Case_3.2 Ef (Star Tcc)

  • Upload
    joshi

  • View
    216

  • Download
    0

Embed Size (px)

Citation preview

  • 7/25/2019 Case_3.2 Ef (Star Tcc)

    1/1

    K02-RP - G

    OC1

    11kV B/S

    ABB

    REF615

    CT Ratio 2500:1

    IEC - Normal Inverse

    Pickup = 20 (1 - 100 xCT Sec)

    Time Dial = 0.27

    3x = 1.7 s, 5x = 1.16 s, 8x = 0.89 s

    K03-RP - G

    OC1

    11kV AX. T/F

    ABB

    REF615

    CT Ratio 150:1

    IEC - Normal Inverse

    Pickup = 20 (1 - 100 xCT Sec)Time Dial = 0.06

    3x = 0.378 s, 5x = 0.257 s, 8x = 0.198 s

    TR1-SBEF - G

    OC1

    20MVA SBEF

    ABB

    REF615

    CT Ratio 1200:1

    IEC - Normal Inverse

    Pickup = 42 (1 - 100 xCT Sec)

    Time Dial = 0.44

    3x = 2.77 s, 5x = 1.88 s, 8x = 1.45 s

    K09-RP - G

    OC1

    11kV I/C

    ABB

    REF615

    CT Ratio 1200:1

    IEC - Normal Inverse

    Pickup = 42 (1 - 100 xCT Sec)Time Dial = 0.35

    3x = 2.21 s, 5x = 1.5 s, 8x = 1.15 s

    10.5 1 10 100 1K3 5 30 50 300 500 3K 5K

    Amps X 10 Bus13 (Nom. kV=11, Plot Ref. kV=11)

    10.5 1 10 100 1K3 5 30 50 300 500 3K 5K

    Amps X 10 Bus13 (Nom. kV=11, Plot Ref. kV=11)

    1K

    .01

    .1

    1

    10

    100

    .03

    .05

    .3

    .5

    3

    5

    30

    50

    300

    500

    Seconds

    ETAP Star 12.5.0C

    N7733-ZAKHER CASE:3.2 EF

    Project: 220/33/11kV Zakher Grid

    Location: Zakher Area of Al Ain

    Contract: N7733

    Engineer: JM

    Filename: C:\ETAP 1250\N7733\N7733.OTI

    Date: 21-01-2016

    SN: LARSENTRN2

    Rev: Base

    Fault: Ground

    Circuit: 20MVASBEF,11kVI/C,B/S,AUX.