survey findings and produce a better diagnosis result diagnosis result

Page 23: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 2323

Perfect match of Ultrasound and Thermography

11kV RMU required immediate attention11kV RMU required immediate attention

Sp1:temp 32.0

26.0

39.0 °C

30

35

y

Ar1:max 34.5

26.0

39.0 °C

30

35

y

Page 24: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 2424

Perfect match of Ultrasound and Thermography

Localizing the fault areaLocalizing the fault area

29.0

40.0 °C

30

32

34

36

38

F LI R Sys tem s

Ar1:max 67.6

Sp1:temp 44.6

25.0

70.0 °C

30

40

50

60

FLIR Systems

Page 25: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 2525

Perfect match of Ultrasound and Thermography

Localizing the fault areaLocalizing the fault area

27.0

31.9 °C

28

30

Ar1:max 36.1

24.0

39.0 °C

25

30

35

y

Page 26: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 2626

High Voltage Electrical Equipment Failure Diagnosis

NDT technology ease the inspector / owner to NDT technology ease the inspector / owner to visualize & localize the faultsvisualize & localize the faults

How is the HV partial discharge look like in our How is the HV partial discharge look like in our visual view???visual view???–– TxTx HV corona ring; HV corona ring;

Ar3:max 30.5

Ar1 :max 40.1

Ar2:max 40.2

19.0

43.0 °C

20

30

40

Page 27: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 2727

TxTx HV Cable HV Cable -- corona ring partial dischargecorona ring partial discharge

Page 28: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 2828

TxTx HV bushing partial discharge HV bushing partial discharge

Page 29: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 2929

TxTx HV bushing partial discharge HV bushing partial discharge

Ar1:max 46.1

Ar3:max 44.3

Ar2:max 49.1

38.0

50.0 °C

40

45

Page 30: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 3030

Electrical partial discharge effect to plant/climberElectrical partial discharge effect to plant/climber

Page 31: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 3131

HV flashover

Page 32: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 3232

High Voltage Electrical Equipment Failure Diagnosis

To conduct a safe and effective inspection To conduct a safe and effective inspection on high voltage electrical equipment, we on high voltage electrical equipment, we should well understand and aware on:should well understand and aware on:–– The safety measure of the HV equipment to The safety measure of the HV equipment to

be inspected;be inspected;–– Our NDT instrumentsOur NDT instruments’’ strength and limitation;strength and limitation;–– Be observant and sensitive to the onBe observant and sensitive to the on--site site

condition of the HV equipment;condition of the HV equipment;–– ““a careful inspector will live longer than a hero a careful inspector will live longer than a hero

(fool) in HV electrical system(fool) in HV electrical system””

Page 33: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 3333

230kV GIS230kV GIS

:max 30.8

:max 32.8 :max 30.7

25.0

46.0 °C

30

35

40

45

FLIR Systems

25.0

46.0 °C

30

35

40

45

FLIR Systems

Page 34: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 3434

230KV GIS 230KV GIS

:max 30.9 :max 32.8

25.5

46.0 °C

30

35

40

45

FLIR Systems

Page 35: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 3535

3MVA 3MVA PauwelsPauwels TrafoTrafo

Page 36: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 3636

Page 37: High Voltage Electrical Equipment Failure Diagnosis · High Voltage Electrical Equipment Failure Diagnosis ... High Voltage Electrical Equipment Failure Diagnosis ... E.P.D. at 132kV

Ultrasound World VII 2011Ultrasound World VII 2011 3737

High Voltage Electrical Equipment Failure Diagnosis

Glad to share with you,Glad to share with you,

Thank youThank you