Page 1: Emergency Depressurisation: 690 kPa or 50% in 15 Minutes?

Emergency Depressurisation:

690 kPa or 50% in 15 Minutes?

Cameron Milne, Lead Technical Safety Engineer, px Limited

Duncan Talbert, Principal Consultant, MMI Thornton Tomasetti

Page 2: Emergency Depressurisation: 690 kPa or 50% in 15 Minutes?

Overview

Objectives:

• To consider emergency depressurisation of process plant

and reduced risk of failures due to fire.

• To review generic depressurisation criteria.

• To describe a scenario specific approach.

Content:

• Requirement for depressurisation.

• Commonly applied criteria.

• “Specific Calculations”.

• Benefits of Specific Calculations over Generic Criteria.

Page 3: Emergency Depressurisation: 690 kPa or 50% in 15 Minutes?

Emergency Depressurisation: Why?

Reduction in harm:

• People; Environment; Plant

• Immediate Harm; Escalation

Vessel Wall Strength, decreases

with increasing temperature

Load on Vessel Wall – increases with

temperature

TIME

STR

ES

S RUPTURE

Page 4: Emergency Depressurisation: 690 kPa or 50% in 15 Minutes?

Emergency Depressurisation: How?

HOW:

EDP System:

• Actuated valves; Collection/header pipework; Flare or vent

• Design Standards: typically API 521

Vessel Wall Strength

Vessel Wall Stress

TIME

STR

ES

S

RUPTURE

Page 5: Emergency Depressurisation: 690 kPa or 50% in 15 Minutes?

EDP: How fast?

Vessel Wall Strength

Vessel Wall Stress

TIME

STR

ES

S

FAILURE

Page 6: Emergency Depressurisation: 690 kPa or 50% in 15 Minutes?

Depressurisation Rate Constraints

Rapid depressurisation is generally good however;

• Equipment and piping low temperature constraints.

• Equipment protection – compressor seals.

• Flare/Vent Capacity on an existing plant.

• Flare/Vent size and weight on a new plant.

Page 7: Emergency Depressurisation: 690 kPa or 50% in 15 Minutes?

How fast?

API 521:

• Depressurise to 50 % of Design Pressure in 15 minutes

• Or 690 kPa in 15 minutes

• Or perform more specific calculations

Page 8: Emergency Depressurisation: 690 kPa or 50% in 15 Minutes?

EDP: How fast?

API 521:

Depressurise to 50 % of design pressure in 15 minutes

• Pool fire exposure – not jet fire

• Carbon steel vessel

• Wall thickness approximately 25.4mm,

690 kPa in 15 minutes

• “Vessel leak or failure case”

• “Commonly applied for both fire and leak scenarios”

• Or perform more specific calculations

Page 9: Emergency Depressurisation: 690 kPa or 50% in 15 Minutes?

Specific Calculations

What do we do with the answer?

• What is the organisation’s tolerance of risk?

• What’s the nature of the fire threat, pool or jet, size and

duration?

• What governs the depressurisation rate?

• How does vessel rupture under fire attack contribute to

overall risk?

Page 10: Emergency Depressurisation: 690 kPa or 50% in 15 Minutes?

Fire Risk Assessment

• Fire type

• Fire size

• Fire duration

• Fire frequency

Page 11: Emergency Depressurisation: 690 kPa or 50% in 15 Minutes?

Fire Sources

Fire sources are determined from:

• Installation description: 3D models, P&IDs, equipment

layouts

• Fire and Explosion Risk Assessment ,QRA

Page 12: Emergency Depressurisation: 690 kPa or 50% in 15 Minutes?

Specific Calculations

Take cognisance of:

• Vessel, material, size, orientation,

• Vessel contents, composition, conditions,

• Contiguous pipework, etc.

• Fire type, size and duration

• Where does the fire contact the vessel

• Pressure relief fitted to the vessel

• Blowdown

Page 13: Emergency Depressurisation: 690 kPa or 50% in 15 Minutes?

Specific Calculation Results

Vessel Wall Strength

Vessel Wall Stress

TIME

ST

RE

SS

Page 14: Emergency Depressurisation: 690 kPa or 50% in 15 Minutes?

Governing Inventory

TARGET

VESSEL

SOURCE

VESSEL

Emergency

Depressurisation

Valves

To

Flare

1

2

Page 15: Emergency Depressurisation: 690 kPa or 50% in 15 Minutes?

Source vessel to target

vessel separation

Target vessel fire endurance

Jet flame length versus

time

TIME

DIS

TAN

CE

Target Vessel Fails

Page 16: Emergency Depressurisation: 690 kPa or 50% in 15 Minutes?

TIME

DIS

TAN

CE

Increase Source Vessel EDP rate to

reduce fire threat to Target Vessel

Target Vessel Survival – 1

Page 17: Emergency Depressurisation: 690 kPa or 50% in 15 Minutes?

TIME

DIS

TAN

CE

Increase Target Vessel EDP rate to

increase Target Vessel endurance in fire

Target Vessel Survival – 2

Page 18: Emergency Depressurisation: 690 kPa or 50% in 15 Minutes?

Optimisation

On a real plant;

• Optimisation may involve adjustment of depressurisation

rates across a number of vessels.

• It may involve reducing the depressurisation rates of some

vessels to accommodate increasing the rates on others.

• Where multiple vessels are involved a number of iterations

may be required to determine the best result.

• Optimisation is unlikely to be achieved by applying generic

rules.

Page 19: Emergency Depressurisation: 690 kPa or 50% in 15 Minutes?

Other Mitigation

If depressurisation rates cannot be adjusted to give tolerable failure times, other measures are available;

Plant Configuration

• Separation

• Orientation

• Screening

Passive Fire Protection

• Wet applied systems

• Precast systems or boxes

Active Fire Protection

• Deluge

• Fire response team

Page 20: Emergency Depressurisation: 690 kPa or 50% in 15 Minutes?

Conclusions

There are benefits of using specific calculations to determine

emergency depressurisation rates rather than applying generic

rules;

• Gives better understanding of the fire risk to process

vessels, and the contribution of this hazard to overall risk.

• Allows optimisation of risk reduction on an existing facility.

• Allows optimisation of depressurisation system design on a

new facility.

Page 21: Emergency Depressurisation: 690 kPa or 50% in 15 Minutes?

Thank You

Page 22: Emergency Depressurisation: 690 kPa or 50% in 15 Minutes?

w w w. T h o r n t o n To m a s e t t i . c o m

w w w. M M I E n g i n e e r i n g . c o m

w w w. p x l i m i t e d . c o m

c a m e r o n . m i l n e @ p x l i m i t e d . c o m