Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

Embed Size (px)

Citation preview

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    1/46

     

    o l um n F l o t a t i o n e l l  

    Operating and

    Maintenance Manual 

    Prepared By:

    Canadian Process Technologies Inc. 1636 West 75

    th Avenue

    Vancouver, B.C.

    Canada V6P 6G2Tel: +1 604 264 5610

    Fax: +1 604 264 5555

    Email: [email protected]

    URL: http://www.cpti.bc.ca

    May 2002

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    2/46

    CPT Inc. Column Cell   Operating & Maintenance Manual 

    The purpose of this manual is to provide an overall guide to column flotation technology along with

    detailed operating instructions for the CPT  Flotation Column and the SlamJet®  Gas Sparging

    System. This manual has been divided into seven sections as follows;

    1. Introduction

    2. Column Operation

    3. Instrumentation and Control

    4. System Maintenance

    5. Collection Zone Theory

    6. Froth Zone Theory

    7. Production Column Testwork

    Companion Manual

    SlamJet® Operating and Maintenance Manual

    including the following sections;

    1. Introduction

    2. Components

    3. Installation

    4. Operation

    5. Maintenance

    6. Control System

    7. Cracking Pressure Adjustment

    8. SlamJet® Repair Procedures

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    3/46

    CPT Inc. Column Cell   Operating & Maintenance Manual 

    TABLE OF CONTENTS

    1.0  INTRODUCTION...........................................................................................................1 

    1.1  DESCRIPTION OF A FLOTATION COLUMN...................................................................................... 1 

    1.2  SlamJet® DESCRIPTION............................................................ ERROR! BOOKMARK NOT DEFINED. 

    1.3  GLOSSARY OF COLUMN FLOTATION TERMINOLOGY ..................................................................... 4 

    1.3.1  Bias ................................................................................................................................... 4 1.3.2  Carrying Capacity ............................................................................................................. 5 1.3.3  Difference Wash ...............................................................................................................5 1.3.4  Displacement Wash.......................................................................................................... 5 1.3.5  Entrainment....................................................................................................................... 5 1.3.6  Flow Conventions ............................................................................................................. 5 1.3.7  Gas Holdup.......................................................................................................................5 1.3.8   Air Sparger........................................................................................................................ 6 1.3.9  Superficial Velocities.........................................................................................................6 

    1.4  TERMS ....................................................................................................................................... 6 

    1.4  W ASH W ATER ............................................................................................................................ 7 

    2.0  COLUMN OPERATION ................................................................................................8 

    2.1  INTRODUCTION........................................................................................................................... 8 

    2.2  COLUMN KEY ............................................................................................................................. 8 

    2.3  COLUMN START-UP .................................................................................................................... 8 2.3.1  Start-up Options................................................................................................................ 8 2.3.2  Set-up ............................................................................................................................... 9 2.3.3  Sparger Check.................................................................................................................. 9 2.3.4  Pressurise the Flowmeters ............................................................................................... 9 2.3.5   Air Line Checks............................................................................................................... 10 2.3.6  Sparger Air Pressurisation.............................................................................................. 10 

    2.3.7  Sparger Hose Connections............................................................................................. 10 2.3.8  Wash Water Check......................................................................................................... 10 2.3.9  Gas Holdup Calibration................................................................................................... 11 2.3.10  Empty Column Start-up .................................................................................................. 11 2.3.11  Check Launder Sprays ................................................................................................... 12 2.3.12  Starting of Slurry Flows................................................................................................... 12 2.3.13  Oil in Sparger Air Supply ................................................................................................ 13 

    2.4  COLUMN SHUTDOWN......................................................................................................... 13 2.4.1  Emergency Shutdown..................................................................................................... 13 2.4.2  Initial Procedure..............................................................................................................13 2.4.3  Final Procedure............................................................................................................... 13 2.4.4  Short Term Shutdown.....................................................................................................13 2.4.5  Long Term Shutdown .....................................................................................................13 2.4.6  Power Failure Shutdown................................................................................................. 14 

    2.5  COLUMN RE-START FOLLOWING SHUTDOWN ............................................................................ 14 2.5.1  Re-Pulping ......................................................................................................................14 2.5.2  Re-Starting Underflow ....................................................................................................14 

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    4/46

    CPT Inc. Column Cell   Operating & Maintenance Manual 

    2.6  OPERATING GUIDES ................................................................................................................. 15 

    2.6.1  Sparger Air...................................................................................................................... 15 2.6.2  Interface Level ................................................................................................................15 2.6.3  Wash Water .................................................................................................................... 16 2.6.4  Wash Water Bias ............................................................................................................ 16 2.6.5  Reagent Dosage............................................................................................................. 16 

    2.7  TROUBLESHOOTING .......................................................................................................... 17 2.7.1  Is Froth Purity Low?........................................................................................................ 17 2.7.2  Is Flotation Recovery Low? ............................................................................................17 

    3.0  INSTRUMENTATION AND CONTROL ......................................................................19 

    3.1  INTRODUCTION......................................................................................................................... 19 

    3.2  SPARGER PRESSURE ............................................................................................................... 19 

    3.3  SPARGER AIR FLOW................................................................................................................. 19 

    3.4  COLUMN INTERFACE LEVEL ...................................................................................................... 20 

    3.5  W ASH W ATER .......................................................................................................................... 20 

    4.0  SYSTEM MAINTENANCE ..........................................................................................21 

    4.1  INTRODUCTION......................................................................................................................... 21 

    4.2  COLUMN M AINTENANCE............................................................................................................ 21 

    4.3  SPARGER M AINTENANCE .......................................................................................................... 22 

    4.3.1  Orifice Wear .................................................................................................................... 22 4.3.2  Tip Blockage ................................................................................................................... 22 4.3.3  External Scaling ..............................................................................................................22 4.3.4  Sparger Removal............................................................................................................ 23 4.3.5  Poor Air Distribution........................................................................................................ 24 

    4.4  COMPRESSOR AND AIR LINES ................................................................................................... 24 

    5.0  COLLECTION ZONE THEORY.................................................................................. 25 

    5.1  INTRODUCTION......................................................................................................................... 25 

    5.2  RESIDENCE TIME...................................................................................................................... 25 

    5.2.1  Column Volume ..............................................................................................................26 5.2.2  Gas Holdup.....................................................................................................................26 

    5.3   AIR R ATE................................................................................................................................. 26 

    5.3.1  Maximum ........................................................................................................................26 5.3.2  Optimum ......................................................................................................................... 27 

    5.4  PARTICLE AND BUBBLE SIZE ...................................................................................................... 28 5.4.1  Gas Velocity....................................................................................................................28 5.4.2  Probability of Collection .................................................................................................. 28 5.4.3  Solids Carrying Capacity ................................................................................................ 29 

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    5/46

    CPT Inc. Column Cell   Operating & Maintenance Manual 

    6.0  FROTH ZONE THEORY............................................................................................. 30 

    6.1  INTRODUCTION......................................................................................................................... 30 

    6.2  FROTH CLEANING ..................................................................................................................... 30 

    6.3  G AS VELOCITY ......................................................................................................................... 31 

    6.4  FROTHER CONCENTRATION ...................................................................................................... 33 6.5  SUPERFICIAL BIAS R ATE .......................................................................................................... 33 

    6.6  SELECTIVITY ............................................................................................................................ 35 

    6.7  REFERENCES ........................................................................................................................... 35 

    7.0  PRODUCTION COLUMN TESTING........................................................................... 36 

    7.1  INTRODUCTION......................................................................................................................... 36 

    7.2   AIR R ATE................................................................................................................................. 36 

    7.3  W ASH W ATER BIAS.................................................................................................................. 37 

    7.4  OPERATING LEVEL ................................................................................................................... 37 

    7.5  BUBBLE SIZE ........................................................................................................................... 38 

    7.6  RESIDENCE TIME...................................................................................................................... 38 7.7  W ASH W ATER DISTRIBUTOR HEIGHT......................................................................................... 39 

    7.8  S AMPLING................................................................................................................................ 39 

    7.9  COLLECTION ZONE DENSITY ESTIMATION..................................................................................39 

    7.10  FROTH ZONE DENSITY ESTIMATION ....................................................................................... 40 

    7.11  COLUMN TEST D ATA SHEET - S AMPLE...................................................................................41 

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    6/46

     

    1.0 INTRODUCTION

    1.1 DESCRIPTION OF A FLOTATION COLUMN 

     A Flotation Column is a type of flotation machine that incorporates some design features to enhance

    metallurgical performance. Some of these features include:

    • Reduced surface area to cell volume ratio to promote froth stability

    • Froth washing system to minimise the entrainment of impurities

    • Quiescent flotation conditions to promote selectivity

    • Air sparging system to generate a supply of uniform bubbles

    1.2 UNIQUE DESIGN FEATURES OF THE CPT COLUMN 

    The CPT Column Flotation System incorporates a number of unique, advanced features that

    significantly enhance performance, such as . . .

    •  QuickLift adjustable wash water manifold that provides overhead or submerged (in-froth) wash

    water addition to allow adjustment of cleaning and froth density as required.

    •  Internal feed distribution with lateral dispersion plates to promote uniform, low pressure

    distribution of the incoming slurry.

    •  Circular internal launders to reduce the travel distance for loaded bubbles, thus enhancing

    recovery of coarse particles.

    •  Launder baffles extending slightly into the slurry, to provide froth stabilization and minimize lateral

    mixing during froth drainage.

    •  The patented SlamJet® Gas Sparging System providing air only or air + water injection through a

    single ceramic wear-protected nozzle, and featuring a self-adjusting mechanism that provides

    automatic fail closed operation on loss of air.

    •  Internal conical tank bottom to promote underflow removal and minimize the potential for sanding

    at the bottom of the column.

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    7/46

     

    Flotation Columns derive their name from the

    geometric shape of the vessel. Unlike conventional

    mechanically agitated flotation machines which tend

    to use relatively shallow rectangular tanks, column

    cells are tall vessels with heights typically ranging

    from 8 m to 15 m. The tank cross-section may be

    either round, square or rectangular depending on the

    specific application. For an equivalent volumetric

    capacity, the surface area of the column cell is much

    smaller than a conventional cell. This reduced area

    is beneficial for promoting froth stability and allowing

    very deep froth beds to be formed.

    Figure 1 - Typical Column Cell

     An important feature of flotation columns is the froth washing system. Froth washing provides an

    additional means for removing unwanted impurities from the flotation froth. Wash water, added at the

    top of the column, filters through the froth zone displacing process water and entrained particles

    trapped between the bubbles. In addition, froth wash water serves to stabilise the froth by separating

    bubbles into a “packed bed” of spherical, and therefore very strong, bubbles.

    Unlike conventional flotation machines, columns do not use mechanical agitation. The absence of

    intense agitation promotes selectivity and aids in the recovery of very fine particles. The basic flow

    streams in a column are illustrated in Figure 1. Feed slurry enters the column at one or more feed

    points located in the upper third of the column body and descends against a rising swarm of fine

    bubbles generated by the air sparging system. Particles which collide with, and attach to the bubbles,

    rise to the top of the column, eventually reaching the interface between the pulp (collection zone) and

    the froth (cleaning zone). The location of the interface, which can be adjusted by the operator, is held

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    8/46

     

    constant by means of an automatic control loop which regulates a valve on the column tailings line.

    Varying the location of the interface will increase or decrease the height of the froth zone.

    Flotation air is introduced into an external manifold and is injected through a series of air lances

    (sparger tubes) located near the bottom of the column. The air rate used in the column is selected

    according to the feed rate and concentrate production requirements and will determine, in part, the

    point on the grade / recovery curve at which the column operates.

    CPT’s patented SlamJet®  air sparging system, shown schematically in Figure 2, comprises an air

    manifold that surrounds the column cell and supplies air to a series of SlamJet® sparger tubes. The

    top of the manifold is fitted with connections for air as well as connections for a pressure gauge and a

    pressure transmitter. The side of the manifold is equipped with a series of couplings for connecting to

    the sparger tubes and is also fitted with one or more drains located at the bottom of the manifold.

    Inser t ion Port As sembly

    S l a m J e t

    ®

    S l a m J e t

    ®

     Advanced Gas

    Sparging SystemColumn BodyVessel Wall

      SLAMJET

    Gas

    Mani fo ld

     

    Figure 2 - SlamJet® System

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    9/46

     

     Air enters the manifold through the connections located on the top of the manifold and exits through

    the series of threaded couplings, (Figure 2) located on the side of the header. The manifold is sized

    to act as a buffer against turbulence and to provide sufficient reservoir capacity to ensure even air

    distribution to all spargers. The volume of the header also provides some opportunity for foreign

    material to settle out.

    The air then flows through the connecting hose to the sparger tube and is injected into the column

    through the single ceramic lined orifices of the SlamJet®s. The number and length of SlamJet

    ®s and

    the pattern of insertion is designed so as to ensure an even distribution of fine bubbles.

    The exact number and size of SlamJet®s included for each column is specifically designed to provide

    for a maximum superficial gas velocity of 2.5 cm/s. Each SlamJet®  is attached to the header by a

    single flexible hose fitted with a quick-disconnect swing coupling to allow for easy removal for

    inspection or maintenance.

    The sparger elements have been designed to allow easy removal from the column. A full port ball

    valve and liquid-tight seal assembly comprises the sparger insertion port, and prevents process

    slurries from exiting the column when the sparger is removed. Each SlamJet® is also fitted with a self-

    adjusting mechanism that actuates a nozzle-mounted needle valve to control air flow and also allows

    the SlamJet® to fail closed on loss of air, thus eliminating any possibility of slurry back-flow into the air

    delivery system..

     A quick-disconnect coupling is used to isolate the sparger air flow during removal.

    For the first few months of operation, SlamJet® nozzles should be checked monthly for fouling and

    wear. Worn nozzles can be quickly and easily replaced while the column is in full operation. The

    inspection frequency can then be adjusted on an experience basis.

    The SlamJet® Model SLJ-75 has a larger (7.62 mm Ø) bore and incorporates a small flow of water to

    promote generation of small bubbles. The sparger water flow, about 8 L/min, is administered by

    means of an additional distribution manifold located just below the main air manifold.

    1.3 GLOSSARY OF COLUMN FLOTATION TERMINOLOGY 

    The study of column flotation systems has resulted in new ways of examining flotation and somespecific terminology has evolved to describe the process. Some of the common terms are:

    1.3.1 Bias

    The term Bias (Superficial bias - Jb) is used to describe the flow of water (magnitude and direction)

    through the froth zone into the collection zone. A positive bias is a net downward flow. It is often

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    10/46

     

    estimated as the difference between the volumetric flow of the column underflow slurry and the

    volumetric flow of the feed slurry rates divided by the cross-sectional area of the column.

    1.3.2 Carry ing Capacity

    Three different carrying capacities have evolved;

    Ca - The maximum overflow mass that a column can produce. This is commonly quoted in terms

    of tonnes of solids per hour per square meter of cross sectional column area - t/h•m2. A

    theoretical value can be estimated from Ca = 0.03 D80 ρs.

    Cg - The maximum solids floated per unit of air, commonly expressed in units of kilograms of

    concentrate solids per cubic meter of air - kg/m3.

    Cl - The maximum mass of pulp that can be transported over the lip of the column, normally

    expressed as tonnes per hour per meter of lip length - t/h•m. Note that lip length must include

    the length of all internal launders. This figure is critical in the design of large columns.

    1.3.3 Difference Wash

    The volume of water in the feed subtracted from the volume of water in the underflow is one

    difference wash. Any wash water added in excess of this amount is assumed to report to the

    overflow.

    1.3.4 Disp lacement Wash

    Displacement wash is the ratio of wash water to overflow water. A displacement wash of 1.0 means

    that all the wash water reports to the overflow, while a displacement wash of 2.0 indicates an equal

    amount of the water flow in the bias and overflow streams (assuming no feed water in the overflow).

    1.3.5 Entrainment

    Non-selective flotation caused by particles riding in a bubble's wake thereby passing into the column

    overflow. Entrainment is common in mechanical cells, particularly with small particles, but is virtually

    eliminated in column flotation by the use of wash water.

    1.3.6 Flow Conventions

    Downward flow of slurry or liquid, and upward flow of air are defined as positive.

    1.3.7 Gas Holdup

    There are three types of holdup in a column reflecting it's three phase nature - solids (mineral), liquid

    (water) and gas (air).

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    11/46

     

    Gas Holdup (f g, or εg) is the fractional volume of gas. A typical value of gas holdup is 0.15 (or 15%)

    but this value may range between 0.05 and 0.25 (5% to 25%).

    Solids Holdup (f s, or εs) is the solids fractional volume.

    Liquid Holdup (f l, or εl) is the fractional volume of liquid.

    1.3.8 Air Sparger

     Any device used to create the bubbles in a flotation column. The common types are the CPT

    SparJet® System, the CPT SlamJet

    ® System and various constructions of porous media.

    1.3.9 Superfic ial Velocities

    Superficial velocity is the volumetric flow rate of the material in question (slurry, water or air) dividedby the cross sectional area of the column, normally expressed in cm/s. This normalised variable

    allows evaluation of column performance characteristics independent of column diameter.

    1.4 TERMS 

    (Units may vary according to local use)

    Cx  Carrying capacity where x = :

    a = theoretical bubble loading (t/h•m2)

    g = loading per gas unit (kg/m3)

    l = removal capacity per unit lip length (t/h•m)

    x  Holdup (all either fractional or %) where x = :

    g = gas

    l = liquid

    s = solids

    Jx  Superficial Velocity where x = :

    b = bias

    o = overflow

    f = feed

    g = gas

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    12/46

     

    sl = slurry

    u = underflow

    w = wash water

    spa = sparger air

    Qx  Mass flow rate, with x values the same as for superficial velocities

    Vx  Volumetric flow rate

    x  Density of x = :

    col = bulk, collection zone

    fro = bulk, froth zone

    s = average concentrate solids

    sl = column slurry estimated by using tails density

    u = underflow density

    (l) = liquids fraction

    (s) = solids fraction

    Hc  = height of column (m)

    Hf   = height of interface (m)

    Hspa  = height of spargers (m)

    P = pressure (kPa)

    L = distance from column lip to pressure transducer (m)

    1.4 W ASH W ATER 

    Wash water (Jw) is the water added to clean the froth zone. In positive bias operation this J w forms

    both the overflow liquid (Jo) and the bias (Jb).

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    13/46

    CPT Column  Column Operation Page 8 

    2.0 COLUMN OPERATION 

    2.1 INTRODUCTION 

    This section covers column start-up and shut-down, and gives estimates of column parameters and

    guidelines for operation. It is intended to familiarise operators with column operation as a reference

    and as a start to determining the column's operational characteristics. The values it contains are

    estimates which must be confirmed in plant practice.

    2.2 COLUMN KEY 

    (Start-up and Shut-Down)

     A key is a written flow chart of questions and directions. These keys are meant to serve only as a

    guide. Not all steps are needed all of the time. Warnings and notes draw attention to important

    features. Advance in order unless instructed otherwise. Each key describes steps performed on one

    column.

    End indicates completion of instructions. This may be followed for each column.

    2.3 COLUMN START-UP 

    2.3.1 Start-up Options

    First start-up, go to 2.3.2 

    Normal operation, column empty, go to 2.3.10; column full, go to 2.3.11

    CONTROL WARNING:

    For mineral columns operating at higher densities (20% to 30% solids or higher) a minimum flow must

    be set on the underflow valve to prevent sanding. This is done by setting a minimum position on the

    underflow valve. Whenever possible this minimum should be maintained.

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    14/46

    CPT Column  Column Operation Page 9 

    2.3.2 Check All Auto Valves

    The automatic valves should all be “stroked” using the control system.

    Ensure that all air and water lines are de-pressurized and the column is empty.

    Ensure that the instrument air supply to all automatic valves (for valve actuation) is fully pressurized.

    Check all auto valves for air leaks and correct if necessary.

     Apply power to all automatic valve controllers and ensure that all controllers are set for MANUAL

    operation.

    One at a time, manually change the controller valve position set-points from fully closed to fully open.

    Visually confirm that all valves move in the desired direction and to the desired limits.

    Change the controller set-points back to fully closed and again verify valve movement.

    Close all column drain valves and water lance.1

     Activate the level control system.

    2.3.3 Sparger Check

    Check that all SlamJet®  spargers are installed in the correct location as per Sparger General

     Arrangement drawings:

    The SlamJet® tubes should be pushed fully into the insertion port assembly.

    Note that the self-adjusting mechanism will ensure that all SlamJet®s are closed when not pressurised.

    Turn all the individual sparger isolation header valves OFF (see Fig. 2) to isolate the header from the

    spargers.

    2.3.4 Pressurise the Flowmeters

    Manual shutoff valves at the battery limits on the air and wash water supply must be confirmed

    CLOSED.

    Leave all control valves CLOSED.

    SLOWLY OPEN the air supply manual control valve. Check for leaks. Do the same for the wash water

    and sparger water supply control valves.

    1  The water lances are located opposite the underflow exit pipe and can be used to unplug the

    column if either the underflow line or bottom of the column sand out.

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    15/46

    CPT Column  Column Operation Page 10 

    2.3.5 Air Line Checks

    The air pressure should be between 500 kPa (70 psi) and 600 kPa (90 psi).

    Make sure that the air filter is clear.

    Check for air line leaks and correct if necessary.

    2.3.6 Sparger Air Pressurisation

    Open the air manifold drain valves, then gently open the manual air flow control valve to approximately

    10% of full flow.

    Slowly increase to full flow to purge the air system.

    Purge the piping at full flow for several minutes, then check for oil entrained in the air.

    If oil persists, go to 2.3.13.

    NOTE: 

    It is important that as little oil as possible is present in the airlines. Although small amounts of oil will not

    adversely affect operation of the SlamJet®s, the presence of oil may interfere with metallurgical

    performance of the column by causing non-selective flotation. An oil filter may be required.

    Check that the air flowmeter indicates a flow. Record this flow.

    Close the drain valve, then close the air flow control valve to ensure stoppage of flow.

    2.3.7 Sparger Hose Connections

    Close all sparger isolation valves. (done in 2.3.3)

    Pressurise the air manifold to approximately 500 kPa (70 psi) and check for leaks.

    One at a time, slowly open each SlamJet®  isolation valve to check sparger hose connections and to

    verify that the SlamJet® auto-close mechanism opens and allows air flow to commence.

    Correct any leaks.

    Close all air manifold valves.

    2.3.8 Wash Water Check

    Purge the wash water line so that no tramp material reaches the wash water distributor.

    NOTE: 

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    16/46

    CPT Column  Column Operation Page 11 

     Air, sparger water and wash water supply lines should be flushed and verified clean PRIOR to

    installation of flowmeters and control valves.

    Make sure that the manual wash water flow control valve is closed, then pressurize the wash water

    piping system.

    Slowly open the wash water isolation valve. Check for leaks.

    Open the wash water flow control valve to ensure it is operative with water flow.

    Clear any blocked distributor holes and check for even wash water distribution at low flow.

    Close the control valve.

    Check for tramp material in the distributor.

    2.3.9 Gas Holdup Calibration

    Check the holdup reading with the column filled with water (εg=0).2

    Set the air rate to approximately 10% of full flow and open all ½" header sparger valves except the drain.

    2.3.10 Empty Column Start-up

    If the column is empty, fill it with water using the wash water distributor, the feed pump or a simple water

    hose.

    CALIBRATION NOTE: 

    From time to time, confirm the actual level with a hand held float probe. This simple confirmation should

    be conducted on a regular basis, particularly if the slurry or pulp density changes.

    Check the interface calibration by filling the column with water. The underflow pinch valve should open

    to maintain column level.

    Check the gas holdup reading with the column filled with water - ie., εg = 0. 

    2  Pressure transducer readings at εg = 0 should be equal to ρgh where ρ = 1 (water), g = 9.81,

    h = distance from transducer to water level (m).

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    17/46

    CPT Column  Column Operation Page 12 

    NOTE:

    Due to density variations within the froth zone, locating the interface may require detection of the

    point at which a distinct difference in the buoyancy force is felt.

    WARNING:

    To avoid unnecessary start-up problems it is recommended that the column be filled with water prior to

    feeding pulp. The column can be shut down by stopping the feed, air and wash water. The column may

    sand out, but can be re-started using the repulping lances (see 2.4.4 & 2.4.5). A recycle line (not

    installed) between the underflow and feed would allow the column to be filled with slurry and continue to

    operate during periods when no feed is available.

    2.3.11 Check Launder Sprays

    Check for proper water flow from the launder spray system, if installed. Leave the launder spray system

    OFF if not required.

    2.3.12 Starting of Slurry Flows

    Make sure that all valves are positioned to send flow through the desired pumps and pipes.

     Adjust the sparger air and water to normal operational levels.

    Set desired wash water flow.

    Open the underflow isolation valve.

    Start the column feed pump. End

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    18/46

    CPT Column  Column Operation Page 13 

    OPERATING NOTE: 

    The column should now be running. It will take some time before enough solids accumulate in the

    column to permit formation of a stable froth.

    2.3.13 Oil in Sparger Air Supply

    Close the header drain and clean the air line filters.

    Repeat Step 2.3.6. If oil continues to flow, shut off the air supply and check for the cause of the oil.

    2.4 COLUMN SHUTDOWN

    2.4.1 Emergency Shutdown

    If the shut down is caused by a power failure go to 2.4.6.

    2.4.2 Initial Procedure

    When the feed supply is discontinued, adjust the wash water so that the underflow pinch valve can

    maintain the interface level without sanding out lines. This may involve increasing the wash water flow.

    2.4.3 Final Procedure

    The column will continue to float the contained material and any material being sent to it from existing

    recycle flows. When this flotation ceases, assess the type of shut down expected. If the shut down is to

    be for longer than one to two hours go to 2.4.5.

    2.4.4 Short Term Shutdown

    When the column is to be shut down for a short period of time it need not be emptied. Sparger air flow

    can be shut off and the SlamJet®s will automatically fail closed to prevent backflow of slurry. Wash water

    flow can be shut off, and the underflow isolation valve can be closed (see Operations Note below).When feed is reintroduced, simply open the underflow isolation valve, and reset the wash water rate and

    sparger settings to their previous levels. End

    2.4.5 Long Term Shutdown

    When the column is not to be used for extended periods it can be drained. Reduce the wash water

    addition rate and allow the column to slowly drain by opening the underflow valve manually. When the

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    19/46

    CPT Column  Column Operation Page 14 

    interface level is below the spargers, the wash water and air may be shut off. If an underflow pump is

    present it may be shut off. End

    OPERATING NOTE: 

    In a shutdown situation, the column underflow line between the underflow isolation valve and the flow

    control pinch valve should be drained to prevent sanding.

    2.4.6 Power Failure Shutdown

    Turn off all sparger header isolation valves. Note that all SlamJet®s should automatically fail closed on

    loss of air. Immediately shut off all streams in and out of the column. This includes pump gland water

    and sparger air. The underflow valve may continue to bypass material due to the minimum setpoint (if

    used), so the underflow isolation valve must also be closed. The underflow line downstream of the

    isolation valve should be drained to aid start up. When power is restored, return the sparger air flows,

    then the underflow followed by the remaining streams, to normal operating levels. End

    2.5 COLUMN RE-START FOLLOWING SHUTDOWN 

    If the column is shutdown during operation, it is possible that the column will sand out. If the column

    is operating at higher density and there is a probability of sanding, the following re-start procedure

    should be observed;

    2.5.1 Re-Pulping

    To repulp the column, connect water lines to the repulp lances and apply a water flow. After a short

    period of time (15 minutes), the air should be re-started. The combination of lance water and sparger

    air will serve to repulp the sanded contents at the bottom of the column.

    See Warning Below – Possibility of SEVERE Damage to Spargers

    2.5.2 Re-Starting Underflow

     After the repulp lances and sparger air flows have been running for a period of time (15 to 30

    minutes), the underflow isolation valve should be opened SLOWLY to initiate flow.

    WARNING: 

    If, during the shutdown period, material settles to a level  ABOVE  the spargers, it is IMPERATIVE  to

    thoroughly repulp the sanded contents and to open the underflow valve SLOWLY. Failure to observe

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    20/46

    CPT Column  Column Operation Page 15 

    this procedure can cause a large “slug” of sanded material to move suddenly downward, resulting in

    SEVERE damage to the spargers by bending them down with the moving slug of material.

    2.6 OPERATING GUIDES 

    This section suggests approximate settings for some of the more common variables which should be

    optimised during operation. Also given here are the general effects that changing one variable will

    have on a column at steady state. Compensation for variations can be made for gradual changes, but

    quick swings in flow rates or pulses of high or low grade material may cause poorer performance

    than would otherwise be expected. Therefore the feed volumetric slurry rate and total flux of floatable

    material should be kept as constant as possible. Make sure that all the control loops are tuned to

    prevent unwanted oscillations.

    2.6.1 Sparger Air

    The column air rate is the most commonly adjusted control variable. The response to changes in air rate

    will be very rapid. The normal operating levels for air addition rates for column cells range from 0.5 cm/s

    to about 2.0 cm/s depending on the application. The optimum rate will vary depending on bubble size,

    bubble loading and slurry velocities and must be determined during the commissioning period.

    Increasing the air flow will generally have the following effects:

    •  reduce the grade of the froth product

    •  increase the recovery of solids to the column overflow

    •  reduce the percent solids in the overflow

    These effects are only valid within a specific region of flow. As the air rate is increased, the bubble size

    will eventually change producing a different flow regime that may be detrimental to performance. Some

    indications of excessive air rates are the loss of a well defined interface or excessive turbulence in the

    froth zone. Increases in air will lead to increases in overflow production and will require a corresponding

    increase in wash water rates to maintain a positive bias. Air volumetric flows below 0.5 cm/s may cause

    froth bed collapse. In this case the froth zone depth will have to be decreased. (i.e. pulp level raised).

    2.6.2 Interface Level

    The interface level between the froth and pulp zones can influence both the concentrate grade and

    mineral recovery to overflow. A deeper froth will increase the purity of the froth by providing more time

    for the entrained impurities to drain from the froth. It will also, however, result in a decrease in the

    recovery of the minerals being floated due to an increase in "drop-back".

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    21/46

    CPT Column  Column Operation Page 16 

    The column level should normally be controlled in a range from 500 mm to 1,000 mm but can vary

    depending on the stability of the froth. Little benefit is expected at depths greater than 1,500 mm. Much

    shallower froths are possible and may be desirable if the column is being used in a reverse flotation

    application or as a scavenger. Tests can be performed to predict performance at various interface

    levels.

    2.6.3 Wash Water

    Wash water is increased or decreased to control the bias (see section 2.6.4).

    2.6.4 Wash Water Bias

    The non-selective entrainment of hydrophilic minerals can be reduced by preventing feed water from

    entering the overflow. This is done by operating with a positive bias (+Jb). Jb should be operated within

    the range of 0.0 to 0.3 cm/s. A Jb of 0.05 cm/s is suggested at startup.

    Increased bias flow will:

    •  increase the displacement wash and underflow/feed ratio3 

    •  increase the grade of the froth

    •  decrease the recovery of the minerals being floated.

    These effects do not continue indefinitely with increased amounts of bias. Eventually channelling of the

    water and breaking of the froth occurs that negates all the benefits of extra wash water. To ensure a

    positive bias, maintain an underflow liquid flow greater than the feed liquid flow by altering the wash

    water rate.

    2.6.5 Reagent Dosage

    In order for a column to function properly, it is imperative that the chemical conditions of the feed are

    correct prior to feeding the column. If the process is sensitive to fluctuations in pH, measurements

    should be made at the column underflow to account for dilution effects caused by wash water addition.

    Increasing the frother concentration will:

    •  reduce the bias rate

    •  reduce the percent solids in the overflow.

    •  increase the gas holdup of the collection zone

    •  reduce froth zone gas holdup

    3  Displacement wash, differential wash, bias ratio and superficial bias rates are all different ways of

    describing the liquid flux through the column froth zone. 

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    22/46

    CPT Column  Column Operation Page 17 

    •  reduce the maximum air rate

    •  reduce bubble size

    Frother acts to stabilise the froth zone. Increased frother produces smaller bubbles which may or may

    not improve collection of particles.

    2.7 TROUBLESHOOTING

    This section gives possible causes of poor performance and suggests improvements. Two conditions

    are dealt with: poor froth grades and poor mineral recovery. Each is then subdivided into two categories:

    problems originating with the column and those that originate in the rest of the circuit. Possible solutions

    are given in order from most to least likely.

    2.7.1 Is Froth Purity Low?

    2.7.1.1 Column Problems

    For direct flotation applications, the column froth product is the concentrate and hence the objective is to

    minimise the entrainment of impurities. For reverse flotation applications, the overflow is considered

    tailings and therefore entrainment can result in recovery losses. High air rates may cause an increase in

    material entrained in the overflow by increasing the amount of feed water that is carried by the bubbles.

    To counteract this try, one at a time:

    Reduce the air rate.

    If the wash water bias rate Jb is less than 0.25 cm/s, increase the wash water flow QW

    The interface level may be too high which reduces the froth zone cleaning action. Increase the froth

    depth.

    2.7.1.2 Circuit Problems

    High reagent dosages or incorrect feed pH could cause excessive amounts of feed water to report to the

    overflow causing increased entrainment and increased wash water rates. Check reagent addition rates.

    Grind size may be too large creating middling particles that are recovered to the froth. Check the size

    distribution of the feed, concentrate and tailings streams. Analyse the various size fractions to determine

    if there is a possible liberation problem.

    2.7.2 Is Flotation Recovery Low?

    2.7.2.1 Column Problems

    Low recoveries of the minerals being floated are quite often caused by low air rates. Increase the air

    rate, but watch for loss of interface, and approach air rates greater than 2.0 cm/s with caution. If the

    column is operating with a deep froth (greater than 1,000 mm) try reducing the froth depth.

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    23/46

    CPT Column  Column Operation Page 18 

    High air rates may cause a turbulent flow in the column which is not conducive to good flotation

    separation. The interface may also be lost. This may appear as volcanoes or geysers in the froth. (The

    volcanoes can also be caused by very high froth density). Reduce the air rate.

    Excessive wash water may cause froth breakage which reduces the production capacity. This will be

    seen as an unstable froth. Reduce the wash water rate.

    Poor air distribution causes eddies within the collection and froth zones that decrease the effective

    column residence time. This may be seen as an unstable froth. Ensure that all spargers are clear, and

    accelerate the sparger tube inspection and cleaning schedule.

    2.7.2.2 Circuit Problems

    Insufficient collector addition or incorrect pH may contribute to poor flotation performance. Check

    reagent addition rates and adjust as required. If frother is being used, low frother dosages may cause

    froth instability and can result in an increase in bubble size. Increase frother dosage or increase sparger

    air flow rate.

    Grind size may be too large creating middling particles that are difficult to float. This can be determined

    by microscopic examination for locked particles.

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    24/46

    CPT Column  Instrumentation & Control Page 19 

    3.0 INSTRUMENTATION AND CONTROL

    3.1 INTRODUCTION 

    Columns can be instrumented with up to three automatic control loops: Column Interface Level,

    Sparger Air Flow and Wash Water Flow. In many applications the wash water addition rate is

    manually controlled and only two automatic control loops are required. For small diameter columns, it

    is common to control both the air and water with manual control valves, and to employ automatic

    control only for column level.

    The description of the operation of the control loops should be read in conjunction with the Process

    and Instrumentation Diagram (P&ID). This drawing lists the normal, maximum and minimum flows for

    each process stream.

    3.2 SPARGER PRESSURE 

    The pressure in the sparger manifold must be maintained between approximately 400 kPa and 700

    kPa. Sparger manifold pressure is a function of

    •  SlamJet® Control Setting (factory pre-set cracking pressure)

    •  Sparger Air Flow Rate

    •  Battery Limit Air Supply Pressure

     An initial operating pressure of 550 kPa is recommended. During the course of commissioning,

    different operating pressures should be tested to determine the optimum value for each application.

    The maximum pressure of the system is the point at which air flow becomes limited which is a

    function of the supply pressures.

    For systems requiring remote sensing of the header pressure, a pressure transmitter can be mounted

    on the gas header.

    3.3 SPARGER AIR FLOW 

     Air flow control is the most critical parameter for maintaining proper column operation. The air flow

    rate is measured by a flowmeter (rotameter, orifice plate or vortex flowmeter) and is controlled

    automatically with a ball valve.

    The recovery of solids to the column overflow is dependant on the air rate. Air flows corresponding to

    a superficial gas rate below 0.5 cm/s are not recommended but can be run with appropriate care.

    The estimated maximum air rate should correspond to a superficial gas rate of approximately 2.0 to

    2.5 cm/s. This rate could be lower or higher depending on column conditions. The air flow rate should

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    25/46

    CPT Column  Instrumentation & Control Page 20 

    be changed in a stepwise fashion using small set-point changes in order to minimise process upsets.

     A maximum change of 10% of total flow at a time is recommended.

    The maximum and minimum air flow rates are only estimates. The exact values should be

    determined under operating conditions. Below the minimum gas rate the froth becomes unstable.

     Above the maximum gas rate recovery of solids to the overflow will decrease as bubble coalescence

    begins to occur. Both of these values will vary with changes in interface level, reagent dosages, feed

    tonnages and grades, and percent solids.

    The amount of air needed to meet grade / recovery requirements depends on the particle size and

    amount of material to be floated but should fall within the previously mentioned ranges.

    3.4 COLUMN INTERFACE LEVEL 

    The position of the froth / pulp interface is measured using either a ball float and ultrasonic detector or

    single or dual pressure transducers. Both systems deliver a 4 to 20 mA signal proportional to the

    position of the froth / pulp interface. The interface level is controlled by a PID Controller (or DCS or

    PLC) which adjusts an automatic pinch valve on the column underflow line.

    Slight variations in column level are not critical to performance as long as the level remains within a

    certain range. Variations of ± 100 mm are acceptable over a time span of 10 minutes as long as the

    variations are gentle. Column performance will improve with more stable control especially when

    operating with a bias close to zero.

    It is suggested that the level be operated at depths greater than 300 mm and less than 1,500 mm

    with normal operation at 750 mm.

    3.5 W ASH W ATER 

    The wash water flow is measured by a flowmeter (rotameter, orifice plate or magnetic flowmeter) and

    is controlled either manually or automatically with a flow control valve. The expected range of flow will

    be approximately 0.15 to 0.40 cm/s. Slow variations in flow are acceptable but better performance will

    be achieved with smooth control. The wash water rates quoted are estimates and should be adjusted

    to produce the proper bias rate. Actual rates should be determined through column tests during

    operation as they will depend on the feed rate, feed grade and expected mass recovery to the column

    overflow. The minimum bias occurs when no wash water is added to the column. As bias is

    increased, the purity of the froth will increase due to the displacement of entrained particles. An initial

    bias setpoint of approximately 0.1 cm/s is suggested.

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    26/46

    CPT Column  System Maintenance Page 21 

    4.0 SYSTEM MAINTENANCE

    4.1 INTRODUCTION 

     All maintenance should be done on a scheduled basis. Operators should regularly inspect all parts of

    the circuit. Operational and performance trends from the column should be noted for indications of

    instrument problems including faulty calibration and tuning.

    4.2 COLUMN M AINTENANCE 

    The overflow launders, both external and internal, should be kept clear of scale and accumulated

    solids. This will ensure that the overflow of froth is not hindered. Scale and/or solids can have a

    tendency to build up on the lip of the launder and on the column walls at a point just below the lip.

    This material should be routinely scraped or washed off by the operators.

    The wash water system must be maintained so that the flow of water is evenly dispersed within the

    froth. Periodically inspect the distributor for build-up of solids or for blocked holes. The distributor

    holes must remain clear.

    MAINTENANCE NOTE: 

    Pinch valve sleeves can wear out quickly if they are required to operate at low opening percentages

    or with high pressure drops across the valve. Careful attention must be paid to the wear of this valve

    as indicated by the valve percent opening Vs flow rate relationship and regular inspections.

    If pressure transducers are installed on the column, regular inspections should be made to ensure

    that they are functioning properly. The calibration should be checked from time to time by noting the

    readings when the column is full of water. Any scaling should be carefully removed according to

    manufacture's maintenance procedures.

    Level control systems that use a ball float should be cleaned regularly to prevent a build-up of solids

    on the float or target.

    Level calibration can be checked by using a manual float. At times the density of the froth is high

    enough to “float” the ball float but little resistance will be encountered when the ball float is pushed

    further down. This condition is commonly called a double interface: the true interface will be the lower

    one.

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    27/46

    CPT Column  System Maintenance Page 22 

    4.3 SPARGER M AINTENANCE 

    The spargers have been designed for reliability and durability, but some maintenance is required.

    Regular inspections should be made both to maintain performance and to prevent a build-up of scale

    on the tube surfaces.

    4.3.1 Orif ice Wear

    No rapid deterioration is expected at the tip orifice, but they are expected to enlarge slowly over a

    number of years. However, in the unlikely event that the sparger orifices become enlarged they must

    be replaced to avoid a decrease in the metallurgical performance.

    Care should be taken to limit the SlamJet®’s exposure to highly acid environments. Hydrochloric acid will

    corrode both the stainless steel tubes and the adhesive compound which holds the ceramic inserts in

    place.

    WARNING: 

    Cleaning spargers with a strong acidic solution could result in corrosion to the stainless steel tubes as

    well as damage to the retaining compound used to adhere ceramic inserts in the sparger nozzles.

    4.3.2 Tip Blockage

     A maintenance program should be devised based on inspections for blocked nozzle orifices and poor air

    distribution. Each sparger tube should be pulled on a regular basis. The interval of inspections depends

    on the scale forming tendency of the slurry and sparger water. Note that the SlamJet® orifice diameter is

    7.62 mm, and blockage is not expected to be a problem.

    Initially CPT recommends that spargers be checked monthly. This interval can then be extended if no

    plugging or serious scale formation problems are encountered.

    In the case of blocked orifices the blockage should be removed. If tip blockage becomes a recurring

    problem, consideration should be given to the installation of additional filters for the air lines.

    4.3.3 External Scaling

    In the presence of highly scale-forming slurries, the external surfaces of sparger tubes will become

    scaled, making them difficult to remove for inspection. In severe cases, the external scale can cause

    damage to the rubber seal in the liquid-tight insertion port seal assembly.

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    28/46

    CPT Column  System Maintenance Page 23 

    If scale formation is a problem then different spargers should be pulled on a rotating basis, as often as

    required, and the external surfaces cleaned with an emery cloth. If scaling is a persistent problem,

    please contact CPT.

    4.3.4 Sparger Removal

    Close the isolation valve at the manifold. The SlamJet® will then automatically fail closed.

    Remove the air hose by disconnecting the coupling.

    Slightly loosen the compression fitting so that the sparger can be slowly withdrawn from the column.

    WARNING: 

    Slurry will leak from the compression fitting if it is loosened too much.

    Each sparger tube has been marked with a groove located approximately 300 mm from the end. This

    groove provides a visual indication of when the end of the sparger tube has cleared the insertion port

    ball valve.

    When the groove appears, close the ball valve. If this is not done before fully removing the sparger, a

    stream of slurry will emerge from the column at high velocity through the sparger nipple.

     Assess the condition of the sparger nozzle by direct visual observation and clear any blockages. If the

    blockages are serious, remove the plug at the end of the tube to allow loosened material to flow out ofthe sparger.

    Removal of exterior scaling of the sparger tube will ensure that the tubes are always easy to remove.

    To re-install the SlamJet®, insert the tube until the end comes into contact with the closed ball valve in

    the insertion port. Tighten the compression fitting enough to stop leaks. Open the ball valve and push

    the sparger tube into the column, then tighten the compression fitting by hand.

    WARNING: 

    If SlamJet®s are pressurised while outside the column, the resulting high velocity air jet is extremely

    hazardous. As a precautionary measure, always wear gloves when handling spargers that are

    operating outside the column and DO NOT direct the air jet at personnel.

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    29/46

    CPT Column  System Maintenance Page 24 

    4.3.5 Poor Air Distribution

    Uneven swelling of froth in the column may be a sign of poor air distribution caused by one or more

    partially or fully blocked SlamJet®s.

    This may be caused by insufficient air pressure in the system, blocked hoses which prevent air entry

    into the sparger or one or more spargers being turned off.

    In the unlikely event that the sparger holes become enlarged, the sparger nozzles must be replaced to

    avoid a loss in metallurgical performance.

    4.4 COMPRESSOR AND AIR LINES 

    Oil from the compressor should not be allowed to enter the column. This oil may cause flotation

    problems, such as a excessive frothing and poor selectivity.

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    30/46

    CPT Column  Collection Zone Theory Page 25 

    5.0 COLLECTION ZONE THEORY

    5.1 INTRODUCTION 

    The collection zone of the column is located between the froth interface (Hf ) and the point of maximum

    descent of the bubbles below the spargers (Hspa). In this zone floatable material from the feed stream

    and material returned after rejection from the froth zone (dropback) are collected by rising bubbles.

    Recovery of material within the collection zone is dependent on the zone's residence time and mixing

    characteristics.

    5.2 RESIDENCE TIME 

    Collection zone residence time, as mentioned in the testwork section, is estimated for round columns by

    the following equation;

    sl

    c2

    c spa f   col sl

    tail

    ( )=15 d   ( H  - H  - H  )(1 - / )

    V τ 

    π   ρ ρ min  

    Where

    τ sl  = collection zone residence time (min)

    dc  = column diameter (m)

    Hc  = total column height (m)

    Hspa  = sparger level (m)

    Hf   = interface level (m)

    ρcol  = collection zone density (t/m3)

    ρsl  = concentrate slurry density (t/m3)

    Vtail  = tailing (underflow) volumetric flowrate (m3/hr)

    The equation has three parts: column volume, gas holdup and slurry velocity.

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    31/46

    CPT Column  Collection Zone Theory Page 26 

       G  a  s   H  o   l   d  u

      p  -   E

      g   (   %   )

    Superficial Gas Velocity - Jg (cm/s)

    Figure 3 - Gas Holdup Vs Gas Velocityfrom Dobby & Finch - 1988

    10

    30

    20

    Frother Concentration (ppm)15

    10

    5

    0

    1 2 3 4

     

    Figure 4 - Gas Holdup Vs Slurry Velocityfrom Dobby & Finch - 1988

       G  a  s   H  o   l   d  u

      p  -   E  g

       (   %   )

    Superficial Slurry Velocity - Jsl (cm/s)

    0.5 1.0 1.5

    10

    30

    20

    Liquid Velocity JL ( cm/s)

    0.38

    1.00

    1.26

     

    5.2.1 Column Volume

    The volume of the collection zone is essentially fixed. Hf , the interface level, is the only variable which

    can be easily changed to increase collection zone volume but the impact on residence time will be

    small. The only significant way to influence residence time is to vary the column feed rate.

    5.2.2 Gas Holdup

    Gas holdup is the volume fraction of gas in the column. It is a parameter dependant on other variables

    such as volumetric air rate, size of the bubbles, slurry density, solids bubble loading, and slurry velocity.

    Increased gas holdup reduces collection zone residence time.

    Gas holdup may increase due to three factors:

     An increase in gas flow will increase the number of bubbles present in the column as more bubbles are

    being generated in any time period.

     A bubble size decrease caused by sparger operation or frother dosage will cause each bubble to rise

    more slowly in the slurry, again causing an increased amount of air in the column.

     An increase in downward slurry velocity will decrease bubble rise velocity relative to the column, also

    resulting in an increase in the quantity of air “held up” in the column.

    5.3 AIR R ATE 

    5.3.1 Maximum

    The maximum air rate which a column is capable of handling is determined by three limits: (i) the

    superficial feed rate must be less than the bubble rise velocity, (ii) the collection zone density must be

    greater than the froth zone density and (iii) bubble coalescence must not form air slugs.

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    32/46

    CPT Column  Collection Zone Theory Page 27 

       S  u  p  e  r   f   i  c   i  a   l   G  a  s   V  e   l  o  c

       i   t  y  -   J

      g   (  c  m   /  s   )

    Superficial Slurry Velocity - Jsl (cm/s)

    Figure 5 - Column Flood ingfrom Dobby & Finch - 1986

    1

    3

    2

    -2.0 -1.5 -1.0 -0.5 0.0 +0.5

    Countercurrent Cocurrent

    0.020.04

    0.07

    0.10

    db = 0.13 cm

     

    Particle Size ( )祄

    Figure 6 - Bubb le & Particle Size Effects

    from Dobby & Finch - 1988

       E  c

       *   E  a

       (   %   )

    Bubble Diameter (mm)

    1.3

    0.5

    0.7

    1.0

    20 40 60

    0.5

    3.0

    1.0

     (i) Bubble rise velocity depends on bubble size, the difference between the apparent collection

    zone and bubble densities, and downward slurry velocity. A distribution of bubbles sizes is produced by

    any sparging system. Therefore, when the slurry feed rate exceeds the rise velocity of the smallest

    bubble, a percentage of the air is lost to the underflow.

    (ii) As the gas rate to the column increases the three phase density of the collection zone

    decreases. At the same time the density of the froth zone will increase until the two are equal. At this

    point the gas holdup will suddenly increase from about 15% to over 50%. When this occurs, the column

    is said to be “frothed up”. Recoveries drop significantly under these conditions.

    (iii) The increased turbulence and larger bubbles formed at higher gas rates cause an increase in

    bubble coalescence which results in a decrease in the incremental gas holdup. Eventually, severe

    coalescence will result in the formation of large “slugs” of air. This effect changes the column mixing

    characteristics and reduces both the surface area available for flotation and the collection of particles on

    the bubble surface. One of these factors will probably limit the maximum column gas velocity to between

    1.8 and 3.5 cm/s.

    5.3.2 Optimum

    The optimum gas rate usually occurs at the point at which solids loading per gas volume is maximised

    (Cg) rather than at the maximum gas holdup. Maximum gas holdup usually occurs at a gas rate larger

    than optimum.

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    33/46

    CPT Column  Collection Zone Theory Page 28 

    5.4 PARTICLE AND BUBBLE SIZE 

    Both the average size of bubbles and distribution of bubble sizes are important to column flotation. They

    affect maximum gas rate, probability of particle collection on the bubble, and solids gas carrying capacity

    (Cg). Bubbles used are typically between 0.8 and 1.6 mm in diameter with the actual size depending on

    reagent conditions, sparger design, and operating pressure.

    5.4.1 Gas Veloci ty

    Smaller bubbles have a reduced rise velocity, therefore, the maximum gas rate will be less than that

    possible with larger bubbles.

    5.4.2 Probabil ity of Collection

    The flotation rate constant of a column has been related to the probability of particle - bubble collision

    and attachment by the following equation:

    c

    g a c

    b

    k  =1.5 J 

     ε ε   c

    g a c

    b

    K  =1.5 J E E 

     D 

    Where

    kc  is the flotation rate constant (min-1

    ).

    εc  is defined as the fraction of particles contained in the cylindrical volume travelled by

    the bubble which collide with that bubble.

    εa  is defined by the fraction of particles which have collided with the bubble that attach

    to that bubble.

    db is defined as the bubble diameter in µm.

    Bubble size should be adjusted for changing particle size to fully optimise a column. This can be

    achieved in two ways: (i) by adding a frother to the feed or (ii) by increasing the sparger pressure.

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    34/46

    CPT Column  Collection Zone Theory Page 29 

    5.4.3 Solids Carrying Capacity

    0.05 0.10 0.15

       B  u   b   b   l  e   D   i  a  m  e   t  e  r   (  m  m   )

    Frother Consumption (mg/s m昪 2)

    Figure 7 - Effect of Frother on Holdupfrom Dobby & Finch - 1988

    Slurry

    Frother 

    Sparger 

    Frother 1.0

    2.5

    2.0

    1.5

     

    The amount of solids which can be carried by a bubble are influenced by the following factors: surface

    area to volume ratio, solids density, and particle size, hydrophobicity, and particle shape.

    Smaller bubbles have larger surface areas per volume and therefore can carry more solids per air

    volume. (The slower rise velocity of the smaller bubbles reduces the air volume which can be added to

    the column.) Very small bubbles (micro bubbles) may cause loss of collected solids to the underflow

    stream when bubble density (collected solids plus air) reduces bubble rise velocity to values smaller

    than the slurry velocity. More hydrophobic particles attach to the bubble faster therefore have a larger

    Ea. Particles which are highly angular tend to attach more quickly.

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    35/46

    CPT Column  Froth Zone Theory Page 30 

    6.0 FROTH ZONE THEORY

    6.1 INTRODUCTION 

    The froth zone extends from the collection or pulp zone interface to the column lip. In this zone solids

    and water are carried between bubbles. The three phase density of this zone usually ranges from 0.2

    to 1.0 g/cm3, depending on the solids floated, location of measurement, froth depth, wash water, and

    frother dosage.

    Wash water stabilises the bubbles and reduces coalescence. Figure 8 illustrates this effect by showing

    the change in holdup with level of the column (with wash water) and a mechanical cell (without wash

    water).

    20 40 60 80

    Gas Holdup - Eg (%)

       F  r  o   t   h   D  e  p   t   h   (  a  p  p  r  o  x .   1 .   0  m   )

    Figure 8 - Conv. Vs Column Holdupfrom Dobby & Finch - 1988

    Overflow

    Interface

    ConventionalFroth

    Collection

    Zone

    Froth Zone

    Column Froth

     

    Wash Water Concentrate

    Negative

    Bias

    Positive

    Bias

    Interface

    Level

    Draining

    Froth Bed

    Eg > 0.80

    Packed

    Bubble Bed

    Eg > 0.74

    Expanded

    Bubble Bed

    Eg < 0.74

    Bubbling

    Zone

    Eg < 0.20

    Figure 9 - Froth Zone Profilefrom Yianatos - 1985  

     As the bubbles ascend the froth zone a certain amount of coalescence occurs. This reduces the

    bubble surface area available for solids and also decreases the volume of the voids between bubbles

    occupied by water. This property appears as an increase in gas holdup with height and is illustrated

    in Figure 9.

    6.2 FROTH CLEANING 

    Since there is a net downward flow of water in the froth zone (assuming a positive bias) particles not

    attached to bubbles will be carried back into the collection zone. This includes particles that are

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    36/46

    CPT Column  Froth Zone Theory Page 31 

    carried with, but not attached, to bubbles (non-selective entrainment) and particles that become

    detached from the bubble due to coalescence. These particles, returned to the collection zone via the

    wash water, form a partial internal solids recycle. This is commonly termed "drop-back", and is the

    reason behind the increased grade and lower recovery at deeper interface levels (Figures 10 and

    11).

       C  o  p  p  e

      r   R  e  c  o  v  e  r  y   (   %   )

    Froth Depth (m)

    Figure 10 - Cu Recovery Vs Froth Depthfrom Huls - 1989

    50

    80

    70

    60

    0.8 1.0 1.2 1.4

     

       C  o  n  c  e  n   t  r  a   t  e   G  r  a   d  e   (   %   N   i   )

    Froth Depth (m)

    Figure 11 - Ni Grade Vs Froth Depthfrom Huls - 1989

    0.8 1.0 1.2 1.4

    0.4

    1.0

    0.8

    0.6

     

    6.3 G AS VELOCITY 

     An increase in gas velocity results in an increased collection zone holdup and a decreased froth zone

    holdup (Figure 12). Less coalescence occurs in the froth zone as gas rate is increased, therefore,

    froth grade deteriorates. Very high air rates may result in a loss of the interface.

    This is apparent when the holdup in the froth and collection zones are equal. This condition can

    contribute to the rapid drop in grade found at high recoveries on typical column grade / recovery

    curves (Figure 13).

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    37/46

    CPT Column  Froth Zone Theory Page 32 

    Overflow

    Interface

    Collection

    Zone

    Froth Zone

    Gas Holdup - Eg (%)

       F  r  o   t   h   D  e  p   t   h   (  a  p  p  r  o  x .   1 .   0  m   )

    Figure 12 - Effect of Jg on Gas Holdup

    from Dobby & Finch - 1988

    20 40 60 80

    Jg

    Jg

     

       G  r  a   d  e   (   %   )

    Recovery (%)

    Figure 13 - Rghr Column Grade/Recovery

    48

    54

    52

    50

    92 94 96 98

     

    20 40 60 80

    Gas Holdup - Eg (%)

       F  r  o   t   h   D  e  p   t   h   (  a  p  p  r  o  x .   1 .   0  m

       )

    Overflow

    Interface

    Collection

    Zone

    Froth Zone

    Figure 14 - Effect o f Frother on Gas Holdupfrom Dobby & Finch - 1988

    Frother 

    Frother 

     

    20 40 60 80

    Gas Holdup - Eg (%)

       F  r  o   t   h   D  e  p   t   h   (  a  p  p  r  o  x .   1 .   0  m

       )

    Overflow

    Interface

    Collection

    Zone

    Froth

    Zone

    Figure 15 - Effect of Bias on Gas Holdupfrom Dobby & Finch - 1988

    Jb

     

    Increased gas velocity also results in a higher possibility of feed water reporting to the overflow (Figure

    14) which lowers the purity of the froth product.

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    38/46

    CPT Column  Froth Zone Theory Page 33 

    6.4 FROTHER CONCENTRATION 

    For applications where frothers are used, an increase in frother concentration has an effect similar to

    that of high air addition rates. The froth zone gas holdup (Figure 15) decreases causing lower froth

    percent solids and a decrease in froth grade. High frother dosages, especially when combined with

    high air rates, can be detrimental to column performance.

    20 40 60 80

    Feed Water in Froth (%)

       F  r  o   t   h   D  e  p   t   h   (  a  p  p  r  o  x .   1 .   0  m   )

    Overflow

    Interface

    Collection

    Zone

    Froth

    Zone

    Figure 16 - Effect of Jg on Entrainmentfrom Dobby & Finch - 1988

    Feed Water  Bias

    Water 

    Jg

    >2.5 cm/s

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    39/46

    CPT Column  Froth Zone Theory Page 34 

    20 40 60 80

    Feed Water in Froth (%)

       F  r  o   t   h   D  e  p   t   h   (  a  p  p  r  o  x .   1 .   0  m   )

    Overflow

    Interface

    Collection

    Zone

    Froth Zone

    Figure 18 - Effect o f Jb on Feed Water in Conc

    from Dobby & Finch - 1988

    Jb ~0.5 cm/s

    Jb ~0.3 cm/s

    Jb ~0.1 cm/s

     

       S  o   l   i   d  s   R  e  c  o  v  e  r  y   (   %   )

    Water Recovery (%)

    Figure 19 - Recovery of Soli ds Vs Water 

    40

    5祄

    10祄

    20祄

    20 40 60

    10

    30

    20

     

       C  o  n  c  e  n   t  r  a   t  e   G  r  a   d  e   (   %   )

    Distance Below Column Lip (cm)

    Figure 20 - Grade & Selectivity with Depthfrom Dobby & Finch - 1988

    20

    60

    30

    10

    70

    50 1000 150

    Column Size 45 x 45 x 1,200 cm

    Molybdenum

    Chalcopyrite

    Silica

    Pyrite   W  a  s   h   W

      a   t  e  r   I  n  p  u   t

       I  n   t  e  r   f  a  c  e

     

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    40/46

    CPT Column  Froth Zone Theory Page 35 

    6.6 SELECTIVITY 

    Selectivity occurs in the froth zone; the less floatable particles drop back into the collection zone as

    indicated in Fig 20. In this diagram Silica, Chalcopyrite and Pyrite grade reductions are traced.

    There is also a size class selection. Larger particles are usually the ones that remain locked and are

    therefore "middling" in nature and subject to washing. Larger particles project further from the bubble

    surface and are subject to more force from the passing wash water stream.

    6.7 REFERENCES 

     Amelunxen, R.L., (1985). The Mechanics of Operation of Column Flotation Machines.

    Proceedings of the 17th Annual CMP Meeting, Ottawa, January 1985Egan, J.R., Fairweather, M.J., and Meekel, W.A., (1988). Applications of Column Flotation to Lead and

    Zinc Beneficiation at Cominco.

    1st International Symposium on Column Flotation, AIME, Phoenix

    del Villar, R., Gomez, C.O., Finch, J.A., and Espinosa-Gomez, R.,(1989) . Flotation column

    amenability and scale-up parameter estimation tests. C.I.M. International Symposium on the Processing

    of Complex Ores, Halifax.

    Dobby, G.S., and Finch, J.A., (1988). Column Short Course, Cambourne School of Mines, Cornwall,

    England.

    Huls, B.J., Lachance, C.D., and Dobby, G.S., (1989). Gas rate and froth depth effects on performance

    of a Cu-Ni separation flotation column. C.I.M. International Symposium on the Processing of Complex

    Ores, Halifax.

    Wheeler, D.A., (1988). Historical View of Column Cell Development. Presented at 1st Int. Symp. on

    Column Flotation, A.I.M.E., Phoenix

    Wilson, S.W., (1987). The Study of Flotation Column Rate Constants as a Function of Particle Size.

    B.A.Sc. Thesis, Dept. of Geological Engineering, University of Toronto.

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    41/46

    CPT Column  Production Column Testing Page 36 

    7.0 PRODUCTION COLUMN TESTING

    7.1 INTRODUCTION 

    The purpose of conducting testwork is to determine the optimum parameter settings to maximise

    column performance under varying plant operating conditions. Generally, a column operates best

    under steady-state conditions; the fewer disturbances in the system the better. Considering this,

    operation should be as smooth as possible, and any changes in interface level, wash water, air or

    reagent additions should be made slowly.

    When performing testwork, a minimum number of variables should be changed at one time -

    ideally only one - so that the fewest number of effects in teract. 

    It is important to remember that a column has a significant residence time and therefore an ability to

    accumulate floatable solids through internal recycle. If solids are building up due to insufficient air rate

    or other froth transport problems, excellent grades can be achieved without immediately sacrificing

    recovery. These solids, however, will eventually report to the underflow resulting in a significant

    deterioration of metallurgical performance. High solids loading may cause excessive coalescence in

    the froth zone and appear as "burping" or "volcanoes" in the froth. Therefore, whenever a grade /

    recovery curve is being constructed, values should not be recorded until a steady state is reached -

    which may take as long as three column residence times after the last change.

    7.2 AIR R ATE 

    The amount of material floated is very sensitive to the rate of air introduced through the spargers. In

    the first few days of operation with a new type of feed material, the reagent dosages and air flow rate

    should be adjusted to give optimal grade/recovery performance. Record the air loading (amount of

    solids carried per unit of air) as kg/m3. When the column feed rate changes, repeat the test. The

    purpose of these tests is to create a chart of air requirement Vs overflow tonnage production that can

    be used by operators. The amount of air needed to float a specific amount of solids is dependant on

    both the particle size and the bubble size. A decrease in particle size will increase the required air

    while an decrease in bubble size will decrease the required air.

  • 8/18/2019 Column Flotation Cell. Operating and Maintenance Manual - Canadian Process Technologies Inc. (2002)

    42/46

    CPT Column  Production Column Testing Page 37 

    7.3 W ASH W ATER BIAS 

    Jb values should be determined for each test in order to optimise the wash water addition rate. During

    these tests the feed tonnage and all operating parameters should remain constant while the wash

    water is altered.

     As wash water addition is reduced from the optimum, a slight, possibly unnoticeable, decrease in

    froth purity should occur. This will be accompanied by a decrease in the overflow percent solids. This

    relationship between the bias flow and decreasing percent solids continues until a critical point is

    reached at which time some water from the pulp zone moves upward and overflows with the froth.

    When this happens, the column is said to be operating at negative bias and entrainment of fine

    impurities in the froth will increase.

     At high gas rates the froth will be much more turbulent causing both a higher froth density and

    entrainment at higher bias rates.

     As the water addition is increased, the recovery of gangue to overflow will begin to decrease and the

    froth density will increase. As the water is further increased, larger particles and middling particles will

    begin to detach from the bubbles causing a decrease in the recovery of the floated minerals. This will

    continue until channelling of the wash water occurs in the froth, or the wash water beats the froth too

    severely causing collapse. These conditions will cause a rapid deterioration of performance.

    Under normal production rates the wash water should be increased until performance deteriorates.

    This value is the maximum wash water rate. This upper flowrate should be consistent at different

    production rates.

    The minimum wash water rate can be determined by reducing the wash water flow until froth impurity

    levels become too high. This lower limit will depend on the production rate.

    7.4 OPERATING LEVEL 

    Both the maximum and minimum column froth levels should be determined.

    The maximum froth depth or lowest pulp level is the point at which the froth collapses. This level will

    depend on the gas rate, reagent concentration, and the amount of solids being floated. Generally,

    there is little benefit to operating at depths greater tha