30
Fan-Powered Low-Height Parallel VAV-PRC008-EN LHP 1 Service Model Number Description LHP 2 – 3 General Data – Valve/Controller Airflow Guidelines LHP 4 Performance Data – Air Pressure Requirements LHP 5 – 6 Performance Data – Fan Curves LHP 7 –8 Performance Data – Hot Water Coil LHP 9 – 10 Performance Data – Electrical Data LHP 11 – 12 Performance Data – Acoustics LHP 13 – 16 Dimensional Data LHP 17 – 26 Mechanical Specifications LHP 27 – 29 Table of Contents

Fan-Powered Table of Low-Height Contents Parallel

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

VAV-PRC008-EN LHP 1

Service Model Number Description LHP 2 – 3

General Data – Valve/Controller Airflow Guidelines LHP 4

Performance Data – Air Pressure Requirements LHP 5 – 6

Performance Data – Fan Curves LHP 7 –8

Performance Data – Hot Water Coil LHP 9 – 10

Performance Data – Electrical Data LHP 11 – 12

Performance Data – Acoustics LHP 13 – 16

Dimensional Data LHP 17 – 26

Mechanical Specifications LHP 27 – 29

Table ofContents

Page 2: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

LHP 2 VAV-PRC008-EN

Low-Height Parallel Fan-Powered Terminal UnitsThe features of the low-height parallelfan-powered terminal units aredescribed by the product categoriesshown in bold. Within each categorythe options available are listed.

ServiceModel NumberDescription

Digit 1, 2—Unit TypeLP VariTrane fan-powered low-height parallel

Digit 3—ReheatC Cooling OnlyE Electric HeatW Hot Water Heat

Digit 4—Development SequenceF Sixth

Digit 5, 6—Primary Air Valve05 5” inlet (350 maximum cfm)06 6" inlet (500 maximum cfm)08 8" inlet (900 maximum cfm)RT 8" x 14" inlet (1800 maximum

cfm)

Digit 7, 8—Secondary Air Valve00 N/A

Digit 9—FanV 08SQ 500 nominal cfmW 09SQ 900 nominal cfmX 10SQ 1800 nominal cfm

Digit 10, 11—Design SequenceE0 Fifth (factory assigned)

Digit 12, 13, 14, 15—ControlsENON No controls, field-installed

DDC/electricPNON No controls, field-installed

pneumaticDD00 Trane elec actuator onlyDD01 DDC – cooling onlyDD02 DDC – N.C. on/off water valve

controlDD03 DDC – prop hot water valve

controlDD04 DDC – on/off electric heat

controlDD05 DDC – pulse-width modulation

controlDD07 DDC – N.O. on/off water valve

controlDD11 LonTalk DDC Controller—

Cooling onlyDD12 LonTalk DDC Controller w/ N.C.

on/off hot water controlDD13 LonTalk DDC Controller w/

proportional hot water controlDD14 LonTalk DDC Controller–on/off

electric heat controlDD15 LonTalk DDC Controller w/

pulse-width modulationelectric heat control

DD17 LonTalk DDC Controller w/ N.O.on/off hot water control

FM00 FM customer actuator &control

FM01 FM Trane actuator w/customer-supplied controller

HNY2 FM Honeywell W7751HINV3 FM Invensys MNL-V2RPWR1 FM Siemens 540-100 w/

GDE131.1 actuator

PWR2 FM Siemens 540-103 w/GDE131/1 actuator

PW12 FM Siemens 550-065PW13 FM Siemens 550-067VMA2 FM Johnson VMA-1420EI05 Analog – fan-powered parallel

with optional on/off reheatPN00 PN – N.O. Trane pneumatic

actuator, R.A. statPN05 PN – N.O. PVR, R.A. stat

Notes:N.C. = Normally-closedN.O. = Normally-openedDA Stat = Direct-acting pneumatic t-stat

(by others)RA Stat = Reverse-acting pneumatic t-stat

(by others)PN = PneumaticFM = Factory installation of customer-

supplied controllerPVR = Pneumatic Volume Regulator

Digit 16—InsulationA 1/2" Matte-facedB 1" Matte-facedC 1/2" Foil-facedD 1" Foil-facedF 1" Double-wallG 3/8" Closed-cell

Digit 17—Motor TypeD PSC MotorE High-efficiency motor (ECM)

Digit 18—Motor Voltage1 115/60/12 277/60/13 347/60/15 230/50/1

Digit 19—Outlet Connection1 Flanged2 Slip & Drive

Digit 20—Not Used0 N/A

Digit 21—Water Coil0 None1 1-Row–Plenum inlet installed2 2-Row–Plenum inlet installed3 1-Row–Discharge installed, LH4 1-Row–Discharge installed, RH5 2-Row–Discharge installed, LH6 2-Row–Discharge installed, RH

Digit 22—Electrical ConnectionsL Left (airflow hitting you in theface)

Digit 23—Transformer0 N/A (provided as standard)

Digit 24—Disconnect Switch0 NoneW With

Note: LPCF, LPWF – Toggle DisconnectLPEF – Door Interlocking Power

LPCF

LPWF

LPEF

Page 3: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

VAV-PRC008-EN LHP 3

ServiceModel NumberDescription

Digit 25—Power Fuse0 NoneW With

Digit 26—Electric Heat Voltage0 NoneA 208/60/1B 208/60/3C 240/60/1D 277/60/1E 480/60/1F 480/60/3G 347/60/1H 575/60/3J 380/50/3

Digit 27, 28, 29—Electric Heat kW000 None005 0.5 kW010 1.0 kW015 1.5 kW020 2.0 kW025 2.5 kW030 3.0 kW035 3.5 kW040 4.0 kW045 4.5 kW050 5.0 kW055 5.5 kW060 6.0 kW065 6.5 kW070 7.0 kW075 7.5 kW080 8.0 kW090 9.0 kW100 10.0 kW110 11.0 kW120 12.0 kW130 13.0 kW140 14.0 kW

Digit 30—Electric Heat Stages0 None1 1 Stage2 2 Stages Equal

Digit 31—Contactors0 None1 24-volt magnetic2 24-volt mercury3 PE with magnetic4 PE with mercury

Digit 32—Airflow Switch0 NoneW With

Page 4: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

LHP 4 VAV-PRC008-EN

General Data—Valve/ControllerAirflow Guidelines

Primary Airflow Control Factory Settings – I-PControl Air Valve Maximum Valve Maximum Controller Minimum Controller Constant Volume

Type Size (in.) Cfm Cfm Cfm Cfm

5 350 40–350 0, 40–350 40–350Direct Digital Control/ 6 500 60–500 0, 60–500 60–500

UCM 8 900 105–900 0, 105–900 105–9008x14 2200 200–2200 0, 220–2200 220–2200

5 350 63–350 0, 63–350 63–350Pneumatic with 6 500 73–500 0, 73–500 73–500

Volume Regulator 8 900 134–900 0, 134–900 134–9008x14 2100 297–2100 0, 297–2100 297–2100

5 350 82–350 0, 82–350 82–350Analog Electronic 6 500 120–500 0, 120–500 120–500

8 900 210–900 0, 210–900 210–9008x14 2200 440–2200 0, 440–2200 440–2200

Primary Airflow Control Factory Settings – SIControl Air Valve Maximum Valve Maximum Controller Minimum Controller Constant Volume

Type Size (in.) L/s L/s L/s L/s

5 165 19–165 0, 19–165 19–165Direct Digital Control/ 6 236 28–236 0, 28–236 28–236

UCM 8 425 50–425 0, 50–425 50–4258x14 1038 104–1038 0, 104–1038 104–1038

5 165 30–165 0, 30–165 30–165Pneumatic with 6 236 35–236 0, 35–236 35–236

Volume Regulator 8 425 63–425 0, 63–425 63–4258x14 991 140–991 0, 140–991 140–991

5 165 39–165 0, 39–165 39–165Analog Electronic 6 236 57–236 0, 57–236 57–236

8 425 100–425 0, 100–425 100–4258x14 1038 208–1038 0, 208–1038 208–1038

Note: Maximum airflow must be greater than or equal to minimum airflow.

Page 5: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

VAV-PRC008-EN LHP 5

PerformanceData—Air PressureRequirements (I-P)

Notes:1. Units with Electric Coils per fan size add 0.01" (3 Pa) to cooling

only value.2. HW Coil only pressure drops are just for the heating coil.

Unit Air Pressure Drop – in. wg (I-P)Fan/Inlet Airflow Cooling Only Unit

Size Cfm (in. wg)

08SQ–05 150 0.01200 0.02250 0.03350 0.05

08SQ–06 200 0.01300 0.04400 0.06500 0.09

08SQ–08 400 0.01600 0.09800 0.16900 0.20

09SQ–06 200 0.01300 0.04400 0.06500 0.09

09SQ–08 400 0.01600 0.09800 0.16900 0.20

09SQ–8x14 700 0.101100 0.251500 0.471900 0.75

10SQ–08 400 0.01600 0.09800 0.18900 0.24

10SQ–8x14 725 0.181000 0.361200 0.531450 0.78

Attenuator AirPressure Drop (I-P)Fan PlenumSize Cfm Attenuator

08SQ 150 0.01250 0.03350 0.05450 0.07

09SQ 350 0.05500 0.08650 0.13800 0.18

10SQ not available

Note: HW Coil Only pressure drops do not include unitpressure drop.

Coil Air Pressure Drop – in. wg (I-P)Fan Airflow 1-Row HW 2-Row HWSize Cfm (in. wg) (in. wg)

08SQ 100 0.00 0.01200 0.01 0.02300 0.02 0.04400 0.03 0.06450 0.04 0.07

09SQ 250 0.01 0.03400 0.03 0.06550 0.05 0.10700 0.08 0.15850 0.11 0.20

10SQ 725 0.09 0.17800 0.11 0.20900 0.13 0.241000 0.16 0.291100 0.19 0.331150 0.20 0.35

Page 6: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

LHP 6 VAV-PRC008-EN

PerformanceData—Air PressureRequirements (SI)

Fan PlenumSize L/s Attenuator

08SQ 71 0.01118 0.01165 0.02212 0.02

09SQ 165 0.02236 0.03307 0.04378 0.05

10SQ not available

Attenuator AirPressure Drop (SI)

Coil Air Pressure Drop – Pa (SI)Fan Airflow 1-Row HW 2-Row HWSize L/s (Pa) (Pa)

08SQ 47 1 294 2 5142 4 10189 7 15212 9 18

09SQ 118 3 7189 7 15260 12 25330 19 36401 27 51

10SQ 342 22 43375 26 49425 33 60475 40 72520 46 82543 49 87

Note: HW Coil Only pressure drops do not include unitpressure drop.

Unit Air Pressure Drop – Pa (SI)Inlet/Fan Airflow Cooling Only Unit

Size L/s (Pa)

08SQ–05 71 294 5118 7165 13

08SQ–06 200 0.01142 10189 16236 24

08SQ–08 189 2283 21378 40425 51

09SQ–06 94 2142 10189 16236 24

09SQ–08 189 2283 21378 40425 51

09SQ–8x14 330 26519 63708 116897 185

10SQ–08 189 2283 23378 45425 59

10SQ–8x14 345 47475 91565 131685 195

Notes:1. Units with Electric Coils per fan size add 0.01" (3 Pa) to cooling

only value.2. HW Coil only pressure drops are just for the heating coil.

Page 7: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

VAV-PRC008-EN LHP 7

PerformanceData—Fan Curves

Notes:

1. When attenuator is required, addinlet attenuator pressure to dischargestatic pressure for final fan performance.

Airflow

Dis

char

ge

Sta

tic

Pre

ssu

re

25

50

75

189 236 273 330 378

Cfm

L/s

Pa In. wg Low-Height Parallel 09SQ—PSC

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

400 500 600 700 800 900 1000

174

199

150

125

100

472425

410 c

fm m

in(1

93 L

/s)LPCF and LPEF maximum

Minimum

1-row coil maximum

2-row coil maximum

Airflow

Dis

ch

arg

e S

tati

c P

ressu

re

25

50

75

11894 142 212 260

Cfm

L/s

Pa In. wg Low-Height Parallel 08SQ—PSC

0.10

0.20

0.30

0.40

0.50

0.60

150 200 250 300 350 400 450 500 550

125

150

100

165 189 23671175 c

fm m

in(8

3 L

/s)

Low-Height Parallel 10SQ—PSC

0.10

0.20

0.30

300 500 700 900 1100

Airflow

Dis

ch

arg

e S

tati

c P

res

su

re

25

50

75

142 236 330 425 519

Cfm

L/s

Pa In. wg

0.80199

0.70174

0.60150

0.50125

0.40100

1500

708

1300

614

Page 8: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

LHP 8 VAV-PRC008-EN

ECM Data—Fan Curves

Airflow

Dis

char

ge S

tatic

Pre

ssur

e

25

50

75

24 71 118 165 212

Cfm

L/s

Pa In. wg LPxF 08SQ—ECM

0.10

0.20

0.30

0.40

0.50

50 150 250 350 450

125

100

100

cfm

min

(47

L/s

)

Airflow

Dis

char

ge S

tatic

Pre

ssur

e

25

50

75

94 142 189 236

Cfm

L/s

Pa In. wg LPxF 09SQ—ECM

0.10

0.20

0.30

0.40

0.50

200 300 400 500 600 700 800 900 1000 1100

125

100

283 519472425378330

25

0 c

fm m

in(1

18

L/s

)

LPCF and LPEF maximum

Minimum

1-row coil maximum

2-row coil maximum

Notes:

1. ECMs (Electrically CommutatedMotors) are ideal for systems seekingmaximum motor efficiency.

2. When attenuator is required, add inletattenuator pressure to dischargestatic pressure for final fan performance.

Page 9: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

VAV-PRC008-EN LHP 9

PerformanceData—Hot WaterCoil (I-P)

Fan Size 10SQ (I-P)Water

Pressure Airflow (Cfm)Rows Gpm Drop (ft) 700 800 900 1000 1100 1200 1240

1-Row 0.7 1.52 17.64 18.47 19.20 19.86 20.46 — —Capacity 1.0 2.82 19.71 20.79 21.77 22.66 23.49 24.25 24.53

MBH 1.5 5.72 21.59 22.94 24.17 25.32 26.39 27.39 27.772.0 9.48 22.74 24.20 25.55 26.85 28.07 29.22 29.672.5 14.08 23.49 25.05 26.51 27.89 29.18 30.43 30.91

2-Row 1.5 1.06 33.60 35.36 36.86 38.16 39.30 — —Capacity 2.0 3.09 36.26 38.38 40.22 41.84 43.27 — —

MBH 3.0 6.34 39.22 41.80 44.08 46.10 47.91 — —4.0 10.60 40.83 43.69 46.22 48.49 50.54 — —5.0 15.84 41.85 44.88 47.59 50.02 52.22 — —

Fan Sizes 08SQ & 09SQ (I-P)Water

Pressure Airflow (Cfm)Rows Gpm Drop (ft) 100 200 300 400 500 600 700 800 900

1-Row 0.5 0.77 7.58 10.13 11.78 12.98 13.92 14.68 15.32 15.87 16.35Capacity 1.0 2.57 8.45 11.86 14.10 15.85 17.35 18.69 19.86 20.91 21.85

MBH 1.5 5.23 8.78 12.56 15.12 17.17 18.93 20.49 21.89 23.21 24.432.0 8.69 8.95 12.94 15.69 17.92 19.85 21.57 23.14 24.58 25.912.5 12.89 9.06 13.18 16.05 18.40 20.44 22.28 23.96 25.51 26.96

2-Row 1.0 0.79 9.63 15.93 20.20 23.26 25.60 27.47 28.94 30.14 31.13Capacity 2.0 2.64 10.07 17.49 23.10 27.48 31.02 33.93 36.37 38.46 40.26

MBH 3.0 5.39 10.22 18.04 24.17 29.13 33.22 36.68 39.64 42.21 44.464.0 8.98 10.29 18.32 24.74 30.00 34.42 38.18 41.45 44.31 46.845.0 13.36 10.34 18.49 25.08 30.55 35.16 39.13 42.60 45.65 48.37

1. Fouling Factor = 0.000252. The off-coil temperature of the hot water coil on parallel fan-powered units must not exceed 140°F when mounted

on plenum inlet.3. The following equations may be used in calculating Leaving Air Temperature (LAT) and Water Temperature

Difference (WTD).

4. Capacity based on 70°F entering air temperature and 180°F entering water temperature. Refer to correction factorsfor different entering conditions.

Water Coil Notes (I-P)

Temperature Correction Factors for Water Pressure Drop (WPD)

Average Water Temperature 200 190 180 170 160 150 140 130 120 110Correction Factor 0.970 0.985 1.000 1.020 1.030 1.050 1.080 1.100 1.130 1.150

Temperature Correction Factors for Coil Capacity (MBH)

Entering Water Minus Entering Air 40 50 60 70 80 90 100 110 120 130Correction Factor 0.355 0.446 0.537 0.629 0.722 0.814 0.907 1.000 1.093 1.187

(LAT = EAT + MBH x 921.7Cfm ) WTD = EWT - LWT = 2 x MBH

Gpm( )

Page 10: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

LHP 10 VAV-PRC008-EN

PerformanceData—Hot WaterCoil (SI)

Fan Sizes 08SQ & 09SQ (SI)Water

Pressure Airflow (L/s)Rows L/s Drop (kPa) 47 94 142 189 236 283 330 378 425

1-Row 0.03 2.30 2.22 2.97 3.45 3.80 4.08 4.30 4.49 4.65 4.79Capacity 0.06 7.67 2.48 3.48 4.13 4.65 5.09 5.48 5.82 6.13 6.40

MBH 0.09 15.60 2.57 3.68 4.43 5.03 5.55 6.01 6.42 6.80 7.160.13 25.92 2.62 3.79 4.60 5.25 5.82 6.32 6.78 7.20 7.590.16 38.45 2.66 3.86 4.70 5.39 5.99 6.53 7.02 7.48 7.90

2-Row 0.06 2.36 2.82 4.67 5.92 6.82 7.50 8.05 8.48 8.83 9.12Capacity 0.13 7.88 2.95 5.13 6.77 8.05 9.09 9.94 10.66 11.27 11.80

MBH 0.19 16.08 3.00 5.29 7.08 8.54 9.74 10.75 11.62 12.37 13.030.25 26.79 3.02 5.37 7.25 8.79 10.09 11.19 12.15 12.99 13.730.32 39.86 3.03 5.42 7.35 8.95 10.31 11.47 12.49 13.38 14.18

1. Fouling Factor = 0.000252. The off-coil temperature of the hot water coil on parallel fan-powered units must not exceed 60°C when mounted

on plenum inlet.3. The following equations may be used in calculating Leaving Air Temperature (LAT) and Water Temperature

Difference (WTD).

4. Capacity based on 21°C entering air temperature and 82°C entering water temperature. Refer to correction factorsfor different entering conditions.

Water Coil Notes (SI)

Temperature Correction Factors for Water Pressure Drop (kPa)

Average Water Temperature 93 88 82 77 71 66 60 54 49 43Correction Factor 0.970 0.985 1.000 1.020 1.030 1.050 1.080 1.100 1.130 1.150

Temperature Correction Factors for Coil Capacity (kW)

Entering Water Minus Entering Air 22 27 33 38 44 50 55 61 67 72Correction Factor 0.355 0.446 0.537 0.629 0.722 0.814 0.907 1.000 1.093 1.187

LAT = EAT +L/s

kW x 0.83 WTD = EWT - LWT = )(4.19)L/s)( kW(

Fan Size 10SQ (SI)Water

Pressure Airflow (L/s)Rows L/s Drop (kPa) 330 378 425 472 519 566 585

1-Row 0.04 4.53 5.17 5.41 5.63 5.82 6.00 — —Capacity 0.06 8.41 5.78 6.09 6.38 6.64 6.88 7.11 7.19

MBH 0.09 17.06 6.33 6.72 7.08 7.42 7.73 8.03 8.140.13 28.28 6.67 7.09 7.49 7.87 8.23 8.56 8.700.16 42.00 6.88 7.34 7.77 8.17 8.55 8.92 9.06

2-Row 0.09 3.16 9.85 10.36 10.80 11.18 11.52 — —Capacity 0.13 9.22 10.63 11.25 11.79 12.26 12.68 — —

MBH 0.19 18.91 11.50 12.25 12.92 13.51 14.04 — —0.25 31.62 11.97 12.81 13.55 14.21 14.81 — —0.32 47.25 12.27 13.15 13.95 14.66 15.31 — —

Page 11: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

VAV-PRC008-EN LHP 11

PerformanceData—Electrical Data

Notes:1. Coils available with 24 VAC magnetic or mercury contactors, load carrying P.E. switches, and P.E. switch with magnetic or mercury contractors.2. Available kW increments are by 0.5 from 0.5 kW to 8.0 kW and by 1.0 kW from 9.0 to 14.0 kW.3. Each stage will be equal in kW output.4. All heaters contain an auto thermal cutout and a manual reset cutout.5. The current amp draw for the heater elements is calculated by the formula below.6. Only two stages of electric reheat available with Trane controls.

LPEF—Electric Coil kW Guidelines – Minimum to Maximum (PSC Motor Units)Fan Single-Phase Voltage Three-Phase VoltageSize Stages 120V 208V 240V 277V 347V 480V 208V 480V 600V

08SQ 1 0.5*–4.5* 0.5–7.0 0.5–7.0 0.5–7.0 0.5–7.0 0.5–7.0 0.5–7.0 1.0–7.0 1.5–7.02 0.5*–4.5* 0.5–7.0 0.5–7.0 1.0–7.0 1.0–7.0 1.0–7.0 1.0–7.0 2.0–7.0 3.0–7.0

3** — — — — — — — — —09SQ 1 0.5*–4.5* 0.5–8.0 0.5–10.0 0.5–12.0 0.5–14.0 0.5–14.0 0.5–14.0 1.0–14.0 1.5–14.0

2 0.5*–4.5* 0.5–8.0 0.5–10.0 1.0–12.0 1.0–14.0 1.0–14.0 1.0–14.0 2.0–14.0 3.0–14.03** — — — — — — — — —

10SQ 1 0.5*–4.0* 0.5–8.0 0.5–9.0 0.5–12.0 0.5–14.0 0.5–14.0 1.0–13.0 1.0–14.0 1.5–12.02 0.5*–4.0* 0.5–8.0 0.5–9.0 1.0–12.0 1.0–14.0 1.0–14.0 1.0–13.0 2.0–14.0 3.0–12.0

3** — — — — — — — — —*Special heater offering** Three stages of electric heat available only with pneumatic controls.

LPEF–Electric Coil kW Guidelines – Minimum to Maximum (ECM Units)Fan Single-Phase Voltage Three-Phase VoltageSize Stages 120V * 208V 240V 277V 347V 480V 208V 480V 600V

08SQ 1 0.5*–5.0* 0.5–7.0 0.5–7.0 0.5–7.0 — 0.5–7.0 0.5–7.0 1.0–7.0 —2 0.5*–5.0* 0.5–7.0 0.5–7.0 1.0–7.0 — 1.0–7.0 1.0–7.0 2.0–7.0 —3 — — — — — — — — —

09SQ 1 0.5*–4.5* 0.5–8.0 0.5–9.0 0.5–12.0 — 0.5–14.0 0.5–14.0 1.0–14.0 —2 0.5*–4.5* 0.5–8.0 0.5–9.0 1.0–12.0 — 1.0–14.0 1.0–14.0 2.0–14.0 —3 — — — — — — — — —

*Special heater offering

Formulas

Minimum Circuit Ampacity (MCA) Equation• MCA = (motor amps + heater amps) x 1.25

Maximum Overcurrent Protection (MOP) Equation• MOP = (2.25 x motor amps) + heater amps

General Sizing Rules:• If MOP = 15, then fuse size = 15

• If MOP = 19, then fuse size = 15 with one exception. If heateramps x 1.25 > 15, then fuse size = 20.

• If MOP ≤ MCA, then choose next fuse size greater than MCA.

• Control fusing not applicable.

• Standard Fuse Sizes: 15, 20, 25, 30, 35, 40, 45, 50, and 60.

Notes:1. Electric Heat Units - Units with Primary Voltage of 208/60/1, 208/

60/3 or 240/60/1 use 115 VAC fan motors.2. Electric Heat Units - Units with Primary Voltage of 277/60/1,

480/60/1 or 480/60/3 use 277 VAC fan motors.3. Electric Heat Units - Units with Primary Voltage of 347/60/1 or

575/60/3 use 347 VAC fan motors.4. Values are for standard, single-speed, permanent split capacitor

type motors. Consult factory for non-standard motorperformance.

5. Motor amps for 10SQ are total amps for two motors.

Useful formulas:

kW = 1214 x L/s x ATD

1φamps = kW x 1000Primary Voltage

ATD = kW x 3145Cfm

3145Cfm x ATDkW =

3φamps =kW x 1000

Primary Voltage x √ 3

1214 x L/sATD = kW

Fan Electrical Performance (PSC)Maximum Fan Motor Amperage (FLA)

Fan Size HP 115 VAC 277 VAC 347 VAC

08SQ 1/3 5.5 2.5 1.809SQ 1/3 5.5 2.5 1.810SQ* 2 x 1/8 9.4 3.5 3.0

Fan Size HP 115 VAC 277 VAC

08SQ 1/2 2.0 1.109SQ 1/2 6.7 3.6

Fan Electrical Performance (ECM)Maximum Fan Motor Amperage (FLA)

Page 12: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

LHP 12 VAV-PRC008-EN

PerformanceData—Electrical Data

Unit L/skW 08SQ 09SQ 10SQ

0.5 82 208 3401 82 208 340

1.5 82 208 3402 82 208 340

2.5 82 208 3403 82 208 340

3.5 95 208 3404 109 208 340

4.5 123 208 3405 137 208 340

5.5 151 208 3406 164 208 340

6.5 178 208 3407 192 208 340

7.5 — 221 3408 — 234 3409 — 261 34010 — 287 34011 — 313 34012 — 340 34013 — 366 34014 — 393 —

Minimum Unit ElectricHeat L/s Guidelines (PSC)

Unit CfmkW 08SQ 09SQ 10SQ

0.5 173 440 7201 173 440 720

1.5 173 440 7202 173 440 720

2.5 173 440 7203 173 440 720

3.5 202 440 7204 232 440 720

4.5 261 440 7205 290 440 720

5.5 319 440 7206 349 440 720

6.5 378 440 7207 407 440 720

7.5 — 468 7208 — 496 7209 — 552 72010 — 608 72011 — 664 72012 — 720 72013 — 776 72014 — 832 —

Minimum Unit ElectricHeat Cfm Guidelines (PSC)

Unit CfmkW 08SQ 09SQ

0.5 188 4901 188 490

1.5 188 4902 188 490

2.5 188 4903 188 490

3.5 220 4904 251 490

4.5 283 4905 314 490

5.5 346 4906 377 490

6.5 409 4907 440 490

7.5 — 5148 — 5399 — 58810 — 63711 — 68512 — 73413 — 78314 — 832

Minimum Unit ElectricHeat Cfm Guidelines (ECM)

Unit L/skW 08SQ 09SQ

0.5 89 2311 89 231

1.5 89 2312 89 231

2.5 89 2313 89 231

3.5 104 2314 118 231

4.5 133 2315 148 231

5.5 163 2316 178 231

6.5 193 2317 208 231

7.5 — 2438 — 2549 — 27710 — 30011 — 32312 — 34713 — 37014 — 393

Minimum Unit ElectricHeat L/s Guidelines (ECM)

Page 13: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

VAV-PRC008-EN LHP 13

PerformanceData—Acoustics

Discharge Sound Power (dB)Discharge Sound Power (dB)

Fan Inlet 0.5" ∆∆∆∆∆Ps 1.0" ∆∆∆∆∆Ps 2.0" ∆∆∆∆∆Ps 3.0" ∆∆∆∆∆PsSize Size Cfm L/s 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7

08SQ 5 150 71 50 46 43 39 32 29 53 49 48 45 38 38 53 50 49 47 44 46 55 52 51 49 47 50200 94 53 49 46 42 36 31 56 52 50 47 40 39 57 54 52 50 46 47 58 55 54 52 49 51250 118 57 52 48 45 40 33 58 55 52 48 42 40 60 58 55 53 48 48 61 59 57 54 51 52300 142 60 54 50 48 43 37 61 58 54 50 45 42 64 60 58 55 50 48 64 62 60 57 54 54350 165 62 57 53 50 46 41 64 60 56 53 49 44 66 63 60 57 51 49 68 66 63 61 58 55

08SQ 6 200 94 51 47 44 40 34 29 53 50 49 44 38 37 56 53 51 50 47 48 58 55 53 51 49 5208SQ 280 132 55 51 48 44 40 33 57 54 53 48 44 40 60 57 55 53 50 48 62 59 57 55 52 52

350 165 58 55 52 48 44 37 60 58 56 52 48 42 63 60 58 56 53 49 65 62 60 58 55 53430 203 62 60 56 52 50 42 63 62 59 56 54 46 66 64 62 59 56 50 68 66 64 61 58 54500 236 66 63 60 56 53 45 66 65 62 59 57 49 68 67 65 62 60 53 70 69 67 64 62 56

08SQ 8 350 165 53 49 47 44 39 31 56 53 52 48 44 40 60 58 56 53 50 49 62 60 59 55 53 5209SQ 500 236 56 53 51 48 44 36 60 57 55 52 48 43 64 62 60 57 54 51 66 64 63 59 57 54

600 283 59 56 53 50 47 39 62 59 58 54 51 45 66 65 63 60 57 53 68 67 65 62 59 56800 378 63 61 58 56 52 44 66 64 62 59 56 49 70 69 67 64 62 56 73 72 70 68 64 59900 425 65 63 60 58 55 47 68 66 63 61 58 51 72 70 68 66 63 57 75 73 72 70 67 61

09SQ 8x14 780 368 59 61 57 52 48 45 64 67 61 56 52 54 68 68 71 61 56 55 72 72 77 66 59 561100 519 61 62 60 54 52 48 65 67 65 59 56 55 71 70 74 64 61 58 74 74 79 68 63 591500 708 64 65 64 58 56 51 68 67 70 62 61 57 74 73 78 69 66 62 78 76 81 72 68 631800 850 66 67 67 61 59 53 70 69 73 65 63 58 76 74 79 71 68 63 78 76 81 73 70 65

10SQ 8x14 780 368 60 58 51 48 41 34 63 64 59 57 45 42 65 66 65 65 51 50 67 67 68 69 56 541170 552 — — — — — — 67 67 61 58 51 46 70 72 69 68 56 52 71 74 74 73 59 561560 736 — — — — — — — — — — — — 73 74 71 68 60 55 74 77 75 74 63 591800 850 — — — — — — — — — — — — 74 75 74 70 63 57 76 78 76 74 65 602000 944 — — — — — — — — — — — — 75 76 77 71 65 59 77 78 77 74 67 61

1. All data are measured in accordance with Industry Standard ARI 880-98.2. All sound power levels, dB re: 10-12 Watts.3. Where ∆Ps is inlet static pressure minus discharge static pressure.

Radiated Sound Power (dB)Radiated Sound Power (dB)

Fan Inlet 0.5" ∆∆∆∆∆Ps 1.0" ∆∆∆∆∆Ps 2.0" ∆∆∆∆∆Ps 3.0" ∆∆∆∆∆PsSize Size Cfm L/s 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7

08SQ 5 150 71 53 44 38 33 28 21 54 45 40 36 31 25 54 47 42 40 38 34 56 49 45 46 42 38200 94 55 46 41 35 29 21 56 48 42 37 32 25 57 50 45 42 38 34 58 51 47 46 42 38250 118 56 49 44 36 30 22 59 50 44 38 33 26 60 52 48 43 39 34 61 53 48 47 43 38300 142 59 50 45 38 31 24 62 52 47 40 34 28 62 54 50 45 40 34 63 55 50 48 44 38350 165 62 51 46 39 33 26 65 55 50 43 36 30 65 56 51 47 41 35 65 57 53 50 45 39

08SQ 6 200 94 53 45 40 33 27 21 56 48 43 35 29 22 57 48 44 40 37 32 58 50 45 45 42 3709SQ 280 132 54 46 40 33 27 22 57 50 45 37 30 24 59 51 47 42 37 33 61 53 48 46 42 37

350 165 54 46 41 34 28 22 58 51 46 38 31 25 62 54 49 44 38 34 63 55 50 47 43 38430 203 56 49 43 36 30 25 60 53 48 40 33 27 64 57 52 46 39 35 66 58 53 49 43 38500 236 59 53 47 40 34 29 62 55 50 42 35 30 66 58 53 47 41 36 68 60 55 51 44 39

08SQ 8 350 165 57 50 45 38 34 23 59 54 46 40 34 26 61 55 48 43 39 35 63 56 50 47 44 3709SQ 500 236 60 53 47 40 34 24 62 56 49 42 36 28 65 58 51 46 41 35 67 60 54 50 45 38

600 283 62 54 49 41 34 24 65 58 51 44 37 29 68 60 54 47 42 35 70 62 56 51 46 38800 378 65 57 52 44 36 26 69 61 54 46 40 32 73 64 58 50 44 36 74 66 60 54 48 40900 425 66 58 53 45 37 28 71 63 56 48 41 33 75 66 60 52 45 37 76 67 62 55 48 40

09SQ 8x14 780 368 62 59 55 48 40 31 66 61 57 51 44 38 70 63 61 53 48 43 72 66 63 55 51 461100 519 64 60 56 47 40 32 68 63 60 52 45 38 72 66 65 57 52 45 74 68 66 59 54 481500 708 68 62 58 47 39 32 71 65 64 53 46 39 75 69 70 62 56 47 77 72 70 63 58 501800 850 71 63 59 47 39 32 73 67 68 54 47 39 77 71 72 62 56 47 79 73 73 64 59 50

10SQ 8x14 780 368 60 55 47 41 32 28 63 61 55 48 38 34 66 63 60 55 45 41 69 66 64 59 50 451170 552 — — — — — — 68 65 57 50 41 39 71 69 66 59 48 45 74 74 69 64 53 481560 736 — — — — — — — — — — — — 74 72 66 59 49 47 76 74 71 65 54 501800 850 — — — — — — — — — — — — 75 74 68 61 51 49 77 76 72 65 55 512000 944 — — — — — — — — — — — — 76 75 70 62 52 50 78 77 72 65 55 52

1. All data are measured in accordance with Industry Standard ARI 880-98.2. All sound power levels, dB re: 10-12 Watts.3. Where ∆Ps is inlet static pressure minus discharge static pressure.

Page 14: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

LHP 14 VAV-PRC008-EN

PerformanceData—Acoustics

Fan Only Sound PowerOutlet Discharge Sound Power (dB) Radiated Sound Power (dB)

Fan Static Octave Bands Octave BandsSize (in. wg) Cfm L/s 2 3 4 5 6 7 2 3 4 5 6 7

08SQ 175 83 56 51 50 47 41 34 65 56 57 50 41 350.25 250 118 59 54 54 50 44 40 68 58 60 53 44 38

(63 Pa) 320 151 62 56 57 53 48 45 72 61 63 56 48 42400 189 66 60 60 58 54 51 75 64 65 61 52 47470 222 69 63 64 62 58 56 77 67 69 64 56 50

09SQ 400 189 65 59 57 54 48 44 69 65 62 56 46 380.25 500 236 66 60 58 56 49 46 70 66 64 58 48 40

(63 Pa) 700 330 69 63 62 61 54 53 72 69 68 64 54 46800 378 71 65 64 64 57 56 74 71 70 67 57 49900 425 73 68 68 67 61 61 77 74 72 69 60 53

10SQ 700 330 62 57 55 51 45 40 67 61 57 54 49 440.25 840 396 64 58 57 53 48 43 68 63 58 55 50 46

(63 Pa) 980 463 65 61 58 56 51 47 70 65 60 57 53 501200 566 69 65 63 61 56 54 73 69 64 61 57 551400 661 72 69 66 65 60 57 76 72 67 64 60 58

1. All data are measured in accordance with Industry Standard ARI 880-98.2. All sound power levels, dB re: 10-12 Watts.

ARI 885-98 RADIATED TRANSFER FUNCTION ASSUMPTIONS:Octave Band

2 3 4 5 6 7

Type 2- Mineral Fiber Insulation -18 -19 -20 -26 -31 -36Total dB reduction -18 -19 -20 -26 -31 -36Subtract from terminal unit sound power to determine radiated soundpressure in the space.

ARI 885-98-02add DISCHARGE TRANSFER FUNCTION ASSUMPTIONS:

Octave Band2 3 4 5 6 7

Medium Box (300-700 CFM) -27 -29 -40 -51 -53 -39Large Box (> 700 CFM) -29 -30 -41 -51 -52 -39Subtract from terminal unit sound power to determine discharge soundpressure in the space.

1. "—" represents NC Values below NC15.2. Where ∆Ps is inlet static pressure minus discharge static pressure.

Sound Noise Criteria (NC)Valve Only

Discharge RadiatedNC Level (∆(∆(∆(∆(∆Ps) NC Level (∆(∆(∆(∆(∆Ps)

Fan Inlet 0.5" 1.0" 2.0" 3.0" 0.5" 1.0" 2.0" 3.0"Size Size Cfm L/s (127 Pa) (254 Pa) (508 Pa) (762 Pa) (127 Pa) (254 Pa) (508 Pa) (762 Pa)

08SQ 5 150 71 — — — — — 15 15 19200 94 — — — 15 16 17 19 21250 118 — — 15 16 17 21 22 24300 142 — 15 17 20 21 25 25 26350 165 — 17 21 25 25 29 29 29

08SQ 6 200 94 — — — 16 — 17 19 2009SQ 280 132 — — — 16 15 19 21 24

350 165 — 15 17 20 15 20 25 26430 203 17 20 22 25 17 22 27 30500 236 21 24 26 29 21 25 30 32

08SQ 8 350 165 — — 15 17 19 22 24 2609SQ 500 236 — — 20 22 22 25 29 31

600 283 — 16 24 26 25 29 32 35800 378 19 22 29 32 29 34 39 40900 425 21 25 30 34 30 36 41 42

09SQ 8x14 780 368 17 25 26 31 30 32 36 381100 519 19 25 29 34 31 35 40 411500 708 22 25 32 36 33 39 46 461800 850 25 27 34 36 36 44 48 49

10SQ 8x14 780 368 21 24 25 24 31 35 391170 552 25 31 34 36 41 461560 736 34 37 44 471800 850 35 38 46 492000 944 36 38 47 50

Page 15: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

VAV-PRC008-EN LHP 15

PerformanceData—Acoustics

Octave Band2 3 4 5 6 7

Small Box (< 300 CFM) -24 -28 -39 -53 -59 -40Medium Box (300-700 CFM) -27 -29 -40 -51 -53 -39Large Box (> 700 CFM) -29 -30 -41 -51 -52 -39Subtract from terminal unit sound power to determine discharge soundpressure in the space.

ARI 885-98-02add DISCHARGE TRANSFER FUNCTION ASSUMPTIONS:

ARI 885-98 RADIATED TRANSFER FUNCTION ASSUMPTIONS:Octave Band

2 3 4 5 6 7

Type 2- Mineral Fiber Insulation -18 -19 -20 -26 -31 -36Total dB reduction -18 -19 -20 -26 -31 -36Subtract from terminal unit sound power to determine radiated soundpressure in the space.

Radiated Sound Power (dB)Valve OnlyARI ConditionsFan Inlet 1.5" Inlet Pressure (381 Pa)Size Size Cfm L/s 2 3 4 5 6 7

08SQ 5 250 118 59 50 46 41 36 3208SQ 6 400 189 62 55 50 42 36 3109SQ08SQ 8 700 330 69 61 55 47 40 3309SQ09SQ 8x14 1560 736 73 68 67 58 51 4310SQ 8x14 1560 736 73 71 64 56 47 46

Discharge Sound Power (dB)Valve OnlyARI ConditionsFan Inlet 1.5" Inlet Pressure (381 Pa)Size Size Cfm L/s 2 3 4 5 6 7

08SQ 5 250 118 60 57 55 51 45 4408SQ 6 400 189 64 62 59 56 54 4709SQ08SQ 8 700 330 67 65 63 60 57 5109SQ09SQ 8x14 1560 736 70 71 73 66 63 6010SQ 8x14 1560 736 71 72 69 65 59 53

Radiated Sound Power (dB)Fan OnlyARI ConditionsFan InletSize Size Cfm L/s 2 3 4 5 6 7

08SQ 5, 6, 8 460 217 76 66 69 63 55 5009SQ 6, 8, 8x14 900 425 77 74 72 69 60 5310SQ 8, 8x14 1420 670 76 72 67 64 60 58

Discharge Sound Power (dB)Fan OnlyARI ConditionsFan InletSize Size Cfm L/s 2 3 4 5 6 7

08SQ 5, 6, 8 460 217 68 62 63 62 58 5609SQ 6, 8, 8x14 900 425 73 68 68 67 61 6110SQ 8, 8x14 1420 670 72 69 66 65 60 57Notes:1. All sound data rated in accordance with current Industry

Standard ARI 880, version 1998.2. All sound power levels, dB re: 10-12 Watts.

Sound Noise Criteria (NC)Fan Only

RadiatedFan Outlet Discharge NC/NC withSize Cfm L/s Static NC Level Attenuator

08SQ 175 83 0.25 — 32/31250 118 0.25 — 35/ *320 151 0.25 — 38/ *400 189 0.25 19 41/ *470 222 0.25 22 45/ *

09SQ 400 189 0.25 15 37/36500 236 0.25 16 39/37700 330 0.25 20 44/40800 378 0.25 22 46/42900 425 0.25 26 48/46

10SQ 700 330 0.25 — 32/ *840 396 0.25 — 34/ *980 463 0.25 17 36/ *1200 566 0.25 22 40/ *1400 661 0.25 27 44/ *

*Attenuator not recommendedNotes:1. “–“ represents NC levels below NC 15.2. NC Values are calculated using current Industry Standard ARI

885, 2002 addendum to revision 1998. Radiated Transfer Functionobtained from Appendix E, Type 2Mineral Fiber Insulation.

Page 16: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

LHP 16 VAV-PRC008-EN

PerformanceData—Acoustics

Inlet Attenuator Appurtenance Effects(Fan Noise Only)

Discharge Sound Effect* (dB) Radiated Sound Effect* (dB)Fan 2 3 4 5 6 7 2 3 4 5 6 7

Matte-faced and foil-faced insulation**08SQ, 09SQ 2 3 4 5 5 6 2 0 -4 -8 -7 -7

Closed-cell insulation08SQ, 09SQ 2 3 4 5 4 5 2 1 2 -3 -4 -4

* Add to sound power, a negative effect represents a sound reduction, a positive effect represents asound increase** Note: Attenuators on double-wall units contain foil-faced insulation.

Cabinet Lining Appurtenance Effects(Fan Noise and Valve Noise)

Discharge Sound Effect* (dB) Radiated Sound Effect* (dB)Fan 2 3 4 5 6 7 2 3 4 5 6 7

Solid double-wall08SQ, 09SQ 1 0 2 3 4 6 2 1 2 5 9 13

Closed-cell insulation08SQ, 09SQ 2 1 3 2 2 2 2 2 4 5 5 8

*Add to sound power, a negative effect represents a sound reduction, a positive effect represents asound increase

Heating Coil Appurtenance EffectsDischarge Sound Effect* (dB) Radiated Sound Effect* (dB)

Fan 2 3 4 5 6 7 2 3 4 5 6 7

Hot Water Coil (Fan Noise)08SQ, 09SQ 3 3 4 5 4 5 2 2 3 3 3 4

Electric Heat08SQ, 09SQ 0 -1 0 1 1 3 1 1 1 2 2 3

*Add to sound power, a negative effect represents a sound reduction, a positive effect represents asound increase.

Page 17: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

VAV-PRC008-EN LHP 17

DimensionalData

DISCHARGE VIEW

TOP VIEW

LOW-HEIGHT PARALLEL COOLING (LPCF) FAN SIZES 08SQ & 09SQ

5.

Actuator, Controller andFan Controls located in this area

H

AirflowDischarge Outlet

PrimaryAirflow

Fan Controls located in this areaActuator, Controller and

5.

L

W

A

B

(457 mm)18.00"

(813 mm)32.00"

Plenum InletAirflow

B9.5" (241 mm)

DISCHARGE DIMENSIONS

203 x 356

152, 203

127, 152, 203

INLET SIZEAVAILABILITY

NOMINAL Ø (mm)

09SQ

FAN

08SQ

SIZE NOMINAL Ø (INCHES)AVAILABILITY

5, 6, 8

6, 8

8 x 14

INLET SIZE

11.00" (279 mm)

H

40.00" (1016 mm)

W

19.25" (489 mm)30.00" (762 mm)

LA

WT LBSUNIT WT

4.00" (102 mm)

3.25" (83 mm)

D(kg)

(203 mm X 356 mm)

Fan Controls located in Enclosure

Rectangular Damper Detail

Rectangular Damper

8" x 14"

Actuator, Controller and

5.

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet clearance for unducted installations.

2. Flanged discharge outlet accepts up to 1" (25 mm) duct flange.

3. Bottom Access panel standard.

4. Air valve centered between top and bottom panel.

5. Control box enclosure provided with all control types.

6. All high & low voltage controls have same-side NEC jumpback clearance. (Left-hand shown, right-hand/mirror image optional.)

7. Flange adds 2" to width and length of unit.

Fan Size

09SQ08SQ

Attn WtWt. Lbs.

(kg)

(254 mm x 508 mm x 25 mm)10" x 20" x 1"

Filter Size

(445 mm)17.50"

(127 mm)5.00"

(267 mm)10.50"

10 (4.5)

69 (31.3)

74 (33.6)

83 (37.7)

nal Attenuatoreld Installed

Optional AttenuatorField Installed

09SQ

D

4.00(102 mm)( )

7.

Valve 5" 6.50"

(165 mm)

Page 18: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

LHP 18 VAV-PRC008-EN

DimensionalData

DISCHARGE VIEW

TOP VIEW

LOW-HEIGHT PARALLEL COOLING (LPCF) FAN SIZE 10SQ

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet clearance for unducted installations.2. Flanged discharge outlet accepts up to a 1" (25 mm) duct flange.

6. Maximum dimensions for controls area shown. Configurations and types of control boxes vary according to control type selected. See "Enclosure Details"

g ypg yp

for specific layout.y

5. Air valve centered between top and bottom panel.4. See Installation Documents for exact hanger bracket location.

Rectangular Damper Detail

Fan Controls located in this areaActuator, Controller and

6.

4.

B

6.

11.30" Max.(287 mm)

6.

5.50" Max.(140 mm)

18.875" Max.(479 mm)

Flow Ringtubing

A

AirflowDischarge Outlet

W

PrimaryAirflow

Air

4.

L

20.00"(508 mm) (508 mm)

20.00"

H

(254 mm x 508 mm x 25 mm)10" x 20" x 1"10SQ

Fan Size Filter Size

Fan Controls located in this areaActuator, Controller and

6.

90 (41)

92 (42)

(203 mm X 356 mm)8" x 14"

Rectangular DamperD

10.00" (254 mm)

INLET SIZEAVAILABILITY

203 x 356

NOMINAL Ø (mm)SIZEFAN

10SQ

10SQ

INLET SIZEAVAILABILITY

NOMINAL Ø (INCHES)

88 x 14

203 50.00" (1270 mm)11.50" (292 mm)

H

40.00" (1016 mm)

WA

DISCHARGE DIMENSIONS

19.25" (489 mm)

LB

4.00" (102 mm)

3.25" (83 mm)

D WT LBSUNIT WT

(kg)

3. Bottom Access panel standard.

4.00(102 mm)

Page 19: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

VAV-PRC008-EN LHP 19

DimensionalData

DISCHARGE VIEW

TOP VIEW

LOW-HEIGHT PARALLEL HOT WATER (LPWF) FAN SIZES 08SQ & 09SQ

NOTES:

(254 mm x 508 mm x 25 mm)10" x 20" x 1"08SQ

Fan Size Filter Size

SIZE

08SQ

FAN INLET SIZEAVAILABILITY

8 x 14

09SQ

5.

Actuator, Controller andFan Controls located in this area

H

AirflowDischarge Outlet

PrimaryAirflow

Fan Controls located in this areaActuator, Controller and

5.

L

W

A

B

(457 mm)18.00"

(813 mm)32.00"

09SQ

5, 6, 8

NOMINAL Ø (INCHES) NOMINAL Ø (mm)

INLET SIZE

127, 152, 203

6, 8 152, 203

203 x 356

30.00" (762 mm)40.00" (1016 mm)11.00" (279 mm)

H WDISCHARGE DIMENSIONS

19.25" (483 mm)

LA

9.50" (241 mm)B

UNIT WTD

3.25" (83 mm)

WT LBS(kg)

Attn WtWt Lbs(kg)

Plenum InletAirflow

20.00"(508 mm)

(173 mm)6.80"

5. Control box enclosure provided with all control types.

4. Air valve centered between top and bottom panel.

1. Allow a minimum 6" (152 mm) plenum inlet clearance for unducted installations.

2. Flanged discharge outlet accepts up to a 1" (25 mm) duct flange.

3. Bottom Access panel standard.

(203 mm x 356 mm)

Fan Controls located in Enclosure

Rectangular Damper Detail

Rectangular Damper8" x 14"

Actuator, Controller and

5.

6. All high & low voltage controls have same-side NEC jumpback clearance. (Left-hand shown, right-hand/mirror image optional.)

g g j pg g j p

7. Flange adds 2" to width and length of unit.

10 (4.5)(127 mm)

5.00"

(445 mm)17.50"

10.50"

98 (44.5)103 (46.7)

112 (50.8)

Optional AttenuatorField Installed

Optional AttenuatorField Installed

09SQ

D

4.00

Valve 5" 6.50"

(165 mm)

7.

Page 20: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

LHP 20 VAV-PRC008-EN

DimensionalData

LOW-HEIGHT PARALLEL HOT WATER (LPWF) FAN SIZE 10SQ

Rectangular Damper Detail

WaterCoil

ConnectionCoil

6.30"(160 mm)

Discharge OutletAirflow

AirflowPrimary

(508 mm)20.00"

7.

(479 mm)18.875" Max.

Flow Ringtubing

ValveAir

(508 mm)20.00"

TOP VIEW

5.

L

A

11.30" Max.(287 mm)

B

9.

(140 mm)5.50" Max.

DISCHARGE VIEW

W

H

NOTES:

1. Coil furnished with female sweat connections.

2. Allow a minimum 6" (152 mm) plenum inlet clearance for unducted installations.

3. Flanged discharge outlet accepts up to a 1" (25 mm) duct flange.

4. Bottom Access panel standard.

5. See Installation Documents for exact hanger bracket location.

6. Air valve centered between top and bottom panel.

7. Maximum dimensions for controls area shown. Configurations and types of control boxes vary according to control type selected. See "Enclosure Details" for specific layout.

(254 mm x 508 mm x 25 mm)10SQ

Fan Size

10" x 20" x 1"

Filter Size

Fan Controls located in this areaActuator, Controller and

7.

50.00" (1270 mm)

101 (46)

99 (45)

D

C

Rectangular Damper

(203 mm X 356 mm)8" x 14"

10.00" (254 mm)

203 X 356

203

INLET SIZEAVAILABILITY

NOMINAL Ø (mm)

10SQ

FAN

10SQ

SIZE

INLET SIZE

NOMINAL Ø (INCHES)AVAILABILITY

8

8 X 14

11.50" (292 mm)

H

40.00" (1016 mm)

W

19.25" (489 mm)

DISCHARGE DIMENSIONSL

A B

4.00" (102mm)

3.25" (83mm)

4.00" (102mm)

C D(kg)

WT LBSUNIT WT

Actuator, Controller andFan Controls located in this area

7.

5.

Page 21: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

VAV-PRC008-EN LHP 21

DimensionalData

DISCHARGE VIEW

TOP VIEW

PARALLEL LOW-HEIGHT HOT WATER (LPWF) COIL ON DISCHARGEFAN SIZES 08SQ & 09SQ

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet clearance for unducted installations.

2. Flanged discharge outlet accepts up to a 1" (25 mm) duct flange.

3. Bottom Access panel standard.

4. Air valve centered between top and bottom panel.

5. Control box enclosure provided with all control types.

6. All high & low voltage controls have same-side NEC jumpback clearance. (Left-hand shown, right-hand/mirror image optional.)

7. Flange adds 2" to width and length of unit.

(254 mm x 508 mm x 25 mm)10" x 20" x 1"08SQ

Fan Size Filter Size

SIZE

08SQ

FAN INLET SIZEAVAILABILITY

8 X 14

09SQ

H

AirflowDischarge Outlet

PrimaryAirflow

L

W

A

B

(457 mm)18.00"

(813 mm)

32.00"

09SQ

5, 6, 8

NOMINAL Ø (INCHES) NOMINAL Ø (mm)AVAILABILITYINLET SIZE

127, 152, 203

6, 8 152, 203

203 X 356

30.00" (762 mm)40.00" (1016 mm)11.00" (279 mm)

H WDISCHARGE DIMENSIONS

20.00" (508 mm)

LA

10.00" (254 mm)

B

UNIT WT

D

3.25" (83 mm)

4.00" (102 mm)

WT LBS(kg)

Attn WtWt Lbs

(kg)

Plenum InletAirflow

(203 mm X 356 mm)

Fan Controls located in Enclosure

Rectangular Damper Detail

Rectangular Damper

8" x 14"

Actuator, Controller and

5.

10 (4.5)(127 mm)5.00"

(445 mm)17.50"

10.50"

98 (44.5)

103 (46.7)

112 (50.8)

Optional AttenuatorField Installed

09SQ

D

Actuator, Controller andFan Controls located in this area

Fan Controls located in this areaActuator, Controller and

5.

ptional Attenuator

5.

(508 mm)20.00"

(173 mm)6.80"

4.00

Valve 5" 6.50"

(165 mm)

7.

Page 22: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

LHP 22 VAV-PRC008-EN

DimensionalData

PARALLEL LOW HEIGHT HOT WATER (LPWF) COIL ON DISCHARGE FAN SIZE 10SQ

Rectangular Damper Detail

Discharge OutletAirflow

AirflowPrimary

(508 mm)20.00"

7.

(479 mm)18.875" Max.

Flow Ringtubing

ValveAir

TOP VIEW

5.

L

A

11.30" Max.(287 mm)

B

9.

(140 mm)5.50" Max.

DISCHARGE VIEW

W

H

Fan Controls located in this areaActuator, Controller and

7.

5.

NOTES:

1. Coil furnished with female sweat connections.

2. Allow a minimum 6" (152 mm) plenum inlet clearance for unducted installations.

3. Flanged discharge outlet accepts up to a 1" (25 mm) duct flange.

4. Bottom Access panel standard.

5. See Installation Documents for exact hanger bracket location.

6. Air valve centered between top and bottom panel.

7. Maximum dimensions for controls area shown. Configurations and types of control boxes vary according to control type selected. See "Enclosure Details" for specific layout.

(254 mm x 508 mm x 25 mm)10SQ

Fan Size

10" x 20" x 1"

Filter Size

Fan Controls located in this areaActuator, Controller and

7.

50.00" (1270 mm)

101 (46)

99 (45)

D

C

Rectangular Damper

(203 mm X 356 mm)8" x 14"

10.00" (254 mm)

203 X 356

203

INLET SIZEAVAILABILITY

NOMINAL Ø (mm)

10SQ

FAN

10SQ

SIZE

INLET SIZE

NOMINAL Ø (INCHES)AVAILABILITY

8

8 X 14

11.50" (292 mm)

H

40.00" (1016 mm)

W

20.00" (508 mm)

DISCHARGE DIMENSIONSL

A B

4.00" (102 mm)

3.25" (83 mm)

4.00" (102 mm)

C D(kg)

WT LBSUNIT WT

(508 mm)20.00"

Connection

WaterCoil

(160 mm)6.30"

Coil

20.00"(508 mm)

Page 23: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

VAV-PRC008-EN LHP 23

DimensionalData

1. Location of coil connections is determined by facing air stream. R.H. Coil connections shown, L.H. not available.

2. Coil furnished with stub sweat connections.

NOTES:

INLET/FAN

10SQ

CONNECTION

B HLA

COILSIZE

1-ROW

AIR FLOW

OUTLET

INLET

B

20.00" (508 mm)9.00" (229 mm) 2.80" (71 mm) 10.00" (254 mm).375" (10 mm) O.D.

A

OPERATING

FAN SIZELBS (KG)GAL (L)

0.07 (.27) 9.7 (4.4)

VOLUMEINTERNAL

WEIGHT

(10 mm).40"

10SQ

7.40"(188 mm)

COIL INFORMATION FOR LOW-HEIGHT PARALLEL 1-ROW COIL

H

L

Page 24: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

LHP 24 VAV-PRC008-EN

DimensionalData

NOTES:

1. Location of coil connections is determined by facing air stream. R.H. Coil connections shown. L.H. not available.

2. Coil furnished with female sweat connections.

B

A AIR FLOW

H

L

OUTLET

INLET

10SQ

FANSIZE

.875" (22 mm) O.D.

COIL

2 ROWCONNECTION

6.20" (157 mm) 2.18" (55 mm)

A

20.00" (508 mm)

B L

10.00" (254 mm)

H

(51 mm)2.00"

(22 mm).85"

7.40"(188 mm)

OPERATINGINTERNALVOLUMEGAL (L)

10SQ

FAN SIZE

0.16 (.61) 13.7 (6.2)

WEIGHTLBS (KG)

COIL INFORMATION FOR LOW-HEIGHT PARALLEL 2-ROW COIL

1.97"(50 mm)

Page 25: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

VAV-PRC008-EN LHP 25

DimensionalData

DISCHARGE VIEW

TOP VIEW

LOW-HEIGHT PARALLEL ELECTRIC HEAT (LPEF) FAN SIZES 08SQ & 09SQ

5.

H

PrimaryAirflow

5.

L

W

A

B

(457 mm)18.00"

(813 mm)32.00"

Plenum InletAirflow

B9.50" (241 mm)

DISCHARGE DIMENSIONS

203 x 356

152, 203

127, 152, 203

INLET SIZEAVAILABILITY

NOMINAL Ø (mm)

09SQ

FAN

08SQ

SIZE NOMINAL Ø (INCHES)AVAILABILITY

5, 6, 8 6, 8

8 x 14

INLET SIZE

11.00" (279 mm)

H

40.00" (1016 mm)

W

19.00" (483 mm)30.00" (762 mm)

LA

WT LBSUNIT WT

4.00" (102 mm)

3.25" (83 mm)

D(kg)

Rectangular Damper Detail

(203 mm X 356 mm)

8" x 14"

Rectangular Damper

5.

Filter Size

10" x 20 " x 1"(254 mm x 508 mm x 25 mm)

08SQ09SQ

Fan Size(kg)Lbs

Atten Wt

Fan Controls located in EnclosureActuator, Controller and

Fan Controls located in EnclosureActuator, Controller and

Fan Controls located in EnclosureActuator, Controller and

20.00"(508 mm)

Ter

min

al B

ox

Discharge OutletAirflow

Heater

6.00"(152 mm)

NOTES:

1. Allow a minimum 6" (152 mm) plenum inlet clearance for unducted installations.2. Flanged discharge outlet accepts up to a 1" (25 mm) duct flange.

5. Control box enclosure provided with all control types.4. Air valve centered between top and bottom panel.3. Bottom Access panel standard.

6. All high & low voltage controls have same-side NEC jumpback clearance. (Left-hand shown, right-hand/mirror image optional.)

g gg g

7. Flange adds 2" to width and length of unit.

10 (4.5)

(127 mm)5.00"

(445 mm)17.50"

(267 mm)10.50"

104 (47.2)

109 (49.4)

118 (53.5)

al AttenuatorInstalled

Optional AttenuatorField Installed

09SQ

D

4.00

Valve 5" 6.50"

(165 mm)

7.

Page 26: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

LHP 26 VAV-PRC008-EN

DimensionalData

LOW-HEIGHT PARALLEL ELECTRIC (LPEF) FAN SIZE 10SQ

Page 27: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

VAV-PRC008-EN LHP 27

MechanicalSpecifications

MODELS LPCF, LPWF,and LPEFLow-height parallel fan-poweredterminal units.

LPCF – Cooling Only

LPWF – With Hot Water Coil

LPEF – With Electric Coil

CASING22-gage galvanized steel. Hangerbrackets, bottom access, and plenuminlet filter are provided as standard.

AGENCY LISTINGThe unit is UL and Canadian ULListed as a room air terminal unit.

ARI 880 Certified.

INSULATION

1/2" (12.7 mm) Matte-facedInsulation—The interior surface ofthe unit casing is acoustically andthermally lined with ½-inch, 1.5 lb/ft3

(12.7 mm, 24.0 kg/m3) compositedensity glass fiber with a high-densityfacing. The insulation R-Value is 1.9. Theinsulation is UL listed and meets NFPA-90A andUL 181 standards. There are noexposed edges of insulation (completemetal encapsulation).

1" (25.4 mm) Matte-facedInsulation—The interior surface ofthe unit casing is acoustically andthermally lined with 1-inch, 1.0 lb/ft3

(25.4 mm, 16.0 kg/m3) compositedensity glass fiber with a high-densityfacing. The insulation R-Value is 3.85.The insulation is UL listed and meetsNFPA-90A and UL 181 standards. Thereare no exposed edges of insulation(complete metal encapsulation).

1/2" (12.7 mm) Foil-facedInsulation—The interior surface ofthe unit casing is acoustically andthermally lined with ½-inch, 1.5 lb/ft3

(12.7 mm, 24.0 kg/m3) density glassfiber with foil facing. The insulationR-Value is 2.1. The insulation is ULlisted and meets NFPA-90A and UL 181standards as well as bacteriologicalstandard ASTM C 665. There are noexposed edges of insulation (completemetal encapsulation).

1" (25.4 mm) Foil-facedInsulation—The interior surface ofthe unit casing is acoustically andthermally lined with 1-inch, 1.5 lb/ft3

(25.4 mm, 24.0 kg/m3) density glassfiber with foil facing. The insulationR-Value is 4.1. The insulation is ULlisted and meets NFPA-90A and UL 181standards as well as bacteriologicalstandard ASTM C 665. There are noexposed edges of insulation (completemetal encapsulation).

1" (25.4 mm) Double-wallInsulation—The interior surface ofthe unit casing is acoustically andthermally lined with a 1-inch, 1.0 lb./ft3

(25.4 mm, 16.0 kg/m3) compositedensity glass fiber with high-densityfacing. The insulation R-value is 3.8.The insulation is UL listed and meetsNFPA-90A and UL 181 standards. Theinsulation is covered by an interiorliner made of 26-gage galvanizedsteel. All wire penetrations are coveredby grommets. There are no exposededges of insulation (complete metalencapsulation).

3/8" (9.5 mm) Closed-cellInsulation—The interior surface ofthe unit casing is acoustically andthermally lined with 3/8-inch, 4.4 lb/ft3

(9.5 mm, 70.0 kg/m3) closed-cellinsulation. The insulation is ULrecognized and meets NFPA-90A andUL 181 standards. The insulation hasan R-Value of 1.4. There are no exposededges of insulation (complete metalencapsulation).

PRIMARY AIR VALVE

Air Valve Round—The primary airinlet connection is an 18-gagegalvanized steel cylinder sized to fitstandard round duct. A multiple-point,averaging flow sensing ring isprovided with balancing taps formeasuring +/-5% of unit catalogedairflow. An airflow-versus-pressuredifferential calibration chart is provided.The damper blade is constructed of aclosed-cell foam seal that ismechanically locked between two22-gage galvanized steel disks. Thedamper blade assembly is connectedto a cast zinc shaft supported by self-lubricating bearings. The shaft is castwith a damper position indicator. Thevalve assembly includes a mechanicalstop to prevent over-stroking. At 4 in.wg, air valve leakage does not exceed1% of cataloged airflow.

FAN MOTOR

PSC—Single-speed, direct-drive,permanent split capacitor type.Thermal overload protection provided.Motors will be designed specifically foruse with an open SCR. Motors will besingle-speed with standard SCR forspeed control. Motors willaccommodate anti-backward rotationat start up. Motor and fan assembly isisolated from terminal unit.

ECM—Electrically Commutated Motoris designed for high-efficient operationwith over 70% efficiency throughoutthe operating range

FAN SPEED CONTROL

Variable Speed Control Switch(SCR)—The SCR speed control deviceis provided as standard and allows theoperator infinite fan speed adjustmentso the fan output may be modified toachieve exact cfm requirements.

TRANSFORMER

The 50-VA transformer is factory-installed in the fan control box toprovide 24 VAC for controls.

DISCONNECT SWITCH

A toggle disconnect is provided asstandard and allows the operator toturn the unit on or off by toggling tothe appropriate setting. This switchbreaks both legs of power to the fanand the electronic controls (ifapplicable). Not provided on LPEFpneumatic controls.

Air Valve Rectangular—Inlet collar isconstructed of 22-gage galvanized steelsized to fit standard rectangular duct.An integral multiple-point, averagingflow-sensing ring provides primaryairflow measurement within +/-5% ofunit cataloged airflow. Damper is22-gage galvanized steel. The damperblade assembly is connected to a solidmetal shaft supported by self-lubricating bearings. The shaft is castwith a damper position indicator. Thevalve assembly includes a mechanicalstop to prevent over-stroking. At 3.0 in.wg, air valve leakage does not exceed44 cfm (21 L/s).

LSXFInlet 08SQ 09SQ 10SQ

5" X6" X X8" X X

8x14" X X

Fan–Inlet Combinations:

Page 28: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

LHP 28 VAV-PRC008-EN

MechanicalSpecifications

OUTLET CONNECTION

Flanged Connection—Arectangular opening on the unitdischarge to accept a 90° flangedductwork connection.

FILTER

A 1" (25 mm) filter is provided on theplenum inlet and attaches to the unitwith a filter frame.

ACCESS PANEL

Internal access to unit is achievedthrough the removable bottom accesspanel.

HOT WATER COIL

Parallel Water Coils—factory-installed on the plenum inlet.

The coil has 1-row with 144 aluminumfins per foot (.305 m) and, if needed, 2-row with 144 aluminum fins per foot(.305 m). Full fin collars provided foraccurate fin spacing and maximum fin-tube contact. The 3/8" (9.5 mm) ODseamless copper tubes aremechanically expanded into the fincollars. Coils are proof tested at450 psig (3102 kPa) and leak tested at300 psig (2068 kPa) air pressure underwater. Coil connections are brazedwith right-hand configuration.

ELECTRIC HEAT COIL

The electric heater is factory-providedand -installed, UL recognizedresistance open-type heater. It alsocontains a disc-type automatic pilotduty thermal primary cutout, andmanual reset load carrying thermalsecondary device. Heater elementmaterial is nickel-chromium. The heaterterminal box is provided with 7/8"(22 mm) knockouts for customerpower supply. Terminal connectionsare plated steel with ceramicinsulators. Heater control access ison the same side as fan control units.All fan-powered units with electricreheat are single-point powerconnections.

ELECTRIC HEAT OPTIONS

Magnetic Contactor—An optionalelectric heater 24-volt contactor for usewith direct digital control (DDC) oranalog electronic controls.

Mercury Contactor—An optionalelectric heater 24-volt contactor for usewith direct digital control (DDC) oranalog electronic controls.

P.E. Switch with MagneticContactor—This optional switch andmagnetic contactor is for use withpneumatic controls.

P.E. Switch with MercuryContactor—This optional switch andmercury contactor is for use withpneumatic controls.

Airflow Switch—An optional airpressure device designed to disablethe heater when the system fan is off.

Power Fuse—If power fuse is chosenwith a unit with electric heat, then asafety fuse located in the line of powerof the electric heater to prevent powersurge damage to the electric heater.

Any electric heat unit with a calculatedMCA greater than or equal to 30 willhave a fuse provided.

Disconnect Switch—An optionalfactory-provided door interlockingdisconnect switch on the heatercontrol panel disengages primaryvoltage to the terminal.

UNIT CONTROLS SEQUENCE OFOPERATIONThe controller continuously monitorsthe zone temperature against itssetpoint and varies the primary airflowas required to meet zone setpoints.Airflow is limited by minimum andmaximum setpoints. For a low-heightparallel unit, the controller willintermittently start the fan upon a callfor heat. Upon a further call for heat,any hot water or electric heatassociated with the unit is enabled.

1. Primary Airflow—The fan energizeswhen primary airflow drops belowthe fan setpoint airflow. The fanautomatically starts when the zonetemperature drops to the heatingtemperature setpoint.

2. Zone Temperature—The fanenergizes when the zone temperaturedrops to a selectable number ofdegrees above the heatingtemperature setpoint.

DIRECT DIGITAL CONTROLS

DDC Actuator—Trane 3-wire,24-VAC, floating-point control actuatorwith linkage release button. Torque is35 in-lb minimum and is non-springreturn with a 90-second drive time.Travel is terminated by end stops atfully-opened and -closed positions. Anintegral magnetic clutch eliminatesmotor stall.

Direct Digital Controller—Themicroprocessor based terminal unitcontroller provides accurate, pressure-independent control through the useof a proportional integral controlalgorithm and direct digital controltechnology. The controller, named theUnit Control Module (UCM), monitorszone temperature setpoints, zonetemperature and its rate of change,and valve airflow using a differentialpressure signal from the pressuretransducer. Additionally, the controllercan monitor either supply duct airtemperature or CO2 concentration viaappropriate sensors. The controller isprovided in an enclosure with 7/8"(22 mm) knockouts for remote controlwiring. A Trane UCM zone sensoris required.

DDC Zone Sensor—The UCMcontroller senses zone temperaturethrough a sensing element located inthe zone sensor. In addition to thesensing element, zone sensor optionsmay include an externally-adjustablesetpoint, communications jack for usewith a portable edit device, and anoverride button to change theindividual controller from unoccupiedto occupied mode. The override buttonhas a cancel feature that will return thesystem to unoccupied. Wired zonesensors utilize a thermistor to vary thevoltage output in response to changesin the zone temperature. Wiring to theUCM controller must be 18- to 22-awg.twisted pair wiring. The setpointadjustment range is 50–88ºF (10–31°C).Depending upon the features availablein the model of sensor selected, thezone sensor may require from a 2-wireto a 5-wire connection. Wireless zonesensors report the same zoneinformation as wired zone sensors,but do so using radio transmittertechnology. Therefore with wireless,wiring from the zone sensor to theUCM is unnecessary.

Digital Display Zone Sensor withLiquid Crystal Display (LCD)—The digital display zone sensorcontains a sensing element, whichsends a signal to the UCM. A LiquidCrystal Display (LCD) displays setpointor space temperature. Sensor buttonsallow the user to adjust setpoints, andallow space temperature readings tobe turned on or off. The digital displayzone sensor also includes a

Page 29: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

VAV-PRC008-EN LHP 29

MechanicalSpecifications

communication jack for use with aportable edit device, and an overridebutton to change the UCM fromunoccupied to occupied. The overridebutton has a cancel feature, whichreturns the system tounoccupied mode.

Trane LonTalk—The controller isdesigned to send and receive datausing SCC LonTalk profile. Current unitstatus conditions and setpoints maybe monitored and/or edited from any ofseveral LonTalk-compatible system-level controllers.

ANALOG ELECTRONIC CONTROLS

Analog Actuator—A Trane 3- wire,24-VAC, floating-point control actuatorwith linkage release button. Torque is35 in-lb minimum and is non-springreturn with a 90-second drive time.Travel is terminated by end stops atfully-opened and -closed positions. Anintegral magnetic clutch eliminatesmotor stall.

Analog Electronic Controller—Thecontroller consists of a circuit boardthat offers basic VAV unit operationand additional override functions andoperates using 24 VAC power. Thecontroller uses a capacitive typepressure transducer to maintainconsistent air delivery regardless ofsystem pressure changes. Theenclosure with 7/8" (22 mm) knockoutsfor remote control wiring. A Traneelectronic zone sensor is required.

Analog-Electronic Thermostat—This single-temperature, wall-mountedelectronic device utilizes a thermistor tovary the voltage output in response tochanges in the zone temperature.Connections to the VAV unit circuitboard are made using standard three-conductor thermostat wire. The setpointadjustment range is 63–85ºF (17–29°C).The sensor is available in two models.One model has a concealed, internally-adjustable setpoint. The other modelhas an externally-adjustable setpoint.

PNEUMATIC CONTROLS

Normally Open Actuator—Pneumatic 3 to 8 psig (20 to 55 kPa)spring-range pneumatic actuator.

3011 Pneumatic Volume Regulator(PVR)—The regulator is a thermostatreset velocity controller, whichprovides consistent air delivery within5% of cataloged flow down to 18% ofunit cataloged cfm, independent ofchanges in system static pressure.Factory-calibrated, field-adjustable setpoints for minimum and maximumflows. Average total unit bleed rate,excluding thermostat, is 28.8 scim at20 psig (7.87 ml/min at 138 kPa) supply.

UNIT OPTIONS

Power Fuse (LPCF, LPWF)—Optional fuse is factory-installed in theprimary voltage hot leg.

HOT WATER VALVES

Two-Position Valve—The valve is afield-adaptable, 2-way or 3-wayconfiguration and ships with a cap tobe field-installed when configured as a2-way valve. All connections areNational Pipe Thread (NPT). The valvebody is forged brass with a stainlesssteel stem and spring. Upon demand,the motor strokes the valve. When theactuator drive stops, a spring returnsthe valve to its fail-safe position.

Flow Capacity – 1.17 CvOverall Diameter – ½" NPTClose-off Pressure – 30 psi (207 kPa)

Flow Capacity – 3.0 CvOverall Diameter – 3/4" NPTClose-off Pressure – 14.5 psi (100 kPa)

Flow Capacity – 6.4 CvOverall Diameter – 1" NPTClose-off Pressure – 9 psi (62 kPa)

Maximum Operating FluidTemperature – 203ºF (95ºC)

Maximum system pressure – 300 psi(2067 kPa). Maximum static pressure –300 psi (2067 kPa)

Electrical Rating – 7 VA at 24 VAC,6.5 Watts, 50/60 Hz

8 feet (2.44 m) of plenum rated wirelead is provided with each valve.

Proportional Water Valve—The valveis a field-adaptable, 2-way or 3-wayconfiguration and ships with a cap overthe bottom port. This configures thevalve for 2-way operation. For 3-wayoperation, remove the cap. The valve islinear equal percentage design. Theintended fluid is water or water andglycol (50% maximum glycol). Theactuator is a synchronous motor drive.The valve is driven to a predeterminedposition by the UCM controller using aproportional plus integral controlalgorithm. If power is removed, thevalve stays in its last position. Theactuator is rated for plenum applicationsunder UL 94-5V and UL 873 standards.

Pressure and Temperature Ratings –The valve is designed and tested in fullcompliance with ANSI B16.15 Class 250pressure/temperature ratings, ANSIB16.104 Class IV control shutoffleakage, and ISA S75.11 flowcharacteristic standards.

Flow Capacity – 0.7 Cv, 2.2 Cv, 3.8 Cv,and 6.6 Cv

Overall Diameter – ½" NPT, ¾" NPT(6.6 Cv)

Maximum Allowable Pressure – 300 psi(2068 kPa)

Maximum Operating FluidTemperature – 200ºF (93°C)

Maximum Close-off Pressure – 55 psi(379 kPaP

Electrical Rating – 6 VA at 24 VAC.

10 feet (3.05 m) of plenum rated22-gage wire for connection.Terminations are #6 stabs.

Page 30: Fan-Powered Table of Low-Height Contents Parallel

Fan-PoweredLow-HeightParallel

LHP 30 VAV-PRC008-EN