CO2/T/D Installation Instructions TG201170 Issue 5, 22-Dec-2015. 1
Installation Instructions
CO2/T/DDuct CO2 and Temperature Sensor
Important: Retain these instructions
These instructions shall be used by trained service personnel only. If the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired. https://partners.trendcontrols.com
1 Dimensions
2 Choose Location
3 InSTaLLaTIOn
1 BOx COnTenTS 2 STORIng
It is recommended that the installation should comply with the local electrical safety installation practices (e.g. HSE Memorandum of Guidance on Electricity at Work Regulations 1989, USA National Electric Code).
COnTenTS1 Unpacking .....................................................................12 Storing ...........................................................................13 Installation .....................................................................1
4 Cleaning and Maintenance ...........................................45 Disposal .........................................................................4
H O2
+60°C(+140°F)
0 -20°C(-4°F)
90%RHCO2/T/D Installation Instructions (TG201170)
+60 °C (working) (140 °F)
-20 °C(-4 °F)
+40 °C (measurement – recommended) (104 °F)
0 °C(32 °F)
CO2 0 ppm to 2000 ppm
95 %RH0 %RH
H O2
airflow
CO2/T/D
Trend Control SystemsHorsham, UK
M16 gland
57 mm(2.74”)
85 mm (3.35) centres
105
mm
(4.3
1”)
94 m
m (3
.7”)12 mm diam. (0.47”)
258 mm (10.16”)
33 mm (1.3”)
filter cap
air inlet for CO2 sensing
97 mm (3.82”)foam gasket
2 CO2/T/D Installation Instructions TG201170 Issue 5, 22-Dec-2015.
CO2/T/D Installation Instructions
3 Mount in Duct
4 Remove Lid 5 Remove Connector
7 Connect to Controller
6 Insert Cable through gland
3 InSTaLLaTIOn (continued)
FLOW
Made in Austria
CO2/T/D
SENCO- 1 1 0 0 0 1
IP65
2 x No 6 (M3.8) x 20 mm screws DIN 7481
Note: The dedicated 24 Vdc supply should be isolated and greater than 650 mA
42.5 mm (1.67”)
2 pilot holesØ 15 mm (0.59”)
42.5 mm (1.67”)
either use fl exible conduit or use M16 cable gland
FLOW
Made in Austria
CO2/T/D
SENCO- 1 1 0 0 0 1
IP65
Analogue input channel linked for Thermistor (T), polarity independent
Views shows connector detail and housing section typical for all uses of the CO2T/D
GND
GND
V+
CO2
T1
T2
IQ controllers
24 V SupplyCO2/T/D
}}CO2
Temp.
24 V ac/dc0V
IN10V(1)IN20V(2)
Controller Max no of CO2 sensorsIQ41x 0
IQ422/24V 1IQ422/230V 6IQ4E/230V 6
When connecting to an IQ4 controller the following limits apply if the IQ4 is to provide power. If the sensor is powered from a separate power supply these limits do not apply.
Analogue input channel linked for Voltage (V), ensure correct polarity
CO2/T/D Installation Instructions TG201170 Issue 5, 22-Dec-2015. 3
Installation Instructions CO2/T/D
8 Replace Connector 9 Replace Lid
10 Configure Controller
11 Set up IQ Sensor Types
3 InSTaLLaTIOn (continued)
orIQ
IQ
IQ Configuration Manual (90-1533)IQ3 Configuration Manual (TG200768)IQ4 Configuration Manual (TG201253)
Temperature thermistor recommended range: 0 to 40 °C (32 to 104 °F)
CO2 concentration voltage output 0 to 10 V for 0 to 2000 ppm
Units ppm
Y Input type 0 (volts)
E Exponent 4
U Upper 2000
L Lower 0
P Points 2
x Ix Ox
1 0 0
2 10 2000
Units °C °F
Y Input type 1 (thermistor volts)
E Exponent 3
U Upper 50 122L Lower -5 23P Points 6
x Ix Ox (°C) Ox (°F)
1 2.641 50 1222 3.47 40 1043 4.46 30 864 6.663 10 505 7.668 0 326 8.102 -5 23
It is recommended to use SET (Software Tool) for the setting of the sensor type module. For all IQ2 series controllers with firmware version 2.1 or greater, IQ3 or IQ4 series controllers, the following SET Unique Sensor References should be used:
Thermistor HTST DT (°C) Thermistor HTST DT F (°F) CO2 V (ppm) Alternatively set scaling mode to 5 (characterise) and enter scaling manually as defined in appropriate tables below. Note that for IQ3 and IQ4, the scaling mode and exponent (E) do not need to be set up.
For all other IQ controllers see Sensor Scaling Reference Card (TB100521A).
4 CO2/T/D Installation Instructions TG201170 Issue 5, 22-Dec-2015.
CO2/T/D Installation Instructions
Please send any comments about this or any other Trend technical publication to [email protected]
© 2015 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.
Trend Control Systems LimitedAlbery House, Springfi eld Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.com
TR CU Certifi cation
12 Test System
1 Replace Filter
5 DISPOSaL
Weee Directive:At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre.Do not dispose of with normal household waste.Do not burn.
4 MaInTenanCe
IQ
∆ T∆ CO2
See Section 5,Disposal
ACC/HTD/FILTER
Caution: Do not touch sensing element
unscrew
3 InSTaLLaTIOn (continued)
Over time, the sensing element may become covered in dust. The dust can be removed using compressed air. Under no circumstances should water or cleansing agents be used on the sensing elements.
If the sensor falls outside the quoted accuracy, replace the fi lter as shown below.