7/25/2019 Case_3.2 Ef (Star Tcc)
1/1
K02-RP - G
OC1
11kV B/S
ABB
REF615
CT Ratio 2500:1
IEC - Normal Inverse
Pickup = 20 (1 - 100 xCT Sec)
Time Dial = 0.27
3x = 1.7 s, 5x = 1.16 s, 8x = 0.89 s
K03-RP - G
OC1
11kV AX. T/F
ABB
REF615
CT Ratio 150:1
IEC - Normal Inverse
Pickup = 20 (1 - 100 xCT Sec)Time Dial = 0.06
3x = 0.378 s, 5x = 0.257 s, 8x = 0.198 s
TR1-SBEF - G
OC1
20MVA SBEF
ABB
REF615
CT Ratio 1200:1
IEC - Normal Inverse
Pickup = 42 (1 - 100 xCT Sec)
Time Dial = 0.44
3x = 2.77 s, 5x = 1.88 s, 8x = 1.45 s
K09-RP - G
OC1
11kV I/C
ABB
REF615
CT Ratio 1200:1
IEC - Normal Inverse
Pickup = 42 (1 - 100 xCT Sec)Time Dial = 0.35
3x = 2.21 s, 5x = 1.5 s, 8x = 1.15 s
10.5 1 10 100 1K3 5 30 50 300 500 3K 5K
Amps X 10 Bus13 (Nom. kV=11, Plot Ref. kV=11)
10.5 1 10 100 1K3 5 30 50 300 500 3K 5K
Amps X 10 Bus13 (Nom. kV=11, Plot Ref. kV=11)
1K
.01
.1
1
10
100
.03
.05
.3
.5
3
5
30
50
300
500
Seconds
ETAP Star 12.5.0C
N7733-ZAKHER CASE:3.2 EF
Project: 220/33/11kV Zakher Grid
Location: Zakher Area of Al Ain
Contract: N7733
Engineer: JM
Filename: C:\ETAP 1250\N7733\N7733.OTI
Date: 21-01-2016
SN: LARSENTRN2
Rev: Base
Fault: Ground
Circuit: 20MVASBEF,11kVI/C,B/S,AUX.