Page 1: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Applied Packaged Terminal Air Conditionerwith Top-mounted Hydronic Heat16" × 42 " Model PDAN

Catalog 1355-7

Page 2: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the
Page 3: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Catalog 1355 / Page 3 of 32

“McQuay” and “Incremental” are registered trademarks of McQuay International.

©2008 McQuay InternationalBulletin illustrations cover the general appearance of McQuay products at the time of publications and we reserve the right to make changes in

design and construction at any time without notice.

McQuay Applied Packaged Terminal Air Conditioners and Heat Pumps are certified in accordance with the Packaged Terminal Air-Conditioners certification program which is based on ARI Standard 310

and in accordance with the Packaged Terminal Heat Pump certification program, which is based on ARI standard 380.

Beyond “Standard” Expectations ...................................... 4-6 Introduction ..................................................................... 4 The Hydronic Experts Modes ............................................................................... 4 Controls-with built in hydronic logic ............................... 4 Customize to suit your needs ............................................ 4 Quiet Operation .............................................................. 4 Sound Comparison ............................................................ 4 Energy efficient for low operating costs ........................... 5 Room Comfort ................................................................ 5 Easy to use digital controls ............................................... 5 Dehumidification .............................................................. 5 Constant room temperature monitoring ............................ 5 Built-in Reliability & Durable Construction ................ 5 High-grade cabinetry ........................................................ 5 Positive condensate removal ............................................. 5 Room freeze protection ..................................................... 6 Electric heat override ........................................................ 6 Compressor protection ...................................................... 6 Memory recall .................................................................. 6 Corrosion Protection ......................................................... 6 Easy Installation and Service Design ............................ 6 Quick link connections ..................................................... 6 Easy to read LED diagnostics ........................................... 616" x 42" NYC Style Unit Features ................................. 7-10 Digital Touchpad Control ............................................... 9 Standard (non-programmable) Digital Touchpad ....... 9 Premium (7-day programmable) Digital Touchpad .. 10 Wireless Remote Control (optional) ............................ 10 Master-Slave (Primary/Secondary) control (optional) ... 10McQuay Model PDAC/PDHP Product Nomenclature ......11ARI Performance Data ........................................................ 12 Unit Weights - (lbs.) ........................................................ 12

Table of Contents

Dimensional Data ................................................................. 13Applications Considerations .......................................... 14-17 How to Select The Correct Wall Cabinet ........................ 14 Wall Opening Requirements – 16" × 42" ....................... 14 Electrical Service ............................................................ 14 Supply and Return Piping ............................................... 15 Typical Installation Types ....................................... 16-17 Standard Wall Sleeve Installation ................................... 16 Panel/Window Wall Sleeve Installation .......................... 17 Accessories–Options ....................................................... 18-24 Remote Wall Mounted Thermostats ...................... 18-21 Quick Selection Guide .................................................... 18 Wall Mounted, Non-programmable Thermostat ....... 20 Manual changeover one-stage heat and cool or one-stage heat pump ....................................................... 20 Wall Mounted, 7-day Programmable Thermostat ..... 20 Manual changeover one-stage heat and cool or one-stage heat pump ....................................................... 20 Wall Mounted, 7-day Programmable Thermostat ..... 21 Standard auto or manual changeover two stage heat / two stage cool ....................................................... 21 Optional Remote Sensor ............................................... 21 Wireless Temperature Control (T9000) & Remote Control Node (RCN) ....................................... 21 Wall Sleeves ................................................................... 22 Exterior Louvers For Standard Wall Sleeves ............. 22 Wall Sleeve Extension ................................................... 23 Louver Frame ................................................................ 23 Energy Saving Options ................................................. 24Wiring Diagrams ............................................................. 25-26 Digital control board with standby power ...................... 25 Digital control board without standby power ................. 26Engineering Guide Specifications .................................. 27-29

Page 4: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Page � of 32 / Catalog 1355

IntroductionIn 1958, McQuay introduced the Incremental®

system – the first through-the-wall, self-contained heat-ing and air conditioning system – and set the standard for reliable, efficient comfort control in multi-story building applications. With hundreds of thousands of installed units - many of which have been operating for more than 30 years - McQuay has earned its reputation as one of the most trusted names in individually-zoned comfort control.

As one of the world’s largest heating, ventilation and air-conditioning manufacturers, McQuay stands behind its products with the strength of a global organization. And with local McQuay representation and manufactur-ing facility in Auburn, New York, we can provide you the hands-on support you need to make your building project a success.

McQuay Applied Packaged Terminal Air Condi-tioners and Heat Pumps (Applied PTAC/PTHP) are manufactured to institutional quality standards at our ISO 9002 certified manufacturing facility. Strict atten-tion to manufacturing details—from raw materials to the unit packaging—gives you a quality product, delivered on-time to support your construction schedule. Every unit is ETL Listed, MEA agency approved, ARI certified for performance and exceeds ASHRAE 90.1 efficiency requirements.

The high design standards and heavy-duty construc-tion of the McQuay Applied PTAC/PTHP can provide you with years of reliable service, quieter operation and low operating costs. In fact, many of our comfort condi-tioners have been operating for more than 30 years.

The Hydronic ExpertsMcQuay is a leading manufacturer of hydronic heat

equipment. We specialize in providing hydronic heat with a host of configurable options.

Modes • Cooling only mode with hydronic heat • Cooling only mode with hydronic heat and supplemental electric heat. • Top mounted hydronic coil (steam or hot water)

Controls-with built in hydronic logic • Normally open/normally closed valve control • Heat fan lockout – prevent the fan from coming on until there is heat in the pipes.

Customize to suit your needsSelect from a wide variety of features, factory-sup-

plied options and accessories to build the ideal system for your application and help reduce labor and installation costs. See "Accessories - Options" on page 18 to 24 for details on options and accessories.

Quiet OperationThe GentleFlo™ cross-tangential fan wheel design

of Applied PTAC/PTHP units provides whisper quiet operation while delivering maximum airflow required for proper air circulation. Separate indoor and outdoor fan motors further reduce operating sound levels and costs.

The heavy gauge construction of the chassis and cabinet minimizes vibration for quieter operation. Vibration isolators on the rotary compressor keep it running smoothly and quietly. The unit bulkhead is fully insulated to decrease outdoor sound transmission.

Beyond “Standard” Expectations

Sou

nd C

ompa

rison

Typi

cal L

ibra

ry

App

lied

PTA

C -

Size

012

C

oolin

g O

nly

- Low

Spe

ed

Appl

ied

PTAC

- Si

ze 0

12

Fan

Onl

y - L

ow S

peed

Con

vers

atio

nal S

peec

h

Page 5: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Catalog 1355 / Page 5 of 32

Energy efficient for low operating costsApplied PTAC/PTHP units are built with quality

components and exceed industry standards for energy efficiency for both new construction and replacement ap-plications. This helps lower your utility costs by keeping energy consumption down and may allow you to qualify for electrical power company rebates. Unit performance is ARI certified with an Energy Efficiency Ratio (EER) up to 12.1 EER and a heat pump Coefficient of Performance (COP) up to 3.6.

Built-in energy management logic comes standard with the unit’s digital controls. Features such as the Sleep Function allow users to decrease the set temperature at night and during unoccupied periods to conserve energy. For heat pump applications, electric heat comes on only when the outdoor temperature is below 35°F, maximizing the amount of time the unit operates in the more efficient heat pump mode.*Consult your utility provider for rebate opportunities.

Room ComfortEasy to use digital controls

The unit control pad offers digital readout and is easy to use when selecting fan speed, mode of operation and temperature setting. A precise digital temperature display provides guests with an exact comfort setting, thereby eliminating uncomfortable temperature swings and costly overheating/overcooling associated with non-digital electromechanical controls.

Standard digital touchpad control

DehumidificationThe cool/dry mode automatically controls humidity

by extending the cool cycle without sacrificing comfort for dehumidification. This mode comes standard with all units. The desired cooling mode (cool/dry for added dehumidification or regular cool) can be selected and locked by the owner or facility manager to meet comfort and dehumidification requirements.

Constant room temperature monitoringUnits are designed to automatically sample the room

temperature and adjust operation to meet desired tem-perature set points.

Built-in Reliability & Durable ConstructionHigh-grade cabinetry

Applied PTAC/PTHP cabinets are constructed of 18-gauge steel with baked on powder coat paint for maximum durability and aesthetic appeal. Grilles have two-way adjustment allowing air to be directed where it is needed.

Positive condensate removalOur unique three level sloped basepan design pro-

vides positive condensate removal to prevent condensate build-up or overflow.

Positive condensate removal

Beyond “Standard” Expectations

Expect more than Replacement or New Construction efficiency

12.0

11.0

10.0

9.0

8.0

7.0 * ASH

RA

E 90

.1

Rep

lace

men

t R

equi

rem

ent

Orig

inal

Mod

el

8.9

* Based on original model PMES size 012 @ 230 V

8.7

New

App

lied

PDA

C/P

DH

P - S

ize

012

11.2

14% Efficiency

Improvement

Page 6: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Page � of 32 / Catalog 1355

• Condenser Coil – Protected with E-Coating, made up of an epoxy primer and acrylic top coat that is electrostatically applied and baked on. Also, there is a dielectric strip located between the condenser and base pan.

• Condenser Fan Blade and Slinger Ring – Constructed of Noryl® PPO which is a strong engi-neering plastic that has excellent flame resistance and dimensional stability over a wide range of service temperatures. Noryl has low moisture absorption, excellent strength and stiffness.

• Condenser Fan Motor – Specially coated by the manufacturer with zinc end plates.

• Compressor – Protective coating applied by the manufacturer on the exterior to enhance equipment life and performance.

• Outdoor Louver – Made of aluminum, etched and anodized for maximum corrosion protection. Avail-able in stamped or architectural styles.

Easy Installation and Service DesignQuick link connections

Applied PTAC/PTHP units are designed for easy access with quick link connections to the control box. The simple slide in/slide out configuration makes it easy to access the electric heater, indoor and outdoor fans, motors, and compressor.

Easy fan removal

Easy to read LED diagnosticsSensors in the unit continually monitor the indoor

coil, outdoor coil, and outdoor air conditions. If abnormal conditions are detected, an error code is displayed, removing the guess work in troubleshooting a unit.

Easy fan motor removal

Room freeze protectionWhen the unit senses temperatures of 40°F or lower

in an unoccupied room, the heat mode is automatically initiated to prevent freezing. The outdoor fan and com-pressor are stopped to help prevent coil freeze.

Electric heat overrideHeat pump units can be manually switched to electric

heat, providing added freeze protection if the heat pump mode is not available due to a compressor failure.

Compressor protectionThe life of the compressor is extended through built

in protection logic such as: • High temperature protection if the

compressor temperature exceeds 154°F • Minimum run time • Minimum off time • Random restart after a power outage • Low ambient lockout when the outdoor air

temperature falls below 35°F

Memory recallControl settings are saved in a non-volatile memory,

allowing the last settings to be recalled after a loss of power.

Seacoast construction Application of air conditioning equipment in a cor-

rosive environment requires special consideration. The corrosive nature of salt water vapor, chlorine and acid vapor, demands a unit that can withstand these environ-ments. Any metal portion that is exposed to a corrosive vapor must be specially treated.

There is no coating or treatment that will allow a unit to last indefinitely, however, the Applied PTAC is avail-able with parts that receive special corrosion protection that can help dramatically extend the life of the unit.

• Wall Sleeve – The entire Custom Wall Sleeve (CWS) or cabinet/wall sleeve is constructed of G-60 galvanized, phosphatized, 18-gauge steel. Treated inside and outside with a baked-on epoxy based powder coat paint to protect it from the corrosive effects of salt spray. The Basic Wall Sleeve (BWS) is constructed of galvanized, primed and pre-painted antique ivory 18-gauge steel.

• Base Pan – Protected with Casing Guard coating, providing a comprehensive corrosion protection for all exposure conditions.

Beyond “Standard” Expectations

Page 7: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Catalog 1355 / Page � of 32

A. Heavy-Duty Grille• Two-way adjustment allows air to be directed

where it is needed.• Option for extruded aluminum grille. B. Heating Chassis• Top-mounted hydronic (steam or hot water) heat for

easy installation.

C. Room Cabinet• Heavy-gauge steel with powder paint coating

for maximum scratch and dent resistance.• Removable for easy access to filters, controls and piping for routine maintenance and

service.• Option for custom cabinet colors.• Custom depth for varying wall thicknesses.• Available in front or bottom return configurations.

D. Kick Plate• Adjustable height and custom colors for varying floor

treatments. E. Digital Touchpad Control• Reliable and easy to read and operate.• Continuous or cycle indoor fan operation.• Automatic room freeze protection.

F. Wall Sleeve• Heavy-gauge steel with powder paint coating for

maximum scratch, dent and corrosion resistance.• Custom wall sleeve depths available.• Options for brick or panel/curtain wall applications.

G. Outside Air Louver• Heavy-duty, architectural, extruded aluminum to

resist weathering.• Option for recessed louver.

H. Cooling Chassis• Energy efficient, quiet and reliable rotary compressor.

Digital Touchpad Control

Unit Features – 16" × 42" Model PDAN with Top-Mounted Hydronic HeatComplete solution, high efficiency and very quiet – five sizes from 7,000 to 17,000 Btuh

Infrared Remote (Option)

A

B

C

D

E

F

G

H

Page 8: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Page � of 32 / Catalog 1355

Indoor fan motor

Permanent Cleanable FiltersRoom side return air is filtered through this permanent, washable polypropylene mesh filter. It is UL listed class II, 38% average arrestance efficiency (ASHRAE test), with low resistance to airflow (0.02 w.g. at 300 cfm), and high dust holding capacity (55 grams).• Filters all return air to promote good indoor air quality.• Easy to access and maintain.

Optional Automatic Motorized Outside Air Damper • Opens when unit is operating to bring in outside air

for improved indoor air quality.• Closes when unit is idle to prevent cold drafts.• Touchpad configurable to select damper CLOSED or

AUTO Operation.

Separate Indoor and Outdoor Fans (not shown)• Two fan motors provide lower operating costs and quieter operation.• Provide more flexible options for architectural

louvers or special condenser air treatments.

Fan Motors• High efficiency, quiet PSC type.• Permanently lubricated for extended life.• Outdoor fan motor is totally enclosed to help prevent

damage from driving rain or excess condensate accumulation in humid climates.

Compressor• Reliable, high efficiency rotary compressor,

hermetically sealed and designed for continuous operation.

• Isolated to minimize vibration and sound transmission for quiet operation.

High Capacity Heat Transfer Surfaces• Finned/tube coils incorporate state-of-the-art

technology.• Unique design provides high efficiency and low air

pressure drops.• Allows for easy cleaning during scheduled

maintenance.

Outdoor coil

Indoor coil

Permanent, washable polypropylene mesh filter(Shown in front return configuration)

Outdoor fan motor

Unit Features – 16" × 42" Model PDAN with Top-Mounted Hydronic Heat

Page 9: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Catalog 1355 / Page � of 32

Keys and indicators labels ON/OFF, FAN SPEED, MODE

� Push Buttons FAN MODE, SLEEP

Temp buttons: for

Temp UP and for Temp DOWN

� LED Indicators SLEEP, COOL, COOL/DRY, FAN, HEAT, HIGH, LOW, CYCLE, CONT.

LED 2 Digit Displays No Label

Display function legendTr = Room TemperaturehI = High Room TemperatureLo = Low Room TemperatureLA = Low Ambient LockoutrT = Remote Thermostat ControltP = Touchpad Controlt = TimeTs = Temperature Setpoint Rf = Room Freeze ConditionCF = Coil Freeze ProtectionF = FahrenheitC = CelsiusLC = Control Lockout Mode

Remote thermostat control The remote thermostat can be any thermostat that

can interface with an electronic thermostat via RCBW-YG terminals. The Control Selection jumper must be in T’STAT position. During a call the remote thermostat will pass R back to the controller on a respective termi-nal. The push buttons on the touchpad become inactive in the remote thermostat mode. However, the control pad LED display will indicate the mode of operation, and the room temperature.

Digital Touchpad ControlThe PDAC/PDHP Standard Touchpad Control is

used to control both an integral air conditioner and a source of heat. The user will by default control the elec-tronic controller via the touchpad. The user can select with a jumper for the unit to receive commands from a remote thermostat.

Standard (non-programmable) digital touchpad• Provides 5-selectable modes of operation: Sleep, Cool, Cool/Dry, Fan, Heat• Temperature can be displayed in Fahrenheit (default) or Celsius

Inputs and outputs • Indoor coil sensor, (ICS)• Outdoor coil sensor, (OCS)• Indoor air sensor, (IAS)• Outdoor air sensor, (OAS)• Remote thermostat, T’STAT (RCBYWG)• Power supply: (24VAC) • Line voltage input, (L1, L2)• Indoor fan standby voltage, (L1STB L2STB)• Control selection: (LUI, T’STAT • Model selection: (AC/E, HP, HP/E)• Time delay bypass, (TEST) • Indoor off fan cycle: (FAN, OFF CYCLE–10, 20, 30, 1 HR)

Outputs • Compressor output, COM• Indoor fan, BLOWER LO, HI• Outdoor fan, OUTDOOR FAN• Electric heater, ELE• Reversing valve, REV VALVE

�- LED Indicators

LED 2-Digit Display

�- Push Buttons

Unit Features – 16" × 42" Model PDAN with Top-Mounted Hydronic Heat

Page 10: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Page 10 of 32 / Catalog 1355

Display inputs

ON/OFF Turn the unit on and off

Increase the temperature set point

Decrease the temperature set point

MODE Select one from the following modes: COOL, COOL/DRY, FAN, or HEAT

FAN MODE Change the mode of fan operation between CYCLE and CONTINUOUS

FAN SPEED Change the speed of the fan between HIGH and LOW

SLEEP Activate the sleep mode and set the sleep time

PROG ON/OFF Button to activate and deactivate the program mode

LED with Program Setting Display

�- Push Button Display Inputs

�-LED Indicators

Premium (7-day programmable) Digital Touchpad• Provides all the features of the Standard Controller,

plus master/slave, infra-red control, auto damper, wall mounted remote thermostat, heat fan lockout

Wireless Remote Control (Optional)Note: Only available on select models.

The remote consists of 10 push-buttons• Power: Functions the same as the ON/OFF button on

the touchpad.• Sleep: Functions the same as the SLEEP button on the

touchpad. Mode buttons• Heat, Cool, Cool/Dry, Fan: Performs the same function as the MODE button on

the touchpad and allows user to select the specific mode of operation using only one button.

• Temp buttons +, – : Functions same as the buttons on the touchpad and

allows the user to change the setpoint. • Fan speed buttons (high & low): Performs same function as the FAN SPEED button

on the touchpad and allows user to select the specific speed using only one button.

The remote must be aimed in a line of sight of the window in the upper right corner on the front panel, at less than a 45° angle from center of the window.

Note: The control board will beep when any button is pressed on the remote control to confirm signal.

Master-Slave (Primary/Secondary)Control (Optional)

A single master unit can be configured to control up to 32 slave units. The master unit controls on/off, fan, settings and sleep functions for the secondary units.

Unit Features – 16" × 42" Model PDAN with Top-Mounted Hydronic Heat

Page 11: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Catalog 1355 / Page 11 of 32

McQuay Model PDAN Product NomenclatureNote: For Illustration purposes only. Not all options available with all models. Please consult a McQuay Sales Representative for specific availability.

Damper TypeDamper ControlA = Automatic (Required for Hydronic Heating Subbase)M = ManualY = None

Unit TypeP = PTAC

Product IdentifierPDAN = Air Conditioner

Design Series1 = A Design 12 = B Design 23 = C Design 3� = D Design �5 = E Design 5

Unit Size00� = �,00000� = �,000012 = 12,000015 = 15,00001� = 1�,000 (Cooling Only)

VoltageA = 115-�0-1E = 20�/230-�0-1J = 2�5/2��-�0-1P = 20�/230-�0-1 w/stndby 115-�0-1

Brand NameM = McQuay

RefrigerantR = R-22

Heating TypeE = Electric HeatH = HydronicA = Hydronic w/Intermediate Electric

Electric HeatA = 2.5 KwB = 3.5 KwC = 5.0 KwY = None

Hydronic Heat TypeS = Steam Top Mount (Normally Closed)H = Hot Water Top Mount (Normally Open)Y = None

SKUA = StockB = Build to Order

P DAN 1 009 E M R H A B A M A A E

ControlsControl Board TypePNUY = Premium, Non-Programmable, Unit MountedPNWY = Premium, Non-Programmable, Wall MountedPNRY = Premium, Non-Programmable, InfaredPPUY = Premium, Programmable Unit MountedPPWY = Premium Programmable, Wall MountedPPRY = Premium Programmable, Infrared

Room InterfaceCabinet TypeA = Top-Mounted Hydronic Flat top,

Bottom Return

Power ConnectionL = Long Cord – �2" (Standard)S = Short Cord – 1�" (Optional)Y = None

Upgrade PackagesS = SeacoastY = None

WarrantyA = StandardE = ExtendedX = Special

Page 12: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Page 12 of 32 / Catalog 1355

UNITSIZE 007 009 012 015 017 Total Btuh(1) �,�00 �,�00 �,�00 10,200 10,200 10,200 12,�00 12,�00 12,�00 1�,�00 1�,�00 1�,�00 Sensible Btuh(1) �,�00 �,�00 �,�00 �,�00 �,�00 �,�00 �,�00 �,�00 �,�00 �,�00 �,�00 12,000 Cooling EER 12.10 12.10 12.10 11.�0 11.�0 11.�0 11.20 11.20 11.20 10.10 10.10 �.�0 Volts 115 20�/230 2�5 115 20�/230 2�5 115 20�/230 2�5 20�/230 2�5 20�/230 Full Load Amps(5) �.03 3.3� 3.0� �.�3 �.�� �.0� 11.�� 5.�3 5.1� �.�3 �.�� �.�5 Watts(1) �53 �53 �53 ��� ��� ��� 1,1�3 1,1�3 1,1�3 1,��5 1,��5 1,��� Volts 20�/230 2�5 20�/230 2�5 20�/230 2�5 20�/230 2�5 20�/230 kW 2.2/2.� 2.2/2.� 2.2/2.� 2.2/2.� 2.2/2.�

2.5 kW Amps 10.�/11.� 10.�/11.� 10.�/11.� 10.�/11.� 10.�/11.�

ElectricHeat(3) kW 3.1/3.� 3.5 3.1/3.� 3.5 3.1/3.� 3.5 3.1/3.� 3.5 3.1/3.�

3.5 kW Amps 15.2/1�.� 13.� 15.2/1�.� 13.� 15.2/1�.� 13.� 15.2/1�.� 13.� 15.2/1�.�

5.0 kW

kW 3.�/�.� 5.0 3.�/�.� 5.0 3.�/�.�

Amps 1�.0/21.0 1�.3 1�.0/21.0 1�.3 1�.0/21.0

Valve & Fan Motor Amps 0.�� 0.�1 0.32 0.�� 0.�1 0.32 0.�� 0.�1 0.32 0.�1 0.32 0.�1

HydronicHeat(�)

Hot Water (Btuh) Hi/Lo 1�,�00/15,�00 1�,�00/15,�00 1�,�00/15,�00 1�,�00/15,�00 1�,�00/15,�00 Steam (Btuh) Hi/Lo 22,�00/22,300 22,�00/22,300 22,�00/22,300 22,�00/22,300 22,�00/22,300 HeatPumpModel Total Btuh(2) �,300 �,300 �,300 �,�00 �,�00 �,�00 11,�00 11,�00 11,�00 1�,000 1�,000 Sensible Btuh(2) �,�00 �,�00 �,�00 �,�00 �,�00 �,�00 �,000 �,000 �,000 �,100 �,100 EER 11.2 11.2 11.2 11.2 11.2 11.2 10.5 10.5 10.5 �.5 �.5

Cooling Volts 115 20�/230 2�5 115 20�/230 2�5 115 20�/230 2�5 20�/230 2�5 20�/230

Full Load Amps �.03 3.3� 3.0� �.�3 �.�� �.0� 11.�� 5.�2 5.0� �.�2 �.3� Watts(1) �52 �52 �52 ��� ��� ��� 1,11� 1,11� 1,11� 1��� 1��� Btuh(2) �,000 �,000 �,000 �,100 �,100 �,100 10,�00 10,�00 10,�00 13,�00 13,�00 Reverse COP 3.� 3.� 3.� 3.52 3.52 3.52 2.�5 2.�5 2.�5 2.�1 2.�1 Cycle Volts 115 20�/230 2�5 115 20�/230 2�5 115 20�/230 2�5 20�/230 2�5 20�/230 Heat Full Load Amps �.03 3.3� 3.0� �.�3 �.�� �.0� 11.�� 5.�2 5.0� �.�2 �.3� Watts(2) 5�0 5�0 5�0 �5� �5� �5� 1,0�3 1,0�3 1,0�3 1,�00 1,�00 ElectricHeater Voltage 2�0V 2�5V 2�0V 2�5V 2�0V 2�5V 2�0V 2�5V 2�0V

Minimum 2.5 Kw 15.51 15.51 15.51 15.51 15.51

Circuit

3.5 Kw 21.�2 1�.0� 21.�2 1�.0� 21.�2 1�.0� 21.�2 1�.0� 21.�2

Ampacity 5.0 Kw 2�.3� 2�.1 2�.3� 2�.1 2�.3�

Hydronic Heat �.1� 3.�2 3.52 10.�� 5.2� �.�� 13.�2 �.�2 5.�5 �.�2 �.5� �.�2

TimeDelayFuses 2.5 Kw 15 15 15 15 15

orTypeHACR

3.5 Kw 20 15 20 15 20 15 20 15 20

CircuitBreaker 5.0 Kw 25 20 25 20 25

Hydronic Heat 15 15 15 15 15 15 15 15 15 15 15 15

NEMA 2.5 Kw �-15R �-15R �-15R �-15R �-15R Receptacle 3.5 Kw �-20R �-20R �-20R �-20R �-20R �-20R �-20R �-20R �-20R TypeRequired 5.0 Kw �-30R �-30R �-30R �-30R �-30R Hydronic Heat 5-15R �-15R �-20R 5-15R �-15R �-20R 5-15R �-15R �-20R �-15R �-20R �-15R High Low High Low High Low High Low High Low Airflow Cool 3�0 330 3�0 330 3�0 330 3�0 330 5�0 3�0 CFM Heat 3�0 3�0 3�0 3�0 3�0 3�0 3�0 3�0 550 3�0 Vent 50 �0 50 �0 50 �0 50 �0 �0 50

Model 007 009 012 015 0171�" × �2" PDHP (Packaged) 1��.0 153.5 15�.� 1�2.1 1�" × �2" PDAC (Packaged) 1��.5 152.0 152.� 1�0.� 1�0.�1�" × �2" PDHP (Chassis) 131.0 13�.5 13�.� 1��.1 1�" × �2" PDAC (Chassis) 12�.5 13�.0 13�.� 1�5.� 1�5.�

ARI Performance Data

Unit Weights - (lbs.)

(1) Based on ASHRAE and ARI test conditions of �5°F DB/�5°F WB outside, �0°F DB/��°F WB inside.(2) Based on ASHRAE and ARI test conditions of ��°F DB outside, �0°F DB inside.(3) Electric Resistance Heat Watts × 3.�1 = Btuh. Electric Heating Watts and Amps include Indoor Fan Motor.(�) Water – Based on ASHRAE and ARI test conditions of 200°F EWT, 180°F LWT, 70°F EAT with a 1.8 gpm flow rate.(5) Cooling Full Load Amps includes Compressor, Indoor Air Fan and Outdoor Air Fan.

= Not Applicable

Page 13: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Catalog 1355 / Page 13 of 32

11⁄4" RECESS FOR ARCHITECTURAL LOUVER “A” – IN. (MM) “D” – IN. (MM) “B” – IN. (MM) ROOM CABINET WALL SLEEVE WALL THICKNESS 1�3⁄� (���) 133⁄� (3��) �3⁄�–53⁄� (121–1��) 1�3⁄� (�51) 133⁄� (3��) 53⁄�–�3⁄� (1��–1�1) 1�3⁄� (�25) 133⁄� (3��) �3⁄� –�3⁄� (1�1–1��) 153⁄� (�00) 133⁄� (3��) �3⁄� –�3⁄� (1��–222) 1�3⁄� (3�5) 133⁄� (3��) �3⁄� –�3⁄� (222–2��) 133⁄� (3��) 133⁄� (3��) �3⁄� –103⁄� (2��–2�3) 123⁄� (32�) 133⁄� (3��) 103⁄� –113⁄� (2�3–2��) 113⁄� (2��) 133⁄� (3��) 113⁄� –123⁄� (2��–32�) 103⁄� (2�3) 133⁄� (3��) 123⁄� –133⁄� (32�–3��) 103⁄� (2�3) 1�3⁄� (3�5) 133⁄� –1�3⁄� (3��–3�5) 103⁄� (2�3) 153⁄� (�00) 1�3⁄� –153⁄� (3�5–�00) 103⁄� (2�3) 1�3⁄� (�25) 153⁄� –1�3⁄� (�00–�25) 103⁄� (2�3) 1�3⁄� (�51) 1�3⁄� –1�3⁄� (�25–�51)

Note: Electricalrough-inshouldbelocatedbehindkickplate(removablefront)andbelowwallsleeve.

52" (1320mm)

11⁄2"(3�mm)

1�1⁄2"(��5mm)

Wall Space For Piping Rough-in(Typ. R.H. & L.H.)

3"(��mm) Min.

3"(��mm)

Kickplate (RemovableFront) �/�"

(22mm)

Wall Thickness“B”“A”

11⁄�" (32mm)2�⁄�"

(��mm)

1�"(�0�mm)“D”�1⁄�"

(232mm)51⁄2"

(1�0mm)�/�"

(22mm)

15⁄�" (�1mm)

15⁄1�"(33mm)

3" (��mm) Min. Kickplate Height

Standard Size Wall Sleeve

Unit Dimensions – Chassis

Unit Dimensions – Wall Sleeve, Cabinet & Louver

Premium Digital Touchpad Control

Dimensional Data

Page 14: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Page 1� of 32 / Catalog 1355

Panel Wall (thin)

Frame and Brick

Masonry Wall (thick)

1�1/�" × �21/�" Wall Sleeve Rough Opening or 1�5/�" × �25/�" When using a Louver Frame

Floor

Concrete Pillars

Steel Studs

1�" × �2" Wall Sleeve

Lintel (by others)

�21/�" Wide Wall Sleeve Rough Opening

1�1/�" High

Wall Construction ExamplesHow to Select The Correct Wall CabinetThe minimum cabinet depth is 10.75". This is required

because the wall sleeve MUST extend a minimum of 1.625" into the room and 9.125" is required to cover the chassis. This totals 10.75".

Standard cabinets range from 10.75" to 18.75" in 1" increments. For other requirements, consult the factory.

If the wall sleeve extends into the room more than 1.625", add the inside measurement to the 9.125" required to cover the chassis. This will be the depth of the wall cabinet.For example:

The wall sleeve extends 3.25" into room + 9.125" = 12.75" deep cabinet or if the wall sleeve extends 9.25" into room + 9.125" = 18.75" deep cabinet would be the closest fit.

Wall Opening Requirements – 16" × 42"When roughing in the opening for the wall sleeve,

sufficient clearance from the walls and floor is required. The wall sleeve should be positioned a minimum of 5/8" from the finished side wall to accommodate the room cabinet. A minimum distance of 3" above the finished floor is required for return air.

The rough opening should measure 161/4" high × 421/4" wide. When using a louver frame, the opening must mea-sure 165/8" × 425/8". Louver frames should be used for panel wall and thin wall applications to provide positive anchoring to the wall.

Electrical ServiceAll wiring should be in accordance with all local and

National Electrical Code requirements.Units are supplied with an attachment cord and plug

which exit from the bottom of the conditioner on the control side. The cord for 115V, 208V and 230V has a usable length of 72" (1829mm) from where it exits the conditioner. The use of extension cords to increase the length of the plug/cord set is not recommended. Units to operate on 265V are supplied with a 18" (457mm) cord for connection to a subbase.

The attachment plug size should be used to determine the circuit ampacity and overcurrent protection. Time delay, overcurrent protection devices are recommended to prevent unit damage and to avoid nuisance tripping.

Receptacles are generally located beneath the condi-tioner, on or recessed in the wall so it is concealed by the conditioner overhang and kickplate (see page 17).

Wall Sleeve ExtensionSplitters

1�" × �2" Wall Sleeve

Lintels (by others)Room Side

Application Considerations

Page 15: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Catalog 1355 / Page 15 of 32

Supply and Return PipingSame End Connections

Room Cabinet

Wall Sleeve

Opposite End ConnectionsHot Water – Opposite End Supply or Return Steam – Right-hand Supply, left-hand Return

Steam – Left-hand Supply, Right-hand Return

LeftSide RightSide

LeftSide RightSide

LeftSide RightSide

Front Panel

Wall Sleeve

2"

Wall Sleeve

2�/�" 2"

2�/�"

�2"5"

�.�3"

�.�3"

�2"

2�/�"

5"

Wall Sleeve

�.�3"

5"

3�/�"

2�/�"

2"

11/�" Architectural Louver

�2"

Note: Piping connections are 5/8" O.D. copper sweat and are symmetrical R.H. or L.H. for same end supply and return.

�.�3"

Steam Supply Hot Water Return

Steam ReturnHot Water Supply

Steam Return, Hot Water Supply

Steam Supply, Hot Water Return

Application Considerations

Note: Piping connections are 5/8" O.D. copper sweat and are symmetrical R.H. or L.H. for same end supply and return.

Page 16: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Page 1� of 32 / Catalog 1355

“A” “D” “B” RoomCabinet WallSleeve WallThickness 1�3/� (��� mm) 133/� (3�� mm) �3/�–53/� (121–1�� mm) 1�3/� (�51 mm) 133/� (3�� mm) 53/�–�3/� (1��–1�1 mm) 1�3/� (�25 mm) 133/� (3�� mm) �3/� –�3/� (1�1–1�� mm) 153/� (�00 mm) 133/� (3�� mm) �3/� –�3/� (1��–222 mm) 1�3/� (3�5 mm) 133/� (3�� mm) �3/� –�3/� (222–2�� mm) 133/� (3�� mm) 133/� (3�� mm) �3/� –103/� (2��–2�3 mm) 123/� (32� mm) 133/� (3�� mm) 103/� –113/� (2�3–2�� mm) 113/� (2�� mm) 133/� (3�� mm) 113/� –123/� (2��–32� mm) 103/� (2�3 mm) 133/� (3�� mm) 123/� –133/� (32�–3�� mm) 103/� (2�3 mm) 1�3/� (3�5 mm) 133/� –1�3/� (3��–3�5 mm) 103/� (2�3 mm) 153/� (�00 mm) 1�3/� –153/� (3�5–�00 mm) 103/� (2�3 mm) 1�3/� (�25 mm) 153/� –1�3/� (�00–�25 mm) 103/� (2�3 mm) 1�3/� (�51 mm) 1�3/� –1�3/� (�25–�51 mm)

Typical Installation TypesStandard Wall Sleeve InstallationMasonry Wall Construction ApplicationWall Sleeve End View Using Brickstop

D

Outside Louver

B

1" Finished Floor

Wall Sleeve

A

Wood Stool

Casement Window with Insulating Clear Glass

2'-�1/2"

Exposed Projection Concrete Slab

�-1/�"

Brick

1'-�

"�"

2'-�

"

BrickRoom Cabinet

Notes:1. Wall sleeve to extend a minimum of 11/4" past finished sheetrock.2. Wall sleeve should be installed recessed 11/4" from face of

brick so that when louver is installed it is flush with face of building.

Optional Flange

Standard Size Wall Sleeve

Application Considerations

Page 17: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Catalog 1355 / Page 1� of 32

Notes:1. Flange dimension “X” is “as required” and is usually

provided to the factory to be secured to wall sleeve during fabrication.

2. Dimension "B" is wall thickness (see table on page 16).3. Given dimensions are standard.* These are typical but may be adjusted upon request-

by contacting your local McQuay Representative.

Typical Installation TypesPanel/Window Wall Sleeve Installation Wall Sleeve Depth, Wall Thickness, & Optional Continuous Flange Dimensions

Optional Continuous

Flange 1�"

*11/�"

�2"

Outdoor Side of Sleeve

X

�3/�"

Optional Leveling Leg

*133/�" B

Leveling Leg to Support (Optional)

Cabinet

Hydronic Heat Coil Section

31/2" Thick Batt Insulation

15/�" Metal Stud 1�" O.C.

Window Stool

Insulation Wet Panel

133/�" X

Gr Gr Gr Gr 1-23/�" dia. 13/�" dia. 13/�" dia. 21/�" dia. �-20R 5-20R �-20R �-30R 20 Amp, 2�5V 20 Amp, 120V 20 Amp, 202V 30 Amp, 250V

NEMA Receptacles

Application Considerations

Page 18: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Page 1� of 32 / Catalog 1355

Thermostat Item Number 107095701 107095801 107095901

Single Stage • • • Two Stage • Heat Pump • • • Manual Changeover (Cool/Off/Heat) • • • Settable Differential Range • Auto Changeover • Status LEDs • Backlit Display • • �-Day Programmable • • Temporary and Vacation Hold • • Programmable Fan On/Off Delay • Non-Programmable • Hard Wired • • • Wireless � or 5 Wire Capable • • • Freeze Protection • Fan Switch - On/Auto • • • Lockout Feature • Fahrenheit or Celsius Display • Remote Sensor Option • Power Loss Memory Protection • • • Anti-Short Cycle Delay • • • Max/Min. Set Point Control • Energy Management Interface California Title 2� Compliant • • •

Wall Mounted Thermostats – Quick Selection Guide

Accessories–Options

Page 19: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Catalog 1355 / Page 1� of 32

Remote Wall Mounted Thermostats Remote Thermostat Control

The Remote Thermostat can be any thermostat that can interface with an electronic thermostat via RCBWYG terminals. The Control Selection jumper must be in T’STAT position. During a call the remote thermostat will pass R back to the controller on a respective terminal. The push buttons on the touchpad become inactive in the remote thermostat mode. However, the control pad LED display will indicate the mode of operation, and the room tem-perature.

Remote Mounted Thermostat InstallationConsiderations when units are furnished with remote

mounted thermostats:1. When wiring the low voltage plug and receptacle

disconnect, provide enough wire to move harness out of the way for chassis removal.

2. If secondary units are to be employed, see connections in wiring illustration below. The number of secondary units that can be connected is limited to 32 units.

3. When using a programmable wall thermostat, connect it to the terminal board remote thermostat plug. Refer to the instructions furnished with the chosen thermostat.

Thermostat wiring connections for Primary/Secondary wiring

Accessories–Options

Page 20: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Page 20 of 32 / Catalog 1355

Wall Mounted, Non-programmable ThermostatManual changeover one-stage heat and cool or one-stage heat pumpMcQuay Part No. 107095701 (1-Pk, White with Wall Plate)

Features and benefits• Hardwired• Simple operation• Large LCD display• No batteries required• A/C compressor protection - 5-minute time delay to protect compressor after it turns off• Single stage heat pump• Freeze protection feature• Zone capatible• 4- or 5-wire compatible (C is optional for non-heat pump systems)• Manual Changeover

SpecificationsElectrical rating:• 24 VAC (18 to 30 VAC)• 1 amp maximum per terminal• 3 amp maximum total load• 30-minute power loss memory retention

Temperature control ranges:• 45°F to 90°F, Accuracy: ± 1°F

System configurations:• 1 stage heat, 1 stage cool or single stage electric heat pump

Terminations:• R, C, W, Y, O, B, G

Wall Mounted, 7-day ProgrammableThermostatManual changeover one-stage heat and cool or one-stage heat pumpMcQuay Part No. 107095801 (1-Pk, White with Wall Plate)

Features and benefits• SimplesetTM logical programming for set-up and set- back temperatures and times• SimplesetTM feature enables easy copying of one day’s programming for the entire week• Programmable fan to circulate air during any program setting.• Vacation hold overrides programming• Enables separate morning, day, evening, and night settings for every day of the week• Clear, backlit display makes it easy to see time, temperature, and setpoint – even in the dark• A/C and heat pump modes – 4-minute time delay to protect compressor after it turns off• Lockout feature prevents unwanted tampering• Manual Changeover

SpecificationsElectrical Rating:• 24 VAC (18 to 30 VAC)• 1 amp maximum per terminal• 3 amp maximum total load• 30-minute power loss memory retention• Easy access terminal block

Temperature control ranges:• 45°F to 90°F, Accuracy: ± 1°F

System configurations:• 1 stage heat, 1 stage cool or single stage electric heat pump

Terminations:• RC, RH, C, W, Y, O, B, G

Accessories–Options

Page 21: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Catalog 1355 / Page 21 of 32

Optional Remote SensorPart No. 667720401

The fast, easy solution for temperature sensing problems.• For tamper prone areas• Poor airflow areas• Troubled applications• Foam gasket prevents drafts through wall opening• Mounts to standard 2" × 4" outlet box• 23/4"W × 41/2"H

Wireless Temperature Control (T9000)The T9000 Wireless Temperature Control is designed

to provide precision temperature control without the installation labor and expense of wiring. • Powered by AA batteries• Mounts in any suitable location that will provide

good temperature control. • Large LCD display provides the user with

current room temperature, set point temperature, time, program interval, and other system status information.

Remote Control Node (RCN)Used with the Wireless Temperature Control, the

RCN interfaces with specific HVAC equipment, and communicates with its thermostat using unlicensed 900 MHz, radio frequency energy. Contact your local Mc-Quay Representative for details.

Wall Mounted, 7-day ProgrammableThermostatStandard auto or manual changeover two stage heat / two stage coolMcQuay Part No. 107095901 (1-Pk, White with Wall Plate)

Features and benefits• SimplesetTM logical programming for set-up and set-back temperatures and times• SimplesetTM feature enables easy copying of one day’s programming for the entire week• Programmable fan to circulate air during any program setting.• Vacation hold overrides programming• Enables separate morning, day, evening, and night settings for every day of the week• Clear, backlit display makes it easy to see time, temperature, and setpoint — even in the dark• Automatically switches between heating and cooling modes• A/C and heat pump modes – 4-minute time delay to protect compressor after it turns off• Lockout feature prevents unwanted tampering• Optional remote temperature sensor available

SpecificationsElectrical rating:• 24 VAC (18 to 30 VAC)• 1 amp maximum per terminal• 4 amp maximum total load• 30-minute power loss memory retention• Easy access terminal block

Temperature control ranges:• 45°F to 90°F, Accuracy: ± 1°F

System configurations:• Single or two-stage heat/cool• Single or two-stage heat pump

Terminations:• R, C, W1/O/B, Y1, W2, Y2, G

Accessories–Options

Programmable Non-programmable

Page 22: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Page 22 of 32 / Catalog 1355

Custom Depths

Standard Wall Sleeve with Optional Leveling Legs and Wall Flange

Wall Sleeve with Recessed Louver Design

Wall Sleeves Constructed of galvanized, phosphatized, heavy-

gauge steel with an Antique Ivory powder paint corro-sion-resistant finish. Wall sleeves are installed through the wall as shown on the plans and have factory provi-sions for use of appropriate fastening devices to secure the sleeve to the wall. They can be ordered to custom depths, and recessed louver wall sleeves have a pitched bottom for positive removal of moisture to the outside. An optional factory-welded brickstop flange is provided based on architectural specifications.

Brickstop Flange

Pitched Bottom

Flush Stamped Louver Dimensions

Exterior Louvers For Standard Wall SleevesTwo styles of exterior louvers are available. The

standard flush stamped louver is a one-piece stamped aluminum type that is finished natural and clear anod-ized. Attractive, rugged architectural louvers are extruded aluminum and are finished natural and clear anodized (optional colors are also available).

Louvers by others are acceptable as long as they meet factory specifications. They must have a minimum free area of 70% or a pressure drop not exceeding .05 in. w.g. at 300 fpm face velocity, and a blade design that will not cause recirculation of condenser air.

Notes:1. Optional stamped aluminum louver, or architectural

extruded aluminum louver for standard wall sleeves.2. Knockouts are provided in stamped louver for

clearance of external drain for heat pump (both sides).3. Either louver can be installed from inside the building.

15�/1�”

3/�”

15/1�”

�1�/�”

1”

Flush Stamped Louver

Architectural Louver

Louvers – WeightFlush-stamped ................................................6 lbs. (3kg)Architectural ..................................................8 lbs. (3kg)

Accessories–Options

Page 23: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Catalog 1355 / Page 23 of 32

Dimension 1�" × �2"

A 111/�" B 2�" C ��/�"

Wall Sleeve Extension – 16" × 42" PDANThe standard wall sleeve will accommodate the

maximum wall thickness described in Table 2. For thicker walls, wall sleeve extensions are available from your local distributor. Air splitters will be included in the wall sleeve extension as shown in the illustrations below.

Note: When installing a new chassis into an existing wall sleeve with an extension, it will be necessary to relocate the two air splitters to match the dimensions shown in the illustration (see Table 3).

Table 2. Maximum Wall Thickness without Sleeve Extensions

Maximum Wall Thickness Louver No Standard Type Subbase Subbase

Stamped 3/�" 1�1/�" �1/2" Architectural 11/�" 1��/�" 103/�"

�23/1�"(10�2mm)

1�3/1�"(�11mm)

33/�"(�2mm)

��3/1�"(1122mm)

1�3/1�"(10�2mm)

Note: Wall Sleeve rough opening when using a Louver Frame must be 165/8"×425/8"

Louver FrameLouver frames should be used for panel wall and thin

wall applications to assure positive anchoring to the wall. The cabinet/wall sleeve is installed flush with the outside of the building. The louver frame is placed around the cabinet/wall sleeve.

Wall Sleeve Extension

�2"

Room Side

Air Splitters

as required

1�"

16" × 42" PDAN Unit

B

B

A

C

Table 3. Wall Sleeve Extension Splitter Location Dimensions

Accessories–Options

IMPORTANTAir flow required for PTAC units must not be restricted by exterior plants or walls. Plants or shrubs must not be planted in close proximity to the outside grille of the PTAC unit. Vegetation planted too close to grilles will cause discharge air to be recirculated, thereby increasing electrical consumption. Warranty will be voided if it is determined that the compressor life is shortened from overheating due to close proximity of outside obstructions.

Note: Discharge air restrictions include, but are not limited to:

• Vegetation• Concrete walls or barriers• Overhangs that do not allow discharge air to rise• Installation of bug screen of any kind

Page 24: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Page 2� of 32 / Catalog 1355

Accessories–Options

Energy Saving OptionsAutomatic Change over, Remote Mounted Thermostat

Thermostats can be obtained to switch from heating to cooling and from cooling to heating automatically. With automatic change over, the operation of the heating cycle or the cooling cycle is determined by the temperature re-quirement of the space. Most thermostats with this feature are set to change over when the room temperature varies 3-1/2oF from the set-point. The unit is placed in the cooling mode when the set-point is over 3-1/2oF; 3-1/2oF under the set point places the unit in the heating mode. This 3-1/2oF variation is usually adjustable from a 1/2oF dead band to a 5oF dead band. Each cycle is run until the set point tem-perature is reached, then that cycle is de-energized. On some thermostats, the automatic change over function can be overridden manually by moving the thermostat selector switch to “heat” or to “cool.”

The fan operation, with an automatic change over thermostat, is controlled by the fan selector switch. When placed in the “fan” mode, the fan runs continuously. When placed in the “auto” mode, the fan will only energize when the thermostat calls for heating or cooling.

• Program Setback Control With the Programmable Touchpad, four (4) different

periods, Morn., Day, Eve., or Nite, can be indepen-dently programmed for start time, Heat setting and Cool setting. There are additional energy savings with Programmed Setback Control.

• Fresh Air Dampers McQuay Packaged Terminal conditioners can be

furnished with an automatic fresh air damper in lieu of a manual fresh air damper. The automatic damper is wired in parallel to the indoor fan relay.

In the Set-up menu on the touchpad, with the damper set to “AU” (Automatic) and the OAS (Outdoor Air Sensor) is > (greater than) 40º F but is < (less than) 90º F and the IAS (Indoor Air Sensor) is > (greater than) 50º F and if the unit is placed in the cycle mode, the fan and damper cycle as the thermostat cycles. If the unit is placed in the “constant” mode, the fan runs continuously and the damper is always open subject to the sensors.

The automatic damper feature can be overridden in the Set-up menu by placing the automatic damper setting in the “CL” (Closed) position. In this posi-tion, the damper remains closed during all cycles of the unit.

• Special Paint The Standard paint on the NYC Style unit is Antique

Ivory with a contrasting Oxford Brown subbase. This color combination blends well with the most interior color schemes. A durable electrostatically applied, baked on, antique ivory urethane powder paint is used that resists smudges and corrosion. Each steel component is painted separately and oven baked for durability.

Page 25: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Catalog 1355 / Page 25 of 32

LegendDM = Damper MotorHYV = Hydronic ValveCM = Compressor MotorIFM = Indoor Fan MotorOFM = Outdoor Fan MotorHFLO= Heat Fan Lockout SensorOCS = Outdoor Coil SensorOAS = Outdoor Air SensorICS = Indoor Coil SensorIAS = Indoor Air SensorLUI = Local User InterfaceREV = Reversing ValveIR = IR Receiver Board (AP��10)C1 = Indoor Motor CapacitorC2 = Outdoor Motor CapacitorC3 = Compressor CapacitorMP = Motor Protector

Wiring DiagramsDigital Control Board With Standby Power

Note: The gray tinted areas in the wiring diagram; are options available only with the premium control board.For the latest drawing version refer to the wiring diagram located on the inside of the controls access panel of the unit.

Wire Color Voltage WH 120V RD 20�V OR 2�0V BN 2��V

Drawing No. 668001506

Table AThe standby power connections, L1 STBY and L2 STBY are meant to run the indoor motor at a separate voltage from the other motors, compressor and outdoor motor. When used as such, the jumpers, JH1 and JH2, must be cut. This renders L1 & L2 and L1 STBY and L2 STBY isolated from each other.

If there is no need to run the motors at a separate voltage the L1 = L1 STBY and L2 = L2 STBY. Therefore one voltage is used to run all motors.

If the jumpers are accidentally cut, then the connections can be spliced to substitute for the missing jumpers.

Page 26: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Page 2� of 32 / Catalog 1355

Wiring Diagrams Digital Control Board Without Standby Power

LegendDM = Damper MotorHYV = Hydronic ValveCM = Compressor MotorIFM = Indoor Fan MotorOFM = Outdoor Fan MotorHFLO= Heat Fan Lockout SensorOCS = Outdoor Coil SensorOAS = Outdoor Air SensorICS = Indoor Coil SensorIAS = Indoor Air SensorLUI = Local User InterfaceREV = Reversing ValveIR = IR Receiver Board (AP��10)C1 = Indoor Motor CapacitorC2 = Outdoor Motor CapacitorC3 = Compressor CapacitorMP = Motor Protector

Note: The gray tinted areas in the wiring diagram; are options available only with the premium control board.For the latest drawing version refer to the wiring diagram located on the inside of the controls access panel of the unit.

Wire Color Voltage WH 120V RD 20�V OR 2�0V BN 2��V

Drawing No. 668001406

Table A

The standby power connections, L1 STBY and L2 STBY are meant to run the indoor motor at a separate voltage from the other motors, compressor and outdoor motor. When used as such, the jumpers, JH1 and JH2, must be cut. This renders L1 & L2 and L1 STBY and L2 STBY isolated from each other.

If there is no need to run the motors at a separate voltage the L1 = L1 STBY and L2 = L2 STBY. Therefore one voltage is used to run all motors.

If the jumpers are accidentally cut, then the connections can be spliced to substitute for the missing jumpers.

Page 27: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Catalog 1355 / Page 2� of 32

Engineering Guide Specifications – 16" × 42" Model PDAN with Top-Mounted Hydronic Heat Furnish and install where shown on plans packaged terminal air conditioners of the sizes and capacities shown on the schedule.

The units shall be located as shown on the drawings and shall include cabinet/wall sleeve, chassis, outdoor louver, hydronic heat section, valve, and room cabinet. All units shall be ETL. listed for safety and ARI certified for performance. Overall dimensions for the basic unit shall not exceed 52" wide, 22-1/2" high, and 17-3/4" deep. Overall dimensions of the wall sleeve shall be 16" high, 42" wide and (13-3/4"/______) deep. All units shall operate on ______ volts, 60 Hz, 1 phase power. (Units furnished with hydronic heat shall not exceed 43" wide, 241/2" high and 20" deep).

The minimum energy efficiency ratio (EER) in BTU per hour per watt for each PDAN unit must be in compliance with ASHRAE 90.1 replacement or new construction criteria, for all sizes. The minimum COP for heat pumps, at 47oF DB outdoor, must be 2.9 for all sizes.

Heating/Coolingchassis–Chassis shall be slide-in, plug-in type with a self-contained, hermetically sealed refrigerant circuit. All chassis sheet metal parts shall be constructed of either powder-coated A-60 or G-60 galvanized steel for maximum corrosion resistance. The chassis shall consist of the following components:Vibration isolated compressor; rifled copper tubed evaporator and condenser coils with high efficiency raised lance aluminum plate fins mechanically expanded to the tubes for maximum heat transfer; and a capillary restrictor type refrigerant metering device. Coils shall be factory tested at 300 psig. (Heat pump models shall also include reversing valve and charge balancing device). A positive closing (manual) fresh air damper may be located within the chassis to provide fresh air during fan operation.Airflow system shall include separate fan motors for the condenser and evaporator sections. The condenser fan motor shall be a single-speed, totally enclosed, permanently lubricated fan motor. Condenser fan shall be propeller-type with a slinger ring and shall be constructed of aluminum. The indoor fan motor shall be a two-speed, totally enclosed; permanently lubricated fan motor must be positioned on the indoor side of the bulkhead so as to be completely within the conditioned, filtered airstream. The indoor blower fan shall be a forward-curved tangential design to provide even airflow across the evaporator coil.

During the cooling cycle:The compressor, the outdoor fan motor and the indoor fan motor shall be energized. Condensation accumulated on the evaporator coil shall be drained into the outdoor section where it is to be picked up by the condenser fan/slinger ring and evaporated against the outdoor coil. In the cool mode, the compressor will cut in if the space temperature is at least 1°F above the thermostat set point and will cut out when the space temperature is approximately 2°F below set point, subject to timing protections.

During the heating cycle:ElectricResistanceHeat–Control will call for electric heat when the space temperature is 1°F lower that the set point. The control will cease its call when the space temperature is 3°F or higher than set point.Only the indoor fan motor and electric resistance heater are energized. The outdoor condenser fan motor and compressor shall not be energized. Heater shall be open wire type with quick response and high limit cutout. Heaters shall be sized to meet heating require-ments as shown on the schedule. Electric resistance heaters must be placed behind the indoor evaporator coil and must not be visible through the indoor discharge grille. When the heater cuts out the indoor fan continues to run for 15 seconds at the set speed, regard-less of On or Off mode. After 15 seconds the fan will stop running if unit is in Off mode, else the fan operation will depend on Fan Continuous or Fan Cycle setting.Hydronic, Hot water or Steam, heat – Only the indoor fan motor, the (normally open) (normally closed) valve and automatic fresh air damper shall be energized. The outdoor condenser fan motor and compressor shall not be energized.

HydronicHeatWhen the control is in the heat mode and calling for heat, the indoor fan shall not turn on until the HFLO sensor is above 115°F. If at any time while the unit is in heat mode the HFLO sensor is below 95°F, the indoor fan shall turn off immediately. Control will check if the HFLO sensor temperature is above 115°F for 2 seconds before resuming indoor fan operation.

HydronicwithIntermediateElectricheat–Upon the call for heating and thereafter the HFLO sensor temperature will be monitored. A trend in HFLO sensor Temperature shall determine which form of heat is to be used. If during the 90 seconds that Hydronic is the heat source and the HFLO sensor is above 105°F and is increasing at 2°F per minute then Hydronic is the heat source. If during this 90 seconds, the temperature of the HFLO sensor is above 105°F and is not increasing at 2°F per minute then Electric is the heat source. The hydronic valve is opened for 90 seconds. After 90 seconds whether Hydronic or Electric provides the heating is determined by the following:

If HFLO sensor temperature is less that 105°F, Electric provides the heat.If HFLO sensor temperature is greater than 115°F, Hydronic provides the heat

Page 28: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Page 2� of 32 / Catalog 1355

ReverseCycleHeatPumpwithback-upelectricheat–The reversing valve, the compressor, the outdoor condenser fan motor and the indoor fan motor shall be energized. Reverse cycle heating shall occur when the outdoor temperatures are 35°F and above. If outdoor coil temperature drops below 20°F or the Outdoor air temperature drops to 35°F or less, Electric heat is the only source of heat. When the Outdoor coil temperature raises back to 40°F and above, then the Compressor or Electric heater is used.A temperature-sensing device shall be used to monitor the outdoor coil temperature to limit frost buildup. Defrosting of the outdoor coil will be activated when outdoor coil temperature drops below 20°F or outdoor air temperature drops to 35°F or less. Defrosting is terminated when outdoor coil temperature rises back to 40°F. During defrosting, both compressor and the outdoor fan are turned off. The indoor fan will run at its set speed. Condensation accumulated during reverse cycle heating must NOT be evaporated against the indoor coil so as to prevent contami-nation of the indoor air with pollutants and odors. Condensation must be disposed of using a (external) (internal) drain system as shown on plans.

ReverseCycleHeatPumpwithoutback-upelectricheat–The reversing valve, the compressor, the outdoor condenser fan motor and the indoor fan motor shall be energized. Reverse cycle heating shall occur when the outdoor temperatures are 35°F and above. If outdoor coil temperature drops below 20°F or the Outdoor air temperature drops to 35°F or less, the compressor stops and there is no source of heat. When the Outdoor coil temperature raises back to 40°F and above, then the compressor reverse cycle is the heat source.A temperature-sensing device shall be used to monitor the outdoor coil temperature to limit frost buildup. Defrosting of the outdoor coil will be activated when outdoor coil temperature drops below 20°F of outdoor air temperature drops to 35°F or less. Defrosting is terminated when outdoor coil temperature rises back to 40°F. During defrosting, both compressor and the outdoor fan are turned off. The indoor fan will stop if indoor coil temperature falls below 78°F. It will restart at its set speed when indoor coil temperature rises back to 80°F. Condensation accumulated during reverse cycle heating must NOT be evaporated against the indoor coil so as to prevent contami-nation of the indoor air with pollutants and odors. Condensation must be disposed of using a (external) (internal) drain system as shown on plans.

Electricheatoverride– Heat pump units can be manually switched to electric heat, providing added freeze protection if the heat pump mode is not available due to a compressor failure.

Controlmodule–The PDAN Control module is used to control a PDAN unit that includes both an integral air conditioner and a source of heat. The Digital Control is operated with a Touchpad, IR Remote or 24 volt, Wall Mounted Thermostat.

Roomfreezeprotection– When the unit senses temperatures of 40°F or lower in an unoccupied room, the heat mode is automatically initiated to prevent freezing. The outdoor fan and compressor are stopped to help prevent coil freeze.

Compressorprotection– The life of the compressor is extended through built in protection logic such as: • High temperature protection if the compressor temperature exceeds 154°F • Minimum run time • Minimum off time • Random restart after a power outage • Low ambient lockout when the outdoor air temperature falls below 35°F

Engineering Guide Specifications – 16" × 42" Model PDAN with Top-Mounted Hydronic Heat

Page 29: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

Catalog 1355 / Page 2� of 32

Inputs and outputs The PDAC/HP control module offers the following inputs:1. Indoor Coil Sensor (ICS)2. Indoor Air Sensor (IAS)3. Outdoor Air Sensor (OAS)4. Inputs from Remote Thermostat (R, B, G, Y, W)5. Heat Fan Lock Out Sensor (HFLO)6. Power Supply, 24VAC

The PDAC/HP control module offers the following outputs:1. Compressor Output (COM)2. Outdoor Fan (FAN)3. Indoor Fan Fan cycle or Fan Continuous and Blower Hi or Blower Lo shall be incorporated to allow either continuous or automatic fan cycle operation at the selected fan speed. When choosing automatic fan cycle operation, the fan shall be energized only when the compressor or electric resistance heaters are energized. 4. Damper Control (DAMPER)5. Hydronic Valve (HYV)

Digital Control – Shall have solid state digital control operated via a unit mounted touchpad, handheld infra-red or remote wall mounted thermostat. Shall include space temperature control and unit ON or OFF, and the following:

Cooling – Compressor and Outdoor fan, Indoor fan – HI, LOW, CONSTANT or FAN CYCLE, Outdoor air damper.

Heating – Hydronic Valve or Intermediate Electric Heat, Indoor fan – HI, LOW, CONSTANT or FAN CYCLE, Outdoor air damper.

Room Cabinet – Shall be flat top, wrap-around design with a heavy-gauge sheet metal front panel that is phosphatized and coated with a baked on, corrosion resistant finish. Room cabinets with ordinary enamel finish are not acceptable. Discharge grilles shall be tamper-proof. The control access door shall be mounted on the right-hand side.

Fresh Air Damper – A positive closing automatic fresh air damper must be located within the chassis to provide fresh air during fan operation. It will be configurable for selection of AUTO operation or CLOSED.

Filtration(Standard)–Room side return air shall be completely filtered through a permanent, washable polypropylene mesh filter. Foam type filters are not acceptable. Filter must be a UL listed class II, 38% average arrestance efficiency (ASHRAE test) air filter with low resistance to airflow (0.02 w.g. at 300 CFM) and high dust holding capacity of 55 grams.

Filtration(Optional)– Room side return air shall be completely filtered through a permanent, washable polypropylene mesh filter. Foam type filters are not acceptable. Filter must be a UL listed class II, 72% average arrestance efficiency (ASHRAE test) air filter with low resistance to airflow (0.03 w.g. at 300 CFM) and high dust holding capacity of 100 grams.

Wall Sleeve – Shall be entirely constructed of galvanized, phosphatized, heavy-gauge steel with an Antique Ivory powder paint cor-rosion resistant finish. Unpainted, galvanized steel wall sleeves with or without rust inhibiting spray are not acceptable. Wall sleeves with ordinary enamel finish are not acceptable. Wall sleeves shall be installed through the wall as shown on plans and shall have factory provisions for use of appropriate fastening devices to secure sleeve to the wall. In no event shall fasteners be installed through the basepan in the bottom of the cabinet/wall sleeve.

Outside Air Louvers – Shall be (stamped) (architectural) anodized aluminum as shown on plans. Louver shall be (finished natural) (painted) as shown on the schedule. Louvers shall be easily installed from the inside of the building after the cabinet/wall sleeve has been installed. Special field fabricated louvers must be approved by the PTAC manufacturer as to free area and air circulation requirements.

Engineering Guide Specifications – 16" × 42" Model PDAN with Top-Mounted Hydronic Heat

Page 30: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the
Page 31: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the
Page 32: Applied Packaged Terminal Air Conditioner with Top …lit.daikinapplied.com/bizlit/DocumentStorage/PTACUnits/...Page of 32 / Catalog 1355 Introduction In 1958, McQuay introduced the

©200� McQuay International • www.mcquay.com • �00-�32-13�2 Catalog 1355-� / Page 32 of 32 (Rev 12-0�)

McQuayTrainingandDevelopmentNow that you have made an investment in modern, efficient McQuay equipment, its care should be a high priority.For training information on all McQuay HVAC products, please visit us at www.mcquay.com and click on training, or call 5�0-2��-���� and ask for the Training Department.

WarrantyAll McQuay equipment is sold pursuant to its standard terms and conditions of sale, including LimitedProduct Warranty. Consult your local McQuay Representative for warranty details. Refer to Form933-43285Y. To find your local McQuay Representative, go to www.mcquay.com.

This document contains the most current product information as of this printing. For the most up-to-date product information, please go towww.mcquay.com.