8/14/2019 Cooper - Recloser - Type NOVA.pdf http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 1/28 O VA  Technology Kyle ® NOVA™ Recloser T HE ULTIMATE GAS -F REE, OIL -F REE AND M AINTENANCE-F REE S OLUTION FOR AUTOMATION, P ROTECTION AND S WITCHING APPLICATIONS SER ENEFITS  Environmentally-Safe  Reduced Maintenance Costs  Easier Handling and Installation  Maximum Operating Safety  Reliable and Dependable Operation RODUCT EATURES  SF Gas-Free and Oil-Free  Maintenance-Free  Lightweight Design  Axial-Magnetic Vacuum Interruption  Kyle Manufacturing Expertise 

Cooper - Recloser - Type NOVA.pdf

Embed Size (px)

Citation preview

Page 1: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 1/28

N OVA  Technology 

Kyle ®  NOVA™ Recloser 

THE ULTIMATE GAS-FREE, OIL-FREE AND

MAINTENANCE-FREE SOLUTION FOR

AUTOMATION, PROTECTION AND SWITCHING

APPLICATIONS

U SER B ENEFITS 

  Environmentally-Safe 

  Reduced Maintenance Costs 

  Easier Handling and Installation

 Maximum Operating Safety 

  Reliable and Dependable Operation 

P RODUCT F EATURES 

  SF 6 Gas-Free and Oil-Free 

  Maintenance-Free 

  Lightweight Design 

  Axial-Magnetic Vacuum Interruption 

  Kyle Manufacturing Expertise 

Page 2: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 2/28

The Shape of Things to ComeÉ

2

ooper Power Systems introduces a revolution indistri bution switchgear. The new three-phase,

microprocessor-controlled NOVA recloser utilizes

advanced polymer and vacuum technologies to increasevalue for distribution systems. Kyle has combined solidcycloaliphatic-epoxy polymer-encapsulated vacuuminterrupters with a reliable, lightweight operatingmechanism which utilizes a magnetic actuator to providea lifetime of trouble-free recloser operation.

This state-of-the-art design completely replaces liquid andgas dielectric media. It is the maintenance-free alternativein distribution system protection. The NOVA recloser isthe shape of things to come .

Superior Solid InsulationProvides Maintenance-Free andEnvironmentally-Safe OperationThe key to the NOVA recloser is the successfulcombination of two technologies: cycloaliphatic-epoxyencapsulation and the high-performance Kyle vacuuminterrupter.

All existing insulation systems require seals to defendagainst environmental exposure. Life and maintenance aredetermined by these sealing systems. When breached, thedielectric is compromised and must be repaired orreplaced.

As an oil alternative, SF6 gas introduces new and growingconcerns about its effects on the atmosphere. SF6 has anextremely long atmospheric lifetime, estimated between800 to 10,000 years, and has a global warming potential24,900 times that of carbon dioxide. As a result, SF6 isamong the most potent of greenhouse gases. NOVA’ssolid insulation construction eliminates all concern by itsenvironmentally-friendly design. The future is green withNOVA.

Solid dielectric insulation eliminates the need for

insulating gas or liquid, thereby greatly reducing recloserlife-cycle maintenance costs. There is no longer the needto monitor SF6 gas pressure or oil levels, to filter orreplenish the dielectric, to take special precautions whenhandling the dielectric during maintenance, or to worryabout environmental regulations regarding disposal of toxic or environmentally-unfriendly materials.

Kyle Advances Filled EpoxyDesign for Outdoor ApplicationsFilled epoxy casting systems have been successfully utilizedas insulating material in high and low voltage indoor

applications for over 30 years. Recent materialadvancements provide durable environmental propertieswhich enhance epoxy success for outdoor applications.State-of-the-art manufacturing techniques also bring keyimprovements in absorption of elastic energy, resistance tocracking, and crack propagation.

NOVA Cycloaliphatic Epoxy Advantages

Surface TrackingNOVA’s exceptional ability to resist electrical trackingreduces both flashovers and the associated cost of repairs.Results of the industry-standard incline plane test (per

ASTM D2303) revealed that cycloaliphatic epoxy is 50percent more resistant to tracking than polyurethane. Inaddition, independent testing by Arizona State University(per IEC 815) confirmed that NOVA cycloaliphaticepoxy is highly resistant to contaminants and resistedtracking and flashovers under extreme pollution levels.

HydrophobicityNOVA cycloaliphatic epoxy maintains excellenthydrophobicity (a property characterized by waterbeading into isolated drops) and is highly resistant tomoisture absorption. Hydrophobicity prevents continuous

sheets of water from forming leakage current paths which,when heated by continuous flow, create a dry band paththat deteriorates the creepage withstand level.

Ultraviolet ResistanceNOVA cycloaliphatic epoxy resists the damage caused byultraviolet radiation. Over 25 years of proven experienceof cycloaliphatic epoxy in harsh climates confirms thatNOVA maintains a smooth, self-cleansing, unblemishedsurface with low-adhesion to contaminants when exposedto ultraviolet radiation.

Tensile Strength

NOVA modules are tough and non-fragmenting as theypossess outstanding tensile and flexural strengthcharacteristics. A 12-gauge shotgun test supports the non-fragmenting performance and displays the ability of NOVA to thwart vandalism by successfully passing ahigh-potential withstand test.

Combining advanced vacuum technology, a sophisticatedsolid epoxy insulation system, and a proprietary,dielectrically-sound active component, Cooper PowerSystems now provides a non-oil, non-gas, solid insulationsystem destined to be the shape of things to come .

C

THE KYLE® NOVA™ RECLOSER

The Shape of Things to Come…

Page 3: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 3/28

ÉThe Shape of Things to Come

3

Kyle Leads Vacuum Technologyyle revolutionized the protection of high voltagecircuits with the first commercially-successful

recloser, the Kyle Type H. Today, many Kyle reclosers

incorporate vacuum technologies which have advanced thedurability and extended the application base for vacuumproducts. Kyle’s constant development effort represents adetailed understanding of arc control, thermal loads, andcontact erosion. Each is pivotal to the successfulapplication of vacuum to solid dielectric systems.

The patented axial-magnetic field vacuum interrupter,designed and manufactured by Kyle DistributionSwitchgear‚ is the most advanced vacuum interrupterdesign in the world. Rely on Kyle vacuum interrupters toprovide many years of dependable operation.

Axial-Magnetic Design• Provides fast, low-energy arc interruption• Ensures long contact and interrupter life• Experiences low mechanical stress while ensuring

maximum operating safety• Eliminates the production of toxic byproducts

Innovative Design

Many vacuum interrupters employ radial-magnetic fieldcontacts. These use slots that are machined into the contactstructure to affect the direction of current flow during arcinterruption in such a way as to induce a radial-magneticfield. This radial-magnetic field pushes the arc around thecircumference of the contact, minimizing wear in any onespot. Though this method is sufficient for low andmedium current density applications, higher current levelscan cause significant contact erosion or shield burn-out.

Kyle interrupters employ axial-magnetic contacts. Slots aremachined into the contact support structure producing acoil that induces a magnetic field along the axis of theinterrupter. This axial-magnetic field keeps the arc in an

easier-to-interrupt diffuse mode, resulting in less arc powerthat needs to be dissipated. Furthermore, Kyle’s patentedVSAM design uses the entire contact surface, resulting infar less contact erosion. Less power to dissipate means lowthermal stress and longer life. Consequently, Kyle isuniquely qualified to encapsulate vacuum interrupters.

World-Class ProcessElectrically, the heart of the interrupter is the contactmaterial and structure. During the interruption of highcurrent, the surface of the contacts can reach its meltingtemperature, liberating any residual gases or contaminants

into the vacuum.

At Kyle, high purity chrome powder is analyzed, pressedinto a porous disk, infiltrated with copper, and machinedinto contacts. After electro-polishing, parts are assembledin a contaminant-free Class 1000 clean room, then loadedinto a vacuum brazing furnace for final production. Allprocesses are certified to ISO 9001 quality standards.

Cooper Power Systems, Kyle Distribution Switchgear,manufactures the most advanced vacuum interrupter inthe world. Superior to oil interruption and radial-magnetic

field vacuum interruption (see duty cycle comparison), thepatented axial-magnetic field Kyle vacuum interruptersprovide the longest life of any vacuum interrupter in theindustry.

K

AXIAL-MAGNETIC FIELD VACUUM INTERRUPTION

Kyle axial-magneti c field vacuum interrupter.

HIGH-ALUMINA CERAMICDesigned for maximum life and long-term vacuum integrity.

BELLOWSPermits ful l stroke for contactseparation without affecting vacuumseal.

CONTACT ASSEMBLYCopper alloy chosen for anti-weldingand high current interruptingcapabilities.

VAPOR SHIELD

Numberof

Trip

Operations

10

20

30

40

5060

80

100

Fault Interrupting Level (Symmetrical Amperes)

1000 2000 3000 4000 5000 6000 7000 80 00 9 000 10 00 0 11000 12000

70

90

200

300

400

500

600

800

1000

700

900

2000

3000

4000

50006000

8000

10000

7000

9000

Axial-MagneticVacuum Interruption

Radial-MagneticVacuum Interruption

Oil Interruption

Duty cycle compari son of oil , radial-magneti c fi eld, and axial- 

magneti c field fault i nterruption.

Page 4: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 4/28

The Shape of Things to ComeÉ

4

Compact, Lightweight Design

OVA microprocessor-controll ed, three-phaseautomatic circuit reclosers provide reliable and

economical overcurrent protection for distribution

circuits rated through 38kV. Extremely compact andlightweight in design, the NOVA recloser is easilyinstalled on poles or in substations.

Commanded by a Kyle microprocessor-based reclosercontrol, the NOVA automatic circuit recloser offerssuperior coordination and application capabilityunmatched by other system protection apparatus.

Application expertise, backed by worldwide recloserapplication experience, is available when needed.Knowledgeable design capability—based on more than

55 years of recloser manufacturing experience—hasmade Kyle the industry leader.

NOVA reclosers, like all Kyle reclosers, are designed andmanufactured in accordance with ANSI C37.60. Inaddition, the quality system at the Cooper PowerSystems Kyle Distribution Switchgear plant isISO-9001 certified.

Recloser and control accessories provide additionalcustomization of the protective program to achievemaximum system operating flexibility. Mounting

equipment is available for pole or substationapplications.

Operation

Current-sensing transformers, mounted on the recloser,supply fault-sensing information to the electroniccontrol. Trip and close signals from the control energizethe operating circuits in the recloser. By using a singlecurrent-sensing transformer ratio for all ratings,minimum-trip values of the electronic control areindependent of the continuous-current and interrupting

ratings of the recloser. Additional flexibility incoordination with other protective devices is providedby dual time-current characteristics available from awide choice of customizable curves, minimum tripvalues, reclosing and reset time settings, and a selectionof accessories. Stand-by power is supplied by internalsealed lead-acid batteries. The NOVA recloser with dcinterface provides deadline closing independent of 

system voltage.

Operational FlexibilityOperational flexibility is provided by offering thecustomer a choice of either ac or dc interface. Whileeach interface employs the same magnetic actuator and

is essentially mechanically equivalent, they differ inelectrical operation.

Ac InterfaceThe NOVA recloser utilizes a unique ac interface thatprovides exclusive operation with standard Kyle Form4C, Form 5, and FXB microprocessor-based controlsand standard control cables. Ac power is connectedthrough a two-pin connector and cable to theswitchgear.

Dc InterfaceThe NOVA recloser with dc interface is fullyoperational with Kyle Form 4C and Form 5microprocessor-based controls specially equipped with adc-to-dc converter, interface circuit, and a fully shielded19 pin control cable.

N

NOVA DESCRIPTION

ElectronicControl

PotentialTransformer(120/240Vac)

120Vac/240Vac

Power Cable

14 PinControl Cable

2 Pin120/240VacLow-VoltageClosing Cable

NOVA ac

OP 

2 Pin120Vac/240Vac

AlternativePower Connection

NOVA recloser configuration wi th ac interface.

ElectronicControl

PotentialTransformer(120/240Vac)

120Vac/240VacPower Cable

19 PinControl Cable

NOVA dc

OP 

NOVA recloser configuration with dc interface.

Page 5: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 5/28

ÉThe Shape of Things to Come

5

Vacuum Interruption

Vacuum interruption, used in NOVA reclosers, offersgreatly enhanced contact life. A single break on eachphase is accomplished by separating contacts inside thevacuum interrupter. All arcing is contained within the

vacuum envelope. Low-energy arc interruption,provided by axial-magnetic field technology, results infar less mechanical shock, extending the recloser’smechanical life.

Mechanism

The Kyle NOVA recloser meets and exceedsANSI/IEEE C37.60, as it is designed for a minimum of 10,000 operations. The mechanism is operated by amagnetic actuator, which uses a low-voltage powersource for operation. A fully-charged battery and trip

and close capacitors provide interrupter operation uponloss of control power. This feature provides the recloserwith dead-line operation capability–a requirement formany SCADA applications.

Magnetic Actuator

The heart of NOVA is a bi-stable linear actuator whichutilizes neodymium magnets, two opposing coils, aplunger, and a laminated frame. The magnetic actuator

provides a plunger holding force in excess of 136kilograms (300 pounds). It also permits a transfer of theplunger between two stable positions, by means of pulsed energy, to either of two opposing coils.

Advantages

Magnetic actuators provide several distinct advantageswhen utilized in a switchgear mechanism:

Latching – Mechanical latches are replaced by theactuator. Elimination of mechanical latches andassociated linkages leads to longer, trouble-freeoperation of the switchgear mechanism.

Response Time – The magnetic actuator is an electro-mechanical device capable of extremely fast responsetimes. This attribute is particularly advantageous forminimizing response and clearing time in providinginstantaneous reclose.

Size – The magnetic actuator is compact and requiresminimum mounting space. It’s overall dimensions are:20,3 cm x 17,8 cm x 11,4 cm (8 in. x 7 in. x 4.5 in.).

Power – A typical 8 amp-hour control battery hassufficient energy to provide hundreds of open-closeoperations in the absence of ac power.

Kyle Type NOVA™ recloser (dc version) mechani sm (view of operating mechani sm with housing cover removed).

Heater Magnetic Actuator

Stainless SteelMechanism Housing

(Standard)

OPEN/CLOSEContact Posit ion

Indicator

Actuator Board Control CableReceptacle

CT Protection Board Manual OPEN HandleTrip & Close Capacitors

Ground Connector#10 - #2 Stranded

MechanicalOperations Counter

Page 6: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 6/28

The Shape of Things to ComeÉ

6

his specification applies to three-phaseautomatic circuit reclosers with a rated maximum

continuous current of 630 Amps and a 12.5kAsymmetrical interrupting rating. The recloser shall bedesigned to operate at system voltages of 15kV, 27kVand 38kV. Overcurrent sensing, recloser sequencing andtripping shall all be electronically-controlled. Currentinterruption shall be accomplished with axial-magneticfield vacuum interrupters encapsulated in cycloaliphaticepoxy modules. The cycloaliphatic epoxy is a solidpolymer insulation system free of gas and oil. Unit shallbe designed for pole-mount or substation installation.Unit shall be in complete conformance with applicableANSI C37.60 (recloser), IEEE, IEC, and NEMA

standards.

QualityThe quality system of the manufacturing facility shallbe independently certified to meet the followingstandards: ISO 9001 (International Standards),ANSI/ISO/ASQC Q9001 (American NationalStandards), BS EN ISO 9001 (European Standards),and CAN/CSA ISO 9001 (Canadian Standards).

RatingsSee complete ratings information on page 9.

Microprocessor-Based ControlsThe recloser shall be tested as an integrated package tobe compatible with all Cooper Power Systems’ three-phase microprocessor-based recloser controls.

Current SensingCurrent sensing shall be provided by three epoxy-encapsulated current transformers mounted at theterminals of the recloser. Output from thesetransformers is sent to the control for currentmeasurement for protection, instrumentation, andmetering. The current-sensing transformers shall beeasily interchangeable.

ConstructionGeneral Design1. The recloser shall consist of a mechanism housing

that contains a magnetic actuator, which provideslinear trip and close motion to three encapsulatedvacuum interrupter modules.

2. The recloser shall utilize an environmentally-safesolid polymer insulation system.

3. The recloser shall use non-corrosive componentshoused in a stainless steel mechanism housing.

4. SF6 gas and oil are not acceptable for interruption orinsulation mediums.

5. The unit shall be designed for 10,000 open/closeoperations.

6. The unit shall be of lightweight design, constructednot to exceed 136 kilograms (300 pounds), includingcurrent-sensing transformers.

7. Provisions shall be included for electrical close,electrical and manual trip, contact position

indication, and operations counter.8. Operating temperature range shall be -40ºC to +55ºC.

9. The mechanism cabinet shall be designed to permitaccess for service.

Mechanism1. The mechanism shall utilize a bi-stable magnetic

actuator capable of fast closing and openingfunctions. The magnetic actuator is powered byenergy storage capacitors housed in the mechanismcabinet.

2. Design shall permit multiple operations after loss-of-primary-control voltage to allow dead-line operation.

3. The fi rst reclosing interval shall not exceed 0.4seconds.

4. Total clearing time of the recloser shall not exceed 42milliseconds.

Solid Dielectric Insulation1. The recloser system shall employ a cycloaliphatic

epoxy solid polymer insulation system and not relyon gaseous or liquid dielectric.

2. The solid polymer insulation shall be highly resistantto ozone, oxygen, moisture, contamination, andultraviolet light.

3. The solid dielectri c insulation shall contain noenvironmentally-hazardous or toxic components.

Vacuum InterruptersCurrent interruption shall occur in vacuuminterrupters, providing long contact life whileeliminating the production of toxic by-products.

T

NOVA SPECIFICATIONS

Scope

Page 7: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 7/28

The Shape of Things to ComeÉ

Vacuum interrupters in a high-vacuum brazing furnace.

The Kyle ®  NOVA™ Recloser

Microprocessor-Based Recloser Control/Protective Options and Ordering Information:

• Selection Guide for Kyle Microprocessor-Based Recloser Controls 

• Kyle ® Form 5 Microprocessor-Based Recloser Cont rol 

• Kyle ® FXB M icroprocessor-Based Recloser Cont rol 

• Protocol Converters for Kyle ® Form 4C Microprocessor-Based Recloser Control: DNP 3.0 / MODBUS • Kyle ® Form 4C M icroprocessor-Based Recloser Control Custom Control Accessori es 

• Kyle ® Form 4C M icroprocessor-Based Recloser Control 

• Kyle ® Form 5/LS/UDP Loop Secti onalizing Recloser Control System wi th Swi tch Mode 

• Kyle ® NOVA Recloser Ordering Informati on 

• Swi tch vs. Recloser 

Page 8: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 8/28

The Shape of Things to ComeÉ

8

286

(11.25) 1000(39.37)

140(5.5)

A

286

(11.25)

OP

EN

B

C

D

NOTE: All dimensions are mm (inches).Dimensions shown are approximate.

Terminal

Connectors1/0 - 500 MCM

TerminalConnectors

1/0 - 500 MCM

E

394(15.5)

394(15.5)

ControlReceptacle

Auxiliary SwitchAccessory Receptacle

GroundConnector

#10 - #2 Stranded

NOVA three-phase recloser dimensions.

NOVA DIMENSIONS

A B C D E

15kV 729 508 285 178 427(28.7) (20) (11.2) (7) (16.8)

27kV 790 569 285 178 427(31.1) (22.4) (11.2) (7) (16.8)

38kV 914 660 325 218 462(36) (26) (12.8) (8.6) (18.2)

Description 15kV 27kV 38kV

Terminal to terminal* 699 699 851(27.5) (27.5) (33.5)

Lower terminal to ground/earth 630 798 1077(24.8) (31.4) (42.4)

Creepage Distances

* On the same phase.

Description 15kV 27kV 38kV

NOVA recloser - kilograms (pounds) 111 (245) 118 (260) 125 (275)

Mass (Weight)

Page 9: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 9/28

The Shape of Things to ComeÉ

9

• Axial-magnetic field vacuum interrupters encapsulated incycloaliphatic epoxy resin

• Current sensing provided by three epoxy-

encapsulated current transformers

• Mechanism utilizes a bi-stable magnetic actuator forclosing and opening and is powered by energy storagecapacitors housed in the mechanism cabinet

• Electronic interface circuit issues opening and closingsignals to the magnetic actuator in response to inputsignals from the remote control

• Manual operation provided via manual handle

• Position indicator provides OPEN/CLOSE status

STATE OF THE ART DESIGN AND CONSTRUCTION

NOVA Recloser Data 15 kV 27 kV 38 kV

Voltage Ratings

Maximum Voltage. . . . . . . . . . . . . . . . . . . . . . 15.5kV 27.0kV 38.0kV

Rated Basic Impulse Level . . . . . . . . . . . . . . . . 110.0kV 125.0kV 170.0kV

Radio Noise Limit (Microvolts). . . . . . . . . . . . 100 @9.4kV 100 @16.4kV 100 @23.0kV

Power Frequency Withstand (Dry) . . . . . . . . . 50.0kV 60.0kV 70.0kV

Power Frequency Withstand (Wet) . . . . . . . . . 45.0kV 50.0kV 60.0kV

Current Ratings

Rated Continuous Current . . . . . . . . . . . . . . . 630A 630A 630A

Short Circuit Current, Symmetrical. . . . . . . . . 12.5kA 12.5kA 12.5kA

Making Current, Asymmetrical Peak. . . . . . . . 31.0kA 31.0kA 31.0kA

Making Current, Asymmetrical RMS . . . . . . . 20.0kA 20.0kA 20.0kA

Mechanical Ratings

Minimum Mechanical OperationsWithout Maintenance (C-O) . . . . . . . . . 10,000 10,000 10,000

Minimum Electrical OperationsWithout Maintenance (C-O) . . . . . . . . . 10,000 10,000 10,000

M ass (Weight) - Kilograms (Pounds) . . . . . . . . 100 (220) 104 (230) 115 (253)

Page 10: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 10/28

The Shape of Things to ComeÉ

International Offices:

Miami, Florida USA (Latin America)

Phone: 305-477-9400Fax: 305-477-9414

Markham, Ontario CanadaPhone: 905-940-8400Fax: 905-940-8405

Sao Paulo, Brazil

Phone: 011-55-11-524-0051Fax: 011-55-11-524-5250

Athens, GreecePhone: 011-30-1-964-6332Fax: 011-30-1-964-6336

Sydney, Australia

Phone: 011-61-2-9683-1122Fax: 011-61-2-9683-6840

 Jakarta, IndonesiaPhone: 011-62-21-523-9155Fax: 011-62-21-523-9191

Taipei, Taiwan

Phone: 011-886-2-2758-4530Fax: 011-886-2-2758-4535

SingaporePhone: 011-65-298-3191

Fax: 011-65-298-0559

KYLE DISTRIBUTION SWITCHGEAR

SOUTH M ILWAUKEE, WI USA

The quality system at Cooper Power SystemsKyle Distribution Switchgear is ISO 9001 certified.

Over 55 Years Experience

Kyle is a long-established, international leader in theproduction of distribution switchgear, with more than ahalf century of design, testing, and manufacturingexperience, and more than 1.3 million units operating

worldwide.

In 1933, Kyle was founded by W.D. Kyle, Sr. Under thedirection of William Kyle, Jr., the first Kyle automaticcircuit recloser was developed and marketed in 1941.Three years later, a more sophisticated recloser, utilizingdual-timing, quickly established Kyle as the leadingproducer of automatic circuit reclosers.

 ©1998 Cooper Industries, Inc.Kyle ® , McGraw Edison ® , RTE ®  are registered trademarksof Cooper Industries, Inc.NOVA™ is a trademark of Cooper Industries, Inc.

Bulletin 97019 • October 1998 • Supersedes 6/97

P.O. Box 1640Waukesha, WI 53187 USA

http://www.cooperpower.com

KBP

10/9

Page 11: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 11/28

SELECTION GUIDE FORKYLE MICROPROCESSOR-BASED RECLOSER CONTROLS

Features Control

FXB Form 4C Form 5

Power

Power Source Required  

Back-Up Power  

Battery Test  

Function

Local Keypad Programming    – 

Local Status Indication  

Programming Readout  

Sensitive Earth/Ground Fault  

Hot Line Tag   optional   

Power Metering – –    

Programmable Cold Load Pick Up    –   

Fault Target Indication  

Security Protection  

Loop Scheme Option –    

Switch Mode –   optional optional  

Loss of Phase Protection –   optional   

Under/Over Frequency – –    

Directional SEF – –     Extended Cabinet –   optional   – 

Cabinet Heater  

Interface/Communications

Software Programmable  

Serial Communications Capability –    

Discrete SCADA  

Variable Communications Protocol –   optional   

Alarm For Events – –    

Multiple Communications Ports – –    

Data Reader –      – 

V-PRO Compatibility –      – 

Analog Current Metering –      – 

The Shape of Things to ComeÉ

Page 12: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 12/28

Features Control

FXB Form 4C Form 5

Time-Current Curves

TCC Construction    –   

TCC Modifiers  

Sequence Coordination  

High Current Lockout  

Minimum Response Time  

High Current Trip  

Ground Trip Precedence  

Data and Metering

Current Metering, Inst. & Demand  

Power Metering (KW/KVAR/KVA/pf) – –    

Harmonics (2nd thru 15th) – –    

Energy Metering – –    

Event Recorder  

Multiple Protection Profiles – –    

Histograms – –    

Load Profile  

Data Profiler (Configurable) – –    

Duty Cycle (Per Phase)  

The Shape of Things to ComeÉ

 ©1998 Cooper Industries, Inc.Kyle ®  is a registered trademark of Cooper Industries, Inc.NOVA™ is a trademark of Cooper Industries, Inc.

Bulletin 97019A • October 1998 • Supersedes 6/97

P.O. Box 1640

Waukesha, WI 53187 USAhttp://www.cooperpower.com

K BP10/98

Page 13: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 13/28

The Shape of Things to ComeÉ

KYLE® FORM 5 MICROPROCESSOR-BASED

RECLOSER CONTROL

Reduced distribution automationcosts

Minimizes momentary “blinks”

Simplified system analysis

Extensive metering

Reduce planning costs through

histogram analysis

Lower maintenance costs

Future updates via modularconversions

Reliable, surge-resilient performance

Reduced outage times

Increase system reliability

Provides Operational Intelligence for the Entire Kyle Line of

Three-Phase, Electronically-Controlled Reclosers

   F   O   R   M    5

   C   O   N   T   R   O   L

AC

COMMUNICATIONSYSTEM

FRONT PANELDISPLAY 

ALTERNATECOMMUNICATIONS

SCADA   OPERATIONS   ENGINEERING

COMMUNICATIONS 1 COMMUNICATIONS 2 COMMUNICATIONS 3

METERING

HISTOGRAMS

PROFILES

ALARMS

TARGETS

RECLOSER

BATTERY 

BACK-UPINTERFACE

CPU

Page 14: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 14/28

The Shape of Things to ComeÉ

Multiple microprocessor-based design

Dual serial communication ports

Protocols 2179 and DNP 3.0

Microsoft ® Windows-based interfacesoftware

Modular design throughout, includinghardware, firmware and software

Voltage, current and power metering

Frequency and voltage loadshedding

Integrated communications platformdesign (combines RTU and control inone cabinet)

Configurable data profiler and eventrecorder

Easily retrofittable to all Cooper PowerSystems electronically-controlledreclosers

Histograms

Extensive harmonic analysis

KYLE® FORM 5 CONTROL FEATURES

Data Profi ler 

Total Harmonic Distort ion.

 ©1998 Cooper Industries, Inc.Kyle ®  is a registered trademark of Cooper Industries, Inc.NOVA™ is a trademark of Cooper Industries, Inc.

Bulletin 97019B • October 1998 • Supersedes 6/97

P.O. Box 1640

Waukesha, WI 53187 USAhttp://www.cooperpower.com

K BP10/98

Page 15: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 15/28

The Shape of Things to ComeÉ

KYLE® FXB MICROPROCESSOR-BASED

RECLOSER CONTROL

Microprocessor-based operation

Front panel programmability

User-friendly, Microsoft ® 

Windows-based programming

software

Sophisticated data collection

capabilities

Custom TCC construction capability

Designed and tested in accordance

with ANSI-C37.60

Menu-driven keypad operation

Front-panel RS-232 connection port

Fault targeting and status

Front panel indicators

Operator “Hot” keys

Reduced programming cost

Simplified, intuitive operation

Minimum training required

Advanced Overcurrent Protection for Kyle® NOVA™ Three-Phase, Electronically-Controlled Reclosers

DETAILED

REPORTS

TCC EDITOR

 Time-current curvesmay be selected forviewing, printing, ormodification fromeither the FXBStandard CurveLibrary or the Custom

.

All standard curvesand customized curvescan be modified toprovide special systemcoordination solutions.

 The Custom CurveEditor enables the userto create uniquecurves which can thenbe stored in theCustom Curve Library

User-friendly, Windowsapplication.

Control interrogation,programming, andoperation.

Manages load profile,event history, andrecloser duty cycledatabases.

Disk and hard copydocumentation of control parameters andcollected data.

FXB

STANDARD

LIBRARY 

Kyle and IEC time-current curve libraryaccessed via the TCCEditor

CUSTOM CURVE

LIBRARY 

User-defined curvescreated and savedwithin the TCCEditor environmentfor future access orediting.

SYSTEM

DATABASE

Provides convenientstorage of controlconfiguration files andcontrol databases.

Provides permanentdocumentation of controlconfiguration and controldatabase records.

FXB

PROGRAMMER

All curves can besaved and accessedfor use in the TCCEditor.

User-friendlykeyboard application

FRONT PANEL

PROGRAMMING

•Four-line, twenty-character LED

• Manual controlinterrogation,programming andoperation

•Load profile, eventhistory and recloserduty cycle viewing

•Five quick-accesskeys

•Menu-driveninterrogation and

programming

FXB

ProgrammableMinimum Trip Values

Programmable TCC's

Event Recorder

Load Profile Monitor

Duty Cycle Monitor

NOVA

For SpecificApplicationRequirements

Page 16: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 16/28

The Shape of Things to ComeÉ

Four-line, twenty-character alpha-

numeric LCD display

Front-panel programmability

Contact position indication

Hot line tag

SCADA capability

Sensitive Ground/Earth fault

Five quick-access keys (“Hot Keys”)

Operations counter

Current metering

Battery test

KYLE® FXB CONTROL FEATURES

For more information on the Kyle FXB Microprocessor-Based Recloser Control, contact your Cooper PowerSystems representative.

 ©1998 Cooper Industries, Inc.Kyle ®  is a registered trademark of Cooper Industries, Inc.NOVA™ is a trademark of Cooper Industries, Inc.

Bulletin 97019D • October 1998 • Supersedes 6/97

P.O. Box 1640

Waukesha, WI 53187 USAhttp://www.cooperpower.com

K BP10/98

Page 17: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 17/28

The Shape of Things to ComeÉ

PROTOCOL CONVERTERS FOR KYLE® FORM 4C

MICROPROCESSOR-BASED RECLOSER CONTROL:

DNP 3.0 / MODBUS Converts the Form 4C native 2179

Protocol to DNP 3.0 or MODBUSProtocol

Eliminates the need for ancillary

equipment – connects directly to theTTL interface in the Form 4C

Directly-powered – no need

for a separate power supplywhen powered by the

revised Form 4C powersupply

Operates in polled, event-

driven or a combination ofboth modes

Provides a gateway into a

complete SCADA ormonitoring network

Operates over various

communication media

Backed-up power by the existing

battery in the Form 4C control

DNP 3.0 Protocol Converter Accessory for the Form 4C Control 

provides fiber opti c or RS-232 output.

Page 18: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 18/28

The Shape of Things to ComeÉ

Onboard battery-backed memory

allows for configuration andoperating parameters to be storedand modified when required

Provides fiber optic or RS-232 output

signal for connection to a substationLAN or external communicationstransceiver

Diagnostic LED’s for hardware and

communications status

Provides isolation in compliance with

IEC 255-4

PROTOCOL CONVERTERS FOR KYLE® FORM 4C

MICROPROCESSOR-BASED RECLOSER CONTROL:

DNP 3.0 / MODBUS FEATURES

For more information on the DNP 3.0 and MODBUS Protocol Converter for the Kyle Form 4CMicroprocessor-Based Recloser Control, contact your Cooper Power Systems representative.

 ©1998 Cooper Industries, Inc.Kyle ®  is a registered trademark of Cooper Industries, Inc.NOVA™ is a trademark of Cooper Industries, Inc.

Bulletin 97019E • October 1998 • Supersedes 6/97

P.O. Box 1640

Waukesha, WI 53187 USAhttp://www.cooperpower.com

K BP10/98

Page 19: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 19/28

The Shape of Things to ComeÉ

KYLE® FORM 4C MICROPROCESSOR-BASED

RECLOSER CONTROL

CUSTOM CONTROL ACCESSORIES

Incorporates all features of theKyle Form 4C Control PLUS:

Switch Mode

• Enables the Form 4C Control tobecome a switch control, providingindication of overcurrent conditionswithout issuing a trip signal.

Hot Line Tag

• Provides protection for line crews byinterrupting and disabling the closecircuit. Also includes a close circuitdisconnect which provides a remov-able link directly in series with theclose circuit for operating practicesrequiring a visible break in the closecircuit.

Sensitive Ground/Earth Fault ON/OFF

• Provides front-panel access to Sen-sitive Ground/Earth Fault functions.

Trip On TCC2

• Causes all overcurrent trips to timeon the TCC#2 curves for phase andground.

Load Tap Change Disable (LTCD)

Status Indicator

• Allows a regulator to ride through amultiple shot recloser sequencewithout changing tap in an attemptto react to a recloser.

Provides Operational Intelligence for Kyle

®

NOVA™ Three-Phase, Electronically-Controlled Reclosers

SWITCH MODE HOT LINE TAG

SENSITIVE

GROUND

FAULTTRIP ON TCC2

Page 20: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 20/28

The Shape of Things to ComeÉ

KYLE® FORM 4C MICROPROCESSOR-BASED

RECLOSER CONTROL

CUSTOM CONTROL ACCESSORIES

For more information on the Kyle Form 4C Microprocessor-Based Recloser Control Custom Control Accessories,contact your Cooper Power Systems representative.

GROUND TRIPBLOCK

GROUND TRIPNORMAL

NONRECLOSING

NORMALRECLOSING

SWITCH MODE

ON

TRIP CLOSE(LOCKOUT) (HOLD FOR COLD

LOAD PICKUP)

SUPERVISORYON

SUPERVISORYOFF

ALTERNATEMINIMUM TRIP

NORMAL

HOT LINE TAG

NORMAL

KYLE ® 

 FORM 4C RECLOSER CONTROL

CLOSE

OPEN

LAMP TEST

PUSH TO TEST

HOTLINE TAG

ON

SWITCH MODE(AUTO TRIP OFF)

RECLOSER MODE

(AUTO TRIP ON)

CLOSE CIRCUIT

DISCONNECT

Hot Li ne Tag and Uni versal Device Protection features.

 ©1998 Cooper Industries, Inc.Kyle ®  is a registered trademark of Cooper Industries, Inc.NOVA™ is a trademark of Cooper Industries, Inc.

Bulletin 97019F • October 1998 • Supersedes 6/97

P.O. Box 1640

Waukesha, WI 53187 USAhttp://www.cooperpower.com

K BP10/98

Page 21: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 21/28

KYLE® FORM 4C MICROPROCESSOR-BASED

RECLOSER CONTROL

Incorporates microprocessor

technology for enhanced applicationversatility

All standard control operating

parameters are keyboardprogrammable

Convenient programming and

interrogation through simplekeyboard sequences and dedicated

function keys Large LCD display provides control

feedback during programming andinterrogation

Front panel LCD indicators provide

control and recloser status at aglance

Equipped with keyboard-selectable

time-current curves interchangeable

for phase or ground Modify time-current curves for

unlimited coordination flexibility

Provides Operational Intelligence for Kyle® NOVA™ Three-

Phase, Electronically-Controlled Reclosers

Communication Support Equipment

Form 4C INTERFACE™Software

Allows the control to beprogrammed and operated with apersonal computer. A digitalcommunications protocol is usedto ensure secure and reliablecommunications.

Digital CommunicationsAccessory

For SCADA Interface and remoteoperation. Provides real-timedigital communications. A pair of ST type fiber-optic connectors andan RS232 to fiber-optic converteris supplied to interface withcommunication systems.

Data Reader

Stores data gathered from theForm 4C control which can bedownloaded to a personalcomputer for system analysis.Capable of storing data from 20Form 4C controls.

The Shape of Things to ComeÉ

Page 22: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 22/28

Data port for downloading data files

Event recorder

Sequence coordination

Phase and ground fault target

indicators and counters

Contact position indicator

Battery test panel

High current lockout

Minimum response time

Trip test

Alternate minimum trip

Supervisory close

Supervisory trip and lockout

Supervisory ON/OFF switch

Remote trip and lockout

Close-retry feature

Non-reclose operation

Earth trip precedence

Sensitive ground/earth fault

Duty cycle monitor

Load profile monitor

KYLE® FORM 4C CONTROL STANDARD FEATURES

Instructional Video Available

KSPV9 Descripti on and Operation of the Kyle Form 4C Control available in VHS and PAL formats.

More information on the Kyle Form 4C Microprocessor-Based Recloser Control and its accessories can be foundin Catalog section 280-77, Service Information S280-77-1, S280-77-2, S280-77-3, and S280-77-4, or contactyour Cooper Power Systems representative.

The Shape of Things to ComeÉ

 ©1998 Cooper Industries, Inc.Kyle ®  is a registered trademark of Cooper Industries, Inc.NOVA™ is a trademark of Cooper Industries, Inc.

Bulletin 97019G • October 1998 • Supersedes 6/97

P.O. Box 1640

Waukesha, WI 53187 USAhttp://www.cooperpower.com

K BP10/98

Page 23: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 23/28

The Shape of Things to ComeÉ

KYLE® FORM 5/LS/UDP LOOP SECTIONALIZING

RECLOSER CONTROL SYSTEM WITH SWITCH MODE

Provides Loop Sectionalizing Feeder Protection to Reduce

Momentary Blinks and Minimize Customer Outages

Sectionalizing Recloser

Sectionalizing Recloser

Normally OpenTie Recloser

Feeder 2SubstationBreaker

2A

1B

1C

2B

F1

1AFeeder 1SubstationBreaker

F2

Three Recloser Loop

Three-recloser loop diagram.

Provides immediate servicerestoration independent of anycommunication system

Two-, three-, and five-recloser loopoperation

Sectionalizing or tie operation

Programmable single- or three-phaseloss of voltage response mode

Front Panel LED’s provide at-a-glancestatus information for both sources

Performance enhancing supervisoryoperation features

SCADA-ready, communicationsadaptable with DNP and 2179Protocols

Reliable decentralized intelligence

Page 24: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 24/28

The Shape of Things to ComeÉ

KYLE® FORM 5/LS/UDP LOOP SECTIONALIZING

RECLOSER CONTROL SYSTEM

For more information on the Kyle Form 5/LS/UDP recloser control contact your Cooper Power Systemsrepresentative.

SOURCE I & SOURCE II

Six LED indicators providestatus information for each

phase of Source I andSource II and indicate

which phase initiated LSoperation.

LS NOT RESETIndicates the status

position of the LS NOTRESET function.Following an LS

operation, the LED willilluminate.

LS DISABLEDIndicates the LS optionhas been disabled from

either supervisory controlor front panel.

SOURCE I DISABLED &SOURCE II DISABLEDThese function keys willdisable the LS control. In thesectionalizing mode, theSOURCE II disable key doesnot affect controlperformance.

LS RESETResets the LS control back toits normal “reset” position.Depressing this button turnsoff t he LS NOT RESETindicator LED.

Kyle Form 5/LS/UDP recloser control.

SECTIONALIZING/TIEThe LED’s indicate theconfiguration of the LScontrol as set by the Form 5Interface Software.

 ©1998 Cooper Industries, Inc.Kyle ®  is a registered trademark of Cooper Industries, Inc.NOVA™ is a trademark of Cooper Industries, Inc.

Bulletin 97019H • October 1998 • Supersedes 6/97

P.O. Box 1640

Waukesha, WI 53187 USAhttp://www.cooperpower.com

K BP10/98

Page 25: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 25/28

The Shape of Things to ComeÉ

KYLE® NOVA™ RECLOSER ORDERING INFORMATION

Ordering InformationAll NOVAreclosers include a TypeFXB microprocessor-based reclos-er control. To order a NOVA reclos-er, microprocessor-based control,and control cable:

1. Use the chart at right toconstruct a catalog number thatdescribes the required recloser.

2. Use the information in Table 1and Table 2 to specify therequired mounting provisions.

3. Use the information in Table 3to specify auxiliary switchrequirements.

4. Order the required electronic

control (recloser includes anFXB control):

A. From publication 280-01,Part 77 , specify the requiredForm 4C microprocessor-based recloser control.

B. From publication 280-01,Part 78 , specify the requiredFXB microprocessor-basedrecloser control. (For acNOVA only).

C. From publication 280-01,Part 79 , specify the requiredForm 5 microprocessor-based recloser control.

KNOVA Type NOVA recloser with Type FXB base recloser control*

15A Recloser Type:

15A for 15kV, 630A continuous, 12.5kA interrupting

27A for 27kV, 630A continuous, 12.5kA interrupting

1 Bushing Terminals:

1 for eyebolt terminal, 1/0 to 500MCM, 630Amaximum**

3 for 2-hole flat pad terminal, 630A maximum

1 Interface:

1 for AC NOVA - 120Vac closing

(14-pin receptacle & 2-pin receptacle)2 for AC NOVA - 240Vac closing

(14-pin receptacle & 2-pin receptacle)

3 for DC NOVA*** - (19-pin receptacle),120Vac Heater

4 for DC NOVA *** - (19-pin receptacle),

240Vac Heater

KNOVA 15A 1 1KNOVA15A11 is the catalog number for the required basic Type NOVArecloser.

* Include the base catalog number of the selected control when ordering the recloser.

** Price included when ordering a Type NOVA recloser.*** Not available with FXB controls.

Constructing a Catalog NumberTo order a basic Type NOVA recloser with eyebolt terminals, for usewith 120Vac closing, and a 14-pin control cable, the catalog number

would be constructed like this:

Catalog

Description Number

Single pole-mounting hanger with stainless steel hardware . . . . . KNOVA54-2

Surge arrester mounting brackets with stainless steel hardwareInboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KNOVA61-2Outboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KNOVA61-1

Alley pole-mounting hanger with stainless steel hardware . . . . . . KNOVA352-1Arrester brackets (set of 3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KNOVA353-1

Arrester brackets (set of 6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KNOVA353-2Substation mounting frame with stainless steel hardware

includes control mounting bracket for FXA, FXB, Form 4C(single and double-size cabinet) and Form 5 . . . . . . . . . . . . . . . KNOVA59-1

Field kit for NOVA on substation mounting frame KA89WV1 . . . . KNOVA457-1

Field kit for NOVA on substation mounting frame KA584R1 . . . . . KNOVA457-2

TABLE 1Mounting Equipment

Page 26: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 26/28

 ©1998 Cooper Industries, Inc.Kyle ®  is a registered trademark of Cooper Industries, Inc.NOVA™ is a trademark of Cooper Industries, Inc.

Bulletin 97019I • October 1998 • Supersedes 6/97

P.O. Box 1640

Waukesha, WI 53187 USAhttp://www.cooperpower.com

K BP10/98

The Shape of Things to ComeÉ

CatalogDescription Number

Three-stage auxiliary switch with six independent contactsand receptacle for KNOVA178 cable . . . . . . . . . . . . . . . . . . . . . KNOVA66-1

Auxiliary switch cable for KNOVA66-1, auxiliary switch tocontrol, 0 - 80 feet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KNOVA178

Auxiliary switch cable, maximum 200 feet. Replace “X” withnumber of feet. Price per foot over 10 feet . . . . . . . . . . . . . . . . KA1119R2-X

TABLE 3Auxiliary Switch

KYLE® NOVA™ RECLOSER ORDERING INFORMATION

Catalog

Description Number

Recloser in single pole-mounting hanger KNOVA54-2 . . . . . . . . . KNOVA354-1

Recloser in single pole-mounting hanger KNOVA54-2 witharrester brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KNOVA354-2

Recloser on substation mounting frame KNOVA59-1 . . . . . . . . . . KNOVA355-1

Recloser on alley pole-mounting hanger KNOVA352-1 . . . . . . . . KNOVA456-1

Recloser on alley pole-mounting hanger KNOVA352-1 witharrester brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KNOVA456-2

TABLE 2Factory Assembly of NOVA Recloser and Mounting Equipment*

*Covers factory assembly only; recloser, control, and mounting equipment must be ordered separately.

Catalog

Description NumberLow voltage ac input cable (ac NOVA only) . . . . . . . . . . . . . . . . . KA11ME1-15

Source and load wildlife guards (set of 6) . . . . . . . . . . . . . . . . . . . KNOVA56-2

TABLE 4Miscellaneous Accessories

Page 27: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 27/28

The Shape of Things to ComeÉ

SWITCH VS. RECLOSER

Switch vs. Recloser

• By definition, switches and reclosershave basic differences in their appli-cation on a distribution system.

Switches are designed solely for exe-cuting load switching commands,while reclosers execute load switch-ing commands and autonomouslyinterrupt fault currents.

• This autonomous operation can beextended to the entire distributionfeeder, providing either a centralizedor decentralized approach.

Minimum Trip Sensitivity

• The use of a recloser on the distribu-tion system increases the ability tosense additional faults.

• Increased sensitivity and isolation oflower magnitude faults protects distri-bution line equipment, minimizes con-ductor burn down, and reduces thelikelihood of a temporary fault evolv-ing to a permanent fault.

X

F1 Recloser

X

F2

X

F3

50 0 Cu st omer s 5 00 Cus tomer s 500 Customers

Recloser Applications

MAIFI = 1500 + 1000 + 500 + 500 = 2.33E

1500

Recloser

Recloser application diagram.

X

F1 Switch Switch

X

F2

X

F3

500 Customers 500 Customers 500 Customers

Switch Applications

MAIFI = 1500 + 1500 + 1500 + 1500 = 4.00E

1500

Switch application diagram.

Centralized

• Substation breaker is required for fault interruption.

• Entire distribution feeder requires a momentary outage.

• Centralized system with switches for fault isolationrequires 100% reliability of the communication system.

• Switches are to be opened during periods of de-ener-gized line, or load-break ratings.

• Communication and sectionalizing equipment costs

are required for operation.

Decentralized

• Multiple reclosers used on the distribution circuit.

• Only affected areas see momentary outage.

• No communication system is required for immediatefault isolation. Inherent system reliability isimproved due to multiple independent devices.

• Full maximum fault interrupting ratings provideincreased safety.

• Sectionalizing costs only.

Page 28: Cooper - Recloser - Type NOVA.pdf

8/14/2019 Cooper - Recloser - Type NOVA.pdf

http://slidepdf.com/reader/full/cooper-recloser-type-novapdf 28/28

The Shape of Things to ComeÉ

Momentary Outages

• More than 20 percent of utilities todaytrack momentary operations of“blinks.”

• Continual process operations, factoryautomation, and residential demandsrequire new enhancements to theapplication of distribution equipment.

• MAIFI and MAIFIE statistics arebecoming more common indices tomeasure momentary blinks.

• Traditional fault protection based onsubstation device (circuit breaker orrecloser) protection and lateral fusingis being replaced with the addition ofdistribution reclosers to provide faultprotection, minimizing substation tripsand momentary outages.

• Extensive flexibility in time-currentcurves, minimum trip values, andoperation sequences result in simpleinstallations to existing systems pro-viding trip coordination.

Cooper Power Systems Leads inDistribution Automation

• The economic evaluation of momen-tary outages indicates that the cost ofpurchasing a recloser is negligible for

application with industrial and com-mercial facilities.

• Cooper Power Systems is stronglycommitted to improving the reliabilityof the electric power industry.

• Technological advances, including thenewest microprocessor-based con-trols and solid insulation NOVA distrib-ution switchgear products representour investment in the future.

The Shape of Things to ComeÉ

 ©1998 Cooper Industries, Inc.Kyle ®  is a registered trademark of Cooper Industries, Inc.

P.O. Box 1640

Waukesha, WI 53187 USAh //

For more information on reclosers and switches in Distribution Automation, refer to Bulletin 98011 or contactyour Cooper Power Systems representative.

MAIFI = Momentary Average Interruption Frequency Index

= Total number of customer momentary interruptions

Total number of customers served

MAIFIE = Momentary Average Interruption Event Frequency Index

= Total number of customer momentary interruptions events

Total number of customers served