Fire Detection Alarms, Suppression Systems.pdf

Embed Size (px)

Citation preview

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    1/35

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    2/35

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    3/35

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    UNIT OBJECTIVES

    Upon completion of this unit of study, the student should be able to:

    1. Identify supervisory alarm equipment and demonstrate action to take upon

    receipt of an alarm according to local operating conditions.

    2. Identify the various types of detection devices used in fire detection systems.

    3. Identify the components of an automatic sprinkler system and their functions.

    4. Identify the major sprinkler systems and describe their operation.

    5. Identify the actions required for fire department support of an automatic sprin-

    kler system.

    6. Connect a fire department pumper to the fire department connection for a

    sprinkler system.

    7. Demonstrate the procedure to temporarily stop the flow of water from a sprin-

    kler head.

    8. Identify and demonstrate the procedures for inspecting an automatic sprinkler

    system in order to determine the systems state of readiness.

    Fire Detection, Alarm, & Suppression Systems - 1

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    4/35

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    Successful completion of the information in this section is necessary to fulfill the

    requirements of the following sections of NFPA 1001-2008:

    Fire Fighter I Standard

    5.3.14 Conserve property as a member of a team, given salvage tools and equipment and an

    assignment, so that the building and its contents are protected from further damage.

    (A) Requisite Knowledge. The purpose of property conservation and its value to the

    public, methods used to protect property, types of and uses for salvage covers, operations

    at properties protected with automatic sprinklers, how to stop the flow of water from an

    automatic sprinkler head, identification of the main control valve on an automatic sprinklersystem, and forcible entry issues related to salvage.

    (B) Requisite Skills. The ability to cluster furniture; deploy covering materials; roll and

    fold salvage covers for reuse; construct water chutes and catch-alls; remove water; cover

    building openings, including doors, windows, floor openings, and roof openings; separate,

    remove, and relocate charred material to a safe location while protecting the area of origin

    for cause determination; stop the flow of water from a sprinkler with sprinkler wedges or

    stoppers; and operate a main control valve on an automatic sprinkler system.

    Fire Fighter II Standard

    6.5.3* Prepare a preincident survey, given forms, necessary tools, and an assignment, so

    that all required occupancy information is recorded, items of concern are noted, and

    accurate sketches or diagrams are prepared.

    (A) Requisite Knowledge. The sources of water supply for fire protection; the

    fundamentals of fire suppression and detection systems; common symbols used in

    diagramming construction features, utilities, hazards, and fire protection systems;

    departmental requirements for a preincident survey and form completion; and the

    importance of accurate diagrams.

    (B) Requisite Skills. The ability to identify the components of fire suppression and

    detection systems; sketch the site, buildings, and special features; detect hazards andspecial considerations to include in the preincident sketch; and complete all related

    departmental forms.

    NFPA STANDARDS

    2 - Fire Detection, Alarm, & Suppression Systems

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    5/35

    TEACHING OUTLINEMaterial in italics is NOT included in the Student Manual

    SLIDES

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    I. Fire Detection, Alarm, and Suppression Systems

    A. Fire detection, alarm, and suppression systems are

    installed to:

    1. Notify occupants to escape a fire

    2. Summon emergency responders

    3. Initiate fire control and suppression systems and

    sound an alarm

    4. Supervise suppression systems for operational

    status

    5. Initiate environmental and utility controls

    B. Fire fighters must understand the various types of fire

    protection systems which may be encountered in differ-

    ent occupancies and

    1. How these systems function

    2. Their role when these systems function in an emer-

    gency

    II. Types of Alarm Systems (Essentials p. 826)

    A. Protected premises fire alarm systems

    1. Also known as "local warning systems"

    2. Designed to be initiated manually by pull stations

    3. Installed in small schools and public properties

    4. Designed to only alert the building's occupants

    Fire Detection, Alarm, & Suppression Systems - 3

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    6/35

    TEACHING OUTLINESLIDESMaterial in italics is NOT included in the Student Manual

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    5. Does not notify the fire department

    6. Automatic detection devices may be added to the

    system to detect a fire and initiate the signal

    B. Heat detectors

    1. Respond to the thermal energy of a fire

    a. Typically the slowest type of system to activate

    b. Activate at a predetermined temperature or

    when a specified temperature rate of rise occurs

    c. Used in areas unoccupied or environmentally

    unsuitable for application of smoke detectors

    d. Typically used as a property protection device

    2. Fixed temperature heat detectors

    a. Activate when heated to the rated temperature,

    usually 135oF or higher

    b. In a large area, a fire could burn for some time

    without activating a fixed-temperature detector

    c. Fusible devices/frangible bulbs

    (1) Operate identically to fusible links or

    frangible bulbs used in automatic sprinkler

    systems

    (2) To restore a fusible device/frangible bulb

    detector, the entire detector must be

    replaced

    4 - Fire Detection, Alarm, & Suppression Systems

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    7/35

    TEACHING OUTLINEMaterial in italics is NOT included in the Student Manual

    SLIDES

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    (3) Many of these devices are still in service,

    however, they are no longer manufactured

    (4) A fusible device is held in place with

    solder with known melting (fusing) tem-

    perature

    (5) When the temperature rises to the fusing

    temperature, the solder melts, and a spring

    closes the contact points

    (6) The action completes the circuit and ini-

    tiates the alarm signal

    (7) A frangible bulb holds the electrical con-

    tacts apart like a fusible link does

    (8) The bulb is a small glass vial containing a

    liquid with a small air bubble

    (9) When the rated temperature is reached, the

    bulb fractures and falls out and the contacts

    complete the circuit to initiate the alarm

    d. Continuous line detector

    (1) Designed to detect heat over a linear area

    parallel to the detector

    (2) Used to protect long cable channels

    (3) One type is a cable with a conductive metalinner core sheathed in stainless steel tubing

    (a) The core and sheathing are separated by

    an insulating material

    Fire Detection, Alarm, & Suppression Systems - 5

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    8/35

    TEACHING OUTLINESLIDESMaterial in italics is NOT included in the Student Manual

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    (b) At a predetermined temperature, the

    insulation loses some of its electrical

    resistance

    (c) The current flow between the core and

    sheathing increases and initiates the

    alarm

    (4) Another system uses two insulated wires

    with an outer covering

    (a) When the rated temperature is reached,

    the insulation melts and the wires touch

    (b) The circuit is then completed and the

    alarm initiated

    e. Bimetallic element detector

    (1) Uses two metals with different heat expan-

    sion rates

    (2) When heated, one metal expands faster,

    causing the strip to bend

    (3) The deflection makes or breaks the circuit

    causing alarm activation

    (4) Most bimetallic detector reset automati-

    cally when cooled

    3. Rate-of-rise heat detectors

    a. Operates on the assumption that the temperature

    from a fire will increase faster than normal

    atmospheric heating

    b. Designed to operate when the temperature rise

    exceeds 12oF to 15oF in one minute

    6 - Fire Detection, Alarm, & Suppression Systems

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    9/35

    TEACHING OUTLINEMaterial in italics is NOT included in the Student Manual

    SLIDES

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    c. Most are reliable and not subject to false

    activations

    d. Automatically reset if undamaged

    e. Pneumatic rate-of-rise spot detector

    (1) Most common type of rate-of-rise detector

    used

    (2) Consists of a dome-shaped air chamberwith a flexible metal diaphragm in the base

    (3) A small hole allows air to enter and exit the

    chamber during normal temperature changes

    (4) During a fire, the air in the chamber ex-

    pands faster than it can escape

    (5) The expansion causes the pressure in the

    chamber to increase and forces the metal

    diaphragm against the contact points, initi-

    ating the alarm

    f. Rate-compensated detector

    (1) Consists of an outer metallic sleeve housing

    two bowed struts with slower expansion

    rates than the sleeve

    (2) When heated rapidly, the outer sleeve

    expands in length

    (3) The tension is reduced on the inner strips

    causing the contacts to come together

    Fire Detection, Alarm, & Suppression Systems - 7

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    10/35

    TEACHING OUTLINESLIDESMaterial in italics is NOT included in the Student Manual

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    C. Smoke detectors/alarms

    1. Smoke detectors

    a. Typically installed in nonresidential and multi-

    family occupancies

    b. Detect smoke and transmit a signal to another

    device that sounds the alarm

    2. Smoke alarms

    a. Installed in single-family dwellings

    b. Self-contained unit capable of detecting smoke

    and sounding an alarm

    3. Photoelectric smoke detectors

    a. Also called a "visible products-of-combustion

    detector"

    b. Use a photoelectric cell coupled with a small

    light source

    c. Generally more sensitive to smoldering fires

    than ionization detectors

    d. Beam application type

    (1) A beam of light is focused onto a photo-

    electric cell which converts the beam intoan electric current

    (2) When smoke obscures the light beam, the

    amount of current is reduced and an alarm

    sounds

    8 - Fire Detection, Alarm, & Suppression Systems

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    11/35

    TEACHING OUTLINEMaterial in italics is NOT included in the Student Manual

    SLIDES

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    e. Refractory photocell type

    (1) A light beam passes through a small cham-

    ber away from the light source

    (2) The light does not strike the photocell and

    no current is produced

    (3) When smoke enters the chamber, the light

    beam is refracted in all directions and

    strikes the photocell, activating the alarm

    4. Ionization smoke detectors

    a. Tiny particles and aerosols are produced during

    combustion

    b. These particles can be detected by devices

    using a small amount of radioactive material to

    ionize air molecules as they enter the detector

    c. The ionized air particles allow an electrical

    current to flow between plates in the ionization

    chamber

    d. When smoke enters the chamber, its particles

    attach to the air ions making the air less conduc-

    tive

    e. The decrease in current activates the alarm

    D. Flame detectors

    1. Reacts the fastest to fire

    a. Prone to activation by sunlight, welding and

    other bright lights

    Fire Detection, Alarm, & Suppression Systems - 9

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    12/35

    TEACHING OUTLINESLIDESMaterial in italics is NOT included in the Student Manual

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    b. Usually positioned where other light sources are

    unlikely

    c. Must have an unobstructed view of the pro-

    tected area

    d. Used where immediate reaction is necessary

    such as flammable liquid manufacturing and

    dispensing facilities

    2. Infrared detectors

    a. Sensitive to sunlight and usually installed in

    fully enclosed areas

    b. Most are designed to require flickering motion

    of flame to activate

    3. Ultraviolet detectors

    a. Virtually insensitive to sunlight

    b. Not suitable when arc welding is done

    E. Fire-gas detectors

    1. Used to detect the gases produced by a fire in a

    confined space

    2. The gases produced will vary depending on the

    chemical makeup of the burning fuel

    3. Will initiate an alarm more quickly than a heat

    detector but slower than a smoke detector

    4. Can be designed to be sensitive only to those gases

    produced by a hostile fire and ignore those pro-

    duced by a friendly fire in an industrial operation

    10 - Fire Detection, Alarm, & Suppression Systems

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    13/35

    TEACHING OUTLINEMaterial in italics is NOT included in the Student Manual

    SLIDES

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    5. Fire fighters will encounter very few fire-gas

    detectors except in special occupancies

    F. Combination detectors: makes detectors more respon-

    sive to fire conditions

    1. Fixed temperature/rate-of-rise heat detectors

    2. Smoke/heat detectors

    3. Smoke/fire-gas detectors

    G. Detectors have a variety of audible and visual indicat-

    ing devices

    H. Fire department response to heat/smoke alarm calls

    1. Normally a full structure fire response is dispatched

    to the location of a activated smoke or heat alarm

    2. If there are no signs of smoke or fire when they

    arrive, a fire fighter with a portable radio should go

    to the alarm control panel to silence the alarm so it

    can be further investigated

    3. The system must not be reset or turned off until

    fire fighters determine the cause of the alarm

    4. The individual assigned to the alarm panel must

    remain and monitor the panel in case of another

    alarm

    5. If a second alarm sounds, the Incident Commander

    should be immediately notified

    6. The system can be reset after the source of the

    alarm is determined and stabilized

    Fire Detection, Alarm, & Suppression Systems - 11

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    14/35

    TEACHING OUTLINESLIDESMaterial in italics is NOT included in the Student Manual

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    III.Automatic Alarm Signaling Systems (Essentials p. 837)

    A. Fire codes or insurance companies may require an

    occupancy to have an alarm system which transmits a

    signal off site to summon help

    B. Auxiliary systems

    1. Local energy systems: used only in communities

    with municipal fire alarm box systems

    a. An occupancy's alarm system is directly con-

    nected to the municipal master alarm box

    b. When the occupancy's alarm activates, it trips

    the alarm box to which it is attached and trans-

    mits the alarm to the alarm center

    2. Shunt systems where the municipal alarm circuit

    extends ("is shunted") into the protected property

    3. Parallel telephone systems

    a. Do not connect to the municipal alarm system

    b. Transmits the alarm over municipally controlled

    telephone circuits, which are not used for any

    other purpose

    C. Remote station systems

    1. Connected directly to the public dispatch center orother approved answering service

    2. Usually connected over leased telephone lines

    3. Common where central station systems are not

    available

    12 - Fire Detection, Alarm, & Suppression Systems

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    15/35

    TEACHING OUTLINEMaterial in italics is NOT included in the Student Manual

    SLIDES

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    D. Proprietary alarm systems

    1. Used for large commercial and industrial build-

    ings, high rises, and commonly owned facilities in

    a single location (campus or industrial complex)

    2. Have a central alarm receiving point on the prop-

    erty that is constantly staffed by trained personnel

    3. Alarms are transmitted to a supervising stations

    where operators can call the fire department or thefire department is automatically notified

    E. Central station alarm systems

    1. Typically a company that sells alarm services to

    individual customers at different properties

    2. Connected to protected properties by dedicated

    phone lines or radio transmitter

    3. When an alarm is received, central station employ-

    ees initiate an appropriate emergency response

    F. Fire alarm systems are designed to be self-supervising

    1. A distinct trouble signal is generated anytime the

    system is not operating normally, such as when:

    a. A utility power outage occurs and the system

    switches to battery power

    b. A break in a detector or notification circuit

    occurs

    2. Older systems use closed, supervised circuits

    where a tiny current always flows

    Fire Detection, Alarm, & Suppression Systems - 13

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    16/35

    TEACHING OUTLINESLIDESMaterial in italics is NOT included in the Student Manual

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    3. Newer systems microprocessors do an internal

    diagnostic system test at specified intervals

    4. Alarm signals must be distinctively different from

    trouble signals

    5. Some fixed suppression systems depend on a signal

    from a manual pull station or an automatic detection

    device to activate

    6. Alarm systems must also be "addressable," indicat-ing the location of an activated detector or pull

    station or a trouble signal

    G. Auxiliary services interconnected with alarm systems

    1. Modern alarm systems may incorporate environ-

    mental controls, security, and personnel access

    controls

    2. These auxiliary services may include:

    a. Shutting down HVAC systems for smoke control

    b. Closing smoke or fire-rated doors and dampers

    c. Increasing air pressure in stairwells to exclude

    smoke from means of egress

    d. Overriding elevator controls

    e. Monitoring refrigeration systems and cold-storage areas

    f. Controlling personnel access to restricted areas

    g. Detecting combustible or toxic gases

    14 - Fire Detection, Alarm, & Suppression Systems

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    17/35

    TEACHING OUTLINEMaterial in italics is NOT included in the Student Manual

    SLIDES

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    IV. Sprinkler Systems (Essentials p. 842)

    A. Consists of a series of sprinkler heads (sprinklers)

    arranged to automatically apply water directly on a fire

    to either extinguish it or control it until fire fighters

    arrive

    1. NFPA Standards set minimum guidelines for:

    a. Spacing of sprinklers

    b. Size of piping to be used

    c. Methods for hanging piping

    d. Minimum design area per sprinkler

    e. Installation details

    2. General types

    a. Complete system: protects an entire building

    b. Partial system:protects only certain areas,

    such as high hazard areas and exit routes

    B. Factors affecting sprinkler system reliability and

    performance:

    1. Partially or completely closed valves

    2. Poor or improper maintenance

    3. Improper design

    4. Hazards of the occupancy

    5. Distribution obstructions

    Fire Detection, Alarm, & Suppression Systems - 15

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    18/35

    TEACHING OUTLINESLIDESMaterial in italics is NOT included in the Student Manual

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    6. Deficient water supply

    7. Partial sprinkler protection

    8. Frozen or broken pipes

    9. Damaged or painted sprinkler heads

    10. Tampering or vandalism

    C. Properly operating sprinkler systems:

    1. Improve the life safety of a building's occupants by

    applying water when a fire is relatively small

    2. Prevent vertical fire spread in multistory buildings

    3. Protect occupants in other parts of a building from

    fire spread

    D. Sprinklers alone may not be as effective if:

    1. Fires are too small to activate the sprinkler system

    2. Smoke reaches the occupants before the system

    activates

    3. Sleeping, intoxicated, or handicapped people

    occupy the building

    E. Sprinkler system components

    1. Water supply

    a. Public water supply

    b. Gravity tanks

    c. Fire pumps

    16 - Fire Detection, Alarm, & Suppression Systems

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    19/35

    TEACHING OUTLINEMaterial in italics is NOT included in the Student Manual

    SLIDES

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    2. Basic piping

    a. Supply main

    b. Riser: larger vertical piping

    c. Feed main: connects riser to cross mains

    d. Cross mains: services branch lines

    e. Branch lines: smaller piping on which sprin-klers are installed

    3. Sprinkler heads

    a. Parts

    (1) Valve cap

    (2) Frame arms

    (3) Deflector

    (4) Toggle joint

    (5) Lever arms

    (6) Fusible link

    b. Temperature ratings: may be identified by color-

    coded frame arms, colored liquid, or tempera-

    ture stamped into the head

    (1) Fusible link sprinkler heads

    (a) 135o to 170o: uncolored or black

    (b) 175o to 225o: white

    Fire Detection, Alarm, & Suppression Systems - 17

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    20/35

    TEACHING OUTLINESLIDESMaterial in italics is NOT included in the Student Manual

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    (c) 250o to 300o: blue

    (d) 325o to 375o: red

    (2) Frangible bulb heads

    (a) 135o to 170o: orange or red glass bulb

    (b) 175o to 225o: yellow or green bulb

    (c) 250o to 300o: blue bulb

    (d) 325o to 375o: purple bulb

    c. Release mechanisms

    (1) Fusible-link

    (2) Chemical pellet

    (3) Frangible bulb

    (4) Quick-response: has a specially designed

    fusible link with an increased surface area

    d. Fusible link sprinkler head operation

    (1) Two lever arms press against the frame

    arms and valve cap to hold back the water

    (2) The fusible link holds the levers together

    (3) The link melts or fuses when exposed to

    heat and the water pushes the levers and

    cap out of the way

    (4) Water strikes the deflector and becomes a

    spray

    18 - Fire Detection, Alarm, & Suppression Systems

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    21/35

    TEACHING OUTLINEMaterial in italics is NOT included in the Student Manual

    SLIDES

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    e. Frangible bulb sprinkler head operation

    (1) The bulb filled with liquid and a bubble

    holds the orifice shut

    (2) Heat expands the liquid until the bubble is

    absorbed by the liquid

    (3) The increase in internal pressure shatters

    the bulb and the orifice opens

    (4) Water strikes the deflector and becomes a

    spray

    f. Chemical pellet sprinklers

    (1) A pellet of solder, under compression,

    within a small cylinder, melts at a predeter-

    mined temperature

    (2) A plunger then moves down and releases

    the valve cap

    g. Sprinkler head position

    (1) Pendant: extends down from the underside

    of the piping

    (2) Upright: sits on top of the piping

    (3) Sidewall: extends from the side of the pipe

    and has a special deflector to create a fan-shaped pattern

    (4) Special purpose

    (a) Corrosive-resistant coated

    (b) Recessed

    Fire Detection, Alarm, & Suppression Systems - 19

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    22/35

    TEACHING OUTLINESLIDESMaterial in italics is NOT included in the Student Manual

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    4. Sprinkler head storage

    a. A storage cabinet for extra heads and a wrench

    should be installed near the sprinkler system

    b. Normally holds minimum of six extra heads

    5. Control indicator valves

    a. Located between water source and sprinkler

    system to shut off water supply

    b. Indicating valves visually show if opened or

    closed

    c. Outside screw and yoke (OS&Y)

    (1) Has a yoke on the outside with a threaded

    stem which controls the opening and clos-

    ing of the valve gate

    (2) Threaded stem is out of yoke when open

    d. Post indicator valve (PIV)

    (1) Valve stem inside of hollow post

    (2) Has small window on post where "OPEN"

    or "SHUT" is displayed

    e. Wall post indicator valve (WPIV) - similar to

    PIV but extends through wall

    f. Post indicator valve assembly (PIVA)

    (1) Does not have the small window and words

    (2) Has a sight area that is open when the valve

    is open

    20 - Fire Detection, Alarm, & Suppression Systems

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    23/35

    TEACHING OUTLINEMaterial in italics is NOT included in the Student Manual

    SLIDES

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    6. Operating valves

    a. Alarm test valve: simulates activation of the

    system

    b. Inspector's test valve: equipped with a same

    size opening as a sprinkler head to simulate

    activation of a head

    c. Main drain valve: to drain water from the

    system for maintenance

    7. Water flow alarms

    a. Hydraulically operated: to alert occupants and a

    passerby that water is flowing through the

    system

    b. Electrically operated: to alert occupants and

    transmits an alarm when water is flowing

    through the system

    8. Fire department connection (FDC)

    a. Usually a clappered siamese with at least two

    21/2-inch female connections

    b. A check valve is located between the fire

    department connection and the system to prevent

    water from the system flowing into the FDC

    c. Fire department support

    (1) Supply pumper should have a capacity of at

    least 1,000 gpm

    (2) Using same water main as that supplying

    system will rob the sprinkler system of

    water

    Fire Detection, Alarm, & Suppression Systems - 21

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    24/35

    TEACHING OUTLINESLIDESMaterial in italics is NOT included in the Student Manual

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    (3) A minimum of two 21/2-inch or larger lines

    should be attached to the FDC

    (4) Most sprinkler systems are supplied at 150

    psi

    E. Types of sprinkler systems (Essentials p. 852)

    1. Wet pipe systems

    a. Used in locations not subject to freezing

    b. Contain water under pressure at all times

    c. Sprinkler heads will discharge water immedi-

    ately on activation

    d. Usually equipped with an alarm check valve on

    the main riser

    e. Newer systems may have a backflow prevention

    check valve and electronic flow alarm instead

    of an alarm check valve ("straight stick sys-

    tems")

    f. Maybe equipped with a retard chamber

    (1) Designed to catch excess water that may

    come through the alarm valve in a water

    pressure surge

    (2) Reduces chances of false alarms

    g. Gauges

    (1) Installed above and below each alarm

    check valve

    22 - Fire Detection, Alarm, & Suppression Systems

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    25/35

    TEACHING OUTLINEMaterial in italics is NOT included in the Student Manual

    SLIDES

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    (2) Riser pressure gauge showing pressure in

    system

    (3) Owner or owner's representative should

    check and record monthly to ensure normal

    water supply pressure

    2. Dry pipe systems

    a. Used in locations where piping may be sub-

    jected to freezing temperatures

    b. System contains air under pressure instead of

    water

    (1) When a sprinkler head opens, air leaves

    piping and dry-pipe valve automatically

    opens to fill the system with water

    (2) Designed with a dry-pipe valve so that a

    small amount of air pressure holds the

    valve closed over the water pressure on

    other side

    c. Gauges

    (1) One gauge on the water side and another

    gauge on the air side of dry pipe valve and

    at the air pump supplying air

    (2) Owner or owner's representative should

    check and record gauge readings weekly toensure normal air and water pressures are

    being maintained

    3. Preaction sprinkler systems

    a. Used in properties where it is important to

    prevent water damage, even if pipes are broken

    Fire Detection, Alarm, & Suppression Systems - 23

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    26/35

    TEACHING OUTLINESLIDESMaterial in italics is NOT included in the Student Manual

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    b. System pipes are dry until water is released

    into system in response to detectors

    c. Uses a deluge type valve, fire detection devices,

    and closed sprinkler heads

    d. The operation of detectors releases water into

    the system and sounds an alarm

    e. Sprinkler heads open only from functioning of

    fusible links

    4. Deluge system systems

    a. Used to protect extra hazardous occupancies

    b. All sprinklers heads are always open

    (1) System activated by flame or heat detectors

    (2) When system activates, water flows from

    all sprinkler heads

    5. Residential sprinkler systems

    a. Used to prevent fire involvement in area of

    origin and allow occupants to escape

    b. Typically equipped with quick-response sprin-

    kler heads

    c. May be wet or dry system

    d. Components

    (1) May use plastic or steel piping

    (2) Must have a pressure gauge, flow detector,

    and means for draining system

    24 - Fire Detection, Alarm, & Suppression Systems

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    27/35

    TEACHING OUTLINEMaterial in italics is NOT included in the Student Manual

    SLIDES

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    F. Fire department operations with sprinkler systems

    1. Whenever possible, pumpers supplying hose

    streams should operate from mains other than that

    supplying system

    2. Control valves should not be closed until fire has

    been extinguished unless the incident commander

    determines need to prevent further damage

    3. If control valve is closed, a fire fighter should bestationed at valve with a radio to officer-in-charge

    in case the valve needs to be reopened

    4. Fire department personnel should not service

    system components or restore a system to service

    due to the potential liability

    5. Restoring the system to service should be done by

    representatives of the owners or occupants or a

    commercial sprinkler service company

    6. Control of water flow from sprinkler heads

    a. Remove sprinkler wedge or clamp from appara-

    tus

    b. Raise ladder under activated head

    c. Climb ladder

    d. Insert wedge or clamp into flowing head

    e. Gently tap wedge into place to stop flow

    Fire Detection, Alarm, & Suppression Systems - 25

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    28/35

    TEACHING OUTLINESLIDESMaterial in italics is NOT included in the Student Manual

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    V. Standpipe Systems

    A. Allow connection of hoses on various levels of a

    structure to avoid carrying hoselines up several levels

    B. Components

    1. Fire department connection: usually a clappered

    siamese with at least two 21/2-inch male connections

    2. Piping

    3. Interior fire department valves and connections

    C. Class I standpipe: have 21/2-inch hose connections for

    use by fire fighters

    D. Class II standpipe

    1. Have 11/2-inch single jacket linen hose with a

    lightweight nozzle attached

    2. Designed for use by building occupants with no fire

    training

    3. Most have been taken out of service

    E. Class III standpipe

    1. Have 21/2-inch hose connections and 11/2 inch single

    jacket linen hose with a lightweight nozzle attached

    2. Designed for use by building occupants or fire

    fighters

    26 - Fire Detection, Alarm, & Suppression Systems

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    29/35

    TEACHING OUTLINEMaterial in italics is NOT included in the Student Manual

    SLIDES

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    VI.Fire Detection, Alarm, and Suppression Systems Sum-

    mary

    A. Fire fighters are likely to encounter detection and/or

    suppression systems in many commercial occupancies

    and must be familiar with their operations

    B. Personnel have to understand their role in dealing with

    detection and alarm system activations and always keep

    in mind that a sounding alarm should not be taken

    lightly

    C. Sprinkler systems have the capacity to control small

    fires in early stages but should not be depended on to

    completely control every fire

    Fire Detection, Alarm, & Suppression Systems - 27

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    30/35

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    Name: ___________________________________________ Date: ___________________

    1. Which private fire alarm signaling system is designed to only notify the occupants

    within the protected premises of a fire?

    a. Central station system

    b. Remote station system

    c. Proprietary system

    d. Protected premises fire alarm system

    2. Which private fire alarm signaling system is designed to transmit alarms to acommercial company which then sends the alarms to the fire department?

    a. Central station system

    b. Remote station system

    c. Proprietary system

    d. Protected premises fire alarm system

    3. Which private fire alarm signaling system is designed to usually protect large

    plants or complexes and has a supervising station to monitor the system?

    a. Central station system

    b. Remote station system

    c. Proprietary system

    d. Protected premises fire alarm system

    4. Which type of detectors are typically the slowest to respond when a fire occurs?

    a. Heat detectors

    b. Smoke detectors

    c. Flame detectors

    d. Fire-gas detectors

    5. Which is the most common smoke detector used by consumers and is designed to

    activate when the invisible products of combustion are detected by a radioactivematerial in the detector?

    a. Ionization detector

    b. Photoelectric detector

    c. Fixed temperature detector

    d. Rate-of-rise detector

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS QUIZ

    28 - Fire Detection, Alarm, & Suppression Systems

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    31/35

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS QUIZ

    6. A ___________ sprinkler system is designed to be used in areas where freezing is

    likely to occur.

    a. Wet pipe

    b. Dry pipe

    c. Quick response

    d. Dry response

    7. Which of the following factors affect sprinkler system reliability and performance?

    a. Partially or completely closed valves

    b. Poor or improper main

    c. Distribution obstructionsd. All of the above

    8. The smaller piping on which sprinklers are installed are known as the __________.

    a. Risers

    b. Feed main

    c. Branch lines

    d. Cross mains

    9. On which of the following sprinkler system valves is a threaded stem extended

    from the valve when it is open?

    a. Post indicator valve

    b. Outside screw and yoke

    c. Post indicator valve assembly

    d. Wall post indicator valve

    10. Which of the following sprinkler systems is used to protect extra hazardous occu-

    pancies with all sprinklers heads always open?

    a. Preaction

    b. Dry pipe

    c. Quick response

    d. Deluge

    Fire Detection, Alarm, & Suppression Systems - 29

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    32/35

    FIRE DETECTION, ALARM, & SUPPRESSION SYSTEMS

    MISSOURI DIVISIONOF FIRE SAFETY FIRE FIGHTER I & II

    PRACTICAL SKILLS

    These Lead Instructor Practical Skills are designed to provide the Lead

    Instructor for a Fire Fighter I and II course with a more detailed overview

    of the practical skills required of all students.

    The appropriate skills from NFPA 1001-2008 are listed at the front of eachskill's section. Although the skills from NFPA 1001-2008 are written as Job

    Performance Requirements, these have been divided into individual skill

    elements. This is to allow for consistency in the evaluation of each skill

    element.

    Students must successfully complete each step of each practical skill during

    the practical skills evaluation portion of a Fire Fighter I and II course. At

    the time of a Fire Fighter I and II Certification Examination, the skill steps

    have been prioritized to allow a student to miss a predetermined number of

    steps.

    INSTRUCTOR'S GUIDE

    Fire Detection, Alarm, & Suppression Systems - 31

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    33/35

    MISSOURI DIVISIONOF FIRE SAFETY

    FIRE FIGHTER I & II PRACTICAL SKILLS

    Successful completion of the practical skills in this section are necessary to fulfill the

    requirements of the following sections of NFPA 1001-2008:

    Fire Fighter I Standard

    5.3.14 Conserve property as a member of a team, given salvage tools and equipment and an

    assignment, so that the building and its contents are protected from further damage.

    Fire Detection, Alarm, & Suppression Systems

    32 - Fire Detection, Alarm, & Suppression Systems

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    34/35

    MISSOURI DIVISIONOF FIRE SAFETY

    FIRE FIGHTER I & II PRACTICAL SKILLS

    Sill Objective: The candidate, given a supply of 2 1/2" or 3" hose in an apparatus hose bed, shall

    connect two 50' sections of hose to a fire department sprinkler connection and the apparatus. The

    candidate shall then identify the normal minimum water pressure that should be applied to the

    sprinkler system.

    Students are allowed two chances at each skill for successful completion. Any step listed in

    italics missed shall result in failure of the skill. Otherwise, students are allowed to miss a maxi-

    mum of one of the following steps and pass this skill.

    Fire Suppression Systems - NFPA 1001-2008, 5.3.14Demonstrate Connecting to a Fire Department Connection

    Items to be checked

    If the candidate

    1. First, obtains necessary tools and equipment such as two spanner wrenches

    2. Wears gloves during the skill

    3. Removes 50 feet of hose from the hose bed neatly and in organized fashion

    4. Connects female coupling to fire apparatus discharge

    5. Connects male coupling to fire department sprinkler connection

    6. Repeats steps 3, 4, & 5

    7. Arranges all hose in an orderly fashion

    8. Identifies that water pressure in hose lines should be a minimum of 150 psi

    Fire Detection, Alarm, & Suppression Systems - 33

  • 7/29/2019 Fire Detection Alarms, Suppression Systems.pdf

    35/35

    MISSOURI DIVISIONOF FIRE SAFETY

    FIRE FIGHTER I & II PRACTICAL SKILLS

    Skill Objective: The candidate, given a flowing, open sprinkler head, shall stop the flow of

    water using a sprinkler wedge(s) or a set of sprinkler tongs. The candidate shall then identify the

    type and temperature classification of the sprinkler head.

    Skill Procedure: The evaluator shall set up a sprinkler head that has opened and is flowing

    water. The candidate shall stop the flow of water using wedges or tongs his/her department has

    available for the purpose. Then have the candidate identify the type and temperature classifica-

    tion of the sprinkler head.

    Students are allowed two chances at each skill for successful completion. Any step listed in

    italics missed shall result in failure of the skill. Otherwise, students are allowed to miss a maxi-mum of one of the following steps and pass this skill.

    Items to be checked

    If the candidate:

    1. Knows the location of sprinkler stops for his/her department

    2. Inserts the sprinkler stop(s) without complication

    3. Adequately stops the flow of water

    4. Can identify whether the sprinkler head is an upright or pendant style

    5. Can identify the temperature classification of the sprinkler head

    Fire Suppression Systems - NFPA 1001-2008, 5.3.14Demonstrate Stopping the Flow From a Sprinkler Head