Recloser Controller g Energy Protection AC Parameters Level Trips - Phase Over current - Neutral Over current Overvoltage Under voltage Voltage unbalance 3 setting groups for different detection applications Automation & Control Auto-Recloser 4 Shots to Lockout CLP Cold load pickup Auto/Manual, Local/Remote control Customized automation schemes using FlexLogic™ Metering & Monitoring Metering - current, voltage, power, energy, frequency and PF Event Recorder - Up to 256 time tagged events with 1ms res Enhanced system diagnostics and reporting Communications Networking Interface - two wire RS485 - Multiple protocols (Modbus®, DNP3.0) - Optional wireless communications (radio or cellular) User Interface - Front panel USB port - 4 line HMI display - 20 system status LED’s Security & EnerVista™ Software 4-Level device security to maintain authorized access only Simplified device configuration software tool and industry leading suite of software tools to manage and maintain Multilin devices Hardware 3: CT supports traditional as well as line post sensors 6: VT supports traditional as well as LEA inputs Expandable inputs and outputs for advanced applications 4 shot auto-recloser 3 setting groups enable different setting selections based on switched conditions Advanced logic engine and multiple IOs for creating customized control schemes Improve performance and reliability by integrating remote feeders into DMS/OMS/SCADA Real time monitoring of energy to track non-technical losses Improves asset monitoring and maintenance schedules based on measured energy discharge Compatible with low energy analog (0-10V or 0-1V) voltage sensors Enhanced troubleshooting tools including sequence of event records and data logger Reduces setup time and commissioning time with easy-to- use software tools and quick setup keys on front panel Common hardware, firmware and software platform with other Multilin Distribution Automation (DA) controllers Rugged construction designed for outdoor use in harsh environment (-40° C to + 60° C) Automatic control of Over Head & Pad Mounted Reclosers for Fault detection & Isolation. Automatic control of Pad Mounted Switch Gear Interfacing with FDIR/FLISR for fault isolation and & auto- restoration. Recloser Controller Multilin DGCR FEATURES APPLICATIONS KEY BENEFITS

Multilin Recloser Controller DGCR Recloser Controller Recloser Controller Comparison of time taken for different fault isolation and restoration options. Detects Fault – Dispatch

Embed Size (px)

Citation preview

Page 1: Multilin Recloser Controller DGCR Recloser Controller Recloser Controller Comparison of time taken for different fault isolation and restoration options. Detects Fault – Dispatch

Recl

oser

Con

trol

ler

g Energy

Protection • ACParametersLevelTrips

-PhaseOvercurrent

-NeutralOvercurrent• Overvoltage• Undervoltage• Voltageunbalance• 3settinggroupsfordifferentdetectionapplications

Automation & Control• Auto-Recloser4ShotstoLockout• CLPColdloadpickup• Auto/Manual,Local/Remotecontrol• CustomizedautomationschemesusingFlexLogic™

Metering & Monitoring• Metering-current,voltage,power,energy,frequencyandPF• EventRecorder-Upto256timetaggedeventswith1msres• Enhancedsystemdiagnosticsandreporting

Communications• NetworkingInterface-twowireRS485

-Multipleprotocols(Modbus®,DNP3.0)-Optionalwirelesscommunications(radioorcellular)

• UserInterface

-FrontpanelUSBport-4lineHMIdisplay-20systemstatusLED’s

Security & EnerVista™ Software• 4-Leveldevicesecuritytomaintainauthorizedaccessonly• Simplifieddeviceconfigurationsoftwaretoolandindustry

leadingsuiteofsoftwaretoolstomanageandmaintainMultilindevices

Hardware• 3:CTsupportstraditionalaswellaslinepostsensors• 6:VTsupportstraditionalaswellasLEAinputs• Expandableinputsandoutputsforadvancedapplications

• 4shotauto-recloser• 3settinggroupsenabledifferentsettingselectionsbasedon

switchedconditions• AdvancedlogicengineandmultipleIOsforcreating

customizedcontrolschemes• Improveperformanceandreliabilitybyintegratingremote

feedersintoDMS/OMS/SCADA• Realtimemonitoringofenergytotracknon-technicallosses• Improvesassetmonitoringandmaintenanceschedules

basedonmeasuredenergydischarge

• Compatiblewithlowenergyanalog(0-10Vor0-1V)voltagesensors

• Enhancedtroubleshootingtoolsincludingsequenceofeventrecordsanddatalogger

• Reducessetuptimeandcommissioningtimewitheasy-to-usesoftwaretoolsandquicksetupkeysonfrontpanel

• Commonhardware,firmwareandsoftwareplatformwithotherMultilinDistributionAutomation(DA)controllers

• Ruggedconstructiondesignedforoutdooruseinharshenvironment(-40°Cto+60°C)

• AutomaticcontrolofOverHead&PadMountedReclosersforFaultdetection&Isolation.

• AutomaticcontrolofPadMountedSwitchGear

• InterfacingwithFDIR/FLISRforfaultisolationand&auto-restoration.

Recloser Controller

Multilin™

DGCR

FEAtuRES

APPliCAtionS

KEy BEnEFitS

Page 2: Multilin Recloser Controller DGCR Recloser Controller Recloser Controller Comparison of time taken for different fault isolation and restoration options. Detects Fault – Dispatch

Multilin DGCRRecloser ControllerRe

clos

er C

ontr

olle

r

www.GEDigitalEnergy.com

Reliability in networksA key driver andmeasurement of utilityeffectivenessisinthereliabilityofpowertoitscustomers.Asmanyfaultsonoverheaddistribution lines are transient in nature,reclosingatthesubstationandinstallationofmid-linereclosers./switchescanimprovea utilities SAIDI reliability index by up to24%.Whenpermanentfaultsoccuronoverheadlines, having feeders with increasingdegrees or automation can greatlyenhance distribution grid reliabilityand reduce restoration of unfaultedsegments from several hours to a fewsecondsorminutes.Akeycomponentofthese automation schemes is intelligentcontrollers that can integrate with FDIRsystemsthroughsharinglocalinformationandacceptingcontrolcommands.

Fault isolation and Restoration

With adequate deployment of Reclosersand switches, faults on distributionnetworkscanoftenbe isolated allowingunaffected parts of the system to berestored. Twomainmodesof operationof isolation and restoration commonlydeployedare:A,Manual: Fault Isolation&restorationis

donemanuallybythecrewvisitingthesite.

B.Automatic: Intelligenceattheswitchinglocations detect faults and based onthe level of automation available, thefollowingthreeoptionsarepossible.

1. localized Control: Local intelligencefor detecting and isolating a faultedsection of the feeder allowing forautomatic reclosing and restorationtounfaultedupstreamsectionsofthefeeder.

2. operator Control: Operator Controlrequires a DMS application like GE’sPowerOnorGeNesolutionsrunninginthecontrolcenter.Thisisacombinationoflocalintelligencecommunicatingtothe control center with an Operatorexecuting switching plans to isolatethe fault and restore service to non-faultedsections.

3. Automated Control: AutomatedControlrequiresaDMSapplicationlikelikeGE’sPowerOnorGeNerunninginthe control center or a decentralize

system running in the substationlikeGE’s D400-FDIR. FDIR algorithmsdetermines fault location andautomatically reconfigure the feedertoisolatethefault&restoringpowertonon-faultedsections.

overview TheMultilinDGCRisanadvancedRecloserController for detection of faults andcontrollingoverheadreclosers.TheMultilinDGCRiscompatiblewithmanytraditionaland magnetic actuator reclosers andprovides a great degree of flexibility inintegratingwithFDIRsystems.The Multilin DGCR provides integratedprotection, control, and reclosingfunctionality required for protectingfeeders and isolating faulted sections.Utilizing these features, the MultilinDGCR can greatly improve distributionreliabilitywhetheritisbeingusedworkingindependentlyor intandemwithanFDIRscheme.TheMultilinDGCRiscapableofmonitoring3currentsandup to6 voltagesallowingfor3-phasevoltagemeasurementoneachside of the recloser. The Multilin DGCRsupporttraditionalCTsandPTssensorsaswellaslinepostsensorssuchas(Lindsey,FisherPierce).Withthismeasurementcapability,Multilin’sDGCR can measure and communicatecritical information includingvoltageand

current magnitudes to SCADA and DMSsystems. The Multilin DGCR calculatespower factor, phase angle, power flowdirection, power and energy. Multilin’sDGCR performs real time tracking ofrecloser operations, parameters and therecloserweartherebyenablingtheutilityto manage their assets effectively andefficiently

Robust Design

BasedonGE’sprovencontrollerplatformwith tens of thousands of units installedglobally, the Multilin DGCR undergoesextensive Accelerated Life Testing (ALT)andHighlyAcceleratedLifeTesting(HALT)to validate accurate functionality underspecifiedconditionsandtoensureaccurateperformance in extreme operatingconditionsandharshenvironments.Asacompletepackage,theMultilinDGCRis offered in a NEMA-4 certified cabinetthat is suitable for operation of harshenvironmentswithanoperatingrangeof-40°Cto+60°C(-40°Fto+140°F).

Modes of operation

The Multilin DGCR Recloser controllerprovidestwomodesofoperation:

• Remotemode

• Localmode

The Multilin DGCR recloser controllermeasures three phase voltages andcurrents,andbasedonthemeasurements,managesautoreclosefunctionality.

typical loop Feeder Arrangement

The DGCR can play an important part of FDIR/FLISR solutions for improving distribution grid reliability.

Page 3: Multilin Recloser Controller DGCR Recloser Controller Recloser Controller Comparison of time taken for different fault isolation and restoration options. Detects Fault – Dispatch

Multilin DGCRRecloser Controller

Recl

oser

Con

trol

ler

www.GEDigitalEnergy.com

Comparison of time taken for different fault isolation and restoration options.

Detects Fault–Dispatchcrewonreceiptoffaultinformation

Restore upstream–RestorepowerbackfromS/SAtofirstswitchingdevice(SW1).Crewtraveltime,Isolatefault(OpenSW1)

Restore Downstream–RestorepowertosegmentbetweenSW2andTieSW.Crewtraveltime,Isolatefault(OpenSW2)&reroutepower(ClosetieSW)

Fix Fault –Rectifythefault&revertbacktonormal

* Actual restoration time varies based on the circuit configuration.

Automating the reconfiguration of faulted distribution circuits reduce customer outage time on unfaulted sections of the network from hours to seconds

Alert operator Restore upstream Restore Downstream Fix Fault

Alert operatorRestore upstream Restore Downstream Fix Fault

Alert operatorRestore upstream Restore Downstream Fix Fault

Alert operatorRestore upstream

Restore DownstreamFix Fault

ManualMode

AutomaticModeLocalizedControl

AutomaticModeOperatorControl

AutomaticModeAutomatedControl

5-10 min

5-10 min

<10 sec

<10 sec

0.5-1 hr

0.5-1 hr

<3 min

1-1.5 hr

0.5-5 sec*

0.5-5 sec*

0.5-5 sec*

SAiDi: TheSystemAverageInterruptionDurationIndexistheaverageoutagedurationforeachcustomerserved.

SAiFi: TheSystemAverage InterruptionFrequency Index istheaveragenumberofinterruptionsthatacustomerwouldexperience.

CAiDi: TheCustomerAverageInterruptionDurationIndex isSAIDI SAIFI.CAIDIgivestheaverageoutagedurationthatanygivencustomerwouldexperience.CAIDIcanalsobeviewedastheaveragerestorationtime.

nEtwoRK REConFiGuRAtion iMPRoVinG REliABility

Efficientfaultdetection,isolationandrestorationgreatlyenhancesdistributiongridreliability,reducingrestorationtimedrasticallyfromseveralhourstoafewsecondsorminutes.Distributionreliabilityperformancesaregreatlyenhanced,asaretheindexesofCAIDI,SAIFIandSAIDI,whicharecommonlyusedasareliabilityindicatorbyelectricpowerutilities.

Page 4: Multilin Recloser Controller DGCR Recloser Controller Recloser Controller Comparison of time taken for different fault isolation and restoration options. Detects Fault – Dispatch

Multilin DGCRRecloser ControllerRe

clos

er C

ontr

olle

r

www.GEDigitalEnergy.com

Fault ProtectionThe Multilin DGCR provides protectionfunctionalityfordownstreamOverCurrentand Earth Faults. The DGCR can beprogrammedtorecloseafaultedsegmenteitherindependentlyorfromremote.Thisis a key feature for grid reliability TheDGCRalsoofferscontrol,monitoringanddiagnostics in one integrated efficientdesign.

Cold load pickup

The Multilin DGCR can be programmedto block the instantaneous over-currentelements, and raise the pickup level ofthe time over-current elements, when acold load condition is detected. The coldload condition is detectedduring closingof thebreakerona feeder thathasbeende-energized for a long time. The feederinrushcurrentandthemotoracceleratingcurrent during breaker closing maybeabove some over-current protectionsettings.

Phase ioC

TheMultilinDGCRhasone instantaneousovercurrentdetectionfunctionPhaseIOC.Itconsistsofthreeseparateinstantaneousovercurrentelements;oneperphase,withidenticalsettings.

Phase toC

TheTOC in theMultilinDGCRcomeswiththefollowinguserselectablecurves:Extremely/Very/Moderately/NormallyInverse,DefiniteTime,IECCurveA/B/CandShortInverse,IACExtremely/Very/Inverse/Short,UserCurve,FlexCurveA,FlexCurveB.TheTOCsettingsareappliedtoeachofthethreephasestoproducepickupandalarmconditionsperphase

neutral current detection

The Multilin DGCR has one NeutralOvercurrent detection function. Thesettingsofthisfunctionareappliedtothecalculatedneutralcurrent forpickupandtripflags.

overvoltage detection

ThephaseOVprotectionprotectsvoltagesensitivefeederloadsandcircuitsagainstsustained overvoltage conditions. Thephase OV protection generates alarms

when the voltage exceeds the selectedvoltagelevelforthespecifiedtimedelay.

Phase under voltage detection

ThephaseUVprotectionprotectsvoltagesensitivefeederloadsandcircuitsagainstsustained under voltage conditions. Thephase UV protection generates alarmswhenthevoltagedropsbelowtheselectedvoltagelevelforthespecifiedtimedelay.

Voltage unbalance detection

The Voltage Unbalance feature in theMultilinDGCRdetectsvoltageunbalancesonafeeder.Voltageunbalanceisdefinedastheratioofnegative-sequencetopositive-sequencevoltage.Onunbalanceanalarmis issued so themaster station can takeactionto isolateandrepair thedamagedsection.Thiscouldprovideanindicationtothesystemoperatorofabrokenconductorcausingahighimpedancefault .Reverse Power DetectionReverse Powerdetection prevents the recloser OpencommandfrombeingexecutedduringtheAutoSectionalizingsequence.

Auto Recloser

The Auto Recloser element providesa mechanism to localize a fault bycoordinating this function with thereclosingoperationsofthefeederbreakerwithinatimingschedule.The logic implemented in this elementprovidesawaytodetectseveralreclosing

actions from the main circuit breakerandaccordinglyopenthe localswitch, inperiodswhenthevoltageisabsent.The logic uses the information of theovercurrent condition followed by a lossof voltage, loss of current , power flowdirectionandvoltagedetectionfunctionstoexecutethetransitionintointernalstates.

Automation & ControlTheMultilinDGCRofferspowerfulI/Oandprogrammablelogic(FlexLogic™)options for advanced automation andcontrol, reducing the need and costsassociatedwithadditionalprogrammablecontrollersordiscretecontroldevices.

Remote Control

For both operational efficiency andreliability reasons, the Multilin DGCRprovides remote control for operatingover-headrecloseraswellasPadmountedswitchgear. The Multilin DGCR has thecapabilitytolockremotecontroloperationslocally to prevent remote controlfunctionality.TheMultilinDGCRiscapableofprovidingbothlocalandmanualcontroloftheswitchgear.The compact size of the Multilin DGCRenables it to fit in existing out doorDistributionSubstationswithouttheneedforadditionalspace.

50P 50N 51P

27P 59PCLOSETRIP

CLP

Monitoring

METERING

AUTO-RECLOSER

Functional Block Diagram

ANSIDeviceNumbers&FunctionsDeviceNumber Function50P PhaseInstantaneousOvercurrent50N NeutralInstantaneousOvercurrent51P PhaseTimeOvercurrentCLP ColdLoadPickUp27P PhaseTimeOvercurrent59P OverVoltage

Custom FlexCurves can be constructed to coordinate with other Up/down stream protection devices on a lateral

Page 5: Multilin Recloser Controller DGCR Recloser Controller Recloser Controller Comparison of time taken for different fault isolation and restoration options. Detects Fault – Dispatch

Multilin DGCRRecloser Controller

Recl

oser

Con

trol

ler

www.GEDigitalEnergy.com

Set Point Group Control

TheMultilinDGCRhasthreeidenticalsetpointgroups.TheactivationofthegroupcanbedoneeitherfromtheHMIorviaadigitalinput.

Virtual inputs and outputs

TheMultilinDGCRprovides32virtualinputsand32virtualoutputsthatprovideuserswiththeabilitytosendcommandstothedevice.TheMultilinDGCRcanacceptcommandsfromSCADA,throughthefrontHMI,orfrontUSBporttoissuecommandssuchascloseoropen.

Command Setting

TheMultilinDGCRhastheabilitytoforcecommandsfromthemenustructure.ThiscanalsobeachievedviatheEnerVista™softwarethatrunsonaPC.ThissimulationensuresthatthecloseandopencommandscanbesafelyissuedfromadistancewithoutusingtheHMI.

Flexlogic™

FlexLogic in the Multilin DGCR providesthe ability to create customized controlschemes. This minimizes the needand costs associated with auxiliarycomponentsandwiring.SchemescanbeconfiguredwithFlexLogicspecifyingwhatactionsneedbetakenbasedonthestatusoffaultdetectionsorcontrolelements,aswellasinputsdrivenbyconnectedsensorsandequipment.

Battery Management System

TheMultilinDGCRiscapableofcontrollingthe over head recloser in differentconditionsincludingpowerloss.Thepowerlosscanoccurifthefeedercircuitbreakeropens up or there is a distribution gridblackout.Duringallpowerlossconditions,theMultilinDGCRissuppliedfromabackupbattery.Thebatteryisa24VSealedValveRegulatedLeadAcid(SVRLA)battery.ItissizedtokeeptheMultilinDGCRrunningfor8hours.During normal running conditions, thebattery is connected to the charger.SwitchingtodifferentmodesofoperationiscontrolledbytheDGCR.Thebatterymanagementsystemhasthefollowingmodesofoperations.

• Run

• Backup

• Batterytest

• Fusetest

AbatteryalarmLEDisprovidedforalarms,andtheeventwillbeloggedintotheeventrecorder.

Metering & MonitoringThe DGCR recloser controller is able tomonitor the recloser state based on theauxiliary input 52a / 52b provided bytherecloser. Itcanalsobeconfiguredforseveral external inputs for monitoringpossibleerrorsThese inputs can be used to inhibit anypossible local and remote closing andopeningcommandstotherecloserorthepadmountedswitchgear.The Multilin DGCR is able to monitorotherexternalstatessuchas lowbatteryconditions,ambienttemperature.

Power Quality Measurements

TheMultilinDGCRprovideshighaccuracymeteringandrecordingofallACsignals,measuringthefollowingkeyparameters:

• Phase-GroundVoltages(kV)

• PhasetoPhaseVoltages(kV)

• Positive,Negative,ZeroSequenceVoltage

• PhaseA,B,andCCurrents(A)

• Positive,Negative,ZeroSequenceCurrent

• GroundCurrent(A)

• 3-PhaseActivePower(KW)

• 3-PhaseReactivePower(KVar)

• 3-PhaseApparentPower(KVA)

• PowerFactor(LagorLead)

• Pos.&Neg.(Import&Export)RealEnergy(kWh)

Event record enables to analyze the sequence of events after each recloser action. Each event is stored with event number, date, time, and analog data of interest

Data logger helps in better understanding the analogue channel behavior. Sampling at a selectable time interval rate of 1 min to 60 minutes

Page 6: Multilin Recloser Controller DGCR Recloser Controller Recloser Controller Comparison of time taken for different fault isolation and restoration options. Detects Fault – Dispatch

Multilin DGCRRecloser ControllerRe

clos

er C

ontr

olle

r

www.GEDigitalEnergy.com

• Pos.&Neg.(Import&Export)ReactiveEnergy(kVarh)

• 2ndto8thHarmonicupto20%–forCurrent

• 2ndto8thHarmonicupto20%–forVoltage

• THDin20%–forCurrent

• THDin20%–forVoltage

Thesedatapointscanbeeasilyintegratedintoacustomer’sdatabaseforseamlessviewingthroughaSCADAorDMSsystemlikeGE’sPowerOnorGeNe.

Statistics & Counters

• TripCounter

• OpenCounter

• CloseCounter

• KI2TPhaseACounter

• KI2TPhaseBCounter

• KI2TPhaseCCounter

• TotalClose/OpenOperation

Maintenance Elements

Themaintenanceelements in theMultilinDGCR provides alarms to the system

basedonthemaximumnumberofclosing/openingexecutedcommandsperperiodoftimeandI2tmeasurementsperfeeder.

Event Recorder

To significantly reduce time and enablemore effective distribution, post faultanalysisandtroubleshooting, theMultilinDGCR provides an integrated eventrecorderanddetaileddiagnosticfeatures.Thesequenceofeventsrecorderoffersthefollowingfeatures:

• Upto256consecutiveeventsstored

• Enableordisable,operateanddropouteventsbysetpoints

• Phasevoltage/currentandpowermeteringshotisalsoincludedandstoredateachevent

Data Management & DiagnosticsThe Multilin DGCR provides advanceddisturbance diagnostic features thatsignificantly reduce the time and costsassociated with troubleshooting powersystem events and reconstruction.

Recording functions include enhanceddiagnosticswitha10channelRMSrecorderdatalogger.

Advanced Device Health Diagnostics

Comprehensive device health diagnostictestsareperformedbytheMultilinDGCRduringstartupandcontinuouslyatruntimetotestitsownmajorfunctionsandcriticalhardware.ThesediagnostictestsmonitorforconditionsthatcouldimpacttheMultilinDGCRController’sperformance,evaluatesthepotential impactandcriticalityofthiscondition,andpresents thedevicestatustooperatorsviaSCADAand/orthroughthefrontpaneldisplay.

CommunicationsTheMultilinDGCRutilizesindustrystandardcommunications technologies making itoneofeasiestandmostflexiblecontrollerstouseandintegrateintonewandexistingSCADAorDMS infrastructures.Supportedcommunicationprotocolsinclude:

• DNP3.0

• ModbusRTU(RS485)

Front panelDisplay: 4x20 character lCD display

Control Panel: Auto/Manual pushbuttonlocal/Remote pushbuttonManual open/Close pushbuttons

uSB 2.0 Port

Status lEDs

target Reset

Multi-functional menu navigation keypad

Quick access pushbuttons

Status lEDs

Page 7: Multilin Recloser Controller DGCR Recloser Controller Recloser Controller Comparison of time taken for different fault isolation and restoration options. Detects Fault – Dispatch

Multilin DGCRRecloser Controller

Recl

oser

Con

trol

ler

www.GEDigitalEnergy.com

Multiple communication ports andprotocolsallowforremotecontrolandeasyaccesstodeviceandsysteminformation.All communication ports are capable ofsimultaneouscommunications.TheMultilinDGCRcanalsocommunicatetoFDIR/FLISR/SCADAsystemsviawirelesscommunications media. The supportedwirelessmediaincludes:

• Wirelessradio(MDSorcustomerspecific)

• GSM/GPRS

• Pre-wiredforfutureradio

SecurityThe Multil in DGCR Controller andassociatedsoftware toolsprovideasuiteof security features that ensure onlyapprovedpersonnelcanmakechangestotheconfigurationofthesystemorexecutecommands.ThesefunctionsenableautilitytomeetNERC/CIPrequirements.

Password Security

TheMultilinDGCRoffersmultiple levelsofpasswordsecurity to limitaccesscontrolbased on settings or command levels.

Therearefourlevelsofpasswordsecurityprovided:

• Localsettingsaccess

• Localcontrolaccess

• Remotesettingsaccess

• Remotecontrolaccess

Local access refers to users makingchanges using the front USB serial portandtheHMI.RemoteaccessreferstousersmakingchangesusingtherearRS485port

one24hourdayperiod.

Software & configurationTheEnerVista™Suiteisanindustry-leadingset of software programs that simplifieseveryaspectofusingtheMultilinDGCR.EnerVistaprovidesallthetoolstomonitorthestatusoftheprotectedasset,maintainthe controller and integrate informationmeasuredbytheMultilinDGCRintoSCADAortheDMSmonitoringsystems.Theabilitytoeasilyviewsequenceofeventsisanintegralpartofthesetupsoftware,aspostmortem event analysis is critical topropersystemoperation.

EnerVista launchpad

EnerVistaLaunchpadisapowerfulsoftwarepackagethatprovidesuserswithallofthesetupandsupporttoolsneededfor configuring and maintaining GE’sMultilinproducts.ThesetupsoftwarewithinLaunchpad allows configuring devices inreal-timebycommunicatingusing serial,Ethernetormodemconnections,orofflineby creating setting files to be sent todevicesatalatertime.Included in Launchpad is a documentarchiving and management systemthat ensures critical documentation isup-to-date and available when needed.Documentsmadeavailableinclude:

• Manuals

• Applicationnotes

• Guideformspecifications

• Brochures

• Wiringdiagrams

• FAQs

• Servicebulletins

Set up with EnerVista™ Software

EnerVista setup software can reduce device set-up and configuration time with the help of easy to use drag & drop configuration menu.

Page 8: Multilin Recloser Controller DGCR Recloser Controller Recloser Controller Comparison of time taken for different fault isolation and restoration options. Detects Fault – Dispatch

Multilin DGCRRecloser ControllerRe

clos

er C

ontr

olle

r

www.GEDigitalEnergy.com

orderingDGC R E l S S A * * E * * 1 * X X X Description

Application R RecloserControllerLanguage E English(Standard)PowerSupply L Low(20to60vdc)Communication S RS485ModbusRTU/DNP3.0(Standard)Options S StandardI/O A CurrentInputCard(1A/5A)

B B VoltageInputCard(60-300VAC)J J LEAInputCard(0-12V)

E E E E Two(2)10AForm-Arelaysandsix(6)20to60VDCdigitalInputs(2xIO_EStandard),Max3xIO_E

D D Four(4)10Aform-Crelays(Optional,Max1IO_D)G G 3RTD(Optional,Max1IO_G)

WirelessRadioOption X None1 MDSTransNet2 MDSiNET-II4 Prewiredforfutureradiowith12VDCPowerSupplyinstalled5 Prewiredforfutureradiowith24VDCPowerSupplyinstalled

ConnectionType 1 14PinAmphenolconnector2 24PinAmphenolconnectorforABBRecloserwithISDModule

120221-v1

• Downloadtheinstructionmanual

• ReviewapplicationsNotesandsupportdocuments

• BuytheMultilinDGCRRecloserControlleronline

• View/downloadtheMultilinDGCRbrochure

Visit www.GEMultilin.com/DGCR to:

technical SpecificationsPowER SuPPlynominal: 24to48VDCRange: 20to60VDCPower Consumption: 16Wtypical,25W

maximumAC CuRREnt (oPtion A)input type: CombinedIA/SAFrequency: 50or60HzAC VoltAGE: (oPtion B)input type: 60to300VACnominal frequency: 50or60HzAC VoltAGE: (oPtion J)input range: 0-12VACnominal frequency: 50or60HzDiGitAl inPutS: type: opto-isolatedinputsExternal switch: wetcontactMaximum input voltage:

36VAC

DiGitAl outPutS:operate time: 10msMinimum contact load: 10mAat5VDCContinuous current: 10AMake & carry for 0.2s: 30AperANSIC37.90

CoMMuniCAtionSERiAlRS485 port: Opto-coupledBaud rates: upto115kbpsResponse time: 1mstypicalParity: None,Odd,EvenMaximum distance: 1200m(4000ft)isolation: 2kVProtocol: ModbusRTU,DNP3.0uSBStandard specification: CompliantwithUSB2.0Connector: 115kbpstEStinG AnD CERtiFiCAtioniSo: Manufacturedunderan

ISO9001registeredprogramPHySiCAl SPECiFiCAtionSEnclosure Size: 600mm(W)x600mm(H)x

350mm(D);23.6”(W)x23.6”(H)x13.8”(D)

weight (Base): 28kg(excludingbatteries)

EnViRonMEntAmbient operating temperature:

-40°Cto+60°C[-40°Fto+140°F]

Ambient storage / shipping temperature:

–40°Cto+85°C[-40°Fto+185°F]

Humidity: upto90%non-condensingPollution degree: 2installation category: ClassIovervoltage category: ClassIIIiP rating: NEMA4/IP65

ProvidesingressprotectionratingofNEMA4(andequivalentIPrating–IP65)asdefinedbyNEMAIEC60529forpoletopinstallation.

CoMPAtiBlE witH: ABB: OVR-3,

G&w: ViperS

Cooper: Kyle®Form3,3A,4,4A,4C,4D,FXA,FXB

Othertraditional14PinReclosers