RP-TRANSCO-LVAC_I/C-1 - P
OC1
ABB
REF615
CT Ratio 2000:1
IEC - Normal Inverse
Pickup = 0.65 (0.3 - 5 xCT Sec)
Time Dial = 0.14
3x = 0.882 s, 5x = 0.599 s, 8x = 0.462 s
RP-TRANSCO-LVAC_BS - P
OC1
ABB
REF615
CT Ratio 2000:1
IEC - Normal Inverse
Pickup = 0.65 (0.3 - 5 xCT Sec)
Time Dial = 0.073x = 0.441 s, 5x = 0.3 s, 8x = 0.231 s
RP-AADC-LVAC-O/G-1 - P
OC1
ABB
REF615
CT Ratio 2000:1
IEC - Normal Inverse
Pickup = 0.65 (0.3 - 5 xCT Sec)
Time Dial = 0.13
3x = 0.819 s, 5x = 0.556 s, 8x = 0.429 s
RP-AADC-LVAC_I/C-1 - P
OC1
ABB
REF615
CT Ratio 2700:1IEC - Normal Inverse
Pickup = 0.95 (0.3 - 5 xCT Sec)
Time Dial = 0.2
3x = 1.26 s, 5x = 0.856 s, 8x = 0.659 s
RP-AADC-LVAC-BS - P
OC1
ABB
REF615
CT Ratio 2700:1
IEC - Normal Inverse
Pickup = 0.95 (0.3 - 5 xCT Sec)
Time Dial = 0.15
3x = 0.945 s, 5x = 0.642 s, 8x = 0.495 s
10.5 1 10 100 1K3 5 30 50 300 500 3K 5K
Amps X 1000 LVAC-TRANSCO-BUS_A (Nom. kV=0.415, Plot Ref. kV=0.415)
10.5 1 10 100 1K3 5 30 50 300 500 3K 5K
Amps X 1000 LVAC-TRANSCO-BUS_A (Nom. kV=0.415, Plot Ref. kV=0.415)
1K
.01
.1
1
10
100
.03
.05
.3
.5
3
5
30
50
300
500
Seconds
ETAP Star 12.5.0C
N7733-ZAKHER CASE:4.1 EF
Project: 220/33/11kV Zakher Grid
Location: Zakher Area of Al Ain
Contract: N7733
Engineer: JM
Filename: C:\ETAP 1250\N7733\N7733.OTI
Date: 21-01-2016
SN: LARSENTRN2
Rev: Base
Fault : Phase
Circuit: LVAC