Upload
others
View
4
Download
1
Embed Size (px)
Citation preview
1. Introduction
2. Classification of High Voltage Tests
3. Test Voltages
4. High Voltage Testing of Electrical Apparatus
HIGH VOLTAGE TESTING OF
ELECTRICAL APPARATUS
1. INTRODUCTION
Purpose of the testing: To ensure that the electrical
equipments are capable of withstanding the overvoltages that
are met with in service.
Covers basic requirements procedures for testing on several
electrical apparatus. Normally, high voltage (HV) testing is to
investigate the insulation performance.
International/national specifications for testing are outlined
(details of test, specific equipment, procedure and acceptable
limits) to meet the users’ and manufacturers’ requirements.
2. CLASSIFICATION OF HIGH VOLTAGE
TESTS
Destructive Test
Normally the equipment underwent destructive
test cannot be used in the service.
Test voltage is higher than its normal working
voltage.
Breakdown test.
Con’t
Non-Destructive Test
Mainly done to assess the electrical properties,
eg. Resistivity, dielectric constant and loss
factor.
The apparatus is not destroyed during the test
and can be used again.
2.2 TYPES OF TESTS
1. Routine Tests
Made by the manufacturer on every finished piece of product.
To fulfills the specifications.
2. Type Tests
Performed on each type of equipment before their supply on a
general commercial scale – demonstrate performance
characteristics.
No need to repeat the test unless changes are made in the
design of the product.
Con’t
3. Maintenance Tests
Usually carried out after maintenance/repair of
the equipment.
Conducted according to schedule provided.
Purpose of the test : To ensure the equipment
lifetime is achieved.
Types of tests
The range of high voltage tests depends on the nature of the equipment being tested
3.0 TEST VOLTAGES
TEST VOLTAGES
impulse voltages.
power-frequency alternating
voltages (AC)
Direct voltages
(DC)
Con’t
Test with Direct Voltage (DC).
Mainly to test equipment used in HVDC
transmission systems.
Insulation testing, fundamental investigations in
discharge physics and dielectric behavior.
Rate of voltage rise above 75% of its estimated
final value should be about 2% per second.
Con’t
Test with Alternating Voltage (AC).
Frequency range : 40-60 Hz, sinusoidal shape.
Dry withstand test : Most common routine test
for all types of electrical equipment especially
insulators, bushing, rod gaps etc.
Applied voltage between two to three times of
the normal working voltage.
Con’t
Test with Alternating Voltage (AC) – cont.
Wet withstand test : To simulate the effect of natural rain on
external insulation.
Recommended for tests on apparatus which are designed for outdoor
used.
Use artificial rain.
Applied for 30-60 seconds.
Con’t
Test with Impulse Voltage.
Is designed to investigate the
insulation performance due to the
lightning stroke or Lightning
impulse chopped on the front
switching operation.
3 types of impulse voltages, ie;
1) Full wave
2) Chopped wave
3) Switching wave
BS 923: Part 2: 1980
Con’t
BS 923: Part 2: 1980
Lightning impulse chopped
on the tail
Full switching impulse
Con’t
Rated impulse withstand test
For test on non-self-restoring insulation, 3 impulses are applied.
For withstand tests on self-restoring insulation, 2 procedures
are used:
1) 15 impulses (rated withstand voltage) with the specified shape and
polarity are applied
2) Test procedure for determining 50% disruptive discharge voltage is
applied
The method used for determining the levels of applied voltage
is up-and-down methods.
The electrical characteristics of the insulators and other apparatus are normally referred to the reference atmospheric conditions.
According to the British Standard Specifications, they are:
Temperature : 20oC
Pressure : 1013 millibars (or 760 torr)
Absolute humidity : 11 gm/m3
Since it is not always possible to do tests under these reference conditions, correction factors have to be applied.
Atmospheric Correction Factors
Atmospheric Correction Factors
V0 = voltage under actual test conditions,
Vs = voltage under reference atmospheric conditions,
h = humidity correction factor, and
d = air density correction factor.
The air density correction factor is given by,
where, b = atmospheric pressure in millibars, and
T= atmospheric temperature, oC.
Humidity correction factor h is obtained from the temperatures of
a wet and dry bulb thermometer, by obtaining the absolute
humidity and then computing h from the absolute humidity.
Example 1
Sarzaminor conducted an AC flashover test at power
frequency on a cap and pin insulator for his FYP project.
From the test, it was found that flashover occurred at 80 kV.
If the dry and wet temperatures during the test were 25˚C
and 22˚C respectively, and atmospheric pressure was at 1
atm, determine the flashover voltage under the reference
atmospheric condition.
Example 1
Dry Temp. = 25˚C
Wet Temp. = 22˚C
18Absolute humidity =
18g/m3
Example 1
Dry Temp. = 25˚C
Wet Temp. = 22˚C
1 atm = 1013.25 milibar
0.92
h=0.92
4.0 HIGH VOLTAGE TESTING OF
ELECTRICAL APPARATUS
Transformer
Circuit breaker
Insulator
Cable
Impulse testing on transformer
• A change in the waveshape of the voltage and current both before and after the chopped waves have been applied.
• The existing of acoustic noise.• Visual signs of flashover
• According to BS 171: Part 3. Carried out at room temperature with the transformer not energized.
• Used standard impulse waveshapes. Full and chopped waves. Impulse Test
Temperature Rise Test
Short Circuit test
Failure detection (Insulation
failure)
Testing of Circuit Breaker
(BS 5227: Part 2, IEC 56)
• Consist of overvoltage withstand tests of power frequency, lightning and switching impulse voltages.
• Circuit breaker in both the open and closed positions
Dielectric tests or overvoltage tests,
• Type test
Temperature rise and mechanical tests
• The most important test on circuit breaker since these tests assess the primary performance of these devices, i.e. their ability to safely interrupt the fault currents
Short Circuit Tests
Short Circuit Test Methods of conducting short circuit tests are
(I) Direct Tests
(a) using a short circuit generator as the source
(b) using the power utility system or network as the source.
(II) Synthetic Tests
Consists of two separate sources : one power source acting as a current source supplying the required short-circuit current at a (relative) low-voltage level and a second source working as a voltage source supplying the required voltage.
Based on the fact that for certain (short circuit) tests the test object is stressed by a high current and by a high voltage at different time periods.
Tests on Insulator
Test on Insulator
Power Frequency Test
Dry and Wet flashover test
increased at a uniform rate of about 2 % per second of 75% of the estimated test voltage
Dry and Wet Withstand test
Voltage applied under dry or wet conditions for a period of 1 minute with an insulator mounted as in
service conditions. The test piece should withstand the specified voltage.
Impulse Tests
Impulse Withstand Voltage Test
Both positive and negative polarities
Insulator passed the test if five consecutive waves do not cause flashover or puncture
Impulse Flashover Test
Pollution Testing
Due to outdoor electrical insulation and consequent problems of the maintenance of
electrical power systems. Eg. Dust, industrial pollution (smoke & petroleum vapor), desert
pollution, snow
Pollution causes corrosion, non-
uniform gradients, deterioration of the
material, partial discharges and radio
interference.
Routine and Type test on cables According to BS 923: Part 2, IEC 60-2, IEC 55-1, IEC 230 and BS6480.
Different tests on cables may be classified into
I. mechanical tests like bending test, dripping and drainage test, and fire
II. resistance and corrosion tests,
III. dielectric power factor tests,
IV. power frequency withstand voltage tests, (a.c. voltage of 2.5 limes the
rated value for 10 min.)
V. Dc withstand voltage tests, (1.8 times the rated d.c. voltage of negative
polarity for 30 min)
VI. Impulse withstand voltage tests, (withstand five impulse of prescribed
magnitude without any damage
VII. partial discharge tests,