Daikin VRV Catalogue 2015_tcm511-370435.pdf

  • Upload
    saleem

  • View
    247

  • Download
    1

Embed Size (px)

Citation preview

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    1/94

    VRV

    catalogue2015

    Redefining efficiency in climate control

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    2/94

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    3/941VRV catalogue 2015

    Redefining efficiency 

    in climate control

        I   n   t   r   o    d   u   c   t    i   o   n

        A   p   p    l    i   c   a   t    i   o   n   s

        H   e   a   t    R   e   c   o   v   e   r   y

        H   e   a   t    P   u   m   p

        R   e   p    l   a   c   e   m   e   n   t

        M

        i   n    i    H   e   a   t    P   u   m   p

        W   a   t   e   r   c   o   o    l   e    d

        C   o   n   t   r   o    l   s

        I   n    d   o   o   r   u   n    i   t   s

        V   e   n   t    i    l   a   t    i   o   n

        P   o   r   t    f   o    l    i   o

    Introduction to VRV 

    VRV IV total solutions 2

    VRV Heat Recovery 3

    Redefining efficiency 4-5

    Design efficiency 6-9

    Online design software

    Installation efficiency 10-11

    Operation efficiency 12-15

    Outdoor units 

    Heat Recovery VRV 

    Heat Recovery systems 24-28

    Heat Pump VRV 

    Heat Pump systems 30-36

    Replacement VRV 

    Replacement VRV 38-45

    Mini Heat Pump VRV 

    Mini Heat Pump VRV 46-49

    VRV IV range

    Water cooled VRV Water cooled VRV 50-52

    Full Multi BS box capabilities

    Applications

    Retail 16-17

    Workplace 18-19

    Hospitality 20-21

    Public buildings 22-23

    Controls

    Control solutions 54-61

    Intelligent touch Manager II

    Indoor units

    Fan coils 62-77

    Redesigned fan coils

    Hot water production Hydroboxes 78-79

    Air curtains 80-81

    Ventilation

    Heat Recovery Ventilation 82-85

    Air Handling Unit applications 86-87

    Extended range for higher

    capacity AHU’s & new control method

    Product portfolio

    Outdoor units 88-89

    Indoor units 90-91

    Hot water 90-91

    NEW

    NEW

    NEW

    NEW

    NEW

    NEW

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    4/942 VRV catalogue 2015

    VRV IV total solutionsto maximise energy efficiencyEnergy in buildings

    In many commercial buildings, there are energy balance requirements.

    Energy is needed for both heating and cooling, for hot water and

    refrigeration, as well as for ventilation. Typically, these functions are

    powered and operated by separate systems and all of the energycollected by these systems is rejected into the outside air.

    But with a VRV solution, many of these building HVAC services can be

    operated by a single system, which can recover waste energy and reuse

    it to provide heating or cooling capacity elsewhere within the building.

    Understanding whole building needs

    Heating, cooling, refrigeration and air conditioning account for around

    40-50% of a typical building’s energy usage. Most buildings rely mainly on

    primary energy from energy supplier.

    However, by understanding the whole building’s heating and cooling

    needs at the outset, an integrated climate control solution can be delivered

    that offers much higher energy efficiency levels, thus reducing the energy

    consumption and carbon impact of a building.

    Daikin has the technology, and all the products, to deliver the definitive

    answer: a total solution that redefines efficiency.

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    5/943VRV catalogue 2015

           I      n       t      r      o        d     u      c       t       i      o      n

    VRV Heat Recovery heating and cooling solutions

    Air curtains

    Biddle air curtains are the ideal solution for retailers

    and consultants to combat the issue of climate

    separation across their outlet or office doorway. Usinga combination of rectifier technology, air velocity and

    temperature control, they deliver greater comfort to

    staff and customers alike, all year round, in all weathers.

    AHU and VAM connections

    Air handling units provide bulk air movement around

    a building, to provide ventilation and maintain indoor

    air quality. By using a VRV system to connect directly

    via a refrigerant circuit, the VRV IV systems are ableto provide heating and cooling to air handling units

    to reduce or eliminate the increased loads on the air

    conditioning system due to fresh air.

    Hot water

     The waste hea t from offices,

    comms rooms, open reception

    areas, or even industrial

    applications can be re-used

    to provide, not just sanitary

    hot water, but also underfloor

    heating or water for an Air

    handling unit (AHU).

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    6/944 VRV catalogue 2015

    Redefining efficiencyof VRV technology

    For climate control in all types of buildings, the mission to

    achieve ever greater efficiency is relentless. Over time, progress

    is typically made in marginal refinements of technological

    design or operational control. Until now!

    360°efficiency

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    7/945VRV catalogue 2015

           I      n       t      r      o        d     u      c       t       i      o      n

     Today, Daikin’s unique VRV IV Heat Recovery technology completely

    redefines efficiency – of design, installation and operation.

    VRV IV+ =HEATrecovery

    FASTdesign

    Design efficiency> Widest and flexible range of design options

    > Unlimited unused ports

    > 16kW fan coil with NO capacity loss

    > No pump down required when adding fan coils* Accessory required

    QUICKinstallation

    Installation efficiency> New multi BS boxes 4, 6, 8, 10, 12, 16 port

    > Single BS box

    > Lighter, smaller, quieter than any similar system

    > Increased capacity per port

    MOREfree heat

    Operational efficiency> Variable refrigerant temperature

    > New compressor

    > 3 pipe advantage

    > New coil design

    Variable Refrigerant Volume [VRV ] was first developed

    by Daikin over 30 years ago.

     This game-changing innovation revolutionised

    heating and cooling, providing the ability to operate

    different climate control settings simultaneously in

    various areas of a building.

    By circulating only the volume of refrigerant

    required at any given time to meet the capacity

    demand, VRV offered two key benefits: reduced

    energy consumption and greater control for

    building occupants.

    Since its introduction, Daikin has led the way in

    taking this technology to new levels of efficiency,

    comfort and control.

    Now Daikin has completely re-designed this

    technology to create our market-leading climate

    control solution: VRV IV Heat Recovery.

    The result is over 30% more efficient than

    previous systems.

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    8/946 VRV catalogue 2015

    Real efficiency of design takes into account the lifetime of a

    system, not just today’s known requirements. A building’s tenants,

    uses and internal layouts may change – so its HVACR system may

    need to adapt.

    Redefining efficiency 

    in design

    Build in future flexibility

    with Multi-BS boxesA change of tenant or building

    usage typically requires substantial

    changes to branch selector (BS)

    boxes and pipework. BS boxes

    usually have a limited number

    of unused fan coil connections.

    But with Daikin’s new multi-branch

    selector boxes, that restriction no

    longer applies.

    For example, a single fan coil could

    be attached to a 10-way box,

    leaving 9 ports unused for futureneeds. Each of those vacant ports

    could later be used for 14kW fan

    coils, or to serve the high demand

    of a communications room.

     There should be no need to fit

    different or additional BS boxes.

    Only the pipe work needs to be

    changed in order to reposition fan

    coils for the new configuration.

    However, Daikin continues to offer

    single BS boxes, so a dedicated boxcan easily be added to the main

    pipework, if required.

    Reconfigured layout

    with partitioned offices 

    CAT B fit out: Reconfigured

    layout with multiple cellular

    offices, meeting room

    and comms room. 100kW

    cooling load. 22 fan coils

     Two multi-boxes: one now

    with 9 connections (other

    still with 6 connections)

    System designers can now build-in flexibility for future

    re-engineering, without compromising operating costs, energy

    efficiency or environmental performance in years to come.

    How Cat B fit outs are

    made simpleEXAMPLE: Whole floor in

    multi-storey office block 

    Original open plan layout

    CAT A fit out: Open plan.

    100kW cooling load.

    24 fan coils. One separated

    zone (access area –stairwell)

     Two multi-boxes, each

    with 6 connections plus

    unused ports

    BS boxes

    Fan coils

    BS boxes

    Fan coils

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    9/947VRV catalogue 2015

           I      n       t      r      o        d     u      c       t       i      o      n

    VRV Xpressquick design and quotation tool

    VRV Xpress is a software tool that allows you to create professional

    designs and quotations on-the-spot for a Daikin VRV System in

     just six simple steps.

    1 Select indoor units

    2 Connect outdoor units to indoor units

    3 Automatic generation of piping diagram with joints

    4 Automatic generation of wiring diagram

    5 Selection of possible centralised control systems

    6 Visualise result in MS Word, MS Excel and AutoCAD

    VRV Xpress is widely accepted as the most

    comprehensive yet simple VRV design software

    available, allowing you to design systems for peak

    loads accurately and ensuring your system will alwaysmeet the design capacity, giving you peace of mind

    that your clients’ cooling and heating expectations

    are met.

    New for 2015 – VRV Xpress is going online

    A new online version will be available from Summer

    2015 that enables the creation, editing and

    management of VRV design projects across all web

    enabled devices (Tablet, PC, Mac) so your projects will

    be accessible from anywhere.

    VRV Xpress online incorporates all of the latest Xpress

    functions in a new more user friendly way. Further

    details will follow.

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    10/948 VRV catalogue 2015

    Advanced IESmodelling capabilities

     To bring advanced VRV Heat Recovery modelling capabilities

    to the market, Integrated Environmental Solutions (IES) has

    partnered with Daikin UK to integrate the Daikin Dynamic VRV

    Systems Sizing Tool within the IES Virtual Environment (IESVE).

     This software tool enables architects and engineers to

    accurately establish the performance of these state of

    the art systems within their building project.

    Users can automatically size the system and select

    the correct VRV indoor and outdoor unit model-

    number based on the buildings heating and cooling

    loads. Full thermal simulations then reveal annualloads, power input and efficiencies.

     The tool allows users to compare alternative

    configurations so that they can easily evaluate the

    best option to maximise energy efficiency and lower

    building energy use.

     The software can be used with version VE6.5 onwards

    and covers the whole Daikin VRV range.

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    11/949VRV catalogue 2015

           I      n       t      r      o        d     u      c       t       i      o      n

    Sound levels in buildings are a major factor in occupant comfort.

    We have made dramatic reductions in the sound levels of our

    BS boxes with the introduction of new technology so you can

    be confident in achieving your clients’ expectations.

     These reductions have been made possible by completely

    redesigning the expansion valves and carefully refining and testing

    the control logic to deliver the lightest, smallest, most efficient and

    quietest range of Branch Selector boxes available on the market today.

    Branch Selector Boxes designed for low sound levels

     The Daikin 4 way multi box offers a sound reduction of 6.5 dBA when compared against other manufacturers under normal operating

    conditions. It also offers a sound reduction of 13.5 dBA (sound pressure when changing over from one mode to another) when compared

    with previous models.

    Audibly better

    45

    40

    35

    30

    25

    20

        S   o   u   n    d   p   r   e   s   s   u   r   e   >    d    B    A

    Previous version New VRV IV BS Boxes

    Stable operation

    During changeover

    With additional countermeasures sound pressure

    levels of 25 dBA can be achieved. Daikin do not

    recommend BS box installations within bedrooms.

        I   n   t   r   o    d   u   c   t    i   o   n

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    12/9410 VRV catalogue 2015

    Redefining efficiency 

    in installationFor installers, efficiency is all about time and profitability:

    the time taken to fit and commission systems, meet project

    deadlines and avoid delays due to unexpected complexity or

    changing conditions.

    Efficiency in installation is pivotal to competitiveness in project tenders. Ultimately, it can

    also be the difference between profit and loss on the job.

    The new Daikin three-pipe VRV IV Heat Recovery system takes no longer to install than

    a two-pipe system. In fact, our latest technology is designed to make installation faster,

    easier and more flexible than ever before.

    Smaller Multi-Branch Selector Boxes [BS]

     To make system fitting easier for installers, our range now includes

    4, 6, 8, 10, 12 and 16-way BS boxes. Unlike other manufacturers’

    multi-boxes, these do not require complex separators inside.

    Accordingly, all Daikin multi-boxes are at least 30% smaller –

    and our 4-way and 8-way boxes are actually half the size of other

    manufacturers’ equivalents.

    A single BS box is also available if required for a remote area

    requiring independent control of heating and cooling

    [EXAMPLES: comms room, or a newly-added enclosed office].

    All Daikin multi-boxes will fit comfortably into a 300mm ceiling.

     They are also quieter and up to 32% lighter than those of other

    manufacturers. Unlike other manufacturers’ multi-boxes, each

    port can be connected to a 14kW fan without any loss of cooling

    capacity. Those other multi-boxes are also subject to a maximum

    8kW fan coil on each port. So each Daikin BS multi-box can handle

    75% extra capacity.

    Easier commissioning and servicing

    Daikin VRV IV technology includes advanced software to simplify

    system commissioning and servicing as well as multi-site

    commissioning and control of installed systems.

     The VRV configurator incorporates a graphical interface so that

    settings can be pre-prepared off-site for high-speed uploading on

    site. Among other benefits, this reduces the time required on a roof

    to configure outdoor units, as well as reducing set-up errors that

    would otherwise require repeat visits to site.

    In addition, the software allows engineers to check systems,

    evaluate operational data and identify any errors.

    No. of

    Connections

    Physical Size (m3) Daikin Box

    ReductionDaikin Other

    1 0.262 N/A N/A

    4 0.474 0.957 50%

    5 0.743 0.957 22%

    6 0.743 0.957 22%

    8 0.743 1.422 48%

    10 1.051 1.422 26%

    12 1.051 1.422 26%

    16 1.358 1.422 5%

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    13/9411VRV catalogue 2015

           I      n       t      r      o        d     u      c       t       i      o      n

    > Saves time on commissioning

    > Manages multiple systems in exactly the same way

    > Makes it easy to retrieve initial system settings

    Simplified commissioning

     The VRV configurator is an advanced software

    solution for easy system configuration and

    commissioning:

    > Less time is required on the roof configuring the

    outdoor unit

    > Multiple systems at different sites can be managed

    in exactly the same way, thus offering simplified

    commissioning for key accounts

    > Initial settings on the outdoor unit can be

    easily retrieved

    Simplified servicing

    Outdoor unit display makes it quick and easy on-site

    to adjust settings, check basic functions and read out

    errors. The 7-segment indicator saves time via:

    > Easy-to-read error report

    > Indication of standard service parameters to

    quickly check basic functions

    > Clear menu for quick and easy servicing on-site

    Simplified

    commissioning

    Retrieve initial

    system settings

    VRV  configurator software

        I   n   t   r   o    d   u   c   t    i   o   n

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    14/9412 VRV catalogue 2015

    At the core of this technological breakthrough is Variable

    Refrigerant Temperature [VRT]. New generation VRV doesn’t just

    control the amount of refrigerant in the system; it also controlsthe temperature of that refrigerant.

    Totally redesigned withVariable Refrigerant Temperature [VRT]

     This means the evaporating and condensing temperatures can be

    tailored precisely within an HVAC system to achieve the optimum

    balance between comfort and efficiency.

     The system adjusts intelligently to weather variations and real-time

    working situations, as the load requirement fluctuates during the day

    and within individual zones of the building.

    In effect, it delivers a perfectly controlled interior climate without

    wasting energy.

    Multi-stage heat recovery unit

    > Indoor heat recovery coil on four sides: 50% more surface areafor heat exchange

    > Heating and cooling portions variable according to demand rather

    than fixed sections

    > Continuous heating: warm air still being delivered even during

    outdoor unit defrost

    > No cold draughts: no dip in comfort levels

    > Immediate return to full capacity after defrost

    Redefining efficiency 

    in operation

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    15/94

        I   n   t   r   o    d   u   c   t    i   o   n

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    16/9414 VRV catalogue 2015

    Market leading 

    operational efficiency

    VRV IV Efficiency VRF Efficiency

    Operational efficiency is much more than a nominal measure of energy consumption.

    It is now measured in the real-life application of technology throughout the changing

    seasons and the varying demands of building usage across each year.

    VRV IV HR compared with astandard VRF* system*Variable Refrigerant Flow

    Building type: Multi-storey office block  

    Time: Summer

    In this example, the differing energy consumptions

    are show in a multi-storey office block with reception

    area, cellular and open plan offices, meeting rooms,

    washrooms and communications room.

     The building is routinely occupied from 08.00-19.00,

    Monday-Friday and generally unoccupied outside

    these hours.

     The enhanced capabilities of our new systems mean

    that we are already well-placed for imminent changes

    in how efficiency will be rated in future.

    From 2016, VRV systems will no longer be rated

    on the basis of a single measure, but on their

    performance over a typical year.

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    17/9415VRV catalogue 2015

           I      n       t      r      o        d     u      c       t       i      o      n

    Daikin’s new generation VRV IV heat

    recovery extends and enhances the

    capabilities of VRV technology – giving

    greater scope for smarter use of energy

    and a more intelligent response to eachindividual building’s HVAC needs.

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    18/9416 VRV catalogue 2015

    In the current commercial environment, retailers are under pressure

    to reduce both store development and running costs. Legislation

    adds further financial pressure, with initiatives such as the Carbon

    Reduction Commitment Energy Efficiency Scheme meaning that

    larger retailers need to improve energy efficiency dramatically,

    or face stringent penalties.

    Reducing

    retail costs

    Affordable, energy efficient solutions are vital to minimise lifetime

    costs, while ensuring compliance with the latest regulations.

    According to the Carbon Trust, the retail sector is responsible for

    around 21 million tonnes of CO2 emissions per year. The retail

    sector could cut its total spend on heating and cooling by a

    massive £560 million annually by making energy savings of 20%.

     The Carbon Trust also estimates that heating and hot water

    account for 60% of a retailer’s energy bills. Typically, retailers with

    air conditioning systems have double the energy consumption and

    association carbon emissions compared with those that don’t. This

    need not be the case if an energy efficient solution is implemented.

    VRV solutions offer:

    > Energy saving inverter heat pump technology, delivering

    COP’s of up to 8 in mixed mode operation

    > Individual control of each indoor unit

    > A customisable solution using ‘variable refrigerant temperature’

    to achieve the highest seasonal efficiency

    > The highest standards of heating comfort, thanks to continuous

    heating during defrost

    > Flexible installation: the heat pump can be installed outdoors to

    maximise commercial space internally or can be installed indoors

    so there is no visual impact and low noise.

    Versatile climate control

    Climate control is key to creating a comfortable

    browsing environment in store. However a uniform

    temperature across the store is often not the best

    solution. Retailers need the flexibility to control

    multiple indoor units individually, so that the differentareas of a shop – such as the shop floor, storage and

    staff areas – can be set at different temperatures in

    order to provide the highest levels of comfort for staff

    and customers.

    Energy efficient VRV systems help to improve

    comfort levels, while allowing each area to maintain

    its set temperature. Micro processors balance

    the system’s performance with the building’s

    requirements to enable its compressors to operate

    down to power levels 40 to 45% lower than more

    conventional systems, thus reducing running costs

    and carbon emissions.

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    19/9417VRV catalogue 2015

          A     p     p       l      i     c     a      t      i     o     n     s

    Case study

    Porsche Centre, Colchester

    Extending a car showroom ahead of the launch of the sporty

    Macan Turbo SUV meant the Porsche Centre in Colchesterneeded an equally standard-setting heating and ventilation

    system to provide a comfortable environment for customers

    and staff.

    Echoing the Macan’s principles of performance, efficiency

    and comfort the heating and ventilation system now serving

    the enlarged display area – created by converting the former

    workshop – is Daikin’s range-topping VRV IV heat pump and

    a VAM ventilation unit.

     The new heat pump operates alongside an earlier VRV III heat

    recovery system, which serves the existing offices.

     The ceiling units installed at Colchester are ideal for use in shopsand medium sized offices, because they can be used with ducts

    of varying lengths. They consume 20% less electricity than similar

    earlier models, thanks to a new DC fan.

     The Daikin VAM heat reclaim ventilat ion (HRV ) unit, also mounted

    in the ceiling, modulates the temperature and humidity of

    incoming fresh air to match the indoor conditions. This provides a

    balance between indoor and outdoor temperatures, significantly

    reducing the cooling or heating load on the air conditioning

    system while ensuring frequent air-changes.

    > 1 VRV IV heat pump (20hp)

    > 6 Medium static pressure concealed ceiling unitswith inverter fan(10kW and 12.5kW)

    > 1 VAM heat recovery ventilation unit

    > Daikin Intelligent Touch controller

    Case study

    The Range, Warrington

    The Range is a nationwide retail chain offering a variety of

    mid-priced goods for the home – DIY, homewares, furniture,lighting, arts and crafts and garden products.

     The Daikin systems ser ving The Range’s 7,800m2 store in

    Warrington provide a complete solution for climate control

    and hot water. Seven VRV IV heat pump condensing units and

    71 self-cleaning Roundflow Cassettes heat or cool the shop floor

    in response to commands from the Daikin RTD-20 retail control

    system. A VRV III heat recovery system and standard fan coils

    provide simultaneous heating and cooling in the offices and

    other back-of-house facilities – as well as hot water.

     The VRV IV heat pump is 28% more efficient than earlier models,

    as its Variable Refrigerant Temperature technology adjusts to

    provide optimal seasonal efficiency at all times. VRV IV alsoqualifies for ECA approval.

    “ We were very happy to work with Daikin UK to incorporate

    one of the latest fully integrated renewable systems, allowing

     The Range at Warrington to have a fully controllable system

    with operation flexibility according to requirements.”

      Brad Hurter, CDS Group

    > 7 VRV IV heat pump condensing units

    with continuous heating

    > 71 Self-cleaning Roundflow Cassettes

    > 1 VRV III heat recovery condensing unit

    > VRV fan coil units> Hydrobox

    > 200-litre DHW tank 

    > VAM heat recovery ventilation unit

    > RTD-20 intelligent retail control system

    > I-Touch Manager

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    20/9418 VRV catalogue 2015

    Efficient building and facilities management are key to minimising

    operational costs within medium-sized offices and large

    office complexes.

    Efficiency in the

    workplace

    Heating, air conditioning, hot water and ventilation are all

    significant areas of energy consumption. But neither the

    commercial climate, nor the current legislative framework,

    will tolerate wasted resources. Responsible businesses are

    seeking new and innovative ways to rein in their running costs

    and carbon emissions.

    Daikin provides total climate management solutions that put

    building managers in complete control of the indoor climate. VRV

    solutions are ideal for medium to large buildings, helping installers,

    specifiers and building managers to:

    > Dramatically reduce the cost of hot water and heating byre-using heat recovered from areas requiring cooling

    > Ensure controllable comfort, by simultaneously heating

    spaces while cooling others

     > Choose outdoor heat pump installation to maximise commercial

    space internally or indoor installation to minimise the visual

    impact and noise externally.

    A healthier office atmosphereVRV’s integrated capabilities mean that ventilation and air

    conditioning can be combined in one system, with air filtration

    ensuring a steady supply of clean air. Energy waste is minimised

    by recovering heat from the stale air expelled from buildings and

    using it to heat incoming air virtually for free.

    Cutting the cost of hot waterBy using VRV’s heat pump technology to recover

    heat from areas requiring cooling, reclaimed heat can

    be used to produce hot water for sinks, under floor

    heating, showers and radiators. The entire system can

    be connected to solar panels to provide additional

    solar thermal energy for hot water production.

    Centralised controls for officesManaging comfort settings and energy consumption

    is easy with VRV systems, which offer user-friendly

    controls that can be integrated with other buildingservices such as lighting and blinds.

    > Easy to use touch screen

    > Many energy saving functions available including

    movement sensors, controllers with evening and

    holiday schedules

    > Energy consumption can be set per indoor unit

    > Monitoring and control available for up to

    128 indoor units

    > Online monitoring and control available for

    multiple buildings

     > Controls can be integrated with other systems

    e.g. blinds, lights etc.

    > Energy costs can be managed and divided amongmultiple tenants.

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    21/9419VRV catalogue 2015

          A     p     p       l      i     c     a      t      i     o     n     s

    Case study

    Velocity, Brooklands

    Energy efficient heat recovery air conditioning from

    Daikin UK enhances the ‘green’ credentials of a stylish officedevelopment designed to attract ‘head office’ tenants at

    Brooklands, in Surrey.

    With their Breeam ‘excellent’ rating and low B ratings for

    energy performance, the two buildings in the 9,885m2 Velocity

    development sport a range of environment friendly systems to

    create a top-class workplace that is economically attractive to

    both landlord and tenants.

    Named to evoke memories of Brooklands’ aviation and motor

    racing past, the five-storey Velocity buildings symbolise

    streamlined speed and their systems reflect the best in technology.

    Solar shading on the south-facing aspects reduces solar gain,while rooftop photovoltaic and solar thermal arrays provide

    renewable alternatives for some of the buildings’ energy needs.

    Daikin UK’s VRV III heat recovery systems were specified for

    Velocity’s office heating and cooling needs, giving the buildings a

    total of 358hp of air conditioning power.

     The entire air conditioning system is controlled automatically by

    the Building Energy Management System, which is programmed

    to keep indoor temperatures at 22-23°C all year.

    “ Daikin is a personal preference of mine. They were first with

    VRV and have led the field with improvements to the concept. Their systems are very reliable.”

      Peter Wright, Wright Engineering Consultants

    > 28 VRV III heat recovery compact condensing units

    > 2 VRV III heat pumps

    > 256 ducted fan coil units

    Case study

    Flow, Staines-upon-Thames

    A structural extension to suit a major tenant moving into

    a high efficiency new-build office development beside theRiver Thames provided an ideal opportunity to compare

    the performance of two generations of Daikin VRV air

    conditioning systems.

     The original 6,709m2 development at Staines-upon-Thames

    consisted of two buildings – Flow 1 and Flow 2. Respectively four

    and three storeys, they were built speculatively and Category A

    fitted for possible occupation by up to seven individual tenants

    after completion in 2013. Both buildings have BREEAM ‘excellent’

    ratings – exceeding the original aim of ‘very good’ through

    increased on-site efficiency.

    Complementing the buildings’ other efficiencies, seven separate,

    independently controlled Daikin VRV III heat recovery systemswith outdoor units of 20hp to 38hp were installed.

    However, the whole development has been let to an American

    software company on a 10-year lease and contractors have

    added walk-though access between the first and second floors

    of the buildings.

     The two-storey link adds another 173m2 of usable space,

    requiring two additional fan coil units on each level, served by

    the new 8hp VRV IV HR condenser.

    > 7 VRV III Heat recovery systems (20-38hp)

    > 1 VRV IV Heat recovery system (8hp)> 4.9kW ducted inverter fan coil units

    > Daikin Intelligent Touch controls

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    22/9420 VRV catalogue 2015

    A hotel’s reputation depends on how welcome and comfortable

    guests feel during their stay – and Daikin UK has a complete solution

    for hotels to help create the perfect ambience. Yet at the same time,

    hotel operators must maintain complete control of their operating

    costs and energy consumption.

    Hospitalitywith economy

    Daikin’s cost-effective solutions can offer total control of hotel air

    conditioning, ventilation, heating and hot water, with stylish yet

    silent, draft-free indoor units that promise a good night’s sleep.

    And because VRV is a modular solution, upgrade and renovation

    projects can be phased to minimise interruption.

    Integrated heat recovery

    Integrated solutions offer zone by zone control of hospitality areas

    and guest bedrooms:

     > Recovering heat from areas requiring cooling and re-using for

    low cost heating and hot water

    > Creating the perfect environment for guests by simultaneously

    heating spaces while cooling others

     > Maximising hospitality space with outdoor heat pump

    installation, or opting for indoor installation in city centres,

    to minimise external space and noise.

    Heating water with renewable energy

    Renewable energy can be used to produce low-cost hot water for

    bathrooms, under floor heating and radiators, thanks to VRV heat

    recovery solutions, which reclaim waste heat from areas requiringcooling to heat hot water up to 80°C.

    Smart energy management

    Daikin VRV systems can be controlled centrally,

    in tandem with other building services such as

    lighting and fire alarm systems, for optimum comfort,

    efficiency and safety:

    > Centralised management available for VRV systems

    with up to 2,560 indoor units

    > Controls offer intuitive navigation, graphicalinterface and extensive reporting

    > Energy consumption can be set per indoor unit

     > Controls can be integrated with other systems

    e.g. lighting, fire alarms etc.

     > Online monitoring and control is available for

    multiple buildings.

    Intelligent hotel room controller

    Hotel owners need full control of energy use. A Daikin

    intelligent controller can adjust the system setpoint

    when bedrooms are vacant or windows are opened,

    thus preventing unnecessary energy consumption

    to maintain absolute control over the hotel’s runningcosts and environmental impact. Daikin’s intelligent

    room controller:

    > Connects to all types of controllers, including easy

    to use touch screens

     > Integrates easily with hotel management software.

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    23/9421VRV catalogue 2015

          A     p     p       l      i     c     a      t      i     o     n     s

    Case study

    Bloomsbury Hotel, London

    In a nine-month phased project, the Grade II listed

    Bloomsbury Hotel replaced an ageing air conditioningsystem to beat the ban on R22 refrigerant and achieve

    significant energy savings.

    As part of ongoing upgrade programme, the hotel’s owners,

     The Doyle Collection, wanted to cut energy usage and CO2 

    emissions. They opted for a Daikin VRV-Q system, which is

    40% more efficient in heating and 25% better in cooling than

    R22 systems.

    VRV-Q has the added benefit of allowing the re-use of existing

    pipework and some indoor units – reducing replacement costs

    and speeding up installation. At the Bloomsbury, the installation

    cost savings were about 50%. The phased replacement also

    minimised the impact on occupancy rates and therefore theeffect on revenue.

    In its first year of operation, the VRV-Q system helped reduced the

    Bloomsbury Hotel’s energy usage by 15,000kWh – independently

    assessed as a 23.5% year-on-year saving.

    “The Daikin system is more efficient and certainly quieter than

    the old one. Our energy bills are between 23% and 26% lower

    than before the system was changed.”

    Michael Neve, General Manager, Bloomsbury Hotel

    > 56 VRV-Q outdoor units

    > 209 indoor units

    Case study

    Chester Hotel, Aberdeen

    A £5 million refurbishment programme, which saw the

    Simpsons Hotel in Aberdeen transform into the five starChester Hotel, sparked some special creativity in air

    conditioning design for public areas.

    Chris Thoms, Mechanical Design Manager for Hutcheon Services,

    Aberdeen, was tasked with providing a five star air conditioning

    solution for the new-look hotel. The system chosen to air-

    condition the public areas and the conference and wedding

    facilities was Daikin VRV III Heat Recovery.

    “ The client was keen on the Daikin system for its high energy

    efficiency and the benefits of a VRV heating and cooling system,”

    he says.

    “ It was challenging getting the air conditioning for the mainconference room into the project because of the thickness of

    acoustic insulation above the ceiling. There wasn’t really a ceiling

    void to house the units.”

    Various alternatives were considered, but the chosen solution

    was to fabricate ‘domes’ matching the circular overhead light

    fittings selected for the conference room. The domes provided

    depth to accommodate Daikin slim ducted fan coil units, each

    with a nominal 7kW of cooling and 8kW of heating.

    > Daikin VRV III heat recovery

    > Slim ducted fan coil units

    > Ducted inverter fan coil units> VAM heat recovery ventilation unit

    > iTouch Manager

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    24/9422 VRV catalogue 2015

    Public buildings are under increasing pressure to lead the way in

    sustainability, in order to reduce carbon emissions – and improve

    energy efficiency as part of overall strategy to spend public money

    more carefully.

     The government estate makes up a significant part of the built

    environment, providing working places for 5.4 million people –

    about 18% of the workforce. According to the Office of NationalStatistics, ‘public’ buildings are responsible for about 10 million

    tonnes of CO2 annually.

    In seeking to meet energy efficiency targets across both public and

    private sectors, government and its agencies have to demonstrate

    a willingness to replace outdated and wasteful heating and cooling

    systems with efficient modern technology.

    VRV systems provide ideal solutions for most public buildings,

    offering operating cost savings, a reduced carbon footprint,

    high efficiency in all ambient conditions and a working

    environment that is always comfortable for staff and visitors.

    VRV is the established leader in air conditioning technology –and the perfect tool to lead the drive for carbon reduction.

    Public buildings lead the way

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    25/9423VRV catalogue 2015

          A     p     p       l      i     c     a      t      i     o     n     s

    Case study

    Portcullis House, Cardiff 

    Switching to Daikin VRV IV heat recovery air conditioning as

    part of a major refurbishment project has given the ownersof a 3,600m2 Cardiff office building an additional benefit –

    a healthy extra 350m2 of space to let to the new tenant,

    the NHS.

    Portcullis House, previously occupied by HMRC, has three storeys

    of open plan offices and seven storeys of smaller offices and

    meeting rooms in a taller wing behind.

    An old four-pipe air conditioning system, with floor-mounted

    fan coil units, piping and associated trunking on perimeter walls,

    has been removed – yielding the 10% increase in lettable space.

    Heating and cooling for the old system was provided by boilers

    and chillers – all of which were in a poor state.

    Daikin’s brand new VRV IV heat recovery air conditioning was

    specified for its cutting edge technology and high efficiency.

    As an added benefit, its refrigerant piping, branch selector boxes

    and round flow cassettes could all be accommodated within the

    existing ceiling voids.

    Portcullis House has a fairly high degree of solar gain, which

    means that it often requires simultaneous cooling and heating.

     The VRV IV heat recovery facility means rejected thermal energy

    from the ‘hot’ side can be used efficiently to warm the colder

    parts of the building.

    > 3 VRV IV heat recovery condensing units (22h and 26hp)> 38 Roundflow Cassettes (1.8kW to 7.2kW)

    > 21 Wall-mounted fan coil units (1.2kW to 2.9kW)

    Case study

    Palace of Westminster, London

    During a refurbishment project at the Houses of Parliament,

    Daikin’s innovative VRV-Q plug-in system was selectedto replace outdated air conditioning systems using now

    banned R22 refrigerant.

    Like many other buildings with R22 systems, the iconic London

    landmark had to make the change because of the phase-out of

    the gas. New sources of R22 were banned in 2010 and recycled

    gas was also banned from 31December 2014 under European

    environmental legislation.

    VRV-Q uses R410A refrigerant, which has zero ozone depletion

    potential and reduces associated CO2 emissions. VRV-Q also

    improves energy efficiency and is able to reduce energy

    consumption by up to 40%.

    VRV-Q offers a technically secure and cost-effective option to a

    full system upgrade. It can reduce the cost of an R22 upgrade

    by up to 50% because VRV-Q outdoor units are designed to

    work with existing R22 piping – and potentially also controllers

    and indoor units manufactured after 1996. This means only the

    outdoor units and heat recovery branch selector boxes have to

    be changed – saving time and reducing costs.

    A fast and effective upgrade is possible because VRV-Q

    operates at lower pressures to suit existing R22 piping, without

    compromising efficiency levels. In fact, a VRV-Q 10hp system has

    a COP of 3.98 and an EER of 4.00 – around 50% more efficient

    than the equivalent R22 system it replaces.

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    26/9424 VRV catalogue 2015

    Small footprint combination

     > Optimised footprint within heat recovery range

    High COP combination

     > Top energy efficiency in Daikin heat recovery range

    VRV heat recovery, with connection

    to heating only hydrobox > Fully integrated system

     > Free hot water

     > For either heating or cooling operation

    from one system

    VRV Heat Recovery> For simultaneous heating and cooling from the same system

    > Heat recovered from indoor units is recycled to provide heat for indoor spaces,

    to water and for fresh air. This maximises efficiency and reduces running costs

    by delivering high part load efficiencies

    > Select a system with a small footprint or increase even further your efficiency

    by combining higher efficiency condensers to meet the projects requirements

    > Provide cooling even with an ambient temperature as low as -20°C

    > The widest range of installation options available with the smaller, quieter and

    lighter range of single and multi BS boxes

    VRV IV Heat Recovery – REYQ-T 25

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    27/9425VRV catalogue 2015

        H   e   a   t    R   e   c   o   v   e   r   y

    Outdoor Units 13 HP Multi 14 HP Single 16 HP Single 16 HP Multi

    REYQ8T REMQ5T REYQ14T REYQ16T REYQ8T REYQ8T

    Capacity Nominal Cooling kW 36.40 40.00 45.00 45.00

    Nominal Heating kW 33.50 40.00 45.00 45.00

    Dimensions Height x Width x Depth mm 1685 x 930 x 765 1685 x 930 x 765 1685 x 1240 x 765 1685 x 1240 x 765 1685 x 930 x 765 1685 x 930 x 765

    Weight kg 198 198 319 319 198 198

    Fan Air Flow Rate m3/sec 2.70 2.70 3.72 4.33 2.70 2.70

    Electrical Details Power Supply Phase 3ph / 50 Hz / 380~415V

    Running Current amps 8.9 5.3 17.4 21.1 8.9

    Starting Current amps 4

    Fuse Rating amps 20 20 32 40 20 20Refrigerant Circuit Refrigerant Type R410A

    Refrigerant Charge kg data book data book data book data book  

    Additional Charge kg data book  

    Sound Pressure dBA 58 58 61 64 58 58

    Sound Power dBA 78 78 81 86 78 78

    Piping Limits Maximum Total Length m 1000

    Maximum Actual Length m 165

    Piping Connections -Systems

    Liquid inches 1 1/8 1 1/8 1 1/8 1 1/8

    Gas inches 1/2 1/2 1/2 1/2

    Discharge inches 3/4 7/8 7/8 7/8

    Capacity Index Limit 162.5 ~ 422.5 175 ~ 455 200 ~ 520 200 ~ 520

    Maximum Number of Connected Indoor Units 64 64 64 64

    REYQ-T

    VRV IV Condensing Units – Heat Recovery

    Outdoor Units 8 HP Single 10 HP Single 10 HP Multi 12 HP Single

    REYQ8T REYQ10T REMQ5T REMQ5T REYQ12T

    Capacity Nominal Cooling kW 22.40 28.00 28.00 33.50

    Nominal Heating kW 22.40 28.00 28.00 33.50

    Dimensions Height x Width x Depth mm 1685 x 930 x 765 1685 x 930 x 765 1685 x 930 x 765 1685 x 930 x 765 1685 x 930 x 765

    Weight kg 198 205 198 198 205

    Fan Air Flow Rate m3/sec 2.70 2.92 2.70 2.70 3.08

    Electrical Details Power Supply Phase 3ph / 50 Hz / 380~415V

    Running Current amps 8.9 11.8 5.3 15.3

    Starting Current amps 4

    Fuse Rating amps 20 25 20 20 25

    Refrigerant Circuit Refrigerant Type R410A

    Refrigerant Charge kg data book data book data book data book  

    Additional Charge kg data book  

    Sound Pressure dBA 58 58 58 58 61Sound Power dBA 78 79 78 78 81

    Piping Limits Maximum Total Length m 1000

    Maximum Actual Length m 165

    Piping Connections -Systems

    Liquid inches 3/4 7/8 7/8 1 1/8

    Gas inches 3/8 3/8 3/8 1/2

    Discharge inches 5/8 3/4 3/4 3/4

    Capacity Index Limit 100 ~ 260 125 ~ 325 125 ~ 325 150 ~ 390

    Maximum Number of Connected Indoor Units 64 64 64 64

    REYQ-T (8 to 12 HP)

    REYQ-T (13 to 16 HP)

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    28/9426 VRV catalogue 2015

    REYQ-T

    VRV IV Condensing Units – Heat Recovery

    REYQ-T (18 to 20 HP)

    REYQ-T (22 to 28 HP)

    Outdoor Units 18 HP Single 18 HP Multi 20 HP Single 20 HP Multi

    REYQ18T REYQ8T REYQ10T REYQ20T REYQ10T REYQ10T

    Capacity Nominal Cooling kW 50.00 51.00 56.00 56.00

    Nominal Heating kW 51.00 51.00 56.00 56.00

    Dimensions Height x Width x Depth mm 1685 x 1240 x 765 1685 x 930 x 765 1685 x 930 x 765 1685 x 1240 x 765 1685 x 930 x 765 1685 x 930 x 765

    Weight kg 329 198 205 329 205 205

    Fan Air Flow Rate m3/sec 4.18 2.70 2.92 4.35 2.92 2.92

    Electrical Details Power Supply Phase 3ph / 50 Hz / 380~415V

    Running Current amps 24.6 8.9 11.8 31.1 11.8

    Starting Current amps 4

    Fuse Rating amps 40 20 25 50 25 25

    Refrigerant Circuit Refrigerant Type R410A

    Refrigerant Charge kg data book data book data book data book data book  

    Additional Charge kg data book  

    Sound Pressure dBA 65 58 58 66 58 58Sound Power dBA 86 78 79 88 79 79

    Piping Limits Maximum Total Length m 1000

    Maximum Actual Length m 165

    Piping Connections -Systems

    Liquid inches 1 1/8 3/4 1 1/8 1 1/8

    Gas inches 5/8 3/8 5/8 5/8

    Discharge inches 7/8 5/8 1 1/8 1 1/8

    Capacity Index Limit 225 ~ 450 100 ~ 260 250 ~ 650 250 ~ 650

    Maximum Number of Connected Indoor Units 64 64 64 64

    Outdoor Units 22 HP Multi 24 HP Multi 26 HP Multi 28 HP Multi

    REYQ10T REYQ12T REYQ8T REYQ16T REYQ12T REYQ14T REYQ12T REYQ16T

    Capacity Nominal Cooling kW 61.50 67.40 73.50 78.50

    Nominal Heating kW 61.50 67.40 73.50 78.50

    Dimensions Height x Width x Depth mm 1685 x 930x 765

    1685 x 930x 765

    1685 x 930x 765

    1685 x 1240x 765

    1685 x 930x 765

    1685 x 1240x 765

    1685 x 930x 765

    1685 x 1240x 765

    Weight kg 205 205 210 305 205 319 205 319

    Air Flow Rate m3/sec 2.92 3.08 2.70 4.33 3.08 3.72 3.08 4.33

    Electrical Details Power Supply Phase 3ph / 50 Hz / 380~415V

    Running Current amps 11.8 15.3 8.9 21.1 15.3 17.4 15.3 21.1

    Starting Current amps 4

    Fuse Rating amps 25 25 20 40 25 32 25 40

    Refrigerant Circuit Refrigerant Type R410A

    Refrigerant Charge kg data book data book data book data book  

    Additional Charge kg data book  

    Sound Pressure dBA 58 61 58 64 61 61 61 64

    Sound Power dBA 79 81 78 86 81 81 81 86

    Piping Limits Maximum Total Length m 1000

    Maximum Actual Length m 165

    Piping Connections -Systems

    Liquid inches 1 1/8 1 3/8 1 3/8 1 3/8

    Gas inches 5/8 3/4 3/4 3/4

    Discharge inches 1 1/8 1 1/8 1 1/8 1 1/8

    Capacity Index Limit 275 ~ 715 300 ~ 780 325 ~ 845 350 ~ 910

    Maximum Number of Connected Indoor Units 64 64 64 64

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    29/9427VRV catalogue 2015

        H   e   a   t    R   e   c   o   v   e   r   y

    Outdoor Units 38 HP Multi 40 HP Multi 42 HP Multi

    REYQ8T REYQ12T REYQ18T REYQ10T REYQ12T REYQ18T REYQ10T REYQ16T REYQ16T

    Capacity Nominal Cooling kW 106.40 111.50 118.00

    Nominal Heating kW 106.40 111.50 118.00

    Dimensions Height x Width x Depth mm 1685 x 930x 765

    1685 x 930x 765

    1685 x1240 x

    765

    1685 x 930x 765

    1685 x 930x 765

    1685 x1240 x

    765

    1685 x 930x 765

    1685 x1240 x

    765

    1685 x1240 x

    765

    Weight kg 210 218 337 205 205 329 205 319 319

    Fan Air Flow Rate m3/sec 2.70 3.08 4.18 2.92 3.08 4.18 2.92 4.33 4.33

    Electrical Details Power Supply Phase 3ph / 50 Hz / 380~415V

    Running Current amps 8.9 15.3 24.6 11.8 15.3 24.6 11.8 21.1 21.1

    Starting Current amps 4

    Fuse Rating amps 20 25 40 25 25 40 25 40 40

    Refrigerant Circuit Refrigerant Type R410A

    Refrigerant Charge kg data book data book data book  

    Additional Charge kg data book data book data book  

    Sound Pressure dBA 58 61 65 58 61 65 58 64 64

    Sound Power dBA 78 81 86 79 81 86 79 86 86

    Piping Limits Maximum Total Length m 1000 1000 1000

    Maximum Actual Length m 165 165 165

    Piping Connections -Systems

    Liquid inches 1 5/8 1 5/8 1 5/8

    Gas inches 3/4 3/4 3/4

    Discharge inches 1 3/8 1 3/8 1 3/8

    Capacity Index Limit 475 ~ 1235 500 ~ 1300 525 ~ 1365

    Maximum Number of Connected Indoor Units 64 64 64

    REYQ-T

    VRV IV Condensing Units – Heat Recovery

    REYQ-T (30 to 36 HP)

    REYQ-T (38 to 42 HP)

    Outdoor Units 30 HP Multi 32 HP Multi 34 HP Multi 36 HP Multi

    REYQ12T REYQ18T REYQ16T REYQ16T REYQ16T REYQ18T REYQ16T REYQ20T

    Capacity Nominal Cooling kW 83.50 90.00 95.00 101.00

    Nominal Heating kW 83.50 90.00 95.00 101.00

    Dimensions Height x Width x Depth mm 1685 x 930x 765

    1685 x 1240x 765

    1685 x 1240x 765

    1685 x 1240x 765

    1685 x 1240x 765

    1685 x 1240x 765

    1685 x 1240x 765

    1685 x 1240x 765

    Weight kg 205 329 319 319 319 329 319 329

    Fan Air Flow Rate m3/sec 3.08 4.18 4.33 4.33 4.33 4.18 4.33 4.35

    Electrical Details Power Supply Phase 3ph / 50 Hz / 380~415V

    Running Current amps 15.3 24.6 21.1 21.1 24.6 21.1 31.1

    Starting Current amps 4

    Fuse Rating amps 25 40 40 40 40 40 40 50

    Refrigerant Circuit Refrigerant Type R410A

    Refrigerant Charge kg data book data book data book data book  

    Additional Charge kg data book  Sound Pressure dBA 61 65 64 64 64 65 64 66

    Sound Power dBA 81 86 86 86 86 86 86 88

    Piping Limits Maximum Total Length m 1000

    Maximum Actual Length m 165

    Piping Connections -Systems

    Liquid inches 1 3/8 1 3/8 1 3/8 1 5/8

    Gas inches 3/4 3/4 3/4 3/4

    Discharge inches 1 1/8 1 1/8 1 1/8 1 1/8

    Capacity Index Limit 375 ~ 975 400 ~ 1040 425 ~ 1105 450 ~ 1170

    Maximum Number of Connected Indoor Units 64 64 64 64

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    30/9428 VRV catalogue 2015

    Outdoor Units 44 HP Multi 46 HP Multi 48 HP Multi

    REYQ12T REYQ16T REYQ16T REYQ14T REYQ16T REYQ16T REYQ16T REYQ16T REYQ16T

    Capacity Nominal Cooling kW 123.50 130.00 135.00

    Nominal Heating kW 123.50 130.00 135.00

    Dimensions Height x Width x Depth mm 1685 x 930x 765

    1685 x1240 x

    765

    1685 x1240 x

    765

    1685 x1240 x

    765

    1685 x1240 x

    765

    1685 x1240 x

    765

    1685 x1240 x

    765

    1685 x1240 x

    765

    1685 x1240 x

    765

    Weight kg 205 319 319 319 319 319 319 319 319

    Fan Air Flow Rate m3/sec 3.08 4.33 4.33 3.72 4.33 4.33 4.33 4.33 4.33

    Electrical Details Power Supply Phase 3ph / 50 Hz / 380~415V

    Running Current amps 15.3 21.1 21.1 17.4 21.1 21.1 21.1

    Starting Current amps 4

    Fuse Rating amps 25 40 40 32 40 40 40 40 40

    Refrigerant Circuit Refrigerant Type R410A

    Refrigerant Charge kg data book data book data book  

    Additional Charge kg data book data book data book  

    Sound Pressure dBA 61 64 64 61 64 64 64 64 64

    Sound Power dBA 81 86 86 81 86 86 86 86 86

    Piping Limits Maximum Total Length m 1000 1000 1000

    Maximum Actual Length m 165 165 165

    Piping Connections -Systems

    Liquid inches 1 5/8 1 5/8 1 5/8

    Gas inches 3/4 3/4 3/4

    Discharge inches 1 3/8 1 3/8 1 3/8

    Capacity Index Limit 550 ~ 1430 575 ~ 1495 600 ~ 1560

    Maximum Number of Connected Indoor Units 64 64 64

    Outdoor Units 50 HP Multi 52 HP Multi 54 HP Multi

    REYQ16T REYQ16T REYQ18T REYQ16T REYQ18T REYQ18T REYQ18T REYQ18T REYQ18T

    Capacity Nominal Cooling kW 140.00 145.00 150.00

    Nominal Heating kW 140.00 145.00 150.00

    Dimensions Height x Width x Depth mm 1685 x1240 x

    765

    1685 x1240 x

    765

    1685 x1240 x

    765

    1685 x1240 x

    765

    1685 x1240 x

    765

    1685 x1240 x

    765

    1685 x1240 x

    765

    1685 x1240 x

    765

    1685 x1240 x

    765

    Weight kg 319 319 329 319 329 329 329 329 329

    Fan Air Flow Rate m3/sec 4.33 4.33 4.18 4.33 4.18 4.18 4.18 4.18 4.18

    Electrical Details Power Supply Phase 3ph / 50 Hz / 380~415V

    Running Current amps 21.1 21.1 24.6 21.1 24.6 24.6 24.6

    Starting Current amps 4

    Fuse Rating amps 40 40 40 40 40 40 40 40 40

    Refrigerant Circuit Refrigerant Type R410A

    Refrigerant Charge kg data book data book data book  

    Additional Charge kg data book data book data book  

    Sound Pressure dBA 64 64 65 64 65 65 65 65 65

    Sound Power dBA 86 86 86 86 86 86 86 86 86

    Piping Limits Maximum Total Length m 1000 1000 1000

    Maximum Actual Length m 165 165 165

    Piping Connections -Systems

    Liquid inches 1 5/8 1 5/8 1 5/8

    Gas inches 3/4 3/4 3/4

    Discharge inches 1 3/8 1 3/8 1 3/8

    Capacity Index Limit 625 ~ 1625 650 ~ 1690 675 ~ 1755

    Maximum Number of Connected Indoor Units 64 64 64

    REYQ-T

    VRV IV Condensing Units – Heat Recovery

    REYQ-T (44 to 48 HP)

    REYQ-T (50 to 54 HP)

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    31/94

        H   e   a   t    R   e   c   o   v   e   r   y

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    32/9430 VRV catalogue 2015

    VRV IV Heat Pump> Customise your VRV for the greatest seasonal efficiency and comfort,

    with Variable Refrigerant Temperature control

    > Continuous comfort: unique continuous heating technology makesVRV IV Heat Pump the best alternative to traditional heating systems

    > VRV configurator software offers faster and more accurate

    commissioning, configuration and customisation

    > Possibility to combine VRV with a wide range of stylish indoor units

    including Daikin Emura and Nexura

    VRV IV Heat Pump – RYYQ-T 31

    The new standard in heating comfort  32

    VRV IV Heat Pump with continuous heating – RYYQ8-54T  34

    Heat Pump Mini VRV range see page 46NEW

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    33/9431VRV catalogue 2015

        H   e   a   t    P   u   m   p

    4

    5

    3

    1

    2

    VRV configurator

    Simplified commissioning and configuration via

    PC connection 7-segment LED indicator enables quick

    check of basic functions and easy error read-out

    1

    Gas cooled PCB

    Unique design for maximum reliability and higher

    efficiency of the heat exchanger

    2

    Full inverter compressor control

    Frequency control range which delivers stepless control

    of capacity and Variable Refrigerant Temperature Control

    3

    Heat accumulating element

    Provides energy to defrost the outdoor unit while

    continuing to provide indoor heating

    4

    4 side and 3 row heat exchanger

     This unique heat exchanger means 50% more

    surface area, so the coil does more of the work,

    increasing efficiency

    5

    VRV IV Heat PumpRYYQ-T 

    The VRV IV Heat Pump inherits all the renowned technological features of the VRV III and adds

    a number of revolutionary technologies, setting the new standard in the market once again.

    Variable refrigerant temperature

    Customise your VRV for the optimum seasonal efficiency and

    comfort: revolutionary variable refrigerant temperature control

    (optimised by Daikin for UK conditions for maximum efficiency and

    comfort) automatically adapts the system to the individual building

    and climate requirements.

    Continuous heating during defrost via heat pump

     The new standard in heating comfort: unique continuous heating

    technology makes VRV IV Heat Pump the best alternative to

    traditional heating systems.

    VRV configurator

    Software for simplified commissioning, configuration and

    customisation.

    > Simplified commissioning: graphical interface to configure,

    commission and upload system settings > Simplified servicing: additional 7-segment indicator for easy and

    quick access to basic functions and error read out.

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    34/9432 VRV catalogue 2015

    > Unique continuous heating technology

    > The best alternative to traditional heating systems

     The new standard in heating comfort

    VRV IV Heat Pump for continuous comfort,even during defrost

    Because the VRV IV Heat Pump continues to provide continuous

    heating even when in defrost mode, it provides the answer to

    any perceived disadvantages of specifying a heat pump for

    monovalent heating.

    Heat pumps are known for their high energy efficiency in heating,

    but they accumulate ice during heating operation and this must

    be melted periodically using a defrost function that reverses the

    refrigeration cycle. This causes a temporary temperature drop,

    which can reduce comfort levels inside the building.

    Defrosting can take over 10 minutes (depending on the size of thesystem) and occurs most frequently between -7 and +7°C when

    there is most humidity.

    How does it work?VRV IV Heat Pump features a unique heat-accumulating element,

    based on phase change materials, which provides energy to

    defrost the outdoor unit while continuing to provide heating, thus

    maintaining a comfortable indoor climate. The energy needed for

    defrosting is stored in the element during normal heating operations.

    How phase change material works

    A phase change material (PCM) will store or release energy when

    it changes phase from solid to liquid or liquid to solid.

     The outdoor unit coil is defrosted …

    … with the energy stored in the heat accumulating element …

    … while indoors a comfortable temperature is maintained.

    Capsule shell

     Temperature

    rises

    As PCM solidifies, heat

    energy is released back

    into the environment

    As PCM absorbs

    heat energy,

    it liquifies

     Temperature falls

    PCM in liquid state

    Capsule shell

    PCM in solid state

    Continuous heating function

    is only available on RYYQ-T units.

    VRV IV 

    VRF benchmark 

    Room

    temperature

     TimeΔ T 

    new

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    35/9433VRV catalogue 2015

        H   e   a   t    P   u   m   p

    A field trial at a German fashion chain store

    demonstrated how the innovative features of

    VRV IV have improved energy efficiency

    dramatically over previous models.

     The results of the trial showed that the new VRV IV

    system consumed much less energy, particularly

    when cooling, compared with the VRV III system –in some cases up to 60% less. When heating, savings

    were an average of 20%.

     The Unterhaching trial demonstrates how VRV IV heat

    pump technology uses a renewable energy source

    – air – to provide a complete and environmentally

    sustainable solution for heating, cooling, and

    ventilation in commercial environments. The trial also

    shows that businesses can only identify and control

    energy wastage through careful and intelligent

    monitoring of climate control systems, a servicewhich Daikin can offer.

    40% more efficient

    proven in practice

    Monthly power consumption4,500

    4,000

    3,500

    3,000

    2,500

    2,000

    1,500

    1,000

    500

    0Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb

    2012

    2013

    Ambient temp (average min/max)30

    25

    20

    15

    10

    5

    0

    -5

    -10

    2012: Average max

    2013: Average max

    2012: Average min

    2013: Average min

    Date Range Avg kW/h per month Total kW/h Total cost Yearly £/m2

    VRV III March 2012 - Feb 2013 2,796.82 33,561.8 £4,027.42 £10.07

    VRV IV March 2013 - Feb 2014 1,501.92 18,023 £2,162.76 £5.41

    Saved 46%

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    36/9434 VRV catalogue 2015

    Outdoor Units RYYQ8T RYYQ10T RYYQ12T RYYQ14T RYYQ16T RYYQ18T RYYQ20T

    Capacity Nominal Cooling kW 22.40 28.00 33.50 40.00 45.00 50.00 56.00

    Nominal Heating kW 25.00 31.50 37.50 45.00 50.00 56.00 63.00

    EER 4.30 3.84 3.73 3.64 3.46 3.40 3.03

    ESEER 7.53* 7.2* 6.96* 6.83* 6.5* 6.38* 5.67*

    COP 4.55 4.27 4.12 4.02 3.91 3.89 3.71

    Dimensions Height x Width x Depth mm 1685 x 930x 765

    1685 x 930x 765

    1685 x 930x 765

    1685 x 1240x 765

    1685 x 1240x 765

    1685 x 1240x 765

    1685 x 1240x 765

    Weight kg 261 268 268 364 364 398 398

    Air Flow Rate m3/sec 2.70 2.92 3.08 3.72 4.33 4.18 4.35

    External Static Pressure High Pa 78 78 78 78 78 78 78

    Electrical Details Power Supply Phase /Hz / V 3ph / 50 Hz / 380~415V

    Running Current amps 7.2 11.3 12.7 15.4 18.0 20.8 26.9

    Starting Current amps databook  

    Fuse Rating amps 20 25 32 32 40 40 50

    Refrigerant Circuit Refrigerant Type R410a

    Refrigerant Charge kg 5.9 6.0 6.3 10.3 10.4 11.7 11.8

    Additional Charge kg data book  

    Sound Pressure dBA 58 58 61 61 64 65 66

    Sound Power dBA 78 79 81 81 86 86 88

    Piping Limits Maximum Length m 165 165 165 165 165 165 165

    Maximum Vertical Rise m data book  

    Piping Connections Liquid inches 3/8 3/8 1/2 1/2 1/2 5/8 5/8

    Gas inches 3/4 7/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8

    Capacity Index Limit 100~260 125~325 150~390 175~455 200~520 225~585 250~650

    Maximum Number of Connected Indoor Units 64 64 64 64 64 64 64

    * The AUTOMATIC ESEER value corresponds with normal VRV IV Heat Pump operation, taking into account advanced energy saving operation functionality (variant refrigerant temperature control operation).

    Outdoor Units RYYQ22T RYYQ24T

    RYMQ10T RYMQ12T RYMQ8T RYMQ16T

    Capacity Nominal Cooling kW 61.50 67.40

    Nominal Heating kW 69.00 75.00

    EER 3.77 3.70

    ESEER 7.07* 6.81*COP 4.18 4.10

    Dimensions Height x Width x Depth mm 1685 x 930 x 765 1685 x 930 x 765 1685 x 930 x 765 1685 x 1240 x 765

    Weight kg 195 195 188 309

    Air Flow Rate m3/sec 2.92 3.08 2.70 4.33

    External Static Pressure High Pa 78 78 78 78

    Electrical Details Power Supply Phase /Hz / V 3ph / 50 Hz / 380~415V

    Running Current amps 10.2 12.7 7.2 18.0

    Starting Current amps databook  

    Fuse Rating amps 25 32 20 40

    Refrigerant Circuit Refrigerant Type R410a

    Refrigerant Charge kg 6.0 6.3 5.9 10.4

    Additional Charge kg databook  

    Sound Pressure dBA 58 61 58 64

    Sound Power dBA 79 81 78 86

    Piping Limits Maximum Length m 165 165

    Maximum Vertical Rise m databook  

    Piping Connections Liquid inches 5/8 5/8Gas inches 1 1/8 1 3/8

    Capacity Index Limit 275~715 300~780

    Maximum Number of Connected Indoor Units 64 64

    * The AUTOMATIC ESEER value corresponds with normal VRV IV Heat Pump operation, taking into account advanced energy saving operation functionality (variant refrigerant temperature control operation).

    RYYQ-T

    VRV IV Heat Pump with Continuous Heating

    RYYQ-T (up to 20 HP)

    RYYQ-T (22 to 24 HP)

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    37/9435VRV catalogue 2015

        H   e   a   t    P   u   m   p

    Outdoor Units RYYQ26T RYYQ28T RYYQ30T RYYQ32T RYYQ34T

    RYMQ1 2T RYMQ1 4T RYMQ1 2T RYMQ16 T RYMQ12 T RYMQ18 T RYMQ16 T RYMQ1 6T RYMQ1 6T RYMQ1 8T

    Capacity Nominal Cooling kW 73.50 78.50 83.50 90.00 95.00

    Nominal Heating kW 82.50 87.50 93.50 100.00 106.00

    EER 3.68 3.57 3.52 3.46 3.43

    ESEER 6.89* 6.69* 6.6* 6.5* 6.44*

    COP 4.06 4.00 3.98 3.91 3.90

    Dimensions Height mm 1685 1685 1685 1685 1685 1685 1685 1685 1685 1685

    Width mm 930 1240 930 1240 930 1240 1240 1240 1240 1240

    Depth mm 765 765 765 765 765 765 765 765 765 765

    Weight kg 195 309 195 309 195 319 309 309 309 319

    Air Flow Rate m3/sec 3.08 3.72 3.08 4.33 3.08 4.18 4.33 4.33 4.33 4.18

    External Static Pressure High Pa 78 78 78 78 78 78 78 78 78 78

    Electrical Details Power Supply Phase /Hz / V 3ph / 50 Hz / 380~415V

    Running Current amps 12.7 15.4 12.7 18.0 12.7 20.8 18.0 18.0 18.0 20.8Starting Current amps databook  

    Fuse Rating amps 32 32 32 40 32 40 40 40 40 40

    Refrigerant Circuit Refrigerant Type R410a

    Refrigerant Charge kg 6.3 10.3 6.3 10.4 6.3 11.7 10.4 10.4 10.4 11.7

    Additional Charge kg data book  

    Sound Pressure dBA 61 61 61 64 61 65 64 64 64 65

    Sound Power dBA 81 81 81 86 81 86 86 86 86 86

    Piping Limits Maximum Length m 165

    Maximum Vertical Rise m data book  

    Piping Connections Liquid inches 3/4 3/4 3/4 3/4 3/4

    Gas inches 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8

    Capacity Index Limit 325~845 350~910 375~975 400~1040 425~1105

    Maximum Number of Connected Indoor Units 64 64 64 64 64

    * The AUTOMATIC ESEER value corresponds with normal VRV IV Heat Pump operation, taking into account advanced energy saving operation functionality (variant refrigerant temperature control operation).

    Outdoor Units RYYQ36T RYYQ38T RYYQ40T RYYQ42T

    RYMQ16T RYMQ20T RYMQ8T RYMQ10T RYMQ20T RYMQ10T RYMQ12T RYMQ18T RYMQ10T RYMQ16T RYMQ16T

    Capacity Nominal Cooling kW 101.00 106.00 112.00 118.00

    Nominal Heating kW 113.00 120.00 125.00 132.00

    EER 3.21 3.42 3.61 3.54

    ESEER 6.02* 6.36* 6.74* 6.65*COP 3.79 4.01 4.05 4.00

    Dimensions Height mm 1685 1685 1685 1685 1685 1685 1685 1685 1685 1685 1685

    Width mm 1240 1240 930 930 1240 930 930 1240 930 1240 1240

    Depth mm 765 765 765 765 765 765 765 765 765 765 765

    Weight kg 309 319 188 195 319 195 195 319 195 309 309

    Air Flow Rate m3/sec 4.33 4.35 2.70 2.92 4.35 2.92 3.08 4.18 2.92 4.33 4.33

    External Static Pressure High Pa 78 78 78 78 78 78 78 78 78 78 78

    Electrical Details Power Supply Phase /Hz / V 3ph / 50 Hz / 380~415V

    Running Current amps 18.0 26.9 7.2 10.2 26.9 10.2 12.7 20.8 10.2 18.0 18.0

    Starting Current amps databook databook databook databook  

    Fuse Rating amps 40 50 20 25 50 25 32 40 25 40 40

    Refrigerant Circuit Refrigerant Type R410a

    Refrigerant Charge kg 10.4 11.8 5.9 6.0 11.8 6.0 6.3 11.7 6.0 10.4 10.4

    Additional Charge kg data book  

    Sound Pressure dBA 64 66 58 58 66 58 61 65 58 64 64

    Sound Power dBA 86 88 78 79 88 79 81 86 79 86 86

    Piping Limits Maximum Length m 165Maximum Vertical Rise m data book  

    Piping Connections Liquid inches 3/4 3/4 3/4 3/4

    Gas inches 1 5/8 1 5/8 1 5/8 1 5/8

    Capacity Index Limit 450~1170 475~1235 500~1300 525~1365

    Maximum Number of Connected Indoor Units 64 64 64 64

    * The AUTOMATIC ESEER value corresponds with normal VRV IV Heat Pump operation, taking into account advanced energy saving operation functionality (variant refrigerant temperature control operation).

    RYYQ-T

    VRV IV Heat Pump with Continuous Heating

    RYYQ-T (26 to 34 HP)

    RYYQ-T (36 to 42 HP)

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    38/9436 VRV catalogue 2015

    Outdoor Units RYYQ44T RYYQ46T RYYQ48T

    RYMQ12T RYMQ16T RYMQ16T RYMQ14T RYMQ16T RYMQ16T RYMQ16T RYMQ16T RYMQ16T

    Capacity Nominal Cooling kW 124.00 130.00 135.00

    Nominal Heating kW 138.00 145.00 150.00

    EER 3.54 3.51 3.46

    ESEER 6.62* 6.6* 6.5*

    COP 3.98 3.94 3.91

    Dimensions Height mm 1685 1685 1685 1685 1685 1685 1685 1685 1685

    Width mm 930 1240 1240 1240 1240 1240 1240 1240 1240

    Depth mm 765 765 765 765 765 765 765 765 765

    Weight kg 195 309 309 309 309 309 309 309 309

    Air Flow Rate m3/sec 3.08 4.33 4.33 3.72 4.33 4.33 4.33 4.33 4.33

    External Static Pressure High Pa 78 78 78 78 78 78 78 78 78

    Electrical Details Power Supply Phase /Hz / V 3ph / 50 Hz / 380~415V

    Running Current amps 12.7 18.0 18.0 15.4 18.0 18.0 18.0 18.0 18.0Starting Current amps databook databook databook  

    Fuse Rating amps 32 40 40 32 40 40 40 40 40

    Refrigerant Circuit Refrigerant Type R410a

    Refrigerant Charge kg 6.3 10.4 10.4 10.3 10.4 10.4 10.4 10.4 10.4

    Additional Charge kg data book  

    Sound Pressure dBA 61 64 64 61 64 64 64 64 64

    Sound Power dBA 81 86 86 81 86 86 86 86 86

    Piping Limits Maximum Length m 165

    Maximum Vertical Rise m data book  

    Piping Connections Liquid inches 3/4 3/4 3/4

    Gas inches 1 5/8 1 5/8 1 5/8

    Capacity Index Limit 550~1430 575~1495 600~1560

    Maximum Number of Connected Indoor Units 64 64 64

    * The AUTOMATIC ESEER value corresponds with normal VRV IV Heat Pump operation, taking into account advanced energy saving operation functionality (variant refrigerant temperature control operation).

    Outdoor Units RYYQ50T RYYQ52T RYYQ54T

    RYMQ16T RYMQ16T RYMQ18T RYMQ16T RYMQ18T RYMQ18T RYMQ18T RYMQ18T RYMQ18T

    Capacity Nominal Cooling kW 140.00 145.00 150.00

    Nominal Heating kW 156.00 162.00 168.00

    EER 3.44 3.42 3.40

    ESEER 6.46* 6.42* 6.38*COP 3.90 3.89 3.89

    Dimensions Height mm 1685 1685 1685 1685 1685 1685 1685 1685 1685

    Width mm 1240 1240 1240 1240 1240 1240 1240 1240 1240

    Depth mm 765 765 765 765 765 765 765 765 765

    Weight kg 309 309 319 309 319 319 319 319 319

    Air Flow Rate m3/sec 4.33 4.33 4.18 4.33 4.18 4.18 4.18 4.18 4.18

    External Static Pressure High Pa 78 78 78 78 78 78 78 78 78

    Electrical Details Power Supply Phase 3ph / 50 Hz / 380~415V

    Running Current amps 18.0 18.0 20.8 18.0 20.8 20.8 20.8 20.8 20.8

    Starting Current amps databook databook databook  

    Fuse Rating amps 40 40 40 40 40 40 40 40 40

    Refrigerant Circuit Refrigerant Type R410a

    Refrigerant Charge kg 10.4 10.4 11.7 10.4 11.7 11.7 11.7 11.7 11.7

    Additional Charge kg data book  

    Sound Pressure dBA 64 64 65 64 65 65 65 65 65

    Sound Power dBA 86 86 86 86 86 86 86 86 86

    Piping Limits Maximum Length m 165Maximum Vertical Rise m data book  

    Piping Connections Liquid inches 3/4 3/4 3/4

    Gas inches 1 5/8 1 5/8 1 5/8

    Capacity Index Limit 625~1625 650~1690 675~1755

    Maximum Number of Connected Indoor Units 64 64 64

    * The AUTOMATIC ESEER value corresponds with normal VRV IV Heat Pump operation, taking into account advanced energy saving operation functionality (variant refrigerant temperature control operation).

    RYYQ-T

    VRV IV Heat Pump with Continuous Heating

    RYYQ-T (44 to 48 HP)

    RYYQ-T (50 to 54 HP)

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    39/94

        H   e   a   t    P   u   m   p

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    40/9438 VRV catalogue 2015

     The Daik in low-cost upgrade solution

    4   Reuse drain pipes

    Durable PVC pipes can be easily reused. Only flow tests are required.

    4   Reuse refrigerant pipesPipes used for R- will also work with VRV-Q, thanks to lower

    operating pressures of the system.

    4   Reuse refrigerant branch pipes

     There are no restri ctions when upgrading from a Daik in VRV system.

    Other VRF systems require branch pipes to withstand pressure up

    to . MPa.

    !   Replace indoor units and BS boxesContact your local dealer to check compatibility in case you need

    to keep the indoor units.

    4   Reuse remote control wiring

    Reuse wiring when upgrading from a Daikin VRV system. In other cases,

    this will depend on the cable type.

    4   Reuse indoor-outdoor wiring

    Restrictions: see remote control wiring.

    !   Replace outdoor units

    Replacement VRV R22 is a hydrochlorofluorocarbon (HCFC) which was commonly used in air conditioning

    systems. However, both new and recycled sources of R22 are now banned.

    Many systems today are still running on R22. But as R22 is no longer available, now’s

    the time to replace R22 systems. The good news is that Daikin’s VRV-Q solution delivers

    significantly higher energy efficiencies, with the potential of saving up to 50%, compared

    with installing a completely new system.

    Benefits for your customers 39

    VRV-Q how it benefits you 40

    Key guidelines for a quality replacement 41

    Replacement VRV heat pump – RXYQQ-T  42

    Replacement VRV heat recovery – RQCEQ-P3 44

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    41/9439VRV catalogue 2015

         R    e    p     l    a    c    e    m    e    n     t

    Always operational

    Avoid loss of business

    Replacing now prevents unplanned, lengthy

    disruption of air conditioning systems. It also avoids

    loss of business for shops, complaints from guests inhotels, lower working efficiency and loss of tenants

    in offices.

    Quick and easy installation

    No interruption of daily business while replacing the

    system thanks to phased-in, fast installation.

    A future-proof,

    high-quality solution

    Customers can replace systems cost effectively from

    other manufacturers with highly-efficient and flexible

    Daikin VRV technology, featuring higher qualityindoor units that deliver enhanced comfort and

    superior performance.

    A cost saving decision

    Reduce costs

    System upgrades cost less, because only the

    outdoor and indoor units need to be replaced.

     This is also the easiest and fastest way to comply

    with regulations for buildings.

    Environment protection

    Improved efficiency saves energy and lowers CO₂

    emissions as well as reducing your energy costs.

    Reduced energy consumption

    Comparison of HP systems:

     Cooling mode

     Heating mode

    R-A (RXYQQ-T)R-C (RSXYP-L)R- (RSXY-KA)

    EER / COP HP HP

    RXYQQ-T (R-A) . / . . / .

    RSXYP-L (R-C) . / . . / .

    RSXY-KA (R-) . / . . / .

     These benefits will convince

    your customer

    Lower long-term costsEU Directives prohibit system repairs with R-22 after 31 December 2014. Delaying the

    required R-22 replacement until an unplanned system breakdown is a losing game.

    Replacement day will come. Installing a technically advanced system lowers energy

    consumption and maintenance costs from day one.

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    42/9440 VRV catalogue 2015

    Automatic refrigerant

    charging, cleaning andtesting

    Optimise your business

    Tackle more projects in less time

    Due to faster installation. VRV-Q is more economical

    than replacing the full system with new piping.

    Lower installation costs

    Offer customers the most cost-effective solution and

    improve your competitive edge.

    Easy as one-two-three

    A simple solution: Daikin VRV-Q enables you to

    handle more projects for more customers in less time

    and offer them the best price! Everybody wins.

    Compare installation steps

    Conventional solution

    Recover refrigerant

    Remove units Remove refrigerant pipes

    Install new piping & wiring

    Install new units

    Leak test

    Vacuum drying

    Refrigerant charging

    Collect contamination

    Test operation

    Recover refrigerant

    Remove units

    Re-use existing pipingand wiring

    Install new units

    Leak test

    Vacuum drying

    VRV-Q

    One touch

    convenience:> Measure and charge

    refrigerant

    > Automatic pipe

    cleaning

    > Test operation

    Automatic pipe cleaning There is no need to clean inside piping as this

    is handled automatically by the VRV-Q unit.

    Finally the test operation is performed

    automatically to save time.

    Automatic refrigerant

    charge

     The unique automatic refrigerant charge eliminates

    the need to calculate refrigerant volume andensures that the system will operate perfectly.

    Not knowing the exact piping lengths because of

    changes or mistakes in case you didn’t do the

    original installation or replacing a competitor

    installation no longer poses a problem.

    Up to 45%shorterinstallation

    time

    VRV-Q

    how it benefits you

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    43/9441VRV catalogue 2015

         R    e    p     l    a    c    e    m    e    n     t

    Refrigerant branch pipes

    Refrigerant branch pipes, including those from

    other manufacturers, Y-refnets, T-refnets and headers,

    can be reused under the following conditions:

    ✓ Pipes are corrosion-free✓ Pipes are insulated

    ✓ Pipes can withstand a pressure up to . MPa

    ✓ There are no special components that implement

    decompression (e.g. oil trap)

    ✓ Installed copper pipework is in suitable condition

    (piping thickness will generally meet specifications,

    since the unique Daikin VRV solution operates at

    lower pressure levels)

    Refrigerant oil

    Refrigerant piping can be reused if one of thefollowing oils was used: Barrel Freeze, Ethereal,

    Ester, Ferreol, HAB, MS, Suniso.

    Maximum piping lengths

    and level distances

    VRV-Q can be installed for piping systems with a total

    length up to m. See the illustration below for

    further requirements.

     Total piping le ngth: m

    Longest piping length (–) actual / equivalent: m / mMaximum difference between

    shortest (A) and longest (B) branch: m

    m Level difference between

    outdoor units

    m Level difference

    between indoor and

    outdoor units (m if

    outdoor unit is installed

    below indoor unit)

    m

    Piping length between outdoor units

    A (–)

    B (–)

    m Level difference

    between indoor

    units

    Key guidelinesfor a quality replacement with VRV-Q

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    44/9442 VRV catalogue 2015

    Outdoor Units RXYQQ22T RXYQQ24T RXYQQ26T RXYQQ28T

    RXYQQ10T RXYQQ12T RXYQQ8T RXYQQ16T RXYQQ12T RXYQQ14T RXYQQ12T RXYQQ16T

    Capacity Nominal Cooling kW 61.50 67.40 73.50 78.50

    Nominal Heating kW 69.00 75.00 82.50 87.50

    EER 3.77 3.70 3.68 3.57

    ESEER 7.07* 6.81* 6.89* 6.69*

    COP 4.18 4.10 4.06 4.00

    Dimensions Height mm 1685 1685 1685 1685 1685 1685 1685 1685

    Width mm 930 930 930 1240 930 1240 930 1240

    Depth mm 765 765 765 765 765 765 765 765

    Weight kg 194 194 187 305 194 306 194 305

    Air Flow Rate m3/sec 2.92 3.08 2.10 3.88 3.08 3.72 3.08 3.88

    External Static Pressure High Pa 78 78 78 78

    Electrical Details Power Supply Phase /Hz / V 3ph / 50 / 400

    Running Current amps 22.9 25.2 28.1 30.7

    Starting Current amps 88

    Fuse Rating amps 25 32 20 40 32 32 32 40

    Refrigerant Circuit Refrigerant Type R410a

    Refrigerant Charge kg 6.0 6.3 5.2 10.4 6.3 10.3 6.3 10.4

    Additional Charge kg data book  

    Sound Pressure dBA 58 61 58 64 61 61 61 64

    Sound Power dBA 79 81 78 86 81 81 81 86

    Piping Limits Maximum Length m 120

    Maximum Vertical Rise m 50

    Piping Connections Liquid inches 5/8 5/8 3/4 3/4

    Gas inches 1 1/8 1 3/8 1 3/8 1 3/8

    Capacity Index Limit 275~715 300~780 325~845 350~910

    Maximum Number of Connected Indoor Units 64 64 64 64

    *The AUTOMATIC ESEER value corresponds with normal VRV IV Heat Pump operation, taking into account advanced energy saving operation functionality (variant refrifgerant temperature control operation).

    Outdoor Units RXYQQ8T RXYQQ10T RXYQQ12T RXYQQ14T RXYQQ16T RXYQQ18T RXYQQ20T

    Capacity Nominal Cooling kW 22.40 28.00 33.50 40.00 45.00 50.00 56.00

    Nominal Heating kW 25.00 31.50 37.50 45.00 50.00 56.00 63.00

    EER 4.30 3.84 3.73 3.64 3.46 3.40 3.03

    ESEER 7.53* 7.2* 6.96* 6.83* 6.5* 6.38* 5.67*

    COP 4.54 4.27 4.12 4.02 3.91 3.89 3.71

    Dimensions Height mm 1685 1685 1685 1685 1685 1685 1685

    Width mm 930 930 930 1240 1240 1240 1240

    Depth mm 765 765 765 765 765 765 765

    Weight kg 187 194 194 306 305 314 314

    Air Flow Rate m3/sec 2.10 2.92 3.08 3.72 3.88 4.18 4.35

    External Static Pressure High Pa 78 78 78 78 78 78 78

    Electrical Details Power Supply Phase /Hz / V 3ph / 50 / 400

    Running Current amps 7.2 10.2 12.7 15.4 18.0 20.8 26.9

    Starting Current amps 4Fuse Rating amps 20 25 32 32 40 40 50

    Refrigerant Circuit Refrigerant Type R410a

    Refrigerant Charge kg 5.2 6.0 6.3 10.3 10.4 11.7 11.8

    Additional Charge kg data book  

    Sound Pressure dBA 58 58 61 61 64 65 66

    Sound Power dBA 78 79 81 81 86 86 88

    Piping Limits Maximum Length m 120 120 120 120 120 120 120

    Maximum Vertical Rise m 50

    Piping Connections Liquid inches 3/8 3/8 1/2 1/2 1/2 5/8 5/8

    Gas inches 3/4 7/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8

    Capacity Index Limit 100~260 125~325 150~390 175~455 200~520 225~585 250~650

    Maximum Number of Connected Indoor Units 64 64 64 64 64 64 64

    *The AUTOMATIC ESEER value corresponds with normal VRV IV Heat Pump operation, taking into account advanced energy saving operation functionality (variant refrifgerant temperature control operation).

    RXYQQ-T

    VRV IV-Q Condensing Units – Heat Pump

    RXYQQ-T (up to 20 HP)

    RXYQQ-T (22 to 28 HP)

  • 8/20/2019 Daikin VRV Catalogue 2015_tcm511-370435.pdf

    45/9443VRV catalogue 2015

         R    e    p     l    a    c    e    m    e    n     t

    Outdoor