40
Rev. 0 - 11/12/2020 EC FAN FDP OPERATING MANUAL Regal Beloit Italy S.p.A. Via Modena, 18 24040 Ciserano (BG) ITALY Phone +39 035 873 111 Fax +39 035 884 319 www.regalbeloit.com

EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

  • Upload
    others

  • View
    7

  • Download
    0

Embed Size (px)

Citation preview

Page 1: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

EC FAN FDPOPERATING MANUAL

Regal Beloit Italy S.p.A.

Via Modena, 1824040 Ciserano (BG) ITALYPhone +39 035 873 111Fax +39 035 884 319www.regalbeloit.com

Page 2: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt
Page 3: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

3/40

INDEXINDEX

1. DEFINITIONS AND WARNINGS ..............................................................................................................................................5

1.1 Object of this manual .........................................................................................................................................................5

1.2 Symbols used ......................................................................................................................................................................5

1.3Qualifiedpersonnel ............................................................................................................................................................5

1.4Useforintendedpurposeonly ...........................................................................................................................................5

1.5Safetyinstructions ..............................................................................................................................................................6

1.6Informativeletter ...............................................................................................................................................................7

1.7Safeoperatingarea.............................................................................................................................................................7

2. REGULATORY REFERENCES ....................................................................................................................................................8

2.1Mechanicalandelectricalsafety ........................................................................................................................................8

2.2Electro-MagneticCompatibility(EMC) ...............................................................................................................................8

3. DATA PLATE .............................................................................................................................................................................9

4. TRANSPORT AND STORAGE .................................................................................................................................................10

5. PACKING CONTENTS .............................................................................................................................................................10

6. UNPACKING ...........................................................................................................................................................................11

7. PRODUCT DESCRIPTION .......................................................................................................................................................11

8. TECHNICAL FEATURES ..........................................................................................................................................................12

8.1Dimensionaldrawings ......................................................................................................................................................13

8.2Motor-driverconnections ...............................................................................................................................................15

9. INSTALLATION .......................................................................................................................................................................15

9.1Commissioning .................................................................................................................................................................15

9.2Operation .........................................................................................................................................................................16

9.3Ambientoperatingcondition ...........................................................................................................................................16

9.4Faninstallation .................................................................................................................................................................16

9.5Electricalconnections .......................................................................................................................................................17

9.5.1Powersupply ............................................................................................................................................................18

9.5.2Controlboardconnection ........................................................................................................................................18

9.5.3Connectiondetails ...................................................................................................................................................19

9.5.3.1Analog ..........................................................................................................................................................19

9.5.3.2Modbuscommunication ..............................................................................................................................21

9.5.3.3Tachometric,alarmandfilteroutput ...........................................................................................................22

9.5.3.4InputImpedances ........................................................................................................................................22

10. OPERATING MODES AND SETTING OPTIONS .....................................................................................................................22

10.1Speedcontrol .................................................................................................................................................................23

10.1.1Analogspeedcontrol .............................................................................................................................................23

10.1.2Modbustemporaryspeedcontrol .........................................................................................................................23

10.1.3Modbusfixedspeedcontrol ..................................................................................................................................23

10.1.4Speedcontrolcurves:examples ............................................................................................................................24

10.2Asynchronousemulation ................................................................................................................................................24

Page 4: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

4/40

10.2.1Analogasynchronousemulation ........................................................................................................................... 24

10.2.2Modbustemporaryasynchronousemulation ....................................................................................................... 24

10.2.3Modbusfixedasynchronousemulation ................................................................................................................. 24

10.2.4Asynchronousemulationcurves:examples ........................................................................................................... 25

10.3PIDclosedcontrolloop ..................................................................................................................................................25

10.3.1Modbustemporaryref.PIDclosedcontrolloop ....................................................................................................25

10.3.2Modbusfixedref.PIDclosedcontrolloop ............................................................................................................. 25

10.3.3Modbuspositive/negativefeedback ...................................................................................................................... 26

10.4Changingtheoperationmode .......................................................................................................................................26

11. OTHER FEATURES ..................................................................................................................................................................26

11.1Filteralarm .....................................................................................................................................................................26

11.2Softstart .........................................................................................................................................................................27

12. SOA LIMITATIONS .................................................................................................................................................................27

12.1Speedlimitation .............................................................................................................................................................27

12.2Powerlimitation .............................................................................................................................................................27

12.3Outputcurrentlimitation ............................................................................................................................................... 27

12.4Inputcurrentlimitation ..................................................................................................................................................27

13. OTHER VARIABLES ................................................................................................................................................................28

13.1 Busvoltage .....................................................................................................................................................................28

13.2 Motorvoltage .................................................................................................................................................................28

14. DERATING AND OVERHEATING PROTECTIONS ..................................................................................................................28

14.1 Driveroverheating:DERATING .......................................................................................................................................28

14.2 Motoroverheating:THERMALPROTECTOR ...................................................................................................................28

15. MASTER & SLAVE MODE ......................................................................................................................................................29

15.1 MasterandSlave0-5VPWMout(for1.05kW-1-phaseonly) ......................................................................................29

16. COMMUNICATION ................................................................................................................................................................29

16.1 Temporaryholdingregister ............................................................................................................................................31

16.2 Fixedholdingregister .....................................................................................................................................................31

16.3 Holdingregisterdescription ...........................................................................................................................................31

16.4 Inputregisterdescription ...............................................................................................................................................36

16.5 FaninfoandModbusregisters .......................................................................................................................................37

17. ALARM HANDLING ...............................................................................................................................................................38

17.1 Monitoring......................................................................................................................................................................38

17.2 Modbusregisters-Alarmdescription ............................................................................................................................38

17.3 BlinkingLED-Alarmdescription ....................................................................................................................................38

17.4 Digitalalarmoutput .......................................................................................................................................................39

17.5 Alarmreset .....................................................................................................................................................................39

18. AVAILABLE SOFTWARE .........................................................................................................................................................39

Page 5: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

5/40

1. DEFINITIONS AND WARNINGS

1.2 Symbols used

1.3 Qualified personnel

ForthisInstructionManualandproductlabels,a"Qualifiedperson"issomeonewhoisfamiliarwiththeinstallation,mounting,start-upandoperationoftheequipmentandthehazardsinvolved.Heorshemusthavethefollowingqualifications:• Trainedandauthorizedtoenergize,de-energize,clear,groundandtagcircuitsandequipmentinaccordancewithestablished

safetyprocedures.• Trainedinthepropercareanduseofprotectiveequipmentinaccordancewithestablishedsafetyprocedures.• Trainedinrenderingfirstaid.

1.4 Use for intended purpose only

TheequipmentmaybeusedonlyfortheapplicationstatedinthemanualandonlyinconjunctionwithdevicesandcomponentsrecommendedandauthorizedbyNicotra Gebhardt.

As to the "WARNING" and "CAUTION"messages,thesafetymessageisasymbol(atrianglecontaininganexclamationmark)fol-lowedbythetextindicatingtherisklevel.Itspurposeistowarntheuserofthepotentialpersonaldamagethatmayresultfromanincorrectuseofthemachineorfromthenon-compliancewiththeuseandmaintenanceinstructions.Failuretocomplywiththesesafetymessagescouldcausedamageand/orthepartialortotaldestructionoftheproductorotherequipmentconnectedtoitorharmpeople.

As to the "NOTICE"message,thesafetymessagedoesnotindicatepreciselyarisk,itisonlyforinformation.

Pictogram Description

Indicatesapotentialrisksituationthatcanlead to death or serious damage, if it notprevented (ex. amputations, severe burns,loss of vision or hearing loss or visual orauditorysensorialimpairment).Indicatesapotentialrisksituationthatcouldcause less severe orminor damage, if notprevented(ex.cuts,scratches,irritation).

NOTICEmessage:itisusedfornon-physicalinjuries.

Dangertopersonsduetoelectricity.

The operationswhose execution requiresqualified or specialized staff to avoid anydangerareindicatedwiththissymbol.

WARNINGWARNING

CAUTIONCAUTION

1.1 Object of this manual

Theaimofthismanualisgivinginstrutionsconcerninginstallation,useandmaintenanceofFDPfans.

This manual refers to fans having a driver with a 5 firmware revision or higher.

Page 6: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

6/40

This manual is an integral part of the EC Fan FDP and it must be carefully read before using it since it gives important indications with regards to its safe installation, use and maintenance. Keep it with care.

Before using the EC Fan FDP, read carefully the following general safety rules.

• Aftertakingoffthepackagingmakesurethatthefanisintact.Incaseofdoubtdonotuseitandcontactanauthorizedservicecentre.

• Checkthatthefanisnotdamagedinanyofitsparts.Thesafetyconceptofthefanisvalidonlyinperfectconditions.

RISK OF ELECTRICAL SHOCKS

• Anydamagedsocket,connectionterminalorcablemustbereplacedimmediatelybyqualifiedtechniciansorbyauthorizedservicecentre.

• Incaseofrepairorreplacementoftheconnectioncablesand/orofthedamageddevicesorthatdonotworkproperly,pleasecontacttheauthorizedservicecentre.

• Incorrectorimproperinstallationmaycausethesystemtomalfunctionand/orresultindamagetopeopleand/orproperty.• Alwaysdisconnectthepowersupplybeforeopeningthe fan.

Any installation and/or maintenance tasks are only to be carried out by skilled, specialist personnel.Existing electrical systems must comply with the rules in force in the country where the FDP fan is installed.Before doing any maintenance, make sure that the power supply and the batteries have been disconnected.Install an all-pole disconnecting device in the power supply system (in accordance with IEC 60335-1 or IEC 60204-1, as applicable).Conform to the wiring diagrams shown in the section “ELECTRICAL CONNECTIONS” of this manual.

Thefollowingwarnings,cautionsandnotesareprovidedforyoursafetyandhasameansofpreventingdamagetotheproductorcomponentsattheconnectedmachines.Specificwarnings,cautionsandnotesthatapplytoparticularactivitiesarelistedatthebeginningoftherelevantchaptersandarerepeatedorsupplementedatcriticalpointsthroughoutthesesections.Please read the information carefully, since it is provided for your personal safety and will also help prolonging the service life of your fan.

1.5 Safety instructions

WARNINGWARNING

This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge on condition that they are supervised and instructed concerning use of the appliance in a safe way and understand the hazards involved.-> Children shall not play with the appliance-> Cleaning and user maintenance shall not be made by children without supervision

WARNINGWARNING

The use and maintenance manual of any domestic appliance or similar device incorporating a FDP fan shall include the following clauses.

WARNINGWARNING

Page 7: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

7/40

ALL RIGHTS ARE RESERVED ACCORDING TO THE INTERNATIONAL COPYRIGHT CONVENTIONS,

Thereproductionofanypartofthismanual,inanyform,isforbiddenwithoutthepriorwrittenauthorizationofthemanufacturer.

Thecontentofthisguidecanbemodifiedwithoutpriornotice.Greatcarehasbeentakenincollectingandcheckingthedocumentationcontainedinthismanualtomakeitascompleteandcomprehensibleaspossible.

Nothingcontainedinthismanualcanbeconsideredasawarranty,eitherexpressedorimplied-including,notinarestrictiveway,thesuitabilitywarrantyforanyspecialpurpose.

Nothingcontainedinthismanualcanbeinterpretedasamodificationorconfirmationofthetermsofanypurchasecontract.

The Nicotra Gebhardt productshavenotbeenconceivedtoworkinareasatriskofexplosions.Incaseofdamageormal-function,theFDPfansmustnotbeuseduntiltheCustomerCareTechnicalServicehasrepairedit.

Theinstallerandthemaintenancemanmustknowthecontentofthismanual.Althoughthemainfeaturesoftheequipmentdescribedinthismanualarenotsubjecttochange,themanufacturerreservestherighttomodifythecomponents,detailsandaccessoriesitdeemsnecessarytoimprovetheproductortomeetmanufacturingorcommercialrequirementsatanytimeandwithoutbeingobligedtoupdatethismanualimmediately.

1.6 Informative letter

WARNINGWARNING

The original configuration of the fan must not be changed at all, except as prescribed in this manual.On receiving the fan, make sure the supply corresponds to what has been ordered.In case of non-compliance immediately inform the manufacturer.Also make sure the FDP fan has not been damaged during transport.

For information concerning the nearest supporting center, please get in touch with your retailer.

WARNINGWARNING

1.7 Safe operating area

Thedriversareprotectedagainstoverloadconditionsandasafeoperatingareaisdefinedbyalimitofspeed,outputpowerandmotorcurrent.FormoredetailsrefertotheANNEX"AnalogSignalConsiderations".

Customer Care Technical Service

Page 8: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

8/40

2. REGULATORY REFERENCES

ThesefanswithECdrivesystemsaredesignedforincorporationinequipment,fulfillingtherequirementssetbytheMachinery Directive (MD - Dir. 2006/42/EU),andthosepartsoftheLow-Voltage Directive (Dir. 2014/35/EU)whichareapplicableinaccord-ancewiththeMD,whereitconcernselectricalsafety.ElectricalsafetyisgenerallyachievedbyapplicationoftheprovisionsoftheEN 60204-1 standard “Electrical equipment of ma-chines - General requirements”.Selectedrangesmaybedesignedtobesuitableforincorporation(ascomponents)withinproductswhichcomplywiththestand-ardsEN 60335-1 “Household and similar electrical appliances - Safety - General requirements” and 60335-2-40 “Household and similar electrical appliances - Safety - Particular requirements for electrical heat pumps, air-conditioners and dehumidifiers”.Suchsafetyrequirementsarecoveredasfarasnecessaryforapartlycompletemachine,sub-assemblyorcomponent,asthesefansarespecificallyintendedforincorporationwithinothermachines.Theresponsibilityforthemechanicalandelectricalsafetyoftheinstalledfanisthusofthemanufacturerofthecompletemachineand,forthisreason,itisstrictlyforbiddentoputthefaninoperationbeforethemanufacturerofthemachinehasassessedanddeclaredthatthecompletemachinefulfilsalltheessentialsafetyrequirementssetforthbytheMD.Please,checktheDeclarationofIncorporationwhichaccompanieseachproduct,oraskyourNicotra Gebhardtsalesrepresentative,foradditionalinformation.

2.1 Mechanical and electrical safety

Single-phase drive systems: FDP 1 kW,

ThedriversoftheseproductsincorporateanActivePowerFactorControlmodule,toprovideharmonicsfilteringandcompliancewiththeEMCrequirementsapplicabletodomesticandequivalentenvironments(“firstenvironment”),orwiththeadvancedre-quirementsforharmonicdistortionwhichoftenapplytodatacenters.Morespecifically:theycomplywiththerequirementssetin

EN 61000-6-3 – Electromagnetic compatibility (EMC). Part 6-3:Genericstandards.Emissionstandardforresidential,commercialandlight-industrialenvironments.

EN 61000-6-4 – Electromagnetic compatibility (EMC). Part 6-4:Genericstandards-EmissionstandardforindustrialenvironmentswhichthisproductisincorporatedmustcomplywiththeEMCDirective2004/108/EC.

2.2 Electro-Magnetic Compatibility (EMC)

Specific electrical safety and EMC standards are applied according to the available models of conformity declaration (identified as 985732, 985740 and 985748):

EMC standards

61000-6-3 (household)

61000-6-4 (industrial)

Electrical safety

standards

60204 (machines) 985732 985748

60335 (domesticappliances)

985740 n/a

Page 9: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

9/40

3. DATA PLATE

Themanufacturer’sidentificationplateislocatedonthefan.Severalsafetywarningsareappliedtothefan;suchwarningsmustbestrictlyfollowedbyeveryonedealingwiththisproduct.The company is not to be held responsible for damage to property or accidents to people which might occur if the above-men-tioned warnings are not observed. In such a case, the operator is the only person responsible.

Theidentificationplateislocatedonthefanscrollcase.

REF. DESCRIPTION1 MODEL DESIGNATION2 REGAL BELOIT ITALY CODE3 MODIFICATION LEVEL4 PRODUCTION LOT NO.

5 NO. PHASES & CURRENT TYPE

6 ELECTRICAL FREQUENCY7 VOLTAGE8 IP PROTECTION GRADE

9 MOTOR INSULATION CLASS

10 CAPACITORVALUE(WHENPRESENT)11 MAXIMUMCURRENTINPUT12 MOTOR RATED POWER

13 RATED RPM

To improve the Electromagnetic compatibility a ferrite should be put on the power supply cable (close to the driver). The compliancy to the standards is intended for a single fan. No tests have been made on multiple installations.

The EMC tests are conducted without 485 communication wire, analog signals or Bluetooth devices.

WARNINGWARNING

REF. DESCRIPTION14 THERMALPROTECTOR(Y/N)15 OPERATING TEMPERATURE RANGE16 UNITEXCEEDS30KG(Y/N)17 UNITEXCEEDS85dB(A)SOUNDPOWER(Y/N)

18 OPERATING MANUAL

19 OVERALLEFFICIENCY(η)20 EFFICIENCYCATEGORY(STATICORTOTAL)

21 MEASUREMENT CATEGORY USED TO DETER-MINETHEENERGYEFFICIENCY(A-D)

22 EFFICIENCY GRADE AT OPTIMUM ENERGY EFFI-CIENCY POINT

23 ErPCOMPLIANCE24 CUSTOMERCODE(WHENAPPLICABLE)25 PRODUCTION DATE

The compliancy to the standards are intended for a single fan.No tests have been made on multiple installations.

Page 10: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

10/40

4. TRANSPORT & STORAGE

Correct transport, storage, erection and mounting, as well as careful operation and maintenance are essential for proper and safe operation of the equipment.Protect the fan against physical shocks and vibration during transport and storage. Also, be sure to protect it against water (rainfall) and excessive temperatures.

WARNINGWARNING

If the fan must be subject to long-term storage, the storage time without application of any power supply shall not exceed two years since fan production or since operating the fan for at least half-an-hour continuously. The storage site shall have a temperature between -20°C and +70 °C, a Relative Humidity lower than 75%, and not be subject to condensation or exposed to dust.

CAUTIONCAUTION

5. PACKING CONTENTS

6xxxxxfdp xXx xxxx xxxXXX12345

ThefanisdeliveredinacardboardboxinsidewhichtherearetheinstallationinstructionsandtheoptionsrequiredbytheCustomerattimeoforder.AlltheseoptionswillbemounteddirectlybytheManufacturer.

Apartfromthe"options",theCustomercanorder"accessories"afterwards.Inthiscase,theCustomerwillhavetoinstallthembyhim/herself.

Thefollowingdataareprintedonthepackingitself:

REF. DESCRIPTION1 ART. CODE2 MODEL DESCRIPTION3 BATCH CODE

1

2

3

Page 11: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

11/40

6. UNPACKING

Check the fan. Before installing the FDP fan, check to ensure that all of the items listed are present and that there are no visible signs of damage.

1. Removethefanfromthebox.2. Removeallthecomponentsfromthepackaging.

WARNINGWARNING

Dispose of all packing components in compliance with the laws in force in the country of use.

RECYCLE

7. PRODUCT DESCRIPTION

Fan-Decksarecompactfans,designedtoprovidehighvolumeflowrate,withsmallpressure levels,bycombiningsidebysidetwodouble-inletforwardcurvedcentrifugalfans,driveninexpensivelybyasinglecommonelectricalmotor.Theside-by-sidefansarefitted,togetherwiththemotorstand,onamountingplatewhichnormallyactsalsoasapressurebulkheadintheventilationmachine.Single-impeller,aswellastripleofquadrupleversionmayalsobebuilt,forspecialrequirements.

Mounting-plate designBesidesastandardrange,custom-specificFDfansarenormallyco-designedwithourcustomer,toprovidethebestintegrationofthefaninthestructureofseries-producedmachines.Mountingplatesarefrequentlyused,inverticalflowfancoilunits,alsoascondensationdrainagecollectors,includingadrain-pipeconnector.

TheFansofseriesFDPcombinehighenergyefficiencyandlownoiselevel.Thankstothe“EC”(electroniccommutation)motors,theirelectronics integratespeedcontrolandprotectingsystem.Thisreducesthenumberofdifferentcomponentsrequiredtoprovidethesefunctions,comparedtofanswithtraditionalmotors.

ThemainfeatureofEC-motorisoperatingwithoutsliplosses,whichallowconsumingsignificantlylesspowerthanconventionalACmotors.

Thisoccursatallspeedlevels,especiallywithpartialloadoperation.TheECcompletedrivesystem(i.e.thecombinationofthepermanent-magnetmotorwithitselectronicdriver)hasamuchhigherenergyefficiency,incomparisonwithadrivesystembasedonaconventionalACmotor.

Energy saving system• HighefficiencyEC-motor• Compactmotordesign• Highintensityneodymiummagnets• Noobstructionofintakeduetobuild-oncontrolunit-lessaerodynamiclosses

Page 12: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

12/40

REF. DESCRIPTION

1 Scroll2 Inletport3 Outletport4 Rotor(forward-curvedblades)

5 ECmotor

6 Driver7 IDplate

General Features

• Sensorlesscontrol• Simpleinstallationduetoplugandplay• Designedfordoubleinletfans

Interface

• Analogue interface forspeedcontrol

• FullMODBUS interface com-pliancy

High efficiency of direct driven centrifugal fan

• Integratedsolution• Topratingefficiency• Plugandplayoperation• Noneedtoconfigurelong listsofinverterparameters• Lowsoundlevel• Highreliability

8. TECHNICAL FEATURES

Size Motor code Driver code Driver phases

Abs. curr. (A)

Abs. pow. (W)

Min. temp. (°C)

Max. temp. (°C)

IP class protection

180/240 Z 1413G6 1431C1 1 Ph 2.81 A 641 W -20°C +40°C IP 32

200/190 N 1413G6 1431C1 1 Ph 2.65 A 621 W -20°C +40°C IP 32

200/190 N 1413H3 1431C1 1 Ph 4.63 A 1085 W -20°C +40°C IP 32

200/240 N 1413H4 1431C1 1 Ph 4.62 A 1069 W -20°C +40°C IP 44

200/240 N 1413H3 1431C1 1 Ph 4.62 A 1069 W -20°C +40°C IP 32

9/7 A 1413H3 1431C1 1 Ph 4.61 A 1071 W -20°C +40°C IP 32

9/9 A 1413H3 1431C1 1 Ph 4.56 A 1063 W -20°C +40°C IP 32

OtherdatarelatedtothetechnicalfeaturesarereportedontheIDplateshowninchapter3.

1

6

7

2

3 3

4

5

Page 13: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

13/40

8.1 Dimensional drawings

6N4406 - FDP 180/240 Z 1413G6

6N4407 - FDP 200/190 N 1413G6

6N4408 - FDP 200/190 N 1413H3

The plate dimensions and the anchor points can be different.

Page 14: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

14/40

6N4404 - FDP 200/240 N 1413H4

6N4405 - FDP 200/240 N 1413H3

6N4409 - FDP 9/7A 1413H3

6N4410 - FDP 9/9A 1413H3

Page 15: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

15/40

8.2 Motor - driver connections

InthestandardarrangementoftheFDPfan,themotoristurningclockwisewhenseenfromthecable-entryside,andtheelectricalconnectionsofthemotorcabletothedriverboardaremadeasshowninthefollowingfigure.Theactualpositionofthemotorconnectionsontheprintedcircuitboardmaydiffer,betweendifferentdrivermodels.

These connections are carried out by Nicotra Gebhardt and cannot be modified by the end user.

WARNINGWARNING

9. INSTALLATION

The fan installation must be carried out only by competent and qualified staff.

9.1 Commissioning

Work on the device/system by unqualified personnel or failure to comply with warnings can result in severe personal injury or serious damage to material.Only suitably qualified personnel trained in the setup, installation, commissioning and operation of the product should carry out work on the device/system.The FDP fan must be grounded through the PE connector on the driver.The following terminals can carry dangerous voltages even if the driver is inoperative:• the power supply terminals L, N or R, S, T• the motor terminals U, V, W

WARNINGWARNING

In the final installation, the device shall be directly connected to the supply terminals and shall have a contact separation in all poles, providing full disconnection under overvoltage category III conditions.

WARNINGWARNING

Page 16: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

16/40

9.2 Operation

Ensure correct grounding connections. The ground cable must be enough to carry the maximum supply fault current which nor-mally will be limited by the fuses or MCB. Suitably rated fuses or MCB should be fitted in the main supply to the driver, according to any local legislation or codes.

WARNINGWARNING

The driver operates at high voltages.Certain parameter settings may cause the driver to restart automatically after an input power failure.

CAUTIONCAUTION

9.3 Ambient operating conditions

The installation place must be in accordance with the IP protection degree of the fan. In this respect, refer to the ID plate de-scribed in chapter 3.

Humidity Range: 90% non-condensingAltitude: if the fan is to be installed at an altitude > 1000m, derating is required.Shocks: do not drop the fan or expose it to sudden shock.Vibration: do not install the fan in an area where it is likely to be exposed to constant vibrations.

CAUTIONCAUTION

9.4 Fan installation

Placethefanaccordingtoyourneeds,afterhavingcheckeditsdimensionsandthepositionofthefixingholes.

The driver must NOT be removed from the related FDP fan type and size.The driver cannot be used separate from the related fan.

WARNINGWARNING

Page 17: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

17/40

9.5 Electrical connections

REF. DESCRIPTION

1 Powersupply2 Controlboardconnection3 Communication4 BlinkingLED

5 Relayconnection

2 13

4

FDP 1.05kW 1-Phase

Before carrying out any intervention on the electrical system, disconnect the power supply by means of main switch.

Make sure that a differential switch (circuit breaker) has been installed upstream the line and that it functions properly.

Work on the driver/fan by unqualified personnel or failure to comply with warnings can result in severe personal injury or serious damage to material.Only suitably qualified personnel trained in the set-up, installation, commissioning and operation of the product should carry out work on the driver/fan. This driver must be grounded.The power supply terminals L, N (1-Phase) and the motor terminals U, V, W can carry dangerous voltages even if the driver is inoperative.

WARNINGWARNING

Page 18: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

18/40

9.5.1 Power supply

Theendusermustconnectthepowersupplycableandthecommandsignaltothecontrolboard,whilethemotorconnectionisalreadydonebyNicotra Gebhardt.

FDP 1.05kW 1-PhaseSinglePhase220/240V±10%@50/60HzTheperformance in the range [200V-264V]@50Hz/60Hz isalwaysthesameduetothePFCmoduleinsidethedriver.

Min. and max. wire section:Spring-loadedpush-inclamp,suitablefor• 0.2mm²-24AWGupto2.5mm²-12AWG(stranded)or

4mm²(solid)wireUseabladedscrewdriver,0.6x3.5mmmax,tounlock.

As concerns the cable minimum section, check the requirements issued by the country of installation.

Min. and max. section:• 0.13 - 1.31 mm2(26-16AWG)solidorstrandedcable.

9.5.2 Control board connection

FDP 1.05kW 1-Phase

1 GND2 IN3 +10V4 GND

5 B6 A

7 OUT TACHOOUT

ANALOGUESIGNAL IN

MODBUSRS485

7 ← 1

Do not reverse the input signal or connect the +10V to signal ground. The driver could be damaged.Do not apply signals with voltage outside the indicated limits, the driver could be damaged.

WARNINGWARNING

Page 19: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

19/40

9.5.3 Connection details

Inthisparagraphareexplainedthefeatureandthepossibleconnectionofthecontrolboard.Thecontrolboardterminalsareopto-insulated.

The available features can be different depending on the fan model.

9.5.3.1 Analog

ThisisthedriverdefaultmodeandthesignalmustbeconnectedintotheANALOGINPUTandthereferencetoGND.TheanaloginputcanacceptalsoaPWMsignalwithf>1kHz.

WARNINGWARNINGDo not use devices having the signal GND connected to the NEUTRAL cable of the power supply. The driver may be damaged or not functioning properly.

Theavailable+10Vpowersupplyofthedriverisintendedtobeusedwithapotentiometerofminimum2KOhm,withamaxabsorbedcurrentof5mA.Anydifferentdevicesconnectedtoitcouldbring to an undesired functioning of thedriverorofconnecteddevice.Nicotra Gebhardt canprovideadedicatedpotentiometer:REGPOTcodeK43138.

Without using the STOP switch Using the STOP switch

Page 20: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

20/40

Iftwoormorefansareinstalledinthesamecompartmentandoperatedinparallel,thefansmuststartandstopatthesametime.

An auto-restarting alarm occurs when a fan is forced to run forward (or backward) rotation with a speed higher than 150 rpm.

Ifanext.4-20mAdeviceisused,itisnecessarytoadd0.1%precisionresistancesbetweentheANALOGINPUT and GND.Thevalueoftheresistancecanrangefrom:125Ω->Vsignalrangesfrom0.5Vto2.5Vto500Ω->Vsignalrangesfrom2Vto10V

TAC

HO

/ AL

ARM

/ FI

LTER

GN

D

MO

DBU

S -B

MO

DBU

S -A

GN

D

TRAN

SUC

ER IN

PUT

ANAL

OG

INPU

T

ENAB

LE

+10V

+24V

Page 21: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

21/40

9.5.3.2 Modbus Communication

AModbusRTUprotocolisavailableonallthefanmodels.ThelinemustbeconnectedtoMODBUS-A,MODBUS-BandGNDpins.TherearetwopossibleModbusconnections:1)DuringthefanfunctioningthroughanyRS-485serialconnection2)WiththedriverpoweredoffthroughanUARTserialconnection

ToconnectOFFLINEthedrivertoaPCwhenthefanispoweredoff,aUSBtoUARTconvertercanbeused:K431A6for1-phasedrivers.AMOLEXconnector"1"isusedtoconnectthecabletothedriver.

ToconnectthedrivertoaPCduringthefanfunctioning,aUSBto485convertercanbeused:K431F8.

1

Specifications and drivers can be downloaded from Nicotra Gebhardt website: https://www.nicotra-gebhardt.com

1-phase

Page 22: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

22/40

9.5.3.3 Tachometric, Alarm and Filter Output

Theanalogueoutputchannelisconfigured,bydefault,toprovideatachometricoutputsignal.

Thetachometricoutputisa0to5VPWMwaveformat1KHz(forFDP1.05kW-1-Phonly).

whenthespeedisequalorhigherthanthespeedminanditis0%whenthespeedislower.ThedevicereadingtheoutputmustbeconnectedtoTACHO\ALARM\FILTERpinandGND.Themaxcurrentsuppliedoftheoutputis0.2mA.

Remember that the SpeedReal is 0 whenever the required speed is lower than Speedmin unless the fan is in the dragging phase.

Thesameanalogueoutputchannelcanbereconfigured,bychangingthevalueinHoldingRegister46(seeparagraph16.3atpage34),asaDigitalAlarmOutput(refertochapter17andparagraph17.4),orinoneofthealternativealarmmodesdescribedinpa-ragraphs11.1and11.2.

Input Impedances Feature available on

ANALOG INPUT 20kΩ FDP1.05kW1-Phase

9.5.3.4 Input Impedances

10. OPERATING MODES AND SETTING OPTIONS

Dependingonthefanmodel,thereare4possibleOperating Modes andforeachmode3possibleSetting Options.

TheoperatingmodesandthesettingoptionscanbechosenbymodifyingtheINPUTTYPEHolding Register 34.

Speed Control

OPERATING MODES

PID Closed Control

Loop

Asynchro-nous Emulation

Constant Airflow

Sensorless*SETTING OPTIONS

Modbus Control(Temporary setting)

Fixed Modbus(Permanent setting)

Analog Signal Control

*Thissettingisnotcurrentlyavailable.Ifnecessary,contactRegalBeloitItalyS.p.A.

Page 23: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

23/40

10.1 Speed control

(INPUT TYPE = 1 Default factory setting)Throughthissettingthefanspeedisproportionaltotheanalogvoltageinput.ThefanspeedislimitedbytheSafeOperatingArea,therefore,dependingonthefanworkingpoint,thefancouldbenomoreabletoincreasethespeedcoherentlytothesetvoltagevalue.Toavoidthelossofsignaldynamic,aspeedlimitrescalingisnecessarybymodifyingthevalueoftheMaxSpeedHolding Register 2.ItisalsopossibletorescaletheminSpeedbymodifyingtheHolding Register 1.TheanalogsignalcanbereadfromtheInput Register 14.

For more details refer to the ANNEX -> Analog Signal Considerations.

TheMAXandminspeeddefaultvaluesareinfunctionofthefansizes.

10.1.1 Analog speed control

(INPUT TYPE = 0)ThroughthissettingthefanrunsatthespeeddefinedbymodifyingtheHolding Register 66. Thesettingismaintainedmeanwhilethefanispoweredonanditislostwhenthefanispoweredoff.

10.1.2 Modbus temporary speed control

(INPUT TYPE = 2)ThroughthissettingthefanrunsatthespeeddefinedbymodifyingtheHolding Register 21. Thesettingispermanentandfanstartsatthedefinedspeedeachtimeitispoweredon.

10.1.3 Modbus fixed speed control

Therelationshipbetweencontrolvoltageandfanspeedisdescribedinparagraph10.1.4and,withmoredetail,inchapter1oftheTechnicalAnnextothismanual.

Page 24: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

24/40

Thefollowingfiguresshowasetofperformancecurvesatdifferentspeedsettingslimitedbythefanmaxworkinglimitcurve(seeparagraph1.6).

10.1.4 Speed control curves: example

10.2 Asynchronous emulation

(INPUT TYPE = 7)Throughthissettingtheslipisproportionaltotheanalogvoltage.

10.2.1 Analog asynchronous emulation

Throughthismodethereisthepossibilitytoemulatethebehaviorofanasynchronousinductionmotorwithaslipandapowerlimitationdependentontheloadandspeed(thereforetherecouldbesomedifferencesfromeachsize).Thecontrolisexpressedinpercentageinsteadofadefinedmeasureunit.Theloweristheslipthehigheristheperformanceandviceversa.

(INPUT TYPE = 8)ThroughthissettingthefanemulatesanACIMmotorandtheslipisdefinedbymodifyingtheHolding Register 66. Thesettingismaintainedmeanwhilethefanispoweredonanditislostwhenthefanispoweredoff.

10.2.2 Modbus temporary asynchronous emulation

(INPUT TYPE = 9)ThroughthissettingthefanemulatesanACIMmotorandtheslipisdefinedbymodifyingtheHolding Register 30. Thesettingispermanentandfanstartsatthedefinedconstantslipeachtimeitispoweredon.

10.2.3 Modbus fixed asynchronous emulation

Page 25: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

25/40

Thefollowingfiguresshow5curveswiththefollowingslippercentage:100%,80%,60%,40%and20%.

10.2.4 Asynchronous emulation curves: example

The slip has not a physical meaning and must be intended as a 100% full performance and 0% fan stop.

10.3.1 Modbus temporary ref. PID closed control loop

(INPUT TYPE = 11)InthismodethePIDreferenceisdefinedbymodifyingtheHolding Register 66. Thevalueofthereferenceisexpressedinstepsof0.1Volt(thereforetheregisterrangesfrom0to100)ThePIDerroriscalculatedinthefollowingway:

Error=(ModbusREG_66 - ANALOGInput)

10.3.2 Modbus fixed ref. PID closed control loop

(INPUT TYPE = 11)InthismodethePIDreferenceisdefinedbymodifyingtheHolding Register 50. Thevalueofthereferenceisexpressedinstepsof0.1Volt(thereforetheregisterrangesfrom0to100)ThePIDerroriscalculatedinthefollowingway:

Error=(ModbusREG_50 - ANALOGInput)

10.3 PID closed control loop

Page 26: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

26/40

10.3.3 Modbus positive/negative feedback

Dependingontheapplicationitcouldbenecessarytoinvertthefeedbackbehavior.ThroughtheHolding Register 31itispossibletomultiplyby-1thePIDerror.

Whentheregisterissetto0->Error=(Reference - Measure);Whentheregisterissetto1->Error=(Measure - Reference).

10.4 Changing the operation mode

Hereareshowntheactionspassingfromoneoperationmodetoanotherone.

ACTION ACTIONS A ACTIONS B

TemporarySetting->FixedSetting

Thefanmustfollowthetargetcorrespondingtothevaluestoredtherelatedregister.

Fanisputinstopmodeandafterthedataaresavedthefanfollowsthetargetcorrespondingtothevaluestoredintotherelatedregister.

FixedSetting->TemporarySetting Thefanmuststopwaitingforanewregister66value. Thefanmuststopwaitingforanewregister66value.

TemporarySetting->AnalogSignal

Thefanmustfollowthetargetcorrespondingtotheanalogvalueattheinputs.

Fanisputinstopmodeandafterthedataaresavedthefanfollowsthetargetcorrespondingtotheanalogvalue.

AnalogSignal->TemporarySetting Thefanmuststopwaitingforanewregister66value. Thefanmuststopwaitingforanewregister66value.

FixedSetting->AnalogSignal

Thefanmustfollowthetargetcorrespondingtotheanalogvalueattheinputs.

Fanisputinstopmodeandafterthedataaresavedthefanfollowsthetargetcorrespondingtotheanalogvalue.

AnalogSignal->FixedSetting

Thefanmustfollowthetargetcorrespondingtothevaluestoredtherelatedregister.

Fanisputinstopmodeandafterthedataaresavedthefanfollowsthetargetcorrespondingtothevaluestoredintotherelatedregister.

11. OTHER FEATURES

ThisfeatureisusefulwhenthespeedofthefanisnotdirectlysetbytheuserasfanssetinConstantAirflowAsynchronousEmu-lationorPIDmode.Thealarmisactivewhenaspeedthresholdisovertaken(5Vor10Vdependingonthefanmodel).

11.1 Filter alarm

Toactivatethisfeature,theHolding Register 46mustbesetatvalue2andtherequiredSpeedThresholdvaluemustbesetintothe Holding Register 55.Thedigitaloutputofthedriverchangesitsstatus.

Increasing the fan speedThe probe voltage

decreases

The probe voltage decreases

Page 27: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

27/40

Inthefollowingparagraphthestartingphaseofafanisshown.• ThefirstphasewhenthefanreceivesacommandtostartrunningistheALIGNMENT.Duringthisphasethedriveralignstherotor.• Thesecondphaseisthedraggingphase,wherethefangraduallyincreasesitsspeedtotheminimuminopenloop.Inthisphase

thecurrentandspeedvaluespresentintheInputRegistercan’tbetakeninconsideration.• Thelastphaseistheclosedloopwherethesensorlesscontrolisactiveandfromtheminimumspeedtothetargetspeedthe

fanaccelerateswithdifferentrampsbasingonthefansizeandthewheelinertia.Theaccelerationanddecelerationvaluesaredifferentandtoavoidovervoltagealarmorlossofsynchronismalarm,thedecelerationisalwayslower.

11.2 Soft start

During the ALIGNMENT and DRAGGING phases a Loss of Synchronism alarm could occur if there is a condition of wrong rotor starting position or wrong position estimation during the open loop phase. This is not a blocking alarm; therefore the fan stops and auto-restarts after few seconds.

12. SOA LIMITATIONS

Thespeedlimitscanbeadjustedforthesignalrescaling,butalsotolimitthenoiseinthefinalapplication.The Input Register 2indicatestheSpeedReference(minimumspeedduringalignmentanddraggingandtheSetSpeedinClosedControlLoop).The Input Register 3indicatestheMeasuredSpeed.

12.1 Speed limitation

Thedriverissetbyfactorydefaulttothemaxachievableelectricalinputpowertothedriverdependingonthemodel.DuringthefunctioningitispossibletomonitorthepowerabsorptionbyreadingtheInput Register 31.Ifforsomeapplicationitisnecessarytokeeptheabsorptionofthefanbelowadefinedpowervalue,itispossibletoreducethemaxpoweroutbymodifyingtheHolding Register 36.

12.2 Power limitation

Thedriversaresetbyfactorydefaulttothemaxpeakcurrentoutthatchangesdependingonthemotorwindingscharacteristics.DuringthefunctioningitispossibletoreadthepeakmotorcurrenttothemotorbyreadingtheInput Register 12. ItispossibletoreducethemotorcurrentbymodifyingtheHolding Register 7.Itissuggestedtokeepthemotorcurrentabove3500mA.

12.3 Output current limitation

ThisfeatureisnotavailableforFDPs.

12.4 Input current limitation

Page 28: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

28/40

13. OTHER VARIABLES

Thereareothervariablesthatcanbemonitoredforasafeuseofthefan.

13.1 Bus voltage

TheBUSvoltageistheDCvoltageonthebuscapacitors.Thedriveriscontinuouslymonitoringthisvoltageandwillstopthemotorintheeventofunder-voltageorover-voltage.ThevaluecanbemonitoredthroughtheInput Register 9.

13.2 Motor voltage

Themotorvoltageisthepeakvalueofthephasevoltagemodule.Toknowthermslinetolinevalue,itmustbemultipliedby√3/2.ThevaluecanbemonitoredthroughtheInput Register 13.

14. DERATING AND OVERHEATING PROTECTIONS

Whenthetemperatureofthedrivercomponentsovertakesadefinedtemperaturethreshold,theperformanceisautomaticallyreducedtodecreasetheheating.ItispossibletocheckinrealtimethetemperaturebyreadingtheInput Register 15. Ifitisnotpossibletoreachasteadythermalequilibrium,thedrivershutsdown.Theprotectionactslimitingthecurrenttothemotor.Inthisconditionthedrivergoesinalarm(seechapter17).Oncethetemperatureonthedriverdecreasesunder75°C,thealarmisautomaticallyreset.

14.1 Driver overheating: DERATING

ThemotorisprotectedthroughoneormoreThermalProtectors.Ifthemotortemperatureistoohigh,thethermalprotectoropensonephaseandthedriverrecognizestheerrorandstopsthefan(seechapter17).

14.2 Motor overheating: THERMAL PROTECTOR

The Motor Winding temperature and the driver derating are dependent on the fan size and on the fan working point. Therefore, it is possible that the fan could work at 50°C without a performance limitation.

The Driver and motor areas are rated for operating in a temperature range between -20°C and +40°C. The derating is tested and guaranteed from +40°C to +50°C. Higher temperatures could damage the motor winding or the performance could be significantly reduced.

WARNINGWARNING

Page 29: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

29/40

15. MASTER & SLAVE MODE

Thissingle-phasedriverhasatachometricoutputrangingfrom0to5VandaspecialconfigurationmustbesetontheslavefanforaMaster&Slaveconnection.ItispossibletodrivetwofansinamasterandslaveconfigurationbysettingtheMASTERinanypreferredmodeandtheSLAVEinMaster&Slavemodeonly.TheSLAVEoperatingmodemustbechanged(INPUT TYPE = 3).The MASTER must have the Holding Register 46setat0=TACHO.

15.1 Master and Slave 0-5V PWM out (for 1.05 kW 1-phase only)

AMaster&SlaveconnectionisnecessarywhenthefanshavetooperateinparallelandinanyConstant-Airflowmode,orundercontroloftheinternalPIDregulator.Havingtwoormorefansself-controllingindependently,whileoperatinginparallel,canmakethesystemunstable.AMaster&Slaveconnectionisneitherneedednorrecommendedwhenthefansinparallelarerunniginanyspeed-controlmode,evenifundercontrolofacommonexternalPIDregulator.

TAC

HO

/ AL

ARM

/ FI

LTER

TAC

HO

/ AL

ARM

/ FI

LTER

GN

D

GN

D

MO

DBU

S -B

MO

DBU

S -B

MO

DBU

S -A

MO

DBU

S -A

GN

D

GN

D

TRAN

SUC

ER IN

PUT

TRAN

SUC

ER IN

PUT

ANAL

OG

INPU

T

ANAL

OG

INPU

T

ENAB

LE

ENAB

LE

+10V

+10V

+24V

+24V

GND GNDIN IN+10 +10GND GNDB BA AOUT OUT

MASTER SLAVE

MASTER SLAVE

16 COMMUNICATION

Protocol interface:MODBUSRTU(RS485orBluetooth)

Baud rateThebaudratecanbesetthroughtheHolding Register 47 andthepossiblespeedsare:RS-485 CABLE:9.6kbpsand19.2kbps(higherspeedsarenotallowedduetotheboardOpto-Insulators)UART OFFLINE CABLE:9.6kbps,19.2kbps,38.4kbpsand57.6kbps.

Parity and Stop bitsTheparityandthestopbitscanbechosenbymodifyingtheHolding Register 48andthepossiblechoicesare:

0 No parity, 2 Stop Bits (default)

1 Odd parity, 1 Stop Bit

2 Even parity, 1 Stop Bit

The value of the Holding Registers is NOT coerced if trying to set a not allowed value.

Whentryingtoenteravalueinanyholdingregister,thevalueisnotoverwrittenifthenewvalueisoutsidetheloadboundaries.

Page 30: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

30/40

Supported Function:

03 Read Holding Registers

04 Read Input Registers

06 Write Single Holding Register

Modbus Communication TimeoutWiththisfeatureitispossibletostopthefanwhenthecommunicationislost,afteraperiodoftimesetintheHolding Register 56.Theregistercanbesetto:

Broadcast AddressTheBroadcastaddressis0.

1-Phase

1.05kW

Baud rate 9600

Parity and Stop Bits 0

Modbus Address 1

Whenthetimeoutoccurs,thedrivergoesinalarmconditionandthecommunicationmustberestoredandthealarmmustbecleared.ThealarmisindicatedintheInputregister17withthevalueof255(0xFF).

Modbus AddressTheslavedeviceaddresscanbechangedfromvalue1to247bymodifyingtheHolding Register 45.Thedefaultaddressfromfactoryconfigurationis1.

RS-485 Default Communication Parameters

0 No Communication Timeout

1 to 32767 Time expressed in seconds, therefore it is possible to set from 1sec to 9h 6m 8 sec

UART (OFFLINE) Default Communication Parameters

1-Phase

1.05kW

Baud rate 9600

Parity and Stop Bits 0

Modbus Address 1

Changing the Baud rate has an immediate effect, while the other communication parameters require the complete fan power off and consequently power on (wait until the complete discharge of the capacitors and the led turning off, otherwise the changes are not written into the EEPROM).

Page 31: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

31/40

16.1 Temporary holding register

The Holding Register 66isaspecialregisterusedineachoperatingmodeforsettingthespeed,theairflow,theslipandthePIDreference.Itisnotaphysicalregisteranditcanbewritten,butitisnotpossibletoreaditsvalue.Thesettingremainsactiveuntilthefanispoweredon.

If the fan is powered off but there is a residual charge, the microcontroller of the driver is still functioning. Therefore, if it is powered on in this situation the value set through the register 66 is still active.

16.2 Fixed holding register

ThedriversHoldingRegisterspermanentlystoredintotheEEPROMare64,butonly26registersaremodifiablebytheenduser(seethetableinthefollowingpage).ThemostimportantHolding Register 34 is the Input TyperelatedtotheselectionoftheOperatingMode.

0 Reset

1 Min Speed

2 Max Speed

7 Max Current

21 Fixed Speed Setting

30 Asynchronous Slip Setting

31 PID positive/negative

32 Avoid Range Start

33 Avoid Range End

34 Input Type

36 Max Power Out

39 Constant Airflow Setting

42 Min Airflow

43 Max Airflow

45 Modbus Address

46 Tacho\Alarm\Filter

47 Modbus Baud rate

48 Modbus Parity and Stop Bits

50 External PID Setting

51 PID Kp

52 PID Ki

53 PID Kd

54 PID Time

55 Speed Threshold

56 Communication Timeout

16.3 Holding register description

The Holding Register must be set with the fan stopped. Changing the parameters while the fun is running may cause unexpected behavior.

CAUTIONCAUTION

Do not set the values outside the indicated limits, the driver could stop working without any alarm indication, it could be reset or work in an undefined condition.

WARNINGWARNING

If the below reported "Allowed values" are written between square brackets, they must be read as "maximum" and "minimum".

Page 32: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

32/40

Holding Register 0: RESET [Adim] Thisregistercanbeusedtoresetthefanbywritingthevalue1onit.Thisregisterautomaticallyretuntovalue0afterbeingreset.Thedriverwillresetanyerrorconditionanditwilltrytorestart.

Allowed values =0and1 Default value =0

Holding Register 1: Min Speed [RPM] Thisregisterisusedtosettheminimumspeedofthefan.

Allowed values =[DefaultValue,MaxSpeed] Default value =tablebelow

200/1901413H3

200/240 1413H3

9/71413H3

9/91413H3

200/1901413G6

180/2401413G6

200/240 1413H4

1.05kW 1-Phase 400 400 400 400 400 400 400

Holding Register 2: Max Speed [RPM] Thisregistercanbeusedtosetthemaxspeedofthefan.

Allowed values =[MinSpeed,DefaultValue] Default value =tablebelow

Holding Register 7: Max Current [mA] Thisregistercanbeusedtoreducethemaxmotorcurrent.

Allowed values =[1,Defaultvalue] Default value =tablebelow

Although the value of the Max Current can be set at any value being lower than the original default one, it is not recommended using a value that is 0.3 times below the default one.

200/1901413H3

200/240 1413H3

9/71413H3

9/91413H3

200/1901413G6

180/2401413G6

200/240 1413H4

1.05kW 1-Phase 1550 1550 1550 1550 1550 1550 1550

Holding Register 16: Speed Threshold Low [RPM] Thisregistercanbeusedtosetthespeedthresholdlow.Theregisterisactivewhentheregister 46 is set to the value 3.

Allowed values =[0,SpeedThresholdHigh] Default value =0

Holding Register 21: Fixed Speed setting [RPM] ThisregistercanbeusedtosetthespeedinFixed Speed Control Mode. TheregisterisactivewhentheInputTypeHolding Register 34 is set to the value 2.

Allowed values =[MinSpeed,MaxSpeed] Default value =0

200/1901413H3

200/240 1413H3

9/71413H3

9/91413H3

200/1901413G6

180/2401413G6

200/240 1413H4

1.05kW 1-Phase 3850 3850 3850 3850 2450 2450 3850

Page 33: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

33/40

Holding Register 30: Asynchronous Slip. [%] ThisregistercanbeusedtosettheslipofanemulatedACIMmotor.TheregisterisactivewhentheInputTypeHoldingRegisterissettothevalue9.

Allowed values =[0,100] Default value =0

Holding Register 31: PID Positive/Negative [Adim] ThisregistercanbeusedtoinvertthefeedbackbehaviorofthePID.

Allowed values =0and1 Default value =0

Holding Register 32: Avoid Range Start [RPM] ThisregistercombinedwiththeAvoidRangeEndcanbeusedtoskipsomeresonancefrequenciesofthefan.

Allowed values =[0,AvoidRangeEnd] Default value =20000

Holding Register 33: Avoid Range End [RPM] ThisregistercombinedwiththeAvoidRangeStartcanbeusedtoskipsomeresonancefrequenciesofthefan.

Allowed values =[AvoidRangeStart,20000] Default value =20000

Holding Register 34: Input Type [Adim]Thisregisterdefinesallthepossibleoperatingmodes:

Allowed values =[0,12] Default value =1

0 ModbusSpeedControl Thespeedissetbymodifyingtheregister661 AnalogSpeedControl Thespeedissetthroughtheanalogsignal2 ModbusFixedSpeedControl Thespeedissetbymodifyingtheregister213 Master&Slave Thefanisconfiguredasslaveandfollowsthemaster4 AnalogConstantAirflow* Theconstantairflowissetthroughtheanalogsignal5 ModbusTemporaryConstantAirflow* Theconstantairflowissetbymodifyingtheregister666 ModbusFixedConstantAirflow* Theconstantairflowissetbymodifyingthereg.397 AnalogAsynchronousEmulation Theemulationissetthroughtheanalogsignal8 ModbusTemporaryAsynchronousEmulation Theemulationissetbymodifyingtheregister669 ModbusFixedAsynchronousEmulation Theemulationissetbymodifyingtheregister3010 AnalogRef.PIDClosedControlLoop **11 ModbusTemporaryRef.PIDClosedControlLoop ThePIDref.issetbymodifyingtheregister6612 ModbusFixedRef.PIDClosedControlLoop ThePIDref.issetbymodifyingtheregister50

*Thesesettingsarenotcurrentlyavailable.Ifnecessary,contactRegalBeloitItalyS.p.A.**Thissettingisnotavailableinthisdriver.

Page 34: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

34/40

Holding Register 36: Maximum Power [W] Thisregistercanbesettoreducethepowerouttothemotor.

Allowed values =[10,DefaultValue] Default value =tablebelow

Value

1.05kW 1-Phase 1050

Holding Register 39: Constant Airflow [m3/h]*Thisregistercanbeusedtosettheconstantairflowvalue.TheregisterisactivewhentheInputTypeHoldingRegisterissettothevalue6.*Thissettingisnotcurrentlyavailable.Ifnecessary,contactRegalBeloitItalyS.p.A.

Allowed values =[MinAirflow,MaxAirflow] Default value =0

Holding Register 45: Modbus Address [Adim]ThisregistercanbeusedtochangetheModbusaddressofadriver.

Allowed values =[1,247] Default value =1

Holding Register 46: Tachometric / Alarm / Threshold [Adim] Thisregistercanbeusedtosetthedigitaloutputfunction.

Allowed values =tablebelow Default value =0

Thepossiblesettingsare:

0 Tachometric ThedigitaloutputindicatesthemeasuredspeedthroughaPWMsignal

1 Alarm Thedigitaloutputindicateswhenanalarmoccurs

2 Threshold ThedigitaloutputindicateswhenthespeedsetintheHoldingRegister55isovertaken

3 Out of Functioning Range Thedigitaloutputindicateswhenthefanisworkinginadefinedrangeofspeeds

Holding Register 47: Modbus Speed [10−1 kbps] ThisregistercanbeusedtosettheModbusspeed.

Allowed values =tablebelow Default value =96

96 correspondingto9.6kbps

192 correspondingto19.2kbps

384 correspondingto38.4kbps(notavailableusingtheopto-insulatedterminalblock)

576 correspondingto57.6kbps(notavailableusingtheopto-insulatedterminalblock)

Page 35: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

35/40

Holding Register 48: Modbus Stop Bits [Adim] (Default = 0) Thisregistercanbeusedtosettheparityandthestopbits.

Allowed values =tablebelow Default value =0

0 2StopBits/NoParity

1 1StopBit/EvenParity

2 1StopBit/OddParity

Holding Register 50: External Set [10−1 V] ThisregistercanbeusedtosetthereferenceofthePIDcontrol.

Allowed values =[0,100] Default value =0

TheregisterisactivewhentheInputTypeHoldingRegisterissettothevalue12.

Holding Register 51: Kp [Adim] ThisregistercanbeusedtosettheProportionalGainofthePIDcontrol.

Allowed values =[0,32767] Default value =0

Holding Register 52: Ki [Adim] ThisregistercanbeusedtosettheIntegralGainofthePIDcontrol.

Allowed values =[0,32767] Default value =0

Holding Register 53: Kd [Adim] ThisregistercanbeusedtosettheDerivativeGainofthePIDcontrol.

Allowed values =[0,32767] Default value =0

Holding Register 54: Period [ms] ThisregistercanbeusedtosetthetimeconstantofthePIDcontrol.

Allowed values =[0,32767] Default value =0

Holding Register 55: Speed Threshold (or Speed Threshold HIGH) [RPM] Thisregistercanbeusedtosetthespeedthreshold,whenthemeasuredspeedintheInputRegister3overtakesthethresholdvalue.

Allowed values =[0,MaxSpeed] Default value =0

Allowed values (Functioning Indication mode) =[SpeedThresholdLow,MaxSpeed]

SpeedThreshold=0meansthatitis DEACTIVATED

Page 36: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

36/40

Allowed values =[0,9hour8min8sec] Default value =0

AttheendoftheperiodsetintotheregisterthefanstopsandthereisanAlarmindication.Torestartaresetcommandmustbesent.CommunicationTimeout=0meansthatitisDEACTIVATED

16.4 Input register description

TheModbusInputRegistersareintotal33,butonly14areusefulfortheenduser.

2 SpeedReference [rpm] 15 ModuleTemperature [10-1°C]

3 MeasuredSpeed [rpm] 17 Alarm2 [Adim]

9 BusVoltage [10-1V] 28 EnableInput [10/216V]

10 Alarm1 [Adim] 29 AnalogInput [10/216V]

12 MotorCurrent [mA] 30 TransducerInput [10/216V]

13 MotorVoltage [10-1V] 31 MeasuredPower [W]

14 AnalogInput [10-1V] 32 InputCurrent [mA]

Input Register 2: Speed Reference [rpm] Thisregisterindicatesthespeedreferenceduringthefunctioning.Duringthestartingphase,itisequaltotheMinSpeedandthengraduallyincreasestothetargetspeeddependingontheselectedmode.

Input Register 3: Measured Speed [rpm] Thisregisterindicatesthespeedduringthefunctioning.

Input Register 9: Bus Voltage [10−1 V] ThisregisterindicatestherectifiedvoltageafterthePFCstage.

Input Register 10: Alarm 1 [Adim] ThisregistermustbecombinedwiththeAlarm2register(seethetableinparagraph17.2)

Input Register 12: Motor Current [mA] Thisregisterindicatesthepeakvalueofthelinecurrentmodule.Toknowthermsvalue,itmustbedividedby√2.

Input Register 13: Motor Voltage [10−1 V]Thisregisterindicatesthepeakvalueofthephasevoltagemodule.Toknowthermslinetolinevalue,ithastobemultipliedby√3/2.

Input Register 14: Analog Voltage [10−1 V]Thisregisterindicatestheanalogvoltagevaluepresentattheinput.

Input Register 15: Module Temperature [10−1 °C]Thisregisterindicatesthetemperatureofthepowermoduleofthedriver.Whenthevalueexceedsthetemperaturethreshold,thedriverentersinaderatingprocesswheretheperformancesareautomaticallydecreaseduntilathermalequilibriumbelowthetemperaturethresholdisreached.Ifthisequilibriumisnotreached,thefanstopsandanalarmconditionisactivated.Assoonastheheatingdecreasesandthepowermoduletemperatureisbelowthetemperaturethreshold,thealarmisautomaticallyreset.ThisthresholdvaluecanbereadinHolding Register 29.

Holding Register 56: Communication Timeout [s]Thisregistercanbeusedtosetatimeoutperiodforthecommunication.

Page 37: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

37/40

Input Register 17: Alarm 2 [Adim] ThisregistermustbecombinedwiththeAlarm1register.

Input Register 28: Enable Input [Adim] ThisinputindicatestheENABLEstate.Thevaluemustbemultipliedby10V/216tohavethecorrespondingvoltagevalue.

Input Register 29: Analog Input [Adim] ThisinputindicatestheReferenceValue.Thevaluemustbemultipliedby10V/216tohavethecorrespondingvoltagevalue.

Input Register 30: Transducer Input [Adim] ThisinputindicatestheTransducerValue.Thevaluemustbemultipliedby10V/216tohavethecorrespondingvoltagevalue.

Input Register 31: Measured Power [W] Thisregisterindicatestheabsorbedpower.

Input Register 32: Input Current [mA] Thisinputindicatestheinputabsorbedcurrent.

16.5 Fan info and Modbus registers

The Holding Register 44 indicates the fan model.

The Input Register 0indicatesthedriverfirmwareversionandtheInput Register 1indicatesthedrivermodel.

1-Phase

1.05kW

Firmware Version 6

Frequency Converter

Model41505

Frequency Converter

Code1431C1

200/1901413H3

200/240 1413H3

200/2401413H4

9/71413H3

9/91413H3

200/1901413G6

180/2401413G6

1.05kW 1-Phase 1 2 2 3 4 5 6

Page 38: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

38/40

ThesystemstatuscanbedisplayedthroughtheLEDonthedriverplate(seepar.9.6).InthefollowingfigureontherighttheblinkingLEDisshown.

17.3 Blinking LED - Alarm description

17. ALARM HANDLING

Whenamalfunctioningoccurs,thedriverhastwopossiblebehaviorsdependingonthecauseofthealarm:

BLOCKING Thecauseofthealarmisverydangerous->Thedriverstopsimmediately.Torestartthefan,oncetheproblemhasbeencorrected,itisnecessarytoresetthefanorpowerthedriverofffor5minutes.

AUTO-RESTARTING Thecauseofthealarmiscontingenttoawrongsettingorwrongworkingcondition.Thealarmindica-tionsareactivated,butaftersomesecondsthefantriestorestartautomatically.

Thealarmscanbemonitoredthroughthreedifferentways:• ModbusRegisters• BlinkingLED• DigitalOutput

17.1 Monitoring

Inthefollowingtable,thealarmsandthevaluesstoredintherelatedModbus Input Register 10 and Input Register 17 areindicated.

17.2 Modbus registers - Alarm description

Alarm 1 Alarm 2 Description Actions Type0 0 Default operation – No Errors No Actions ALARM 1

1 0 Memory error Blocking condition ALARM 2

2 0 Short Circuit Blocking condition ALARM 3

3 0 Loss of synchronism Auto-restarting condition ALARM 4

4 1 Input Voltage outside range (only with motor stopped) Auto-restarting condition ALARM 4

4 32 BUS overvoltage (instantaneous measurement) Auto-restarting condition ALARM 4

4 33 BUS undervoltage (instantaneous measurement) Auto-restarting condition ALARM 4

4 34 Input relay not closed Auto-restarting condition ALARM 4

4 49 Missing phase – U cable disconnected Blocking condition ALARM 4

4 50 Missing phase – V cable disconnected Blocking condition ALARM 4

4 51 Missing phase – W cable disconnected Blocking condition ALARM 4

4 52 High starting current Auto-restarting condition ALARM 4

4 113 Overtemperature Auto-restarting condition ALARM 4

4 255 Loss of communication Blocking condition ALARM 4

The Driver is NOT protected against a very high-power supply voltage. A very low power supply voltage during the motor running could damage Driver.

WARNINGWARNING

1 sec.

Page 39: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

39/40

ThedriveroutputcanbeconfiguredasAlarmoutputbymodifyingtheHolding Register 46tovalue1.Duringthenormalfunctioning,thevalueis0Vand,whenanalarmoccurs,theoutputvalueis5V(or10Vdependingonthefanmodel).

17.4 Digital Alarm Output

Thealarmsareautomaticallyresetfollowingtheactionofthetablebelow:

17.5 Alarm Reset

Operating Mode Input Type Action

Analog 1,4,7,10 Signalsetto0V

Fixed 2,6,9,12 Registers21,39,30and50setto0

AsconcernstheTemporaryModbusmode,itisnecessarytoresetthefanbysettingtheHolding Register 0tovalue=1insteadofsettingto0theRegister 66.

Temporary 0,5,8,11 Register0setto1

The Holding Register 0 is a general reset and works also in the Analog mode and Fixed mode.

18. AVAILABLE SOFTWARE

AfreewaresoftwareisavailableonNicotra Gebhardtsite(http://www.nicotra-gebhardt.com)formonitoringthefan.Pleaserefertotherelatedmanualformoredetails

The software can be used for configuring the fan and monitoring the performance. The performance is estimated through an algorithm and, therefore, subjected to variable tolerance depending on the working point, airflow stability and the constant algorithm resolution itself.

WARNINGWARNING

Page 40: EC FAN FDP OPERATING MANUAL - Nicotra Gebhardt

Rev. 0 - 11/12/2020

OPERATING MANUALOPERATING MANUALENEN

40/40

Regal Beloit Italy S.p.A.

Via Modena, 1824040 Ciserano (BG) ITALYPhone +39 035 873 111Fax +39 035 884 319www.regalbeloit.com