CO2/T/D Installation Instructions TG201170 Issue 2, 10/10/2011 1 Installation Instructions CO2/T/D Duct CO2 and Temperature Sensor Important: Retain these instructions 1 Dimensions 2 Choose Location +60 °C (working) (140 °F) -20 °C (-4 °F) 95 %RH -20 °C (-4 °F) 0 +60 °C (+140 °F) HO 2 M16 gland 57 mm (2.74”) 85 mm (3.35”) centres 105 mm (4.31”) 94 mm (3.7”) 12 mm diam. (0.47”) 258 mm (10.16”) 97 mm (3.82”) 33 mm (1.3”) 3 INSTALLATION 1 UNPACKING 2 STORING It is recommended that the installation should comply with the HSE Memorandum of Guidance on Electricity at Work Regulations 1989. For USA install equipment in accordance with National Electric Code CONTENTS 1 Unpacking .....................................................................1 2 Storing ...........................................................................1 3 Installation .....................................................................1 4 Maintenance ..................................................................4 5 Disposal .........................................................................4 CO2/T/D Installation Instructions TG201170 foam gasket filter cap air inlet for CO 2 sensing a b +40 °C (measurement – recommended) (104 °F) 0 °C (32 °F) CO 2 0 ppm to 2000 ppm 95 %RH 0 %RH HO 2 airflow

Important: Retain these instructions - Nuaire · CO2/T/D Installation Instructions TG201170 Issue 2, 10/10/2011 3 Installation Instructions CO2/T/D 8 Replace Connector 9 Replace Lid

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Important: Retain these instructions - Nuaire · CO2/T/D Installation Instructions TG201170 Issue 2, 10/10/2011 3 Installation Instructions CO2/T/D 8 Replace Connector 9 Replace Lid

CO2/T/D Installation Instructions TG201170 Issue 2, 10/10/2011 1

Installation Instructions

CO2/T/DDuct CO2 and Temperature Sensor

Important: Retain these instructions

1 Dimensions

2 Choose Location

+60 °C (working) (140 °F)

-20 °C(-4 °F)

95 %RH-20 °C(-4 °F)

0+60 °C(+140 °F)

H O2

M16 gland

57 mm (2.74”)

85 mm (3.35”) centres

105 mm (4.31”)

94 mm (3.7”)

12 mm diam. (0.47”)

258 mm (10.16”)

97 mm (3.82”)

33 mm (1.3”)

3 InSTaLLaTIOn

1 UnpaCkIng

2 STORIng

It is recommended that the installation should comply with the HSE Memorandum of Guidance on Electricity at Work Regulations 1989.For USA install equipment in accordance with National Electric Code

COnTenTS1 Unpacking .....................................................................12 Storing ...........................................................................13 Installation .....................................................................1

4 Maintenance ..................................................................45 Disposal .........................................................................4

CO2/T/D Installation Instructions TG201170

foam gasket

filter capair inlet for CO2 sensing

a

b

+40 °C (measurement – recommended) (104 °F)

0 °C(32 °F)

CO2 0 ppm to 2000 ppm

95 %RH0 %RH

H O2

airflow

Page 2: Important: Retain these instructions - Nuaire · CO2/T/D Installation Instructions TG201170 Issue 2, 10/10/2011 3 Installation Instructions CO2/T/D 8 Replace Connector 9 Replace Lid

2 CO2/T/D Installation Instructions TG201170 Issue 2, 10/10/2011

CO2/T/D Installation Instructions

3 Mount in Duct

4 Remove Lid 5 Remove Connector 6 Insert Cable through gland

7 Connect to Controller

cba

FLOW

Made in Austria

CO2/T/D

SENCO- 1 1 0 0 0 1

IP65

FLOW

Made in Austria

CO2/T/D

SENCO- 1 1 0 0 0 1

IP65

3 InSTaLLaTIOn (continued)

de f

2 x No 6 (M3.8) x 20 mm screws DIN 7481

Connect to IQ1xx/2xx

Note that the dedicated 24 Vdc supply should be dedicated, isolated, and greater than 650 mA

IQ1xx/2xx

24 V Supply

Analogue input channel linked for Thermistor (T), polarity independent

Analogue input channel linked for Voltage (V), ensure correct polarity

CO2/T/D

}}CO2

Temp.

42.5 mm (1.67”)

2 pilot holesØ 15 mm (0.59”)

42.5 mm (1.67”)

either use flexible conduit

or use M16 cable gland

GNDCO2

IN

+24 Vac/dc

GNDT1T2

IN

0 V

continued next page

Page 3: Important: Retain these instructions - Nuaire · CO2/T/D Installation Instructions TG201170 Issue 2, 10/10/2011 3 Installation Instructions CO2/T/D 8 Replace Connector 9 Replace Lid

CO2/T/D Installation Instructions TG201170 Issue 2, 10/10/2011 3

Installation Instructions CO2/T/D

8 Replace Connector 9 Replace

Lid 10 Configure IQ

7 Connect to Controller (continued)

11 Set up IQ Sensor Types

orIQ

IQ

IQ Configuration Manual 90-1533IQ3 Configuration Manual TG200768

3 InSTaLLaTIOn (continued)

or Connect to IQ324 V Supply

IQ3

Analogue input channel linked for Thermistor (T), polarity independent

Analogue input channel linked for Voltage (V), ensure correct polarity

CO2/T/D

0 (0V)N (in)+ (+24V)

0 (0V)

+ (+24V)N+1 (in)

GNDCO2GND

T1T2

+24 Vac/dc0 V

CO2

Temp.

temperaturethermistorrecommended range:0 to 40 °C (32 to 104 °F)

CO2 concentrationvoltage output0 to 10 V for 0 to 2000 ppm

Units ppmY Input type 0 (volts)E Exponent 4U Upper 2000L Lower 0P Points 2x Ix Ox1 0 02 10 2000

Units °C °FY Input type 1 (thermistor volts)E Exponent 3U Upper 50 122L Lower -5 23P Points 6x Ix Ox (°C) Ox (°F)1 2.641 50 1222 3.47 40 1043 4.46 30 864 6.663 10 505 7.668 0 326 8.102 -5 23

It is recommended to use SET (Software Tool) for the setting of the sensor type module. For all IQ2 series controllers with firmware version 2.1 or greater, or IQ3 series controllers, the following SET Unique Sensor References should be used: Thermistor HTST DT (°C) Thermistor HTST DT F (°F) CO2 V (ppm) Alternatively set scaling mode to 5 (characterise) and enter scaling manually as defined in appropriate tables below. Note that for IQ3 the scaling mode and exponent (E) do not need to be set up.For all other IQ controllers see Sensor Scaling Reference Card TB100521A

Note that the dedicated 24 Vac/dc supply should be dedicated, isolated, and greater than 650 mA

Page 4: Important: Retain these instructions - Nuaire · CO2/T/D Installation Instructions TG201170 Issue 2, 10/10/2011 3 Installation Instructions CO2/T/D 8 Replace Connector 9 Replace Lid

4 CO2/T/D Installation Instructions TG201170 Issue 2, 10/10/2011

CO2/T/D Installation Instructions

Please send any comments about this or any other Trend technical publication to [email protected]

© 2011 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative.

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.

Trend Control Systems LimitedAlbery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.comTrend Control System USa6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 869-3900 Fax:(425) 869-8445 www.trend-americas.com

12 Test System

1 Replace Filter

5 DISpOSaL

Weee Directive:At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre.Do not dispose of with normal household waste.Do not burn.

4 MaInTenanCeOver time, the sensing element may become covered in dust. The dust can be removed using compressed air. Under no circumstances should water or cleansing agents be used on the sensing elements.

If the sensor falls outside the quoted accuracy, replace the filter as shown below.

IQ

∆ T∆ CO2

3 InSTaLLaTIOn (continued)

b

See Section 5,Disposal

c ACC/HTD/FILTER d

Caution: Do not touch sensing element

a unscrew