    Typical energy consumption in office building

    Air

    Conditioning

    47%

    Comp.

    20%Heat

    transfer

    27.2%

    Other utilities

    20.5%

    Lighting

    32.3%

    AC consumption reduction is

    prime target of energy

    saving

    47% of electricity is

    consumed by AC

    How does it possible to achieve energy saving and

    comfort simultaneously?

    Energy saving Comfort

  • 8/10/2019 Daikin Presentation -VRV Technology

    2/27

    11/4/2

    This is the time to increase our efforts towards

    Strengthen Green Building Movement

    More energy efficient methods of operations

    High energy efficient products

    Habit of Energy Conservation

    Best utilization of available Energy Resources.

    We are pioneering the movement with a large array of

    energy efficient products

    Central Controller

    Project Name

    Location

    BLD. Type

    Size of Project

    The Size of Bldg

    Uniqueness

    CRISIL House

    Mumbai, India

    Official Building

    9 Floors

    ODU - 73 No., HP1,092VRVIII (Air Cooled)

    I-Manager

    Green building project =>With Platinum rating

    Design by Team of

    leading Architectural andHVAC Consultancy

    organisations.

    LEED certifiedPlatinum rating

    Air-cooled VRV Project withLEED Platinum Certification

    4

  • 8/10/2019 Daikin Presentation -VRV Technology

    3/27

    11/4/2

    Water-cooled VRVProject withLEED Platinum Certification

    LEED certifiedPlatinum rating

    Project Name

    Location

    BLD. Type

    Size of Project

    Central Controller

    The Size of Bldg

    Uniqueness

    Suzlon

    Pune, India

    Official Building

    8Blocks, 32 Floor

    ODU - 134 No., HP1,392

    VRVIII ( WC)

    I-Manager & BACnet

    Green building project =>Highest Platinum ratedbuilding in India

    Appreciation letter fromcustomer for installation

    and project management

    5

    LEED Platinum Certification

    Kirloskar Brother Limited

    Pune, India

    Official Building

    ODU - 69 No., HP704

    Green building project =>Platinum rated building

    1stReference Site of VRVWIII Awarded appreciation letter by

    customer

    G+ 3 Floor

    Project Name

    Location

    BLD. Type

    Aircond. Qty

    Application

    The Size of Bldg

    LEED certifiedPlatinum rating

  • 8/10/2019 Daikin Presentation -VRV Technology

    4/27

    11/4/2

    Discussion Topics

    7

    Energy & Atmosphere

    - Efficiency of the system

    - Environment friendly Refrigerant

    Clean Project Management

    -IAQ management plan

    -Indoor environmental quality

    Emerging Space conditioning technology;Variable Refrigerant Volume (VRV)

    VRV Development

    8

  • 8/10/2019 Daikin Presentation -VRV Technology

    5/27

    11/4/2

    9

    Background of Development of VRV

    1973Global oil crises (The 4th Arab-Israel War )

    1979New energy efficiency laws passes in Japan

    1980Chiller design engineers challenged with

    making a higher efficiency chiller

    1982The worlds first VRV System is launched

    19741973

    Crudeoilprice

    Oil crisis

    Energy saving

    9

    The 1st turning point

    Inverter VRV!

    Its design flexibility expanded sales volume

    drastically.

    0

    1000

    2000

    3000

    4000

    5000

    1998 1999 1990 1991

    The 1stgeneration Inverter VRV G series

    Non-inverter

    VRV

    Inverter VRV

    Turning

    Point10

  • 8/10/2019 Daikin Presentation -VRV Technology

    6/27

    11/4/2

    Technology Advancement

    11

    Standard compressors to variable speed scroll compressors

    Direct driven outdoor fans to variable frequency drive,inverter-driven fans

    Direct driven indoor coil motors to Inverter type motors

    Performance difference between

    1982 and 2014 model

    1982 2014Energy Efficiency (COP) 2.78 4.30

    Max. refrigerant piping length

    difference between indoor &outdoor unit

    70m 165m

    Max. refrigerant piping height

    difference between indoor &outdoor unit

    30m 90m

    Capacity rangeOutdoor unit 1015HP 4~60HP

    Capacity rangeIndoor unit 2.5HP 0.8~20HP

    Max. connectable indoor unitsnumber

    6 units 64 units

    Network control system None

    -Intelligent touch Controller

    -Intelligent Manager

    -Intelligent touch Manager (~2012)

    -BACNet interface

    -LonWorks Interface

    -Home Automation Interface (2012~)

    - A/C Network Service System

    Target project size Approx. 5,000m2 No limit

    12

  • 8/10/2019 Daikin Presentation -VRV Technology

    7/27

    11/4/2

    Expansion of the country of sale

    Sales is undergoing in more than 70 countries

    ustria

    Belgium

    Bulgaria

    Croatia

    Cyprus

    Czech

    Finland

    France

    Germany

    Greece

    Serbia

    Slovakia

    Spain

    Sweden

    Switzerland

    Turkey

    UK

    Ukraine

    Hungary

    Ireland

    Italy

    Lithuania

    Macedonia

    Netherlands

    Poland

    Portugal

    Romania

    Russia

    lgeria

    Burkina

    Fas

    o

    Egypt

    Ivory Coast

    Senegal

    South frica

    Sudan

    Bahrain

    Jordan

    Oman

    Qatar

    Saudi rabia

    U E

    China

    Japan

    Korea

    Taiwan

    Cambodia

    Malaysia

    Myanmar

    Philippine

    Singapore

    Thailand

    Vietnam

    India

    Maldives

    Nepal

    Seychelles

    Sri Lanka

    ustralia

    Fiji

    New Caledonia

    New Zealand

    Tahiti

    Canada

    Mexico

    Puerto Rico

    US

    rgentina

    Brazil

    Panama

    Peru

    13

    x 25!

    Growth path experienced in all key VRV

    markets

    0

    20

    40

    60

    80

    100

    120

    0 3 6 9 12 15 18 21 24 27 30 33

    1. Tipping Point

    2. High

    Growth

    3. Steady

    Growth

    Years after introduction

    Japan

    Australia

    S. Korea

    Singapore

    Europe

    14

  • 8/10/2019 Daikin Presentation -VRV Technology

    8/27

    11/4/2

    Energy: Efficiency of the system

    15

    VRV Architecture

    16

    Outdoor Unit

    Indoor Units

    Independent control of

    each room and zones air

    conditioning according to

    thermal load.

    Automatic control of

    each indoor unit

    Energy conservation.

    Variable Refrigerant Volume

  • 8/10/2019 Daikin Presentation -VRV Technology

    9/27

    11/4/2

    Groundbreaking technology applied

    to VRV

    Compressor Variable speed inverter compressor

    Scroll compressor with relief mechanism

    Reluctance DC motor (IPMInner Permanent Magnet) synchronous motor)

    Neodymium magnet

    Sensor-less DC inverter

    Sign wave inverter

    Heat exchanger Sub cool circuit for longer piping

    e-Pass cooling pipe location

    Control system Hi-speed DIII protocol

    Intelligent-Manager, Intelligent-touch-ControllerIntelligent-touch-Manager

    BACNet Interface, LONWorks Interface

    A/C Network Service System (AIRNET, Energy Saving AIRNET) 17

    Reluctance

    DC Motor

    Scroll Type

    Reluctance

    Scroll Type

    0.1

    1

    10

    150 200 250 300 350 400 450 500

    [J/kg]

    [MPa]

    R410A

    -100 10

    20 040 50

    6 0 7 0 80 9 0 10 0

    -20

    -30

    110120

    Energy saving is achieved by:- Lowering condensing temperature

    - Increasing evaporating temperature

    Output current after correction

    Sine-wave DCInverter Standard Inverter

    Former Fan modelAero Spiral Fan

    HighTemp.gas

    D.I.S.O. CircuitTo compensate refrigerant flow velocityreduction caused by gas condensation, 2passes are combined into 1 restricted to 1.Heat exchange efficiency 11% UP

    Heat exchanger

    Aero Spiral Fan

    Fan

    Compressor

    Essential technologies

    Liquid

    refrigerant

    Enthalpy (Kcal/kg)

    Pressure

    (MPa)

    18

  • 8/10/2019 Daikin Presentation -VRV Technology

    10/27

    11/4/2

    System Parts with built-in Inverters

    The motor of the compressor, the heart of an

    air conditioner, consumes most power.

    PCB

    INV

    INV

    INVINV

    PCB

    PCB

    Outdoor unit

    INV Inverter device

    Compressormotor

    Fan motor

    Indoor unit fan motor

    Air

    Air Air

    Electronic

    expansion

    valve motor

    19

    T1 = Refrigerant IN temp.

    T2 = Refrigerant OUT temp.

    T3 = Return air temp.

    T4 = Set temp. of RC

    According to the readings of 4 sensers, every 5 sec., CPU calculates optimum

    capacity and adjusting EEV in PID (Propotional Integral & Derivative) action.

    PID control ensures optimum comfort.

    Suction

    Discharge

    Liquid

    Gas

    Electronicexpansion valve

    Evaporator

    T4

    T1

    T3

    Fan

    T2

    CPU

    RC

    1 2 3 4

    Condensing unit adjust the inverter

    compressor to provide the required capacity

    (Low or High)

    Each indoor controls its capacity via

    PID control and an E.E.V.

    INDEPENDENT

    BRAIN

    System Capacity Control

    20

  • 8/10/2019 Daikin Presentation -VRV Technology

    11/27

    11/4/2

    0

    20

    40

    60

    80

    100

    120

    140

    160

    18 20 22 24 26 28 30 32 34 36 38 40 42 44 46

    Quick and efficient traceability for the load fluctuationQuick capacity adjustment for changing load

    Adjusting refrigerant flow

    Partial load Performance

    1

    2

    3

    4

    5

    6

    7

    8

    9

    1

    1 2 3 4 5 6 7 8 9 1 11 12 13 14 15 16 17 18 19 2 21 22 23 24

    Daily occupancy ratioYearly Cooling hours

    Design condition

    Less than 10 hrs

    In a year

    Major operation

    range : > 38C

    Randomoccupancy

    Ambient Temperature )Time

    AC is selected for maximum load but operated under

    fluctuating partial load almost all time

    21

    High Efficiency on Partial Load

    22

    COP

    100%

    4.0

    4.5

    5.0

    5.5

    6.0

    6.5

    7.0

    20% 40% 60% 80%

    Load Area

    Cooling Load

    Nominal COP*

    * 8 HP

    Cooling COP

    Partial Load gives high efficiency , Most of the timebuilding run on partial Loads

    COP = Cooling capacity /Power Input

    6.6

    4.3

  • 8/10/2019 Daikin Presentation -VRV Technology

    12/27

    11/4/2

    Operations as per building need

    Precise Temperature Control

    Consumes Energy as per cooling load

    User benefit - User can save

    energy by avoiding useless

    operation

    Individual Control

    23

    Inverter Technology

    24

    Stable temperature control by electronic expansion

    valve and inverter compressor

    30

    25

    20

    15

    10 20 30 40 50 60 70 Min.

    RoomT

    emp

    erature

    Set Temp.

    Time

    Automatically adjusts compressor speed to meet load

    Strives to run long periods at very low speeds

    Reduce cyclic losses

    Improve temperature controls

  • 8/10/2019 Daikin Presentation -VRV Technology

    13/27

    11/4/2

    Latest Development

    25

    VRT Control

    26

    Innovative New Technology !

    VRT VariableRefrigerantTemperature)

    How can we achieve best performance in unstablecondition?

    Targets Methods Results

    Compressor

    speed changeInverter

    Ref. Volume

    change

    Evaporating

    temp. changeVRT

    Comp. Work

    changeNew!

    Cooling load is always changing

  • 8/10/2019 Daikin Presentation -VRV Technology

    14/27

    11/4/2

    VRT Control

    27

    Power consumption

    Inverter

    Reduction

    Comp. Work (power consumption) reduction

    Comp. Work

    Comp. Work

    V

    Ref. Temp.

    TC(Cond. Temp.)

    TE(Eva. Temp.)

    50% 100% Ref. flow

    Reduction

    VRT Control

    28

  • 8/10/2019 Daikin Presentation -VRV Technology

    15/27

    11/4/2

    Because of smallerhigh & low pressure

    difference!

    ReasonHigher efficiency at cooling

    C

    t

    y

    VRT

    Conventional A/C

    R

    E

    e

    m

    p

    oad

    C

    n

    o

    c

    y

    100%

    25%

    C

    P

    Outdoor

    Temp

    35 3 5

    VRT

    Conventional A/C

    2.4 times stronger !

    50% more

    compression volume

    High Efficiency Scroll compressor.

    A 50% thinner & 20% higher scroll blade, which is

    realized by adapting newly developed material,

    increases compression volume by 50%.

    50% thinner

    20% higher

    Iron based alloy casting

    produced by Thixocasting

    process.

    Thixocasting process

    In the way that cast the material

    in a semi-molten state, it is

    capable of producing very high

    strength products.

  • 8/10/2019 Daikin Presentation -VRV Technology

    16/27

    11/4/2

    Maximized

    surface area

    32

    fins!

    30% smaller fin pitch

    New Current

    4-faceheat exchanger

    50% more heat exchange surface

    32

    VRV IV

    Refrigerant cooled inverter

    VRV IV, inverter circuit is cooled by refrigerant

    So, efficient & reliable cooling without influence of

    ambient air temperature

    Refrigerant cooled circuit

  • 8/10/2019 Daikin Presentation -VRV Technology

    17/27

    11/4/2

    Air net System: Energy Saving

    33

    I-Touch

    Controller

    Optimizedenergy saving

    setup

    Operation

    data

    CustomerAirnet Control Center

    (ACC)Optimized

    energy savingsetup

    Remote

    energy saving

    tune-up

    service

    (paid contract)

    Operation datareport

    (via phone line)

    17 Weather data

    locations from India

    Weather

    Association

    Forecast Data

    Spot

    forecast

    System overview

    I-Manager

    or

    This system tunes the air conditioner according to customer's outdoor

    indoor location, operating conditions and day by day weather condition.

    * Optional chargeable service

    Environment

    34

  • 8/10/2019 Daikin Presentation -VRV Technology

    18/27

    11/4/2

    Water

    2.6 watts/lb

    25 watts/ lb

    Refrigerant

    A ir

    0.14 watt s/lb

    VAV VWV VRV

    Heat Transfer Media

    Why Refrigerant?The commonly used methods of Heat Transfer in Air Conditioning solutions each

    exercise different operational characteristics regards adding or removing heatenergy to a conditioned space as follows:

    This diagram represents the energy transfer possible per lb of media due to the

    performance characteristic of the fluid used.35

    Environmental Consciousness

    RoHS (Reduction of Hazardous Substances)

    High COP (lower global warming impact, lower running cost)

    Less refrigerant (zero ODP, lower global warming impact)

  • 8/10/2019 Daikin Presentation -VRV Technology

    19/27

    11/4/2

    Further Energy saving through

    Smart Controller

    37

    Location Time Hour Set Temp. Mode SetRemote

    Restriction

    Lift Lobby/

    Common

    areas

    Morning8:00 -10:00

    26

    C Cooling No

    Up to

    Lunch

    10:00 -

    14:00- Fan Yes

    Afternoo

    n

    14:00 -

    20:0026

    C Cooling No

    Night20:00 -8:00

    - Fan Yes

    Energy Savings Proposal by Controller

    Location Time Hour Set Temp. Mode SetRemote

    Restriction

    Office

    Morning9:00 -

    13:0023-25

    C Cooling No

    Lunch13:00 -14:00

    - Fan Yes

    Afternoon14:00 -

    18:3024-26

    C Cooling No

    Evening 18:30 Stop All Systems

    Case Study: Project @ Pune

    Scheduling Required by client

    Without Energysavings

    25/08/10~31/8/10

    ( Previousconditions)

    With Energysavings Proposal

    1/09/10~7/09/10

    ( Presentconditions)

    Total Testing Area 4 Floors: Right & Left Wing- 1 & 2 Floors

    Centralized System38

  • 8/10/2019 Daikin Presentation -VRV Technology

    20/27

    11/4/2

    0

    50

    100

    150

    200

    250

    300

    350

    25-Aug 26-Aug 27-Aug 28-Aug 29-Aug 30-Aug 31-Aug 1-Sep 2-Sep 3-Sep 4-Sep 5-Sep 6-Sep 7-Sep

    Wed Thur Fri SaturdaySunday M onday Tuesday Wed Thur Fri SaturdaySunday M onday Tuesday

    24 24 24 24 24 25 25 25 25 25 25 25 25 25

    kwh

    kwh

    1545 Kwh 1202 Kwh

    Energy savings weekly = 22 %

    Mean Ambienttemp

    325 kwh

    250 Kwh

    Weekly Energy Savings

    Reduction- 22 %

    Energy savings= (1545-1202)/1545*100

    Day

    before after

    Case Study: Project @ Pune

    39

    System Structure

    For download PPD data anduploading project data

    40

  • 8/10/2019 Daikin Presentation -VRV Technology

    21/27

    11/4/2

    Indoor Environmental quality

    41

    Outdoor Air Processing Unit

    42

    Fresh air treatment and air conditioning with a single system

    Fan coil units for air conditioning and an outdoor-air processing unit can be

    connected to the same refrigerant line.

    Enhanced design flexibility and a significant reduction in total system costs.

  • 8/10/2019 Daikin Presentation -VRV Technology

    22/27

    11/4/2

    Outdoor Air Processing Unit

    43

    Fresh air treatment and air conditioning with a single system

    Fan coil units for air conditioning and an outdoor-air processing unit can be

    connected to the same refrigerant line.

    Enhanced design flexibility and a significant reduction in total system costs.

    Heat Reclaim Ventilation (HRV)

    44

    ON/OFF signal

    Cooling/Heating mode signalSet temperature signal

    Ventilation signal

    Failure detection signal

    LCD remote

    controller for

    indoor unit

    VRV Indoor unit

    HRV

    Air ConditioningLoad Reduced byApproximately 28%

    Ex. air

    23C 50

    Cooled FA

    27.5C 75

    Hot F.A.

    35C 80

    Exhaust air

    HRV recovers heat from Exhaust air

  • 8/10/2019 Daikin Presentation -VRV Technology

    23/27

    11/4/2

    Future Direction

    45

    Future direction

    Super large

    projectIntegration with

    applied system

    Multi functionCooling/heating/

    floor heating/hot

    water supplyCooling+heat

    recovery for hotwater

    Optimization for

    residenceConnection with

    HA automation

    Price optimizationby residenceconcentratedspecification

    Further Hi-

    COPHi-COPrefrigerantRevolutionarycompressor/hea

    t exchanger

    VRVDiversification

    of the heat

    sourceElectricGasGeo thermaletc

    46

  • 8/10/2019 Daikin Presentation -VRV Technology

    24/27

    11/4/2

    Multi function VRV

    4HP48HP

    Hot water supply

    Floor heating

    Air-conditioning

    47

    VRVfor cold area

    2 step compression type

    Hi-COP even at20degC

    10HP20HP

    48

  • 8/10/2019 Daikin Presentation -VRV Technology

    25/27

    11/4/2

    Ice thermal storage VRV

    Ice thermal storage tank

    VRV

    10HP42HP

    49

    CO2VRV

    10HP

    50

  • 8/10/2019 Daikin Presentation -VRV Technology

    26/27

    11/4/2

    Gas heat pump VRV

    8HP50HP

    51

    Typical cluster details:Size: 93,000 sqm

    Average floor plate size:

    Wing 1&4 2,600 sqm

    Wing 2&3 3,000 sqm

    Floor Levels

    Wing 1&4 2 Lower Ground Floor+Ground Floor+5 Floors

    Wing 2&3 2 Lower Ground Floor+Ground Floor+7 Floors

    Equipment Configuration:

    System Selected VRV III (Total Capacity: 16512 HP, 928 ODU)

    Refrigerant R-410A

    Outdoor Units Heat pump types

    ModelRXYQ18PY1: 896 nos.

    RXYQ12PY1: 32 nos.

    Indoor Units FXFQ-MVE (Ceiling Mounted Multi Flow Cassette): 6,600 nos.

    Control System Intelligent Manager III (DAM602B51: 32 nos.)

    Project Detail: EONVRV III was selected for its various practical

    benefits.

    1.Phase wise installation and commissioning;

    2.Energy Savings

    3.Simplified Control and Maintenance

    4.Independent AC system for each tenant

    Customer Criteria for A/C selection :

    SEZ Special Economic Zone project

    => VRV Biggest project

    Location: Pune, India

    Project Details:

    Application of VRV technology on large size projects

    52

  • 8/10/2019 Daikin Presentation -VRV Technology

    27/27

    11/4/2

    Thank you for your attention!