41
Engineered cooling solutions for all applications Email: Website: Website: Motivair Corporation 85 Woodridge Drive Amherst, NY 14228 7166919222 (Ph) 7166919229 (fax) Motivair TM [email protected] www.chilleddoor.com www.motivaircorp.com INSTALLATION <> OPERATION <> MAINTENANCE GUIDE Cooling Distribution Unit Model: MCDU25660

Clean vertical CDU IOM Rewrite - motivaircorp.com · Heat extracted from the Chilled Doors is transferred to the CDU heat exchanger where the ... general manual may be ... Rev1.0

  • Upload
    lehanh

  • View
    215

  • Download
    0

Embed Size (px)

Citation preview

Engineered cooling solutions for all applications

Email: 

Website: 

Website: 

Motivair Corporation85 Woodridge Drive Amherst, NY  14228 716‐691‐9222 (Ph) 716‐691‐9229 (fax)

Motivair TM

[email protected]

www.chilleddoor.com

www.motivaircorp.com

INSTALLATION <>  OPERATION <> MAINTENANCE GUIDE

Cooling Distribution Unit 

Model:     MCDU‐25‐6‐60

CDU IOM Rev1.0

The manufacturer shall not be liable for any damages resulting from misapplication or misuse 

of its products.

Disclaimer

Product Standards and ComplianceAll products conform to industry standards and ratings; contact Motivair for a complete list 

and certificates for specific models.

ATTENTION

Read this page before proceeding 

ABOUT THIS DOCUMENT

Cooling Distribution Unit 

This document may be updated without notice at any time.  Motivair reserves the right to 

update and or change product specifications and performance without notice as design 

improvements occur.  Please contact the factory to ensure that your version is the most up to 

date.  

Page 2

Section 1  SAFETY INSTRUCTIONS

General Safety 5

Owners Responsibility  5

Installation / Handling 5

Application  5

Electrical Warning 5

Section 2  GENERAL DESCRIPTIONGeneral Product Description 6

Technical Data 6

Section 3  TECHNICAL DATAElectrical Data 7

Design Capacities  7

Dimensional Drawings 8

P&ID 9

Primary Loop 10

Secondary Loop 10

Section 4  INSTALLATIONReceiving and Uncrating 11

Floor Preparation 11

Locating and Positioning 12

Electrical  12

Piping Connections 12‐15

Cleaning and Flushing 15

Water Quality  16

Filling and Venting  17

Section 5  COMMISSIONINGPre‐commissioning Checks 18

Commissioning  19

Description/Sequence of Operation 19‐20

Section 6  OPERATIONPLC Controller HMI Introduction 21

PLC Controller Parameter Screens  22

Set Points and Operation 23‐25

Alarm Acknowledgement 26

CDU IOM Rev1.0

Cooling Distribution Unit 

CONTENTS

Page 3

Section 7 TROUBLESHOOTINGGeneral 27

Non‐Alarms  27

Alarms 28

Section 8  MAINTENANCE

Scheduled Maintenance 29

Section 9 SPARE PARTSParts List 30‐31

Section 10 DOCUMENTS AND TABLESBMS Table 32‐34

Electrical Schematics 35‐37

Section 11 SUPPORT AND WARRANTYFactory Support Contact Info  38

Notes 39

Section 12 APPENDIX Supplemental Electrial by Model A1

Start Up Report A2‐A3

CDU IOM Rev1.0

Cooling Distribution Unit 

Page 4

Section 1

CDU IOM Rev1.0

Temperature control equipment, pump stations and electrical devices contained in this 

system present various electrical, mechanical, sound and vibration hazards.  For this reason, 

operation and service procedures should only ever be performed by qualified, fully trained 

and technically competent personnel.

      This equipment contains:

                     • High pressure water generated by the system

                     • Electrically energized components

                     • Hot pipes and heat exchangers

                     • Rotating parts such as pump impellers, wheels and valves.

General Safety

SAFETY INSTRUCTIONS

Operation of this equipment involves potentially lethal dangers (HIGH VOLTAGE POWER and 

High water Pressures.)  Therefore, ALL safety precautions and warnings described in this 

manual must be precisely observed.  Failure to follow these precautions and warnings can 

result in severe or fatal injury

WARNING

Cooling Distribution Unit 

This unit must only be used in the application for which it was designed.  Do not use this 

product in any hazardous environment.

Application

Electrical

WARNING – This unit is powered by HIGH VOLTAGE.  Serious injury or death can occur. Power 

being supplied to the unit must be isolated with an electrical disconnect.  Any and all 

electrical connections or procedures should only be performed by a certified electrician.  All 

electrical work or procedures should be in accordance with local, state and national electrical 

codes and regulations.  NEVER make any electrical connections to this unit unless the power 

supply is OFF at the power supply disconnect switch.  

This equipment must be installed, maintained and operated by a person or persons qualified 

for this equipment.  This system contains water circulation equipment and electrical 

components.  The person most suited to perform any operations or service on this equipment 

is a qualified industrial technician and or electrician with experience and qualifications to 

work with water systems and electrical systems.

Owner's Responsibility

Installation and operation should always be conducted in compliance with local, state and 

national codes and industry best practices.  When moving or installing the unit, CAUTION 

must be observed at all times to ensure the safety and well being of personnel.  Follow all 

local, State and national codes for moving equipment.  Only appropriate and approved 

moving equipment should be used.

Installation

Page 5

Section 2

CDU IOM Rev1.0

The Cooling Distribution Unit (CDU) is designed for use with Motivair Chilled Doors and other 

approved distribution systems and equipment in a data center environment.  The CDU 

includes a plate heat exchanger that creates a divide between customer supplied cold water 

(Primary Loop) and a separate cooling loop that feeds Chilled Doors (Secondary Loop).  The 

Secondary Loop flow and pressure is created by the CDU pumps and valve assemblies.   The 

Secondary Loop is always controlled to operate above room dew point to avoid condensation 

on the Chilled Door coils.  

The Primary Loop water system should always have a micron filtration level of less than 500 

microns.  The water supply can be from various sources such as a chiller plant.  Clean and 

filtered water and or glycol is the sole responsibility of the user.  Large amounts of debris or 

particulate can reduce efficiency or plug the CDU heat exchanger. 

Heat extracted from the Chilled Doors is transferred to the CDU heat exchanger where the 

heat is exchanged to the Primary Loop and removed.  

Various set points and alarms can be monitored and controlled within the CDU.  These can be 

adjusted by the operator via an integrated PLC.

Cooling Distribution Units can be built in various configurations.  Make sure to check specific 

product specifications and design criteria for each specific CDU.  Consult Motivair with any 

questions.

Cooling Distribution Unit 

General Product Description

Technical Data

Technical Data such as pump curves, electrical loads and sound data for any specific CDU that 

is not included in this general manual may be obtained on the CDU nameplate or from the 

product specification or submittal. Consult Motivair with any questions or document requests

GENERAL DESCRIPTION

Page 6

Section 3

Standard Available Power Options:  460/3/60  ‐  575/3/60  ‐  230/3/60  ‐  208/3/60

inInIn

‐GPMGPMPSID°F°FkWkWkW

V/Ph/HzLbsLbs

FLA: 11.8 Amps MCA: 14.0 Amps MOP: 22.8 Amp

The above sample design specifications are based on maximum design load conditionsCapacity and performance will vary based on Primary flow, temp, and fluid type.  

Note:

For your specific design and application refer to your Motivair engineering selection. See Appendix A1 for specific model data

CDU IOM Rev1.0

CDU‐25‐6‐60 Design Data:  

Primary

Estimated Total Fluid Pressure Drop:

72

185

Unit Height:Unit Width:

39

100% Water

Unit Depth:

Fluid Type:Design Fluid Flow:Max Fluid Flow:

1201203.2

Total power consumed at design CDU Power supply:Approximate Shipping Weight: 1,170

Power 460/3/60

Design Capacities 

7.745°55°

100% WaterSecondary

Approximate Operating Weight: 1,300Specifications are subject to change without notice.

75.5°60.0°

31

185

5.5460/3/60

CDU Design Cooling Capacity:CDU MAX Cooling Capacity: 272

Cooling Distribution Unit 

TECHNICAL DATA

Electrical Data

Design Fluid Inlet Temp:Design Fluid Outlet Temp:

272

Page 7

CDU IOM Rev1.0

Cooling Distribution Unit 

Page 8

CDU IOM Rev1.0

Cooling Distribution Unit 

Page 9

Primary Loop

Secondary Loop

CDU IOM Rev1.0

Cooling Distribution Unit 

Hydraulic

The Primary Loop cold water is supplied from the customer’s building chilled water system 

and is outside the scope of this CDU manual.  The Primary Loop is connected to the CDU’s 

Primary IN and Primary OUT connections via either an NPT connection or a customer 

specified connection i.e. sanitary fitting or grooved pipe. This connection type should be 

specified at the time of order.  

The CDU can be built to accept either top or bottom connections.  This should also be 

specified at the time of order.  The prevailing standard is bottom connections piped up from a 

raised floor space.  All Primary Loop piping or hosing connected to the CDU must be self 

supporting, as the CDU is not designed for any external pipe loads.  

All Primary Loop piping should be insulated BY the installer to prevent condensation from 

forming.   

The Secondary Loop connections are made on the underside of the CDU (bottom connections 

for raised floor installation).  These connections can be either NPT or sweat connections and 

can be specified at the time of order.  These Secondary In and Secondary Out connections 

typically run to and from a “supply and return header” that can be mounted under the raised 

floor by the installer.   Connections between the CDU and the “Supply and return header” are 

made by the installer.  This piping should be self supporting as the CDU is not designed for 

any external pipe loads.

The Secondary Loop should be filled with clean softened water.  Consult Chilled Door 

specification for water details.

Page 10

Section 4

Warning: 

CDU IOM Rev1.0

The CDU is heavy and requires an opening in a raised floor for piping egress DO NOT CUT 

raised floor cross supports or remove stanchions around CDU for this opening, consult your 

raised floor contractor or supplier for safe load specs and cutout assistance if necessary. 

Cooling Distribution Unit 

INSTALLATIONReceiving and uncrating

Floor Preparation

Preparing a raised floor for a CDU:

When a CDU is installed on a raised floor, holes must be made to allow for supply and return 

primary and secondary water lines to pass in and out of the CDU.  The drawing below shows a 

typical bottom view of a CDU.  The rectangular cut out is where the water piping enters and 

exits the CDU.  

The CDU arrives in a specially designed crate.  Make sure the crate is on a level and load 

bearing floor.  Typically, 4 workers will be needed to remove the CDU from its crate.  Open 

the front “Drawbridge” door to gain access to the CDU. Note, this drawbridge door folds 

down and creates a ramp down which the CDU is rolled out of the crate.  Once the 

drawbridge door is down, carefully remove the CDU from the crate by pulling from the 

bottom of the CDU’s front bracket.  DO NOT PULL ON UNIT DOORS, THEY ARE NOT DESIGNED 

FOR LOAD PULLING OR RIGGING.  The CDU has heavy components located high up inside the 

structure so the center of gravity is relatively high.  Make sure unloading personnel prevent 

the CDU from tipping over by guiding it down the draw bridge ramp. Thoroughly INSPECT the 

unit, any shipping damage must be reported to Motivair immediately.

Page 11

CDU IOM Rev1.0

Electrical:

The CDU electrical panel is equipped with an opening through which the power wires are 

installed.  All electrical wiring should be performed by a qualified electrician. Wire sizing may 

vary based on CDU electrical loads and building power supply.  

The CDU can be supplied with A/B power feed option allowing for 2 different power sources 

to be fed to the CDU.  If only 1 power source is available, that power can be fed to both the A 

and B power terminals. Consult CDU Model name plate for proper supply voltage and power 

for your unit.   

Piping Connections

Secondary loop 

inlet Return from 

doors  Primary CW supply from building loop

Primary CW return 

to building loop

Secondary loop 

outlet supply to 

doors

Control wiring: The RH% ‐ dew point sensor located below the control panel can be relocated 

(wall mount) if CDU is not installed in the conditioned space.  Relocating will require 

extending a 4 conductor 18ga wire to the space.  BMS wiring is also required per options 

installed either IP network cable or shielded 3 wire.

Cooling Distribution Unit 

Locating and positioning

Position the CDU on a smooth level floor (top Feed units). Bottom feed units typically will 

need to be installed on  12” raised floor or higher to allow for pipe connections to be made to 

the underside of the CDU.  Once in position, there are leveling feet that MUST be adjusted to 

ensure a stable, level operating platform. DO NOT LEAVE ON WHEELS.  There are openings in 

the bottom of the CDU to allow for IN/OUT Primary piping Connections and IN/OUT 

secondary piping connections, the floor cutout should be aligned with CDU opening.

Page 12

CDU IOM Rev1.0

Bottom Feed Top View piping layout position

Bottom Feed Side View

Piping Layout

Cooling Distribution Unit 

Page 13

CDU IOM Rev1.0

Piping Layout cont.…

Top Feed Top View piping layout position

Top Feed Side View

Cooling Distribution Unit 

Page 14

CDU IOM Rev1.0

Piping

16 Port Distribution Header 

All piping should only be performed by qualified piping contractors and all industry standard 

best practices and plumbing codes must be followed.  The piping connections are standard 

2.5" female NPT (unless ordered alternate connection option) and may be attached to the 

building's primary chilled water loop by any acceptable piping material and connection 

method, i.e. flex hose, copper, sch 80 PVC, carbon steel pipe, Grooved (Vic) etc. The piping 

must be supported completely as to not stress the CDU piping or components. Primary piping 

should be insulated to avoid condensation issues. The secondary loop of the CDU will be 

piped per above requirements and will connect  the temperature controlled loop to the 

chilled doors via a Motivair header assembly (per below) or a site provided 

header/distribution system.  All field piping must be pressure tested not to exceed 100 psi on 

any Motivair supplied components.

Cleaning and Flushing

Cleaning and flushing of any field installed piping that may be required must be completed 

before connecting to any Motivair equipment.  Motivair supplied Chilled Doors, CDU's, 

Underfloor Distribution Headers, and all hoses are shipped clean and new, these require no 

cleaning or flushing. 

Cooling Distribution Unit 

Page 15

CDU IOM Rev1.0

A water treatment professional should be consulted regarding the testing and proper 

chemical treatment for a closed loop system’s composition and fluid requirements.  Proper 

levels of all loop and makeup water must be maintained per industry standards and best 

practices. Proper levels of pH, Alkalinity, Chlorides, Nitrite, and Conductivity, along with other 

chemicals and metals in the system must be tested for and monitored. A treatment program 

should be implemented at the time of initial system commissioning to provide long term 

system reliability.  This testing is outside this documents scope.

Cleaning and Flushing

Good installation practice must include Initial system flushing

Cleaning and flushing of any field installed piping that may be required must be completed 

before connecting to any Motivair equipment.  Motivair supplied ChilledDoor®, CDU's, 

Underfloor Distribution Headers, and all hoses are shipped clean and new, these require no 

cleaning or flushing. 

Minimum Water Quality standard for Motivair Equipment

To insure long term reliability and operation of the sealing components of the Motivair 

Chilled doors and coolant loop distribution components clean water with a low to no 

suspended solids level is required for closed loop systems.                               Suspended 

Particles can damage O‐rings, mechanical pump seals and cartridge valve seals and operation. 

Excessive suspended solids will leave deposits in system piping, including critical sealing and 

heat transfer surfaces. The following recommendations are a minimum for and closed loop 

distribution system utilizing the Motivair Chilled door, CDU or header distribution system. 

Water testing and filtration must employed to ensure a system is filtered to <50 microns 

(High limit of a closed loop system per industry standards) The recommendation by Motivair 

is to utilize a 5 micron or less bag/cartage type filter in the closed loop or other suitable 

method of removing suspended solids to a minimum 5 microns or less. Iron levels less than 

<2.0 ppm ‐ Copper levels less than <0.1 ppm ‐ Suspended solids <1 mg/L.

The following table is a guide 

for initial fill water for all 

closed loop system using 

Motivair Chilled Doors and 

components.  Potable water is 

a good source and starting 

point for initial filling. 

Motivair Water QualityMineral Recommended Limit Chloride < 25 ppmCalcium < 15 ppm

Magnesium < 15 ppmTotal Water Hardness <30 ppm

Sulfate < 25 ppmpH 7.3‐8.3softened water should be used

Cooling Distribution Unit 

Page 16

CDU IOM Rev1.0

The secondary loop should be filled slowly using a hose and transfer pump or suitable 

municipal water supply at the drain and fill valve located on the suction inlet piping of the 

CDU pumps. The Bottom feed CDU has auto vents at the high points to purge the air from 

both the primary and secondary water loops. The auto vents are to be open during filling, 

venting, and start‐up. The auto vent manual isolation valves should be closed following the 

completion of the commissioning process.  Top feed CDUs may be filled in the same manner, 

but air venting and purging must be provided at the highest point of elevation in the building 

piping system. 

A CDU connected to a Motivair under floor distribution header and to Chilled Doors will 

require venting at both the CDU per above and at the chilled door coil vent ports. (refer to 

the Chilled Door Manual for installation and venting information).  The under floor 

distribution header contains manual isolation valves, actuator valves, and one way check 

valves.  These valves/circuits should be open and purged one at a time to ensure all air is 

removed. 

Fill & Vent Note:  The flow path is stopped at the check valves on the header.

Cooling Distribution Unit 

Filling and Venting

Warning: Do not use deionized water (DIW) in chilled door closed loop systems as 

DIW is corrosive to certain metals.

The use of Propylene and Ethylene glycol mixtures and water treatment additives that are 

compatible with the piping and wetted materials used in the coolant distribution system are 

acceptable.  A qualified water treatment contractor should be consulted for 

recommendations and water analysis testing that meet your specific requirements.

Water Quality cont…

The CDU Primary Loop should be supplied with clean, particulate free water or glycol.  Note 

that increased glycol concentrations reduce CDU efficiency and cooling capacity.  It is the 

responsibility of the owner to ensure that the Primary Loop supply has less than 500 microns 

of particulate.

TIP: The flow path for purging air is from the fill in CDU pump return pipe through the pump 

and exchanger to the header supply and zone valves through the chilled door coil and back to 

the header check valve inlet. Removing the quick connect hose at the header check valve and 

purging into a suitable container will force the air out at the low point.  Final purging is done 

at the chilled door coil air vents and CDU auto vents. 

The CDU Secondary Loop should be filled with clean, particulate‐free, softened water with 

suitable corrosion inhibitors and biocides.  Consult a water treatment service provider if you 

need assistance.

Page 17

Section 5

CDU IOM Rev1.0

1. If Motivair or one of its agents was not contracted for commissioning assistance, please 

notify Motivair before commencing start up 

6.  Navigate to pump rotation screen, switch lead pump and continue above checks. 

7.  Navigate to the Temperature I/O screen and note the Primary and secondary loop temps. 

The HXP In temp should be below 60°F and the HXS Out temp should be at set point (default 

= 65°F). The "Main Outputs" screen will display the signal (0‐10v) output to the temperature 

control actuator valve and the pump VFD.  Check all HX temperatures are reading as 

expected.  

5. The Pumps will operate at a speed to maintain a differential pressure as per set point 

(default = 25 psi).  The auto vent air bleeders should remain open to remove any entrained 

air in the system. The minimum pump return pressure operating at 60 hz is 10 psi. Add fluid 

as necessary to maintain pressure. 

The CDU will alarm on low pressure below 5 psi operating pressure after 90 seconds  8.  "Know the system". Take another look at the complete hydronic loop and all

2.  Apply power to the CDU by closing the A/B disconnects on the front panel.  The HMI 

display will be visible in about 30 seconds and will display the main screen showing pump 

pressures and "Off by Keyboard" message.

3. Check the display screen and note the pump supply and return static pressures.  The initial 

static charge should be between 15 ‐ 30 psi.  Do not operate pumps "dry". 

4.  Navigate the PLC to command the unit “ON” via the user interface.  (See controls section 

for description and navigation of screens). Open the front door of the CDU and locate the 

operating pump and check that rotation matches the directional arrow on pump.  The CDU's 

are factory wired and phased ABC for proper rotation. If rotation is reversed, stop unit, open 

disconnects and correct phasing.

COMMISSIONING

Cooling Distribution Unit 

7.  Check secondary loop pressure gauges on CDU have a minimum pressure to start.            

 components, controls, valves, pipes, vents, auto bleeders and heat exchangers   before beginning commissioning. Safety is no accident.

Commissioning

Pre‐commissioning checks

1.  Visual inspection of unit to confirm all components and panels are in place. 2.  Check all water piping to CDU and system are properly supported and insulated 3.  Check primary loop water supply is open and within pressure limit of CDU.4.  Check all electrical connection's tightness and proper routing. 5.  Check site electrical supply power matches nameplate voltage on CDU 6.  Confirm the fuse or circuit breaker and wire size are correct for the unit 

Page 18

Section 6

CDU IOM Rev1.0

9.  The Optional leak detection system sensor should be located in the lowest appropriate 

area (floor level or under floor) to detect moisture present.  Make sure water detection LED 

(green) is lit on WDS module, test alarm with water on sensor. 

Cooling Distribution Unit 

OPERATION

1. The PLC set to "ON" and sensing the leaving secondary loop temperature, sends a 0‐10 volt 

output signal to the motorized actuator valve on the inlet building supply. The valve 

modulates to maintain secondary loop temperature to the Chilled Doors at set point.

  

2.  The PLC set to "ON" and monitoring the lead pump supply and return pressure differential 

sends a 0‐10 volt output signal to the VFD to maintain secondary loop flow volume at set 

point per the current system demand.

3. Secondary loop pump pressures and outlet temperature are displayed on the HMI home 

screen.

4. Entering & leaving primary & secondary loop temperatures are displayed on the 

Temperature I/O screen.

5. Chilled doors (CDU heat load) are fitted with their own load‐based modulating control 

valves.  Therefore secondary pump pressure will vary based on the number of Chilled Doors 

in service and/or the actual heat load applied to the Chilled Doors.  Secondary pump pressure 

is monitored by a pressure transducer in the pump discharge header and constant design 

pump pressure is maintained by the VFD connected to the operating pump.

6. Triple duty valves on the discharge of each pump provide:

A.  Final adjustment of operating pump head pressure, if needed, to balance pumps on full 

load to design head pressure.

B.  Check valve to prevent backflow for automatic pump changeover.

C. Isolation of pump for removal.

Description/Sequence of Operation

Commissioning Cont.

8.  Following a suitable period of time to be sure all air has been removed from the closed 

loops, close the auto vent safety caps and valves to prevent accidental leaks.

10.  Record all measurements and readings and complete the "Start up Report"  located in 

the documents section of this manual.

Page 19

CDU IOM Rev1.0

7. Closed diaphragm expansion tank allows for hydraulic expansion of water in closed loop 

during temperature changes that may occur between filling time, operation and shut‐down.

8.  The relative humidity sensor monitors data center humidity to ensure secondary water 

loop temperature remains above the dew point.  This is necessary to prevent condensation 

on the coils inside the Chilled doors.  In the event the data center humidity reaches a dew 

point within 3°F of the leaving secondary water loop temperature, the dew point warning is 

activated and the PLC throttles the primary water control valve to reduce the cooling effect 

on the secondary loop.   The CDU will automatically adjust outlet secondary water 

temperature to stay 3°F above room dew point.

                                                                                                                               

9.  Check communication of all selected PLC points to master control or BMS via BacNet, LON 

or Modbus.

10. CDU is set‐up to accept A/B power supply check/test switch over (if option is connected) 

by opening A disconnect switch.   

Cooling Distribution Unit 

Description/Sequence of Operation cont.

Page 20

“Alarm “ – press to view current alarm & clear alarms

“Program” – press to enter the programming menu screen

“Escape” – press to go back one screen or one space

“Down arrow” – press to scroll down or lower a setting

“Up arrow” – press to scroll up or raise a setting

CDU IOM Rev1.0

Cooling Distribution Unit 

HMI Screen Navigation 

The Human Machine Interface (HMI) is a 6 button Remote panel mount display screen The 6 

button functions on left and right sides as follows: 

The HMI screens are a scrolling menu style the up and down arrows will scroll through all 

available screens in a sub menu, i.e. press alarm, and scroll through all active alarms.

“Enter” – press to navigate to changeable parameters and  confirm/save changes 

PLC control HMI introduction

The above Display is the main screen or “Home Screen” it displays the controlled points and 

the state of the PLC  i.e. "Unit off By Keyboard"

Page 21

CDU IOM Rev1.0

HMI Screen Navigation 

The home screen is displayed when you 

press the ESC key or after a few minutes 

of inactivity.  The home screen displays 

the temperature reading of the CDU. The 

"I" Icon for information is a reminder to 

scroll down for additional info screens.

Pressing the DOWN ARROW key will 

scroll to the next information screen. 

First is the Temperature I/O display 

showing the actual reading of each input 

and is used for monitoring and alarm 

functions.

The next info screen shown by pressing 

the DOWN ARROW key contains the 

actual outputs to the VFD and the chilled 

water valve.  Also the power source for 

dual power feed option and an hour 

count down timer to next pump 

rotation.

The next Info screen is for configuration 

of the pump rotation, and allows for 

manual switching and rotation by hours 

or a specific day and time each week for 

predictable change times.  Also shown is 

the current operating lead pump.  

The last Info screen in this menu series is 

the pump hours, counters, and reset of 

counter function.

Cooling Distribution Unit 

Page 22

CDU IOM Rev1.0

HMI Screen Navigation 

Press the "PRG" key for access to the 

programming menu.  The programming 

menu contains three sub menus as 

shown. Use the UP & DOWN ARROW 

keys to highlight your selection then 

press the ENTER key to confirm your 

selection.

Highlight “Client Settings” press ENTER 

for “User Password “ screen.  Press 

ENTER to highlight the first digit and use 

the UP ARROW to enter the PW (Default 

PW=1234).

Press ENTER to move to the second digit 

to insert “2‐3‐4”. Press ENTER etc…  

Pressing the ENTER key enters the 

“On/Off Unit” screen as shown. Press 

ENTER key to highlight “SWITCH OFF” 

then press the UP or DOWN ARROW key 

to change to “SWITCH ON”. Press ENTER 

key to confirm your selection.  The CDU 

is now On.

On "Main Menu" (above) Highlight 

“Manufacturer setup” press ENTER for 

“Manufacturer Password “ screen.  Press 

ENTER to highlight the PW number 0000 ‐ 

Contact Motivair for password to this 

area of the menu.

Cooling Distribution Unit 

Client Settings Screen 

The following Client setup screens are provided to allow the client/end‐user to make 

adjustments and changes to the default settings if necessary to facilitate an operating 

parameter or site specific condition.  Set points for loop temp and differential pump pressure 

and all alarm thresholds are available on the following screens.

Page 23

CDU IOM Rev1.0

The Low Suction Pressure alarm set up 

screen is to set a minimum pressure on 

the pump suction to alert if pressure loss 

occurs.  This alarm can be disabled from 

this screen also.

The Set‐point/alarm setting screens are 

accessed with the UP/DOWN ARROW 

keys.  The first screen (shown) is the 

pump set‐point screen.  Press ENTER to 

highlight the parameter to change and 

use the UP/DOWN ARROW to change 

setting then press ENTER to confirm 

change.

The HXS outlet temperature set point is 

a PID loop setup (default). The set point 

and other parameters can be adjusted 

on this screen. The Regulation type can 

also be changed form PID to P 

(Proportional only) if desired.  (Factory 

defaults shown)

The next set of screens are ALARM 

setup. The High HXS out temp alarm is a 

differential setting from set point i.e. the 

set point (above) of 65°F  + the ° above 

setpt  10°F = 75°F alarm point temp 

delayed 60 sec. The Low HXS alarm ° 

below setpt ‐ 10°F = 55°F

The High HXP (Primary HX) Inlet 

temperature alarm set point of 65°F 

(default) may need to be adjusted per 

your site requirements and actual 

secondary loop set point and design 

conditions. 

Cooling Distribution Unit 

Client Setup 

Page 24

CDU IOM Rev1.0

Date and time input screen is to set the current 

date and time to display on the "Home screen" and 

history logs.  Note: This screen is not a clock screen. 

Only a set up page and will not display the correct 

time or date.

The probe calibration screens are for adding an 

offset to exact a probe reading max offset is 9.9°F. 

Also in client settings are the probe 

calibration screens for service. 

The water detection system (WDS) alarm 

setup is a On/Off parameter to enable 

the alarm function or not and to choose 

the action the pump should take upon 

an alarm condition. Both are defaulted 

to "Yes". 

Client Setup 

The Supervisor settings setup is a safety 

layer screen to prevent accidental 

On/Off by a BMS system or the digital 

I/O contacts. To use these functions they 

must be set to "Yes".

The BMS set‐up is to select your protocol 

BacNet ‐ Modbus ‐ Lon based on your 

selected communication option. The 

Baud rate is fixed based on protocol 

selected. The BMS address is for Modbus 

only. 

Cooling Distribution Unit 

Page 25

CDU IOM Rev1.0

Factory default parameter reboot screen 

to reboot the PLC to factory default 

conditions.

The Manufacturer setup area of the 

menu is password protected and should 

only be accessed with Motivair 

permission. All parameters in this section 

are preset per the specified CDU and 

should rarely need change.  The first 

screen shows the program version.

Setup screen for background options 

installed and enabled. 

Factory default Pump flow alarm time 

delays are set in this screen.

Manufacturer Setup 

Unit of Measure change over to degrees 

Celsius screen.

Cooling Distribution Unit 

Page 26

CDU IOM Rev1.0

The "ALARM" warning screen appears 

when any alarm is triggered. This screen 

along with a buzzer is to alert of an 

alarm condition.

Pressing the "bell" alarm key 1 time will 

silence the alarm buzzer and display the 

current alarm.  Pressing the alarm button 

a second time will acknowledge and 

clear the alarm if the condition has 

cleared. 

Following the acknowledgement of  the 

alarm (2nd press), the "No active alarms" 

screen will appear and direct you to the 

alarm history log.  If the alarm condition 

has not been cleared  (i.e. overload not 

reset) the alarm screen will re‐trigger 

another alarm.

Cooling Distribution Unit 

Alarms and warning 

Press "Enter" while on the above screen 

to enter the alarm log area.  The alarm 

log entry is recorded at every alarm and 

will store each alarm. The log records the 

alarm number sequence 001, 2, 3…, 

Time, date, and the alarm description. 

Alarms and warnings are to signal a problem or issue with the CDU or the system the CDU is 

connected refer to the Troubleshooting section for information on alarm causes and system 

checks

Page 27

Section 7

CDU IOM Rev1.0

Replace PLC 

{1} Check primary HXP inlet temp is below 55°F 

{2} Check cooling valve actuator is open (10vdc signal to 

actuator)

Cooling Distribution Unit 

CDU Pumps not operating {1} Unit "Off by keyboard" Switch unit "On"

Clock board alarm Failed clock board 

TROUBLESHOOTING ‐ General

High Voltage Warning:

 Serious injury or death could result from High voltage present in this equipment. 

Disconnect (open) all electrical safety switches and disconnects before attempting to open, 

troubleshoot, test or repair any components in this unit . 

Troubleshooting of electrical/mechanical equipment must be performed only by qualified and 

trained service technicians. Factory technical support is available please refer to "support" 

section of this manual.

TROUBLESHOOTING ‐ Non Alarms

Problem Check/Corrective action

No display ‐ No power 

TROUBLESHOOTING ‐ Alarms

Current alarm 

conditionAlarm trigger event Check/Corrective action

WDS alarm (water 

detection sensor)

Water on sensor or 

open sensor circuit

{1} Check for leak or wet sensor strip.  

{2} check for open circuit wire or end resistor.

Display active ‐ press alarm key & 

read alarmSee "troubleshooting alarms"

Alarm high HXS Out 

temp

Secondary HX outlet 

temp exceeded set 

point by amount = to 

"High HXS out temp" 

diff alarm set point ‐ 

default 10°F (Example 

65°F + 10°F = 75°F)  

{3} Check pump pressures and flow both primary and 

secondary loops

TROUBLESHOOTING

{1} Check building power supply and CDU disconnects are ON

No display ‐ with power 

{1} Check display network cable is plugged in at PLC and HMI 

{2} Check Fuses F1, F2, F3, F4, F7, F8, 

{3} Check transformer for 24v secondary voltage

Page 28

{2} Building chilled water pump/flow stopped

{3} Primary 2 way valve closed for extended time 

CDU IOM Rev1.0

B8 probe Rm RH %

B1 Pressure Probe 

alarmPressure transducer 

failed out of range or 

disconnected

{1} check probe connection to PLC connector and 

connection at the transducer 

B2 Pressure Probe 

alarm

{2} Replace Probe with known good transducer

Alarm Low Suction 

Pressure

Suction pressure fell 

below alarm set point 5 

psi for 90 sec {2} Check closed suction isolation valve.

(2) Check pump/VFD overload switch

{1} Check for loss of pressure/leak/air in system 

High Dew Point Temp 

warning

{5} Check for loss of pressure/leak/air in system 

{2} Check for failed open actuator/cooling valve

B6 Probe HXP InAll probe alarms are 

triggered by a failed 

or disconnected 

probe (electrically 

open or shorted). 

B7 Probe Rm DB

B3 Probe HXS Out {1} Check probe connection to PLC connector

B4 probe HXS in

Alarm originating in 

VFD and opening 

alarm contacts.

{1} Check VFD screen alarm code or history 

{1} Building primary chilled water supply too warm

Current alarm 

conditionAlarm trigger event Check/Corrective action

Room dew point has 

increased to within 2°F 

of set point

{1} Set point will be reset + 3°F above dew point

{2} Lower room Humidity levels ‐ vapor barrier 

Low Flow Pump A 

Alarm

{3} Check pumps rotation direction and operation

{4} Check for loop flow blockage/all valves closed 

{1} Same as VFD alarm 

triggered at the same time.

{2} Follow up with VFD trouble shooting manual

TROUBLESHOOTING ‐ Alarms

Cooling Distribution Unit 

Pump 1 or 2 overload The VFD alarm was 

triggered 

Alarm high HXP In 

temp

Heat exchanger primary 

inlet water temperature 

exceeded High HXP 

alarm set point ‐ Default 

65°F

Alarm VFD A

Pressure differential 

across pump dropped 

50 % below set point 

and exceeded time 

delay of 10 sec during 

running mode

{1} Check VFD screen for power/display or alarm  

Low flow Pump B 

Alarm

{1} Check valve minimum position setting at 0% (default 

= 0%)

{3} If none of above remedy issue replace PLC 

{2} Replace Probe

B5 probe HXP out

Alarm VFD B

{3} Check probe B3 calibration/accuracy

Alarm low HXS out 

temp

Secondary HX outlet 

temp below set point by 

amount = to "Low HXS 

out temp" diff alarm set 

point ‐ default 10°F 

(Example 65°F ‐ 10°F = 

55°F)

Page 29

Section 8

1.   Visual inspection of all piping and components for leaks.2.   Visual inspection of all components for integrity.   3.   Check and tighten all electrical connections.4.   Check auto vents stop valves are closed.5.   Check latches and hinges lubricate as necessary.6.   Check floor levelers are down and secure.7.   Check and record any alarm history since last maintenance.8.   Check all set points and record.9.   Check all temperature probes and calibrate as necessary.10. Check all pressure transducers and calibrate as necessary.11. Check system pressures and record.12. Check pump rotation settings and hour counters for even run times.13. Check PLC clock time and date are correct, adjust if necessary and record.14. Check WDS sensor location and integrity.15. Check actuator valve stem is tight and aligned.16. Check VFD parameters and alarm log record any alarms. 17. Check for dual power feed. If present test failover relay. 18. Obtain both loop water samples and lab test (once per year).19. Manual switch pumps and check same.20. Wipe clean all surfaces and close all panels.

CDU IOM Rev1.0

Service and maintenance of electrical/mechanical equipment must be performed only by 

qualified and properly trained service technicians.

Bi‐annual scheduled maintenance 

The scheduled maintenance recommended is two times per year and should include the 

following checks as a minimum.

Other site specific maintenance may be required which is outside the scope of this manual, 

be sure to consult with the proper personnel. 

A copy of all maintenance check lists and documentation should be left on site with the 

owner. 

Scheduled Maintenance

The CDU should be inspected and maintained at regular intervals to provide reliable long 

term operation.  

Cooling Distribution Unit 

If underfloor distribution header option is present this should also be inspected during the 

CDU maintenance service visit. 

MAINTENANCE

Page 30

Section 9

2. Valve Actuator

3. Air Vent

4. Expansion Tank

5. Pressure Gauge

5. Triple Duty Valve

6. Suction Diffuser

7. Pump

8. (12) 2.5" Gasket

9. Leveling Caster

CDU IOM Rev1.0

Spare PartsSPARE PARTS

Recommended spare parts are based on an individual site tolerance for down time, 

geographic location and site access requirements. Most of the CDU components are 

redundant.  

The following list of spare parts and recommended quantities is a minimum for any 

application. This is not a complete list of all parts used or required. Please contact your local 

distributor or Motivair for a full list of your model's spare parts and pricing.

1. Heat Exchanger

10. Door Handle & 

Latch assy

Cooling Distribution Unit 

Page 31

1 1 PLC - PCO3 - Medium Board1 PGD1 - HMI Remote Display1 WDS Leak Detection Control Module1 Main Pump 7.5hp, 3/60/230/460v,1 1 Belimo Actuator for Control Valve1 WDS Dew Point Sensor (wall remote mount)2 1 SPK. 316L Transducer,100 Psi1 SPKC00 - Transducer 6.5 Feet Cable4 2 Temperature Probe1 CM009107 - Water Detection Sensor Ribbon Kit1 Disconnect 25A Non fused1 Overload Motor Protector 6.3-10A1 1 Phase Monitor Relay1 150VA Transformer 460-120-244 4 1.5A CC Fuse2 2 1A Midget Fuse2 2 5A Midget Fuse1 460V 7.5HP Variable Speed Drive (VFD)1 Cabinet Cooling Fan

CDU IOM Rev1.0

Total Used

Qty Recommend

ed

Cooling Distribution Unit 

Spare Parts

Item Description

Page 32

Section 10

CDU IOM Rev1.0

DOCUMENTS & TABLES

Cooling Distribution Unit 

Page 33

CDU IOM Rev1.0

Cooling Distribution Unit 

Page 34

CDU IOM Rev1.0

Cooling Distribution Unit 

Page 35

CDU IOM Rev1.0

Electrical Schematics

Cooling Distribution Unit 

Page 36

CDU IOM Rev1.0

Cooling Distribution Unit 

Electrical Schematics

Page 37

CDU IOM Rev1.0

Cooling Distribution Unit 

Electrical Schematics

Page 38

Section 11

CDU IOM Rev1.0

www.motivaircorp.supportsystem.com also available through our web site link at 

www.motivaircorp.com/service‐support 

https://motivaircorp.supportsystem.com/account.php?do=create  to create an account.  

Once an account is created you can create support tickets from your email account using 

[email protected]

A service support portal is available at the following link 

Visit the Motivair service portal at 

WARRANTY:  This product carries a 1‐year Parts Only Warranty.  A copy of this warranty is 

shipped with your Cooling Distribution Unit.  An additional copy of your warranty can be 

obtained by contacting Motivair at the address listed on this document.  The manufacturer 

shall not be liable for any damages resulting from the misapplication or misuse of its 

products. THIS EXPRESS WARRANTY IS GIVEN IN LIEU OF ALL OTHER WARRANTIES, EXPRESS, 

OR IMPLIED, OR STATUTORY, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY 

AND FITNESS FOR A PARTICULAR PURPOSE, WHICH ARE HEREBY EXCLUDED.  MOTIVAIR SHALL 

NOT BE LIABLE FOR SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES OR LOSSES FROM 

ANY CAUSE WHATSOEVER, INCLUDING, WITHOUT LIMITATION, LOSS OF USE, COMMERCIAL 

PROFITS, OR CUSTOMER GOODWILL, AND ANY OTHER CLAIMS BASED ON CONTRACT OR 

TORT, WHETHER OR NOT ARISING FROM MOTIVAIR’S NEGLIGENCE.

Parts <> Service <> Technical support Email

Additional information on this product may be found at

www.chilleddoor.com

Motivair Corporation

85 Woodridge Drive

Amherst, New York, 14228

716‐691‐9222 Phone

716‐691‐9229 Fax 

Cooling Distribution Unit 

SUPPORT & WARRANTY

Support <> Contact <> Warranty Information

Factory Service & Support:

www.motivaircorp.com

Page 39

Section 12

Model: Model: Model:

Voltage Voltage Voltage

SCCR 10 kA SCCR 10 kA SCCR 10 kA

FLA 10.6 A FLA 9.6 A FLA 5.9 A

MCA 13.3 A MCA 12.0 A  MCA 7.4 A

MOP  23.9 A  MOP  21.6 A  MOP  13.3 A

Model: Model: Model:

Voltage Voltage Voltage

SCCR 10 kA SCCR 10 kA SCCR 10 kA

FLA 4.8 A FLA 3.9 A FLA 26.1 A

MCA 6.0 A MCA 4.9 A MCA 31.0 A

MOP  10.8 A  MOP  8.8A  MOP  58.6 A 

Model: Model: Model:

Voltage Voltage Voltage

SCCR 10 kA SCCR 10 kA SCCR 10 kA

FLA 23.6 A FLA 14.3 A FLA 11.8 A

MCA 28.0 A MCA 17.9 A MCA 14.0 A

MOP  53.0 A MOP  32.2 A MOP  26.5 A 

Model: Model: Model:

Voltage Voltage Voltage

SCCR 10 kA SCCR 10 kA SCCR 10 kA

FLA 9.5 A FLA 48.3 A FLA 42.0 A 

MCA 11.9 A MCA 60.4 A  MCA 52.5 A 

MOP  21.4 A  MOP  108.7 A MOP  94.5 A 

Model: Model: Model:

Voltage Voltage Voltage

SCCR 10 kA SCCR 10 kA SCCR 10 kA

FLA 25.5 A FLA 21.0 A FLA 17.0 A

MCA 31.8 A MCA 26.0 A MCA 21.3 A

MOP  57.2 A  MOP  47.0 A  MOP  38.3 A 

CDU IOM Rev1.0

MCDU‐40‐5‐80

380V/3Ph/50Hz

MCDU‐40‐6‐60

460V/3Ph/60Hz

MCDU‐40‐6‐75

575V/3Ph/60Hz

MCDU‐25‐6‐30

230V/3Ph/60Hz

MCDU‐25‐5‐80

380V/3Ph/50Hz

MCDU‐25‐6‐60

460V/3Ph/60Hz

MCDU‐25‐6‐75

575V/3Ph/60Hz

MCDU‐40‐6‐08

208V/3Ph/60Hz

MCDU‐40‐6‐30

230V/3Ph/60Hz

MCDU‐15‐6‐08

208V/3Ph/60Hz

MCDU‐15‐6‐30

230V/3Ph/60Hz

MCDU‐15‐5‐80

380V/3Ph/50Hz

MCDU‐15‐6‐60

460V/3Ph/60Hz

MCDU‐15‐6‐75

575V/3Ph/60Hz

MCDU‐25‐6‐08

208V/3Ph/60Hz

Supplemental electrical data by model

APPENDIX

Cooling Distribution Unit 

Page 40

Section 12

CDU IOM Rev1.0

Cooling Distribution Unit 

APPENDIX

NOTES:

Page 41