Levitor IIAIR COOLED CONDENSER AND FLUID COOLER

Technical Bulletin

Products that provide lasting solutions.

Page 2: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

Levitor II Air Cooled Condenser

Table of Contents

LEVITOR II AIR COOLED CONDENSERSpecifications subject to change without notice.

Benefits and Features 1

System Selection 2

Levitor Application 3

Model Key 4

LAVE/LEVE Condenser Performance Data, One and Two Fans Wide 5

LAVA/LEVA Condenser Performance Data, One and Two Fans Wide 7

LAVC/LEVC Condenser Performance Data, One and Two Fans Wide 9

LAVF/LEVF Condenser Performance Data, One and Two Fans Wide 11

Dimensional Drawings 13

LAVB Condenser Performance Data, One and Two Fans Wide 14

Dimensional and Electrical Data 15

Control Panel Nomenclature 16

Standard Fan Cycling/Control Arrangements 17

Low Ambient Controls 18

Fan Cycling Sequence 18

Mounted Receivers 19

Mounted Receiver Diagrams 20

Wiring Diagram 22

Replacement Parts 23

12_FIN_KRACK_LEVITOR_COV_2009 8/21/12 4:45 PM Page 3

Page 3: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

Levitor II Air Cooled Condenser

LEVITOR II AIR COOLED CONDENSER 1Specifications subject to change without notice.

Benefits and Features

Low Sound Quietor Fann The “swept-wing” blade design offers lower noise levels atthe same fan speed. For example, the QUIETOR fan bladeon a 575-rpm motor will be much quieter (8 dBA) than theold 575-rpm fan.

n Lower noise condensers can translate into savings for yourcustomer by minimizing the need of costly noise barriers.

n Quietor fan not available on 18” models.

Exclusive 3-year Limited Warrantyn We’re so confident about our new suspended coil design that it is protected by a 3-year limited warranty on workmanship and material. It gives you extra protection from premature tube wear. Seewww.krack.ingersollrand.com for complete warranty.

Computerized Circuitingn Our computerized coil circuiting program is designed tominimize the condenser refrigerant charge and maximizesubcooling. Every condenser will be custom circuited toprecisely meet your application needs.

Modular Designn Arranged for vertical or horizontal air discharge. Multi-fan sections compartmented to allow individual fancycling while preventing off-fan “windmilling”. Largeclean-out access doors standard.

Corrosion Resistantn All models employ mill galvanized steel fan sections and coil side baffles. Legs are heavy gauge mill galvanized steel.

High Efficiency Coiln Copper tubes are mechanically expanded intocorrugated full collared aluminum fins spaced 8, 10 or 12 per inch. Coils are helium leak and pressuretested with 400 psig. dry air, shipped pressurized with dry nitrogen.

n Optional fin materials are copper, heresite, electrofin or polyester coated aluminum. Multi-circuited coils areavailable. Liquid subcooling circuits are available.

Direct Driven Propeller Fansn Quiet multi-bladed propeller fans provide uniform airdistribution through the coil. Venturi fan orificesoptimize efficiency.

Weather Resistant Fan Motorsn Outdoor condenser motors designed with ball bearingsinherent overheat protection in each phase; shaftslingers; enclosure, hardware, and lubrication for allweather conditions. Each motor lead is wired toterminals in an electrical enclosure.

Versatile Fan Cycling Control Methods

n Temperature fan cycling.n Pressure fan cycling.n Temperature and pressure fan cycling.n Electronic relay boards.n Variable speed header end fans.n Inverter ready motors.

LEVITOR Coil Design Eliminates Refrigerant Tube Wear

Environmental concerns and spiraling cost of refrigerants have led tothe development of direct drive remote air-cooled condensers with theLEVITOR coil support system. This innovative design uses dedicated

stainless steel tubes and a unique coil support system to isolaterefrigerant tubes from the unit. Coil support is transferred from the finsto the stainless tubes and truncated tube plates which ride freely in “C”channels. Tubes expand and contract without interference. The result,

contact and friction wear are eliminated.

Quiet by Design

LEVITOR coil design does more than just eliminate tube wear. Soundreduction is an added benefit. Unlike traditional air-cooled condensers,

fan and coil vibration are isolated from the cabinet, so it is nottransmitted to the unit frame and building supports.

The LEVITOR system addresses refrigerant coil wear and leaks due to vibration and thermal stress.

Rooftop condensers have to operate in some of thetoughest conditions imaginable. Temperature extremesresult in constant expansion and contraction of refrigeranttubes as fans cycle and loads vary.

The consequences are costly: rapid tube wear results inleaks, system breakdown and loss of costly refrigerant.

US

Page 4: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

Levitor II Air Cooled Condenser

System Selection

THR Total Heat of Rejectionn Condenser total heat of rejection (BTU/h) is the sum of the evaporator refrigeration effect and the heat of compression which varies with compressor type and operating conditions.

THR Calculation Methodn THR = Open Reciprocating Compressor Capacity (BTU/h) + (2545 x BHP)

n THR = Suction Gas Cooled Hermetic Reciprocating Compressor Capacity (BTU/h) + (3413 x kW)

THR Estimated Methodn THR may be estimated by multiplying the rated compressor BTU/h capacity by the compressor operating condition factor shown in Table 1 or 2. Multiply result by altitude factor when applicable.

Multi-Circuit Selectionn Condenser coils may be divided into several individual refrigeration circuits or systems; each sized for a specific refrigerant,THR capacity and TD. Systems are tagged for identification from left to right; facing the connection end. Avoid locatinghigh TD sections next to low TD sections. Add excess circuits to low TD sections next to High TD sections. Add excesscircuits to outboard sections. Thermal Fantrol fan cycling is recommended with multi-circuited condensers.

Selectionn LAVA-15310 Rated at THR of 459.1 MBH with R-22 at 15°F TD. LAVA-15310 Unit lists 34 Circuits.

n Sample Calculation: THR Req’d./Circuit = 434984 ÷ 34 = 12784. LAVA-15310 = 459100 ÷ 34 = 13503 (Available THR/Circuit).

n Circuits Req’d. = Select THR ÷ THR/Circuit. Example: 57648 ÷ 13503 = 4.3 Circuits.

n Assign Number of Circuits System and System Number Left to Right. Actual TD = (Circuits Req’d ÷ Assign Circuits) x Design TD.Example: 4.3 ÷ 4 x 15 = 16.1.

EVAPORATORTEMP (˚F)

-40-30-20-100510152025304050

901.661.571.491.421.361.331.311.281.261.241.221.181.14

1001.731.621.531.461.401.371.341.321.291.271.251.211.17

1101.801.681.581.501.441.411.381.351.331.311.281.241.20

1202.001.801.651.571.501.461.431.401.371.351.321.271.23

130***

1.641.561.521.491.461.431.401.371.311.26

140****

1.621.591.551.521.491.451.421.351.29

CONDENSING TEMPERATURE (˚F)HERMETIC COMPRESSOR

TABLE 1

*Beyond the normal limits for single stage compressor application.

FEET1,0002,0003,0004,000

FACTOR1.021.051.071.10

FEET5,0006,0007,0008,000

FACTOR1.121.151.171.24

ALTITUDETABLE 3

EVAPORATORTEMP (˚F)

-30-20-1001020304050

901.371.331.281.241.211.171.141.121.09

1001.421.371.321.281.241.201.171.151.12

1101.471.421.371.321.281.241.201.171.14

120*

1.471.421.371.321.281.241.201.17

130**

1.471.411.361.321.271.231.20

140***

1.471.421.371.321.281.24

CONDENSING TEMPERATURE (˚F)OPEN COMPRESSOR

TABLE 2

SAMPLE CALCuLATIOn: 95°F AMBIEnT-SuCTIOn COOLED SEMI-HERMETIC RECIPROCATInG COMPRESSORS

*Beyond the normal limits for single stage compressor application.

COMPNOMHP

6

9

10

12

REF134a

404A

404A

22

DESIGNTD°F15

10

10

15

SATSUCT°F+20

-20

-20

+20

SATCOND°F110

105

105

110

NETBTU/h40090

45900

50640

104000

MOTORkW4.3

8.1

9.6

9.7

BTU14676

27645

32765

33106

TOTALBTU/h54,766

73,545

83,405

137,106

REFFACTOR0.95

0.98

0.98

1.00

TDFACTOR

1.0

1.5

1.5

1.0

x

x

x

x

=

=

=

=

÷

÷

÷

÷

SELECTTHR57648

112569

127661

137106

434984

CAPPER

CIRCUIT13503

13503

13503

13503

CIRCUITREQ’D4.3

8.3

9.5

10.1

#CIR4

10

10

10

34

SYSTEMNUMBERL TO R

1

2

3

4

ACTUALTD°F

16.1

8.3

9.5

15.1

COMPRESSOR RATING BASED ON R-22 AT 15°FTD

UNIT THR REQ’D

REF FACTORR-22- 1.00

* R-134a- 0.95

**R-404A- 0.98

TD FACTOR10°F-1.50

15°F-1.00

20°F-0.75

25°F-0.60*Usable for R-12**Usable for R-502, R-507

Page 5: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

Levitor II Air Cooled Condenser

LEVITOR II AIR COOLED CONDENSER 3Specifications subject to change without notice.

Levitor Application

Locate Condensers no closer than their width from wallsor other condensers. Avoid locations near exhaust fans,plumbing vents, flues or chimneys.

Parallel Condensers should be the same models resultingin the same refrigerant side pressure drops. Compressordischarge lines should have equal pressure drops to eachcondenser.

Condenser Charge will approximate 30% of themaximum flooding charge listed under “Specifications” forsummer design conditions. Low ambient head pressurecontrols require an additional charge, which is difficult topredict with fan cycling and is maximized with holdback.

Receiver Capacity should be sized to store condensersummer charge, plus the condenser low ambientallowance, plus the evaporator charge, plus an allowancefor piping and heat reclaim coil charges.

Compressor Discharge lines should be sized to minimizepressure drops and maintain oil return gas velocities. Eachconnection should be looped to the top of the condenser.

Gravity Liquid Drain Lines should drop from each outlet as low as possible before headering or runninghorizontally. Pitch downhill to receiver.

Off-Line Coil Sections will have refrigerant pressurescorresponding to the ambient. Check valves or isolatingvalves should be installed in the liquid line drains toprevent refrigerant migration and receiver pressure loss.

Liquid Subcooling may be accomplished with a sectionof circuits in the coil. Liquid outlet temperature willapproach the entering air temperature by approximately5°F. Benefit is not economical unless TD is 15°F orhigher.

See Installation & Operating instructions for piping, holdback and fan cycling details.

REFRIGERAnT LInE CAPACITY DATA

n Capacity is compressor suction tons for application between -40°F and +40°F suction at condensingtemperatures between 80°F and 120°F sat.

n For multiple or unloading compressor applications, the vertical discharge riser from the compressor may need to be one size smaller.

n This table data is only to be used as a guide. For exact values, please calculate to your specific job linelengths and design pressure/temp values using ASHRAE handbook or ARI refrigerant tables.

COPPERLINESIZEO.D.

LINE CAPACITY IN TONS

COMPRESSOR DISCHARGE LINE CONDENSER TO RECEIVERLIQUID LINE 100'

LBS. OF REFRIGERANTLIQUID PER 100' OF LENGTH

R-22

1.03.06.515.020.045.075.0

R-404A

0.52.04.57.015.030.045.0

R-134A

0.52.04.57.011.028.043.0

R-22

3.67.412.719.229.047.073.0

R-404A

3.06.010.416.023.040.062.0

R-134A

3.77.713.020.028.546.072.0

R-22

13.025.042.064.090.0160.0245.0

R-404A

11.022.036.055.078.0138.0212.0

R-134A

13.026.043.065.092.0163.0250.0

5/87/81-1/81-3/81-5/82-1/82-5/8

Page 6: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

Levitor II Air Cooled Condenser

Model Key

4 LEVITOR II AIR COOLED CONDENSERSpecifications subject to change without notice.

UNIT TYPE:L = Levitor CondenserF = Fluid Cooler

FIN SPACING:08 = 8 FPI10 = 10 FPI12 = 12 FPI

L A V A 1 2 4 10 M

FAN / MOTOR COMBINATION:A = 1 HP 850 RPM 30"B = 1/2 HP 1140 RPM 24"C = 1-1/2 HP 850 RPM 30"E = 1/2 HP 575 RPM 30"F = 1-1/2 HP 1140 RPM 30"

FANS IN LINE:1234567 = 24" Fan Only

ROWS DEEP:234

FANS WIDE: 1, 2

TUBE DIAMETER:A = 3/8 O.D.E = 1/2 O.D.

FAN DISCHARGE DIRECTIONS:H = HorizontalV = VerticalX = Hinged Vertical*E = Hinged Horizontal*

VOLTAGE:A = 230/1/60**K = 208-230/3/60M = 460/3/60P = 575/3/60U = 380/3/50

NOTE:* Levitor only.

** B units only.

Page 7: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

1/2 H.P. 575 RPM - OnE FAn WIDE

NOTE: Ratings are based on 85°F-115°F entering air temperature. The temperature difference is between the saturated condensing temp. and the entering air temp.to the condenser. Multiply R-22 rating by 0.95 for R-134a. Summer charge based on 25% of condenser volume with 86°F liquid. Multiply by 1.14 for R-22.

Winter charge based on 90% of condenser volume with -20°F liquid. Multiply by 1.10 for R-22.

SHIPWEIGHT(LBS)

43743944446646947849549950871872172977377979283083885510411060112611351153121012231247143714491474155015661599202020352066216021812222255425732610278428082858

ESTSOUND10’(dBA)

5252525252525252525555555555555555555757575757575757585858585858595959595959606060606060

MODEL

TOTAL HEAT OF REJECTION (MBH)R-22 R-404A, R-507

TEMPERATURE DIFFERENCE TEMPERATURE DIFFERENCE

LAVE 112 08LAVE 112 10LAVE 112 12LAVE 113 08LAVE 113 10LAVE 113 12LAVE 114 08LAVE 114 10LAVE 114 12LAVE 122 08LAVE 122 10LAVE 122 12LAVE 123 08LAVE 123 10LAVE 123 12LAVE 124 08LAVE 124 10LAVE 124 12LAVE 132 10LAVE 132 12LAVE 133 08LAVE 133 10LAVE 133 12LAVE 134 08LAVE 134 10LAVE 134 12LAVE 143 08LAVE 143 10LAVE 143 12LAVE 144 08LAVE 144 10LAVE 144 12LAVE 153 08LAVE 153 10LAVE 153 12LAVE 154 08LAVE 154 10LAVE 154 12LEVE 163 08LEVE 163 10LEVE 163 12LEVE 164 08LEVE 164 10LEVE 164 12

10°F33.237.240.443.847.950.653.155.958.166.574.480.987.595.8101.2106.3111.7116.3111.5121.3138.1143.6152.0159.6167.6174.7174.8191.5202.4212.5223.4233.1231.9254.0270.3270.9289.8300.3278.4304.9324.5325.1347.8360.4

15°F49.855.860.665.771.875.979.683.887.199.7111.6121.3131.2143.7151.8159.4167.5174.4167.2181.9207.1215.4228.0239.4251.4262.0262.2287.2303.6318.7335.1349.6347.8381.0405.4406.3434.7450.4417.6457.3486.7487.6521.7540.6

20°F66.474.480.887.695.8101.2106.2111.8116.2133.0148.8161.8175.0191.6202.4212.6223.4232.6223.0242.6276.2287.2304.0319.2335.2349.4349.6383.0404.8425.0446.8466.2463.8508.0540.6541.8579.6600.6556.8609.8649.0650.2695.6720.8

25°F83.093.0101.0109.5119.7126.5132.7139.7145.2166.2186.0202.2218.7239.5253.0265.7279.2290.7278.7303.5345.2359.0380.0399.0419.0436.7437.0478.7506.0531.2558.5582.7579.7635.0675.7677.2724.5750.7696.0762.2811.2812.7869.5901.0

10°F32.336.239.342.646.647.251.754.456.664.772.378.785.193.298.4103.4108.7113.2108.5118.0134.3139.8147.9155.3163.0170.0170.0186.3197.0206.8217.4226.8225.6247.1263.0263.6282.0292.2270.8296.6315.7316.3338.4350.6

15°F48.454.358.963.969.970.877.581.684.997.0108.4118.0127.6139.8147.6155.1163.0169.8162.7177.0201.4209.7221.8232.9244.5255.0255.0279.4295.5310.2326.1340.2338.4370.6394.5395.4423.0438.3406.2444.9473.5474.4507.6525.9

20°F64.672.478.685.293.294.4103.4108.8113.2129.4144.6157.4170.2186.4196.8206.8217.4226.4217.0236.0268.6279.6295.8310.6326.0340.0340.0372.6394.0413.6434.8453.6451.2494.2526.0527.2564.0584.4541.6593.2631.4632.6676.8701.2

25°F80.790.5 98.2106.5116.5118.0129.2136.0141.5161.7180.7196.7212.7233.0246.0258.5271.7283.0271.2295.0335.7349.5369.7388.2407.5425.0425.0465.7492.5517.0543.5567.0564.0617.7657.5659.0705.0730.5677.0741.5789.2790.7846.0876.5

AIRFLOW(CFM)

6480642063606300620061006105597558351296012840127201260012400122001226011950116701926019080189001860018300183151792517505252002480024400244202390023340315003100030500305252887529175378003720036600366303585035010

AVAILCIRCUITS

3434343434343434 3434 34343434343434343434 3434 34343434343434343434343434343434 343434343434

CONDENSERCHARGE R-404A

(LBS)

SUMMER

5557778889991212121515151414181818232323232323292929272727353535585858757575

WINTER

1717172424243131313131314545455858584646676767878787878787114114114107107107141141141235235235310310310

Levitor II Air Cooled Condenser

LAVE/LEVE Performance Data

Page 8: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

Levitor II Air Cooled Condenser

LAVE/LEVE Performance Data

1/2 H.P. 575 RPM - TWO FAnS WIDE

ELECTRICAL DATA - OnE FAn WIDE

SHIPWEIGHT(LBS)

1311132013361437 1425146215391555158818751912204420632100221422382287252626512700285128842950372537553817400540464129475947964870521852685366

MODEL

TOTAL HEAT OF REJECTION (MBH)R-22 R-404A, R-507

TEMPERATURE DIFFERENCE TEMPERATURE DIFFERENCE

LAVE 222 08LAVE 222 10LAVE 222 12LAVE 223 08LAVE 223 10LAVE 223 12LAVE 224 08LAVE 224 10LAVE 224 12LAVE 232 10LAVE 232 12LAVE 233 08LAVE 233 10LAVE 233 12LAVE 234 08LAVE 234 10LAVE 234 12LAVE 243 08LAVE 243 10LAVE 243 12LAVE 244 08LAVE 244 10LAVE 244 12LAVE 253 08LAVE 253 10LAVE 253 12LAVE 254 08LAVE 254 10LAVE 254 12LEVE 263 08LEVE 263 10LEVE 263 12LEVE 264 08LEVE 264 10LEVE 264 12

10°F133.0148.8161.8175.0191.6202.4212.6223.4232.6223.0242.6276.2287.2304.0319.2335.2349.4349.6383.0404.8425.0446.8466.2463.8508.0540.6541.8579.6600.6556.8609.8649.0650.2695.6720.8

15°F199.5223.2242.7262.5287.4303.6318.9335.1348.9334.5363.9414.3430.8456.0478.8502.8524.1524.4574.5607.2637.5670.2699.3695.7762.0810.9812.7869.4900.9835.2914.7973.5975.31043.41081.2

20°F266.0297.6323.6350.0383.2404.8425.2446.8465.2446.0485.2552.4574.4608.0638.4670.4698.8699.2766.0809.6850.0893.6932.4927.61016.01081.21083.61159.21201.21113.61219.61298.01300.41391.21441.6

25°F332.5372.0404.5437.5479.0506.0531.5558.5581.5557.5606.5690.5718.0760.0798.0838.0873.5874.0957.51012.01062.51117.01165.51159.51270.01351.51354.51449.01501.51392.01524.51622.51625.51739.01802.0

10°F129.4144.6157.4170.2186.4196.8206.8217.4226.4217.0236.0268.6279.6295.8310.6326.0340.0340.0372.6394.0413.6434.8453.6451.2494.2526.0527.2564.0584.4541.6593.2631.4632.6676.8701.2

15°F194.1216.9236.1255.3279.6295.2310.2326.1339.6325.5354.0402.9419.4443.7465.9489.0510.0510.0558.9591.0620.4652.2680.4676.8741.3789.0790.8846.0876.6812.4889.8947.1948.91015.21051.8

20°F258.8289.2314.8340.4372.8393.6413.6434.8452.8434.0472.0537.2559.2591.6621.2652.0680.0680.0745.2788.0827.2869.6907.2902.4988.41052.01054.41128.01168.81083.21186.41262.81265.21353.61402.4

25°F323.5361.5393.5425.5466.0492.0517.0543.5566.0542.5590.0671.5699.0739.5776.5815.0850.0850.0931.5985.01034.01087.01134.01128.01235.51315.01318.01410.01461.01354.01483.01578.51581.51692.01753.0

AIRFLOW(CFM)

2592025680254402520024800244002442023900233403852038160378003720036600366303595035010504004960048800488404780046680630006200061000610505975058350756007440073200732607170070020

AVAILCIRCUITS

6868686868686868686868686868686868686868686868686868686868686868686868

***Rows & FPI (1) Minimum Unit Circuit Amps = 1.25 x FLA of OneMotor + FLA of All Remaining Motors. (2) Maximum Unit OverloadProtection = 2.25 x FLA of One Motor + FLA of All Remaining Motors.

FAN MOTOR TOTAL FULL LOAD AMPS208/230/3/60

3.46.810.213.617.020.4

460/3/60

1.73.45.16.88.5

10.2

575/3/60

1.22.43.64.86.07.2

LAVE-11***LAVE-12***LAVE-13***LAVE-14***LAVE-15***LEVE-16***

ELECTRICAL DATA - TWO FAnS WIDE

FAN MOTOR TOTAL FULL LOAD AMPS208/230/3/60

13.620.427.234.040.8

460/3/60

6.810.213.617.020.4

575/3/60

4.87.29.612.014.4

LAVE-22***LAVE-23***LAVE-24***LAVE-25***LEVE-26***

NOTE: Ratings are based on85°F-115°F entering air

temperature. The temperaturedifference is between the

saturated condensing temp. andthe entering air temp. to the

condenser. Multiply R-22 ratingby 0.95 for R-134a. Summer

charge based on 25% ofcondenser volume with 86°F

liquid. Multiply by 1.14 for R-22.Winter charge based on 90%of condenser volume with -20°Fliquid. Multiply by 1.10 for R-22.

CONDENSERCHARGE R-404A

(LBS)

SUMMER

1818182424243030302727373737464646464646585858555555707070116116116150150150

WINTER

6262628989891171171179393134134134174174174174174174228228228214214214281281281469469469620620620

ESTSOUND10’(dBA)

5858585858585858586060606060606060616161616161626262626262636363636363

Page 9: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

LEVITOR II AIR COOLED CONDENSER 7Specifications subject to change without notice.

1 H.P. 850 RPM - OnE FAn WIDE

SHIPWEIGHT(LBS)

43743944446646947849549950871872172977377979283083885510411060112611351153121012231247143714491474155015661599202020352066216021812222255425732610278428082858

MODEL

TOTAL HEAT OF REJECTION (MBH)R-22 R-404A, R-507

TEMPERATURE DIFFERENCE TEMPERATURE DIFFERENCE

CONDENSERCHARGE R-404A

(LBS)

LAVA 112 08LAVA 112 10LAVA 112 12LAVA 113 08LAVA 113 10LAVA 113 12LAVA 114 08LAVA 114 10LAVA 114 12LAVA 122 08LAVA 122 10LAVA 122 12LAVA 123 08LAVA 123 10LAVA 123 12LAVA 124 08LAVA 124 10LAVA 124 12LAVA 132 10LAVA 132 12LAVA 133 08LAVA 133 10LAVA 133 12LAVA 134 08LAVA 134 10LAVA 134 12LAVA 143 08LAVA 143 10LAVA 143 12LAVA 144 08LAVA 144 10LAVA 144 12LAVA 153 08LAVA 153 10LAVA 153 12LAVA 154 08LAVA 154 10LAVA 154 12LEVA 163 08LEVA 163 10LEVA 163 12LEVA 164 08LEVA 164 10LEVA 164 12

10°F42.447.551.756.061.265.365.369.772.385.095.1103.4111.8122.4130.3130.5139.4144.6142.6155.1176.6183.6195.4195.8209.1217.0223.6244.9260.6261.1278.8289.2279.5306.1325.7326.4348.5361.5335.3367.3390.9391.6418.2433.8

15°F63.771.377.683.891.897.797.9104.8108.5127.3142.6155.1183.7183.6195.4195.8209.1216.9213.9232.7251.5275.5293.1293.7313.7325.4335.3367.3390.3391.6418.2433.8419.2459.1488.6489.6522.8542.5509.2550.9586.3587.4627.3650.7

20°F84.995.1103.4111.8122.4130.3130.5139.4144.6169.8190.2206.8223.6244.9260.6261.1278.8289.2285.3310.3335.3367.3390.9391.6418.2433.8447.1489.7521.1522.2557.7578.4588.9612.2651.4652.7697.1723.0670.7734.6781.7783.3836.5867.6

25°F106.1118.9129.3139.7153.0162.9163.2174.3180.8212.2237.7258.6279.5306.1325.7326.4348.5361.5356.6387.8419.2459.1488.6489.6522.8542.3588.9612.2651.4652.7697.1723.0698.6765.2814.3815.9871.3903.8838.4918.2977.1979.1

1045.61084.5

10°F41.648.650.754.960.064.064.068.370.983.393.2101.3109.6120.0127.7127.9136.6141.7139.7152.0173.1179.9191.5191.9204.9212.7219.1240.0255.4255.9273.2283.4273.0300.0319.2319.9341.5354.3328.6360.0383.1383.8409.8425.1

15°F62.469.976.082.190.095.795.9102.7106.3124.8139.7152.0180.0179.9191.5191.9204.9212.6209.6228.0246.5270.0287.2287.8307.4318.9328.6360.0382.5383.8409.8425.1410.8449.9478.8479.8512.3531.5492.9539.9574.6575.8614.9637.7

20°F83.293.2101.3109.6120.0127.7127.9136.6141.7166.4186.4202.7219.1240.0255.4255.9273.2283.4279.6304.1328.6360.0383.1383.8409.8425.1438.2479.9510.7511.8546.5566.8547.7600.0638.4639.6683.2708.5657.3719.9766.1767.6819.8850.2

25°F104.0116.5126.7136.9149.9159.6159.9170.8177.2208.0232.9253.4273.9300.0319.2319.9341.5354.3349.5380.0410.8449.9478.8479.8512.3531.5547.7600.0638.4639.6683.2708.5684.6749.9798.0799.6853.9885.7821.6899.8957.6959.51024.71062.8

SUMMER

5557778889991212121515151414181818232323232323292929272727353535585858757575

WINTER

1717172424243131313131314545455858584646676767878787878787114114114107107107141141141235235235310310310

AIRFLOW(CFM)

9260915190408933876085748582831480251852018302180801786617520171481716416628160502745327120267992628025722257462494224075357323504034296343283325632100446654380042870429104157040125535985256051444514924988448150

AVAILCIRCUITS

3434343434343434 3434 34343434343434343434 3434 34343434343434343434343434343434 343434343434

ESTSOUND10’(dBA)

6363636363636363636666666666666666666868686868686868696969696969707070707070717171717171

Levitor II Air Cooled Condenser

LAVA/LEVA Performance Data

NOTE: Ratings are based on 85°F 115°F entering air temperature. The temperature difference is between the saturated condensing temp. and theentering air temp. to the condenser. Multiply R-22 rating by 0.95 for R-134a. Summer charge based on 25% of condenser volume with 86°F liquid.Multiply by 1.14 for R-22. Winter charge based on 90% of condenser volume with -20°F liquid. Multiply by 1.10 for R-22.

Page 10: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

Levitor II Air Cooled Condenser

LAVA/LEVA Performance Data

1 H.P. 850 RPM - TWO FAnS WIDE

ELECTRICAL DATA - OnE FAn WIDE

SHIPWEIGHT(LBS)

1311132013361437 1425146215391555158818751912204420632100221422382287252626512700285128842950372537553817400540464129475947964870521852685366

MODEL

TOTAL HEAT OF REJECTION (MBH)R-22 R-404A, R-507

TEMPERATURE DIFFERENCE TEMPERATURE DIFFERENCE

LAVA 222 08LAVA 222 10LAVA 222 12LAVA 223 08LAVA 223 10LAVA 223 12LAVA 224 08LAVA 224 10LAVA 224 12LAVA 232 10LAVA 232 12LAVA 233 08LAVA 233 10LAVA 233 12LAVA 234 08LAVA 234 10LAVA 234 12LAVA 243 08LAVA 243 10LAVA 243 12LAVA 244 08LAVA 244 10LAVA 244 12LAVA 253 08LAVA 253 10LAVA 253 12LAVA 254 08LAVA 254 10LAVA 254 12LEVA 263 08LEVA 263 10LEVA 263 12LEVA 264 08LEVA 264 10LEVA 264 12

10°F169.8190.2206.8223.6244.9260.6261.1278.8289.2285.3310.3335.3367.3390.9391.6418.2433.8447.1489.7521.1522.2557.6578.4558.9612.2651.4652.7697.1723.0670.7734.6781.6783.3836.5867.6

15°F254.7285.3310.3335.3367.3390.9391.6418.2433.8427.9465.4503.0550.9586.3587.5627.4650.7670.7734.6781.7783.3836.5867.6838.4918.2977.1979.11045.61084.51006.01101.91172.61174.91254.71301.5

20°F339.6380.3413.7447.1489.7521.1522.2557.7578.4570.5620.5670.7734.6781.7783.3836.5867.6894.3979.41042.31044.41115.31156.81117.81224.31302.81305.51394.11446.11341.41469.21563.41566.61673.01735.3

25°F424.5475.4517.1558.9612.2651.4652.7697.1723.0713.1775.7838.4918.2977.1979.11045.61084.51117.81224.31302.81305.51394.11446.11397.31530.41628.61631.91742.71807.61676.71836.51954.31958.22091.22169.1

10°F166.4186.4202.7219.1240.0255.4255.9273.2283.4279.6304.1328.6360.0383.1383.8409.8425.1438.2479.9510.7511.8546.4566.8547.7600.0638.4639.6683.2708.5657.3719.9766.0767.6819.8850.2

15°F249.6279.6304.1328.6360.0383.1383.8409.8425.1419.3456.1492.9539.9574.6575.8614.9637.7657.3719.9766.1767.6819.8850.2821.6899.8957.6959.51024.71062.8985.91079.91149.11151.41229.61275.5

20°F322.8372.7405.4438.2479.9510.7511.8546.5566.8559.1608.1657.3719.9766.1767.6819.8850.2876.4959.81021.51023.51093.01133.71095.41199.81276.71279.41366.21417.21314.61439.81532.11535.31639.51700.6

25°F416.0465.9506.8547.7600.0638.4639.6683.2708.5698.8760.2821.6899.8957.6959.51024.71062.81095.41199.81276.71279.41366.21417.21369.41499.81596.01599.31707.81771.41643.21799.81915.21919.02049.42125.7

AIRFLOW(CFM)

37040366043616035732350403429634328332563210054906542405359852560514445149249884481507146470080685926865666512642008930087600857408582083140802501071961051201028881029849976896300

AVAILCIRCUITS

6868686868686868686868686868686868686868686868686868686868686868686868

***Rows & FPI (1) Minimum Unit Circuit Amps = 1.25 x FLA of OneMotor + FLA of All Remaining Motors. (2) Maximum Unit OverloadProtection = 2.25 x FLA of One Motor + FLA of All Remaining Motors.

FAN MOTOR TOTAL FULL LOAD AMPS208/230/3/60

4.48.813.217.622.026.4

460/3/60

2.04.06.08.010.012.0

575/3/60

1.452.94.355.87.258.7

LAVA-11***LAVA-12***LAVA-13***LAVA-14***LAVA-15***LEVA-16***

ELECTRICAL DATA - TWO FAnS WIDE

FAN MOTOR TOTAL FULL LOAD AMPS208/230/3/60

17.626.435.244.052.8

460/3/60

8.012.016.020.024.0

575/3/60

5.88.711.614.517.4

LAVA-22***LAVA-23***LAVA-24***LAVA-25***LEVA-26***

CONDENSERCHARGE R-404A

(LBS)

SUMMER

1818182424243030302727373737464646464646585858555555707070116116116150150150

WINTER

6262628989891171171179393134134134174174174174174174228228228214214214281281281469469469620620620

NOTE: Ratings are based on85°F-115°F entering air

temperature. The temperaturedifference is between the

saturated condensing temp. andthe entering air temp. to the

condenser. Multiply R-22 ratingby 0.95 for R-134a. Summer

charge based on 25% ofcondenser volume with 86°F

liquid. Multiply by 1.14 for R-22.Winter charge based on 90%of condenser volume with -20°Fliquid. Multiply by 1.10 for R-22.

ESTSOUND10’(dBA)

6969696969696969697171717171717171727272727272737373737373747474747474

Page 11: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

LEVITOR II AIR COOLED CONDENSER 9Specifications subject to change without notice.

1-1/2 H.P. 850 RPM - OnE FAn WIDE

SHIPWEIGHT(LBS)

43743944446646947849549950871872172977377979283083885510411060112611351153121012231247143714491474155015661599202020352066216021812222255425732610278428082858

MODEL

TOTAL HEAT OF REJECTION (MBH)R-22 R-404A, R-507

TEMPERATURE DIFFERENCE TEMPERATURE DIFFERENCE

CONDENSERCHARGE R-404A

(LBS)

LAVC 112 08LAVC 112 10LAVC 112 12LAVC 113 08LAVC 113 10LAVC 113 12LAVC 114 08LAVC 114 10LAVC 114 12LAVC 122 08LAVC 122 10LAVC 122 12LAVC 123 08LAVC 123 10LAVC 123 12LAVC 124 08LAVC 124 10LAVC 124 12LAVC 132 10LAVC 132 12LAVC 133 08LAVC 133 10LAVC 133 12LAVC 134 08LAVC 134 10LAVC 134 12LAVC 143 08LAVC 143 10LAVC 143 12LAVC 144 08LAVC 144 10LAVC 144 12LAVC 153 08LAVC 153 10LAVC 153 12LAVC 154 08LAVC 154 10LAVC 154 12LEVC 163 08LEVC 163 10LEVC 163 12LEVC 164 08LEVC 164 10LEVC 164 12

10°F46.251.555.660.165.369.169.473.776.392.3102.9111.3120.3130.7138.2138.8147.3152.5154.3166.9180.4196.0207.3208.1221.0238.7240.5261.3276.3277.5294.6305.0300.6326.7345.5346.9368.3381.3360.7392.1414.5416.3441.9457.5

15°F69.377.283.490.298.0103.6104.1110.5114.4138.5154.3166.9180.4196.0207.3208.2221.0228.8231.5250.3270.6294.0310.9312.2331.5343.1360.8392.0414.5416.3441.9457.5430.9490.1518.2520.4552.4571.9541.1588.1621.8624.5662.9686.3

20°F92.4102.9111.3120.3130.7138.2138.8147.3152.5184.7205.7222.5240.5261.4276.4277.6294.6305.0308.6333.8360.8392.0414.5416.2441.9457.5481.0522.7552.7555.1589.2610.0601.3653.4690.9693.9736.6762.5721.5784.1829.1832.7883.9915.0

25°F115.4128.6139.1150.3163.4172.7173.5184.1190.6230.9257.2278.1300.6326.7345.5346.9368.3381.3385.8417.2450.9490.1518.2520.4552.4571.9601.3653.4690.9693.9736.6762.5751.6816.8863.6867.4920.7953.2901.9980.1

1036.41040.81104.81143.8

10°F45.350.454.558.964.067.768.072.274.790.5100.8108.0117.9128.1135.4136.0144.4149.5151.2163.5176.8192.1203.1204.0216.6224.2235.7256.1270.8272.0288.7298.9294.6320.2338.6340.0360.9373.6353.5384.2406.2408.0433.1448.4

15°F67.975.781.788.496.0101.5102.0103.8112.3135.7151.2163.6176.8192.1203.2204.0216.6224.2226.9245.3265.2288.1304.7306.0324.9336.2353.6384.2406.2408.0433.1448.4441.9480.3507.8510.0541.4560.5530.3576.3609.4612.0649.6672.6

20°F90.6

100.8109.1117.9128.1135.4136.0144.4149.5181.0201.6218.1235.7256.2270.9272.0288.7298.9302.4327.1353.6384.2406.2408.0433.1448.4471.4512.2541.6544.0577.4597.8589.3640.3677.1680.0721.9747.3707.1768.4812.5816.0866.2896.7

25°F113.1126.0136.3147.3160.1169.2170.0180.4186.8226.3252.1272.5294.6320.2338.6340.0360.9373.7378.1408.9441.9480.3507.8510.0541.4560.5589.3640.3677.1680.0721.9747.3736.6800.5846.3850.1902.3934.1883.9960.51015.71020.01082.71120.9

SUMMER

5557778889991212121515151414181818232323232323292929272727353535585858757575

WINTER

1717172424243131313131314545455858584646676767878787878787114114114107107107141141141235235235310310310

AIRFLOW(CFM)

10967106821040910159978594419449903186602193421364208182031819570188821889818062173203204631227304772935528323283472709325980406363914037764377963612434640259982824729861300053185032974609545771056646566945418651960

AVAILCIRCUITS

3434343434343434 3434 34343434343434343434 3434 34343434343434343434343434343434 343434343434

ESTSOUND10’(dBA)

6565656565656565656868686868686868687070707070707070717171717171727272727272737373737373

Levitor II Air Cooled Condenser

LAVC/LEVC Performance Data

NOTE: Ratings are based on 85°F 115°F entering air temperature. The temperature difference is between the saturated condensing temp. and theentering air temp. to the condenser. Multiply R-22 rating by 0.95 for R-134a. Summer charge based on 25% of condenser volume with 86°F liquid.Multiply by 1.14 for R-22. Winter charge based on 90% of condenser volume with -20°F liquid. Multiply by 1.10 for R-22.

Page 12: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

Levitor II Air Cooled Condenser

LAVC/LEVC Performance Data

1-1/2 H.P. 850 RPM - TWO FAnS WIDE

ELECTRICAL DATA - OnE FAn WIDE

SHIPWEIGHT(LBS)

1311132013361437 1425146215391555158818751912204420632100221422382287252626512700285128842950372537553817400540464129475947964870521852685366

MODEL

TOTAL HEAT OF REJECTION (MBH)R-22 R-404A, R-507

TEMPERATURE DIFFERENCE TEMPERATURE DIFFERENCE

LAVC 222 08LAVC 222 10LAVC 222 12LAVC 223 08LAVC 223 10LAVC 223 12LAVC 224 08LAVC 224 10LAVC 224 12LAVC 232 10LAVC 232 12LAVC 233 08LAVC 233 10LAVC 233 12LAVC 234 08LAVC 234 10LAVC 234 12LAVC 243 08LAVC 243 10LAVC 243 12LAVC 244 08LAVC 244 10LAVC 244 12LAVC 253 08LAVC 253 10LAVC 253 12LAVC 254 08LAVC 254 10LAVC 254 12LEVC 263 08LEVC 263 10LEVC 263 12LEVC 264 08LEVC 264 10LEVC 264 12

10°F184.7205.7222.5240.5261.3276.3277.5294.6305.0308.6333.7360.7392.1414.5416.3441.9457.5481.0522.7552.7555.1589.3610.0601.3653.4690.9693.9736.5762.5721.5784.1829.1832.7883.9915.0

15°F277.1308.6333.8360.8392.0414.5416.3441.9457.5462.9500.6541.1588.1621.8624.5662.9686.3721.6784.1829.1832.7883.9915.0901.9980.11036.41040.81104.81143.81082.31176.11243.61249.01325.81372.5

20°F369.4411.5445.0481.0522.7552.7555.1589.2610.0617.2667.5721.5784.1829.1832.7883.9915.0962.01045.41105.51110.21178.51220.01202.51306.81381.81387.81473.11525.01443.01568.21658.21665.31767.71830.0

25°F461.8514.4556.3601.3653.4690.9693.9736.6762.5771.5834.4901.9980.11036.41040.81104.81143.81202.61306.81381.81387.81473.11525.01503.21633.51727.31734.71841.41906.31803.81960.22072.72081.62209.72287.6

10°F181.0201.6218.1235.7256.1270.8272.0288.7298.9302.4327.1353.5384.2406.2408.0433.1448.4471.4512.3541.7544.0577.5597.8589.2640.3677.1680.8721.8747.3707.0768.4812.5816.0866.2896.7

15°F271.6302.4327.1353.6384.2406.2408.0433.1448.4453.6490.6530.3576.3609.4612.0649.6672.6707.2768.4812.5816.0866.2896.7883.9960.51015.71020.01082.71120.91060.71152.61218.71224.01299.31345.1

20°F362.0403.3436.1471.4512.2541.6544.0577.4597.8604.9654.2707.1768.4812.5816.0866.2896.7942.81024.51083.41088.01154.91195.61178.51280.71354.21360.01443.61494.51414.11536.81625.01632.01732.31793.4

25°F452.6504.1545.2589.3640.3677.1680.0721.9747.3756.1817.7883.9960.51015.71020.01082.71120.91178.61280.71354.21360.01443.61494.51473.11600.81692.81700.01804.61868.21767.71921.02031.22040.02165.52241.8

AIRFLOW(CFM)

43868427284163640636391403776437796361243464064092624546095458710566465669454186519608127278280755287559272248692801015909785094410944909031086600121908117420113292113388108372103920

AVAILCIRCUITS

6868686868686868686868686868686868686868686868686868686868686868686868

***Rows & FPI (1) Minimum Unit Circuit Amps = 1.25 x FLA of OneMotor + FLA of All Remaining Motors. (2) Maximum Unit OverloadProtection = 2.25 x FLA of One Motor + FLA of All Remaining Motors.

FAN MOTOR TOTAL FULL LOAD AMPS208/230/3/60

6.012.018.024.030.036.0

460/3/60

3.06.09.012.015.018.0

575/3/60

2.55.07.510.012.515.0

LAVC-11***LAVC-12***LAVC-13***LAVC-14***LAVC-15***LEVC-16***

ELECTRICAL DATA - TWO FAnS WIDE

FAN MOTOR TOTAL FULL LOAD AMPS208/230/3/60

24.036.048.060.072.0

460/3/60

12.018.024.030.036.0

575/3/60

10.015.020.025.030.0

LAVC-22***LAVC-23***LAVC-24***LAVC-25***LEVC-26***

CONDENSERCHARGE R-404A

(LBS)

SUMMER

1818182424243030302727373737464646464646585858555555707070116116116150150150

WINTER

6262628989891171171179393134134134174174174174174174228228228214214214281281281469469469620620620

NOTE: Ratings are based on85°F-115°F entering air

temperature. The temperaturedifference is between the

saturated condensing temp. andthe entering air temp. to the

condenser. Multiply R-22 ratingby 0.95 for R-134a. Summer

charge based on 25% ofcondenser volume with 86°F

liquid. Multiply by 1.14 for R-22.Winter charge based on 90%of condenser volume with -20°Fliquid. Multiply by 1.10 for R-22.

ESTSOUND10’(dBA)

7171717171717171717373737373737373747474747474757575757575767676767676

Page 13: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

LEVITOR II AIR COOLED CONDENSER 11Specifications subject to change without notice.

1-1/2 H.P. 1140 RPM - OnE FAn WIDE

SHIPWEIGHT(LBS)

43743944446646947849549950871872172977377979283083885510411060112611351153121012231247143714491474155015661599202020352066216021812222255425732610278428082858

MODEL

TOTAL HEAT OF REJECTION (MBH)R-22 R-404A, R-507

TEMPERATURE DIFFERENCE TEMPERATURE DIFFERENCE

CONDENSERCHARGE R-404A

(LBS)

LAVF 112 08LAVF 112 10LAVF 112 12LAVF 113 08LAVF 113 10LAVF 113 12LAVF 114 08LAVF 114 10LAVF 114 12LAVF 122 08LAVF 122 10LAVF 122 12LAVF 123 08LAVF 123 10LAVF 123 12LAVF 124 08LAVF 124 10LAVF 124 12LAVF 132 10LAVF 132 12LAVF 133 08LAVF 133 10LAVF 133 12LAVF 134 08LAVF 134 10LAVF 134 12LAVF 143 08LAVF 143 10LAVF 143 12LAVF 144 08LAVF 144 10LAVF 144 12LAVF 153 08LAVF 153 10LAVF 153 12LAVF 154 08LAVF 154 10LAVF 154 12LEVF 163 08LEVF 163 10LEVF 163 12LEVF 164 08LEVF 164 10LEVF 164 12

10°F47.553.458.363.870.375.576.082.386.795.1106.8116.5127.6140.7150.9152.1164.5173.3160.3174.8191.4211.1226.3228.1246.7259.9255.3281.4301.7304.1329.0346.5319.1351.8377.2380.1411.3433.2382.9422.1452.6456.2493.5519.8

15°F71.380.187.495.7105.5113.2114.0123.4130.0142.6160.2174.8191.4211.1226.3228.1246.7259.9240.4262.2287.1316.6339.5342.1370.1389.9382.9422.1452.6456.2493.5519.8478.6527.7565.8570.2616.9649.8574.3633.2678.9684.3740.2779.7

20°F95.1106.8116.5127.6140.7150.9152.1164.5173.3190.2213.7233.1255.2281.4301.8304.1329.0346.5320.5349.6382.9422.1452.6456.2493.5519.8510.5565.8603.5608.3658.0693.1638.1703.6754.4760.3822.5866.4765.7844.3905.3912.4987.0

1039.6

25°F118.9135.5145.7159.5175.9188.8190.1205.6216.6237.7267.1291.3319.1351.8377.2380.2411.2433.2400.6437.0478.6527.7565.8570.2616.9649.8638.1703.6754.4760.3822.5866.4797.6879.5943.0950.4

1028.11083.0957.2

1055.31131.61140.51233.71299.5

10°F46.652.357.162.568.974.074.580.684.993.2104.7114.2125.0137.9147.8149.0161.2169.8157.1171.3187.6206.8221.8223.5241.8254.7250.2275.8295.7298.1322.4339.6312.7344.8369.7372.5403.0424.5375.2413.7433.5447.1483.6509.4

15°F69.978.585.793.8103.4110.9111.7120.9127.4139.7157.0171.3187.6206.9221.8223.5241.8254.7235.6257.0281.4310.3332.7335.3362.7382.1375.2413.7443.5447.1483.6509.4469.0517.1554.5558.8604.6636.8562.8620.5665.3670.6725.4764.1

20°F93.2104.7114.2125.0137.9147.9149.1161.2169.8186.4209.4228.4250.1275.8295.8298.0322.4339.6314.1342.6375.2413.7443.5447.1483.6509.4500.3551.5591.4596.1644.8679.2625.3689.5739.3745.1806.1849.1750.4827.4887.2894.2967.31018.8

25°F116.5130.8142.8156.3172.4184.8186.3201.5212.3232.9261.8285.5312.7344.8369.7372.6403.0424.5392.6428.3469.0517.1554.5558.8604.6636.8625.3689.5739.3745.1806.1849.1781.6861.9924.1931.41007.51061.3938.11034.21109.01117.71209.01273.5

SUMMER

5557778889991212121515151414181818232323232323292929272727353535585858757575

WINTER

1717172424243131313131314545455858584646676767878787878787114114114107107107141141141235235235310310310

AIRFLOW(CFM)

1164911541114301132311147109691097410730104862329823082228602264622294219382194821460209723462334290339693344132907329223219031458452924458843876438964292041944566155573554845548705365052430679386688265814658446438062916

AVAILCIRCUITS

3434343434343434 3434 34343434343434343434 3434 34343434343434343434343434343434 343434343434

ESTSOUND10’(dBA)

7272727272727272727575757575757575757777777777777777787878787878797979797979808080808080

Levitor II Air Cooled Condenser

LAVF/LEVF Performance Data

NOTE: Ratings are based on 85°F 115°F entering air temperature. The temperature difference is between the saturated condensing temp. and theentering air temp. to the condenser. Multiply R-22 rating by 0.95 for R-134a. Summer charge based on 25% of condenser volume with 86°F liquid.Multiply by 1.14 for R-22. Winter charge based on 90% of condenser volume with -20°F liquid. Multiply by 1.10 for R-22.

Page 14: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

Levitor II Air Cooled Condenser

LAVF/LEVF Performance Data

1-1/2 H.P. 1140 RPM - TWO FAnS WIDE

ELECTRICAL DATA - OnE FAn WIDE

SHIPWEIGHT(LBS)

1311132013361437 1425146215391555158818751912204420632100221422382287252626512700285128842950372537553817400540464129475947964870521852685366

MODEL

TOTAL HEAT OF REJECTION (MBH)R-22 R-404A, R-507

TEMPERATURE DIFFERENCE TEMPERATURE DIFFERENCE

LAVF 222 08LAVF 222 10LAVF 222 12LAVF 223 08LAVF 223 10LAVF 223 12LAVF 224 08LAVF 224 10LAVF 224 12LAVF 232 10LAVF 232 12LAVF 233 08LAVF 233 10LAVF 233 12LAVF 234 08LAVF 234 10LAVF 234 12LAVF 243 08LAVF 243 10LAVF 243 12LAVF 244 08LAVF 244 10LAVF 244 12LAVF 253 08LAVF 253 10LAVF 253 12LAVF 254 08LAVF 254 10LAVF 254 12LEVF 263 08LEVF 263 10LEVF 263 12LEVF 264 08LEVF 264 10LEVF 264 12

10°F190.2213.7233.1255.3281.4301.7304.1329.0346.5320.5349.6382.9442.1452.6456.2493.5519.8510.5562.9603.5608.3658.0693.1638.1703.5754.4760.3822.5866.3765.7884.3905.3912.4986.9

1039.6

15°F285.3320.5349.6382.9422.1452.6456.2493.5519.8480.7524.4574.3633.2678.9684.3740.2779.7765.7844.3905.3912.4987.01039.6957.21055.31131.61140.51233.71299.51148.61266.41357.91368.61480.41559.4

20°F380.3427.3466.1510.5562.8603.5608.3658.0693.1641.0699.2765.7844.3905.3912.4987.01039.61021.01125.71207.01216.51316.01386.21276.21407.11508.81520.61644.91732.71531.51688.51810.51824.81973.92079.3

25°F475.4534.2582.7638.1703.6754.4760.3822.5866.4801.2874.0957.21055.31131.61140.51233.71299.51276.21407.11508.81520.61644.91732.71595.31758.91886.01900.82056.22165.91914.32110.72263.12281.02467.42599.1

10°F186.4209.4228.4250.2275.8295.7298.1322.4339.6314.1342.6375.2413.7443.5447.1483.6509.4500.3551.6591.5596.1644.8679.2625.4689.5739.3745.1806.0849.0750.4827.4887.2894.2967.21018.9

15°F279.6314.1342.6375.2413.7443.5447.1483.6509.4471.1513.9562.8620.5665.3670.6725.4764.1750.4827.4887.2894.2967.31018.8938.11034.21109.01117.71209.01273.51125.61241.11330.71341.21450.81528.2

20°F372.7418.8456.8500.3551.5591.4596.1644.8679.2628.2685.2750.4827.4887.2894.2967.31018.81000.61103.21182.91192.21289.71358.51250.71379.01478.61490.21612.01698.01500.91654.71774.31788.31934.42037.7

25°F465.9523.5571.0625.3689.5739.3745.1806.1849.1785.2856.5938.11034.21109.01117.71209.01273.51250.71379.01478.61490.21612.01698.01563.41723.71848.31862.82015.12122.61876.02068.52217.82235.42418.12547.1

AIRFLOW(CFM)

465564582445096444124336442344423764105639808687366764466618650466351663564615845971288824867288468884752821127961611103010841010586010594010264099520133236130092127032127128123168119424

AVAILCIRCUITS

6868686868686868686868686868686868686868686868686868686868686868686868

***Rows & FPI (1) Minimum Unit Circuit Amps = 1.25 x FLA of OneMotor + FLA of All Remaining Motors. (2) Maximum Unit OverloadProtection = 2.25 x FLA of One Motor + FLA of All Remaining Motors.

FAN MOTOR TOTAL FULL LOAD AMPS208/230/3/60

7.014.021.028.035.042.0

460/3/60

3.57.010.514.017.521.0

575/3/60

2.44.87.29.612.014.4

LAVF-11***LAVF-12***LAVF-13***LAVF-14***LAVF-15***LEVF-16***

ELECTRICAL DATA - TWO FAnS WIDE

FAN MOTOR TOTAL FULL LOAD AMPS208/230/3/60

28.042.056.070.084.0

460/3/60

14.021.028.035.042.0

575/3/60

9.614.419.224.028.8

LAVF-22***LAVF-23***LAVF-24***LAVF-25***LEVF-26***

CONDENSERCHARGE R-404A

(LBS)

SUMMER

1818182424243030302727373737464646464646585858555555707070116116116150150150

WINTER

6262628989891171171179393134134134174174174174174174228228228214214214281281281469469469620620620

NOTE: Ratings are based on85°F-115°F entering air

temperature. The temperaturedifference is between the

saturated condensing temp. andthe entering air temp. to the

condenser. Multiply R-22 ratingby 0.95 for R-134a. Summer

charge based on 25% ofcondenser volume with 86°F

liquid. Multiply by 1.14 for R-22.Winter charge based on 90%of condenser volume with -20°Fliquid. Multiply by 1.10 for R-22.

ESTSOUND10’(dBA)

7878787878787878788080808080808080818181818181828282828282838383838383

Page 15: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

AL

ELECTRICAL BOX ELECTRICAL BOX

LB C

W

BL

AIR

H

AL

A

AL

B A

AIR

H

WC

A A AL

ELECTRICAL BOX ELECTRICAL BOX

ELECTRICAL BOX

ELECTRICAL BOX

B B

(2)

OnE FAn WIDE

CONNECTIONSOD IN(1)

W

58112166220274328

H

54545454

58-1/258-1/2

A

-108108108108108

B

54-54-54-

W

45-1/445-1/445-1/445-1/445-1/445-1/4

C

41-1/441-1/441-1/441-1/441-1/441-1/4

INLET

1-3/81-5/82-1/82-1/82-1/82-5/8

OUTLET

1-3/81-5/82-1/82-1/82-1/82-5/8

LAV*-11***LAV*-12***LAV*-13***LAV*-14***LAV*-15***LEV*-16***

TWO FAn WIDE

CONNECTIONSOD IN(1)

W

112166220274328

H

545454

58-1/258-1/2

A

108108108108108

B

-54-54-

W

90-1/290-1/290-1/290-1/290-1/2

C

86-1/286-1/286-1/286-1/286-1/2

INLET

(2)1-5/8(2)2-1/8(2)2-1/8(2)2-1/8(2)2-5/8

OUTLET

(2)1-5/8(2)2-1/8(2)2-1/8(2)2-1/8(2)2-5/8

LAV*-22***LAV*-23***LAV*-24***LAV*-25***LEV*-26***

Levitor II Air Cooled Condenser

LEVITOR II AIR COOLED CONDENSER 13Specifications subject to change without notice.

Dimensional Drawings

*Indicates fan/motor combination. Includes standard 22" legs.(1) Connections are approximate. Exact size is determined by computerized circuiting program.

(2) 1 X 3 has six legs; 2 x 3 has eight legs.2 columns of "W" need to

change one to L and W

Page 16: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

Levitor II Air Cooled Condenser

LAVB Performance Data

14 LEVITOR II AIR COOLED CONDENSERSpecifications subject to change without notice.

1/2 H.P. 1140 RPM

ONE FANMODEL

TWO FANMODEL

RATING BASED ON 85°-115°F ENTERING AIR TEMPERATURE TD IS SATURATED CONDENSING TEMP. MINUS ENTERING AIR TEMP.

TOTAL HEAT OF REJECTION CAPACITY (MBH)

R-22 TD R-404A, R-507A TD

LAVB 112 10LAVB 113 10LAVB 114 10LAVB 122 10LAVB 123 10LAVB 124 10LAVB 133 10LAVB 134 10LAVB 143 10LAVB 144 10LAVB 153 10LAVB 154 10LAVB 163 10LAVB 164 10LAVB 173 10LAVB 174 10

15°F30.239.445.460.578.990.9118.3136.3157.8181.7197.2227.1236.7272.6276.1318.0

20°F45.459.168.290.7118.3136.3177.8204.5236.7272.6295.9340.7355.0408.8414.2477.0

25°F60.578.990.9121.0157.8181.7236.7272.6315.6363.4394.5454.3473.3545.1552.2636.0

10°F29.438.444.258.976.788.4115.1132.6153.5176.8191.9221.0230.2265.2268.6309.4

15°F44.257.666.483.3115.1132.6172.7199.0230.2265.2287.8331.5345.5397.8403.0464.1

20°F58.976.788.4117.8153.5176.8230.2265.2307.1353.6383.3441.9460.5530.4537.3618.8

AIRFLOWCFM67506400600013500128001200019200180002560024000320003000038400360004480042000

ROWSDEEP2342343434543434

# OFFANS1112223344556677

AVAILCIRCUITS

30303030303030303030303030303030

WGT INCLFLOODCHARGE(LBS)1811852003523724005596008409008619501070115013491450

WINTERFLOODCHARGE(LBS)10141919293943586486629786116107144

LAVB 222 10LAVB 223 10LAVB 224 10LAVB 233 10LAVB 234 10LAVB 243 10LAVB 244 10LAVB 253 10LAVB 254 10LAVB 263 10LAVB 264 10LAVB 273 10LAVB 274 10

121.0157.8181.7236.7272.6315.6363.4394.5454.3473.3545.1552.2636.0

181.5236.7272.6355.0408.8473.3545.1591.7681.4710.0817.7828.3953.9

242.0315.6363.4473.3545.1631.1726.8788.9908.5946.7

1090.21104.51271.9

117.8153.5176.8230.2265.2307.1353.6383.8441.9460.6530.4537.3618.8

176.5230.2265.2345.5397.8460.6530.4575.7663.0690.8795.6806.0928.2

235.4307.1353.6460.6530.4614.1707.1767.6884.0921.21060.81074.71237.5

27000256002400038400360005120048000640006000076800720008960084000

ESTSOUND10’(dBA)65656568686870707171727273737474

71717173737474757576767777

2443434343434

4446688101012121414

60606060606060606060606060

6548659251118122517051825172219252095222527252925

38648686116126172124194172232214288

NOTE: Ratings are based on 85°F-115°F entering air temperature. The temperature difference is between thesaturated condensing temp. and the entering air temp. to the condenser. Multiply R-22 rating by 0.95 for R-134a.Not available with Quietor fan blades.

Page 17: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

AL

ELECTRICAL BOX

49

Side ViewsHeader End View

11

12, 22

13, 23

14, 24

15, 25

16, 26

17, 27

AL

AL A

L

LA

LL

A A

A

A

A A

A

A

A

AL

A

H

BW

H

BW

DIMEnSIOnAL DATA

Includes standard 18" legs.(1) Connections are approximate. Exact size is determined by computerized circuiting program.

ONE FAN WIDE

L

3975111147183219262

H

41-1/441-1/441-1/441-1/441-1/441-1/441-1/4

W

45-1/445-1/445-1/445-1/445-1/445-1/445-1/4

B

43-1/443-1/443-1/443-1/443-1/443-1/443-1/4

A

367210872/72

72/36/7272/72/72

72/72/36/72

LAVB-11***LAVB-12***LAVB-13***LAVB-14***LAVB-15***LAVB-16***LAVB-17***

ELECTRICAL DATA

ONE FAN WIDE

FAN MOTOR TOTAL RATED FULL LOAD AMPS CONNECTIONS OD IN.(1)

208/230/1

4.28.412.616.821.025.229.4

INLET

1-1/81-3/81-3/81-5/82-1/82-1/82-5/8

OUTLET

1-1/81-3/81-3/81-5/82-1/82-1/82-5/8

208/230/3

2.85.68.411.214.016.819.6

460/3

1.32.63.95.26.57.89.1

575/3

0.761.522.283.043.84.565.32

Levitor II Air Cooled Condenser

LEVITOR II AIR COOLED CONDENSER 15Specifications subject to change without notice.

Dimensional and Electrical Data

Page 18: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

Levitor II Air Cooled Condenser

Control Panel Nomenclature

16 LEVITOR II AIR COOLED CONDENSERSpecifications subject to change without notice.

TYPE OF APPLICATION:1 = Standard2 = 50% Winter Reduction Relay

(Split Condenser)3 = 50/50 Split Dual Panel

(for Two Indep. Slabs)4 = No Control Operation

(Terminal Blocks Only)

RELAY BOARDCONTROLS:

NC = No ControlsPT = Pressure ControlsTF = Temp. ControlsTP = Temperature and

Pressure ControlPV = Pressure Control

w/Variable SpeedHead Fans

TV = Temp. Controlw/Variable SpeedHeader End Fans

VN = No Controlsw/Variable SpeedHeader End Fans

FAN/MOTOR COMBINATION:

A = 1 HP 850 RPM 30"

B = 1/2 HP 1140 RPM 24"

C = 1-1/2 HP 850 RPM 30"

E = 1/2 HP 575 RPM 30"

F = 1-1/2 HP 1140 RPM 30"

FANS WIDE:1 or 2

FANS IN LINE:1 to 7(7 Fans on “B” Units Only)

CONTROL VOLTAGE:A = 208/230V F = 115V w/o TransformerB = 115V G = No Control VoltageC = No Control Voltage w/o TransformerD = 24V H = 24V w/o TransformerE = 208/230V w/o Transformer

CONTROL MANUFACTURER:1 = Johnson Mechanical3 = Johnson Electronic4 = No Controls

POWER VOLTAGE:A = 208/230/1/60K = 208/230/3/60M = 460/3/60P = 550/575/3/60U = 380/3/50

FUSES AND BREAKERS:1 = Individual Fuses and Contactors2 = Individual Circuit Breakers

and Contactors per each Fan3 = Fuses and Contactors per Pair of Fans4 = Terminal Blocks Only5 = Circuit Breaker and Contactor

per Pair of Fans6 = Fuses per Motor

AMBIENT AIR SENSOR FOR SPLIT(50% Winter Reduction):

T = Sensor ProvidedN = Sensor Not Required

PT A 2 6 M B 3 3 1 N

Page 19: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

n Thermal Fantrol-Electronic temperature controlcycles fans in response to entering air temperature.Set points and differential for each step areadjustable.

n Pressurtrol-Electronic pressure control with single point pressure transducer cycles fans in response to condenser pressure. Set points and differential for each step are adjustable.

n Thermal Pressure Fantrol-Electronic temperature control cycle fans in response to entering air temperature, except for header end fan(s). Header end fan(s) are controlled by pressure control.

n Variable Speed Control-Header end fan(s) arecontrolled with a speed controller in response tohead pressure. Electronic pressure control cycles thebalance of fans.

n Fan cycling Sequence-Fans are cycled offindividually or side-by-side in pairs in sequencefrom the end opposite the header to the headerend. Header end fans run continuously ifcompressors are operating.

Control Paneln Standard weather resistant enclosure is mounted on the opposite end of the unit when looking at theheaders.

n Control power is 24, 115 or 230 volts. A transformer is factory installed when required.

n Fan contactor with branch circuit fuse protection. Each motor or bank of motors protected by fuses.

n For horizontal airflow application, consult factory.n Disconnect not included, but may be required tomeet local codes.

Optional Arrangementsn Fan motor contactor and fuses only.n Fan motor contactor and fuses only which operatevia a customer specified solid state board. Circuitboard is factory mounted and wired.

n 50/50 split with two fan wide models. Each side is controlled separately with individual control panels oneach side.

n 50% winter reduction with two fan wide models.The right side fans are isolated in winter. Fans arelocked out via a relay or switch during shutdown.

Levitor II Air Cooled Condenser

LEVITOR II AIR COOLED CONDENSER 17Specifications subject to change without notice.

Standard Fan Cycling/Control Arrangements

Page 20: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

Levitor II Air Cooled Condenser

Low Ambient Controls (Head Pressure Control System)

Fan Cycling Sequence

18 LEVITOR II AIR COOLED CONDENSERSpecifications subject to change without notice.

TABLE A

Piping Schematic For Winter Controln Head Pressure Control for systems with air-cooled condenser is accomplished with two pressureregulating valves designed specifically for this typeof application. When low ambient conditions areencountered during winter operation on air-cooledsystems with a resultant drop in condensingpressure, the Head Pressure control’s purpose is to hold back enough of the condenser liquidrefrigerant so that some of the condenser surface is rendered inactive. This reduction of activecondensing surface results in a rise in thecondensing pressure and sufficient liquid linepressure for normal system operation.

Fan Cycling Controlsn Factory installed and tested fan cycling controlpanels (optional, see below for details).

Eternal Equalizer

Evaporator

Distributor

Condenser

CompressorGas Check Valve

HM Valve LLDrier

Receiver

SolenoidValve

TEV

1st Stage(Not Cycling)

2nd Stage

3rd Stage

4th Stage

5th Stage

6th Stage

CAPACITY MULTIPLIERWITH HEADER FANSRUNNING

1.00 0.55 0.40 0.33 0.28 0.24 0.55 0.40 0.33 0.28 0.24

NOTE:

Data given in table “A” is based on zero wind velocity. If condensers are subjected to wind effect, these multipliers will increase.

Page 21: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

Levitor is available with a mounted receiver for applications where a remote receiver is desired.Included in the option are a heavy-duty base, extended legs, receiver, a 3-way valve, relief valve(s),rotalocks, ball valves, and ORI/ORD valves. Optional heated and/or oversized receivers available.

Receiver models are 12” taller than standard models. Add the following to weights:

SIZE

10-3/4” x 48”10-3/4” x 60”12-3/4” x 72”14-3/4” x 96”

R-22(LBS)

128162275444

R-404A(LBS)

114144245395

RECEIVER CAPACITIES @ 80% FuLL

# OF FANS1 x 11 x 21 x 31 x 41 x 51 x 61 x 72 x 22 x 32 x 42 x 52 x 62 x 7

1350440530620820910100052062072091010201120

2550640730820112012101300700800910121013201420

ADDITIOnAL unIT WEIGHTS

Levitor II Air Cooled Condenser

LEVITOR II AIR COOLED CONDENSER 19Specifications subject to change without notice.

Mounted Receivers

# OF RECEIVERS

Page 22: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

Levitor II Air Cooled Condenser

Mounted Receiver Diagram (One Receiver)

20 LEVITOR II AIR COOLED CONDENSERSpecifications subject to change without notice.

ELECTRICAL

BOX

Page 23: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

Levitor II Air Cooled Condenser

LEVITOR II AIR COOLED CONDENSER 21Specifications subject to change without notice.

Mounted Receiver Diagram (Two Receivers)

Page 24: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

Levitor II Air Cooled Condenser

Wiring Diagram

22 LEVITOR II AIR COOLED CONDENSERSpecifications subject to change without notice.

(-311) Single Fans

(-331) Pairs of Fans

Page 25: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

Levitor II Air Cooled Condenser

Replacement Parts

L_VE unITL_VC unIT

L_VA unIT

DESCRIPTION

MOTOR: 1 HP, 850 RPM, 208-230/460/3/60

MOTOR: 1 HP, 850 RPM, 575/3/60

FAN: 30” DIA. CW 5/8” BORE

GUARD: FOR 30” FAN

PART #

4410138

4410180

4780320

4910218

LAVB unIT

DESCRIPTION

MOTOR: 1/2 HP, 1140 RPM, 208-230/460/3/60

MOTOR: 1/2 HP, 1140 RPM, 575/3/60

FAN: 24” DIA. CW 5/8” BORE

GUARD: FOR 24” FAN

PART #

4410179

CALL

4780141

4914792

DESCRIPTION

MOTOR: 1-1/2 HP, 850 RPM, 208-230/460/3/60

MOTOR: 1-1/2 HP, 850 RPM, 575/3/60

FAN: 30” DIA. CW 5/8” BORE

GUARD: FOR 30” FAN

PART #

4410179

4410313

4780662

4910218

DESCRIPTION

MOTOR: 1/2 HP, 575 RPM, 208-230/460/3/60

MOTOR: 1/2 HP, 575 RPM, 575/3/60

FAN: 30” DIA. CW 5/8” BORE

GUARD: FOR 30” FAN

PART #

4410184

4410315

4780142

4910218

L_VF unIT

DESCRIPTION

MOTOR: 1-1/2 HP, 1140 RPM, 208-230/460/3/60

MOTOR: 1-1/2 HP, 1140 RPM, 575/3/60

FAN: 30” DIA. CW 5/8” BORE

GUARD: FOR 30” FAN

PART #

4410139

4410314

4780142

4910218

OTHER COMMOn PARTS

DESCRIPTION

1/2 HP, 208-230/1/60 FOR VARIABLE SPEED

3/4 HP, 208-230/1/60 FOR VARIABLE SPEED

MOTOR CONTACTOR WITH 24 VOLT COIL

MOTOR CONTACTOR WITH 110 VOLT COIL

MOTOR CONTACTOR WITH 230 VOLT COIL

P352AB-3C PRESSURE CONTROLLER

S352AA-2C ADDER MODULE (PRESSURE)

P399BAC-1C PRESSURE TRANSDUCER

A350AB-1 TEMPERATURE CONTROLLER

PART #

4410176

CALL

4480824

4481721

CALL

4481838

4481839

4481840

4481731

LEVITOR II AIR COOLED CONDENSER 23Specifications subject to change without notice.

Page 26: AIR COOLED CONDENSER AND FLUID COOLER Documents/Krack_Levitor... · Levitor II Air Cooled Condenser Table of Contents LEVITOR II AIR COOLED CONDENSER Specifications subject to change

Levitor II Air Cooled Condenser

Notes

24 LEVITOR II AIR COOLED CONDENSERSpecifications subject to change without notice.