Upload
hermit44535
View
266
Download
3
Embed Size (px)
Citation preview
7/25/2019 Trane Air Cooled Condenser
1/32
Air-Cooled Condensers CAUJ
20-120 Tons
August 2011 ACDS-PRC003-EN
Product Catalog
7/25/2019 Trane Air Cooled Condenser
2/32
2011 Trane All rights reserved ACDS-PRC003-EN
Introduction
Air-Cooled Condensers Built for Every Need
Trane has the right condenser...If you are designing a new system or replacing an existing air-cooled condenser, Trane can satisfy
virtually any application need. Whether coupled with an industrial compressor, a single zone
commercial self-contained unit, compressor chiller or a Cold Generator chiller, Trane has the right
air-cooled condenser for the job. When teamed with any one of a wide range of compressor-
evaporator combinations, Trane air-cooled condensers, available in 20 to 120 tons, are ideal for
multistory office buildings, hotels, schools, municipal and industrial facilities.
7/25/2019 Trane Air Cooled Condenser
3/32
Table of Contents
ACDS-PRC003-EN 3
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
20 to 120 Ton Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Durable Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Microchannel Condenser Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Model Number Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Selection Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Performance Adjustment Factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
7/25/2019 Trane Air Cooled Condenser
4/32
4 ACDS-PRC003-EN
Features and Benefits
20 to 120 Ton Units
Trane 20 to 120 ton air-cooled condensers have an operating range of 40F to 115F, with a lowambient option down to 0F.
The control panel is factory-installed and wired to prevent potential damage and to provide
weathertight protection.
The control panel contains:
fan motor contactors.
fan cycling controls.
terminal point connection for compressor interlock.
115-volt control power transformer.
These standard features reduce installation costs and provide easy interface with control logic.
All Trane air-cooled condenser coils are an all aluminum Microchannel design. The 20 to 30 ton
condensers are single circuit; 40 to 120 ton units are dual circuited; all feature integral subcooling.Units can have optional corrosion protected condenser coil.
Durable Construction
Trane 20 to 120 ton condensers are built for long life. The unit frame is constructed of 14 gauge
galvanized steel. Louvered panels provide excellent coil protection while enhancing unit
appearance and strength. The unit surface is phosphatized and finished with Trane Slate Grey air-
dry paint. This air dry-paint finish exceeds 500 consecutive hour salt spray resistance in accordance
with ASTM B117.
Microchannel Condenser Coils
Microchannel coils are an all aluminum coil that has
been successfully used in the automotive industry for
many years, and is now being applied in the HVACindustry. The coils have a fully-brazed construction
which increases coil rigidity making them more
rugged to withstand the rigors of jobsite handling.
Additionally, the light weight simplifies coil handling.
The all aluminum construction creates an exceptional
heat transfer capability, allowing the refrigerant
charge to be reduced to levels that exceed LEED EA-
Credit 4 requirements. Bottom line, less refrigerant is
being used, which creates a healthier and greener
environment.
Microchannel Flat Tube
Header
(top removed)
Ribbon Fin
7/25/2019 Trane Air Cooled Condenser
5/32
ACDS-PRC003-EN 5
Application Considerations
Certain application constraints should be considered when sizing, selecting, and installing air-
cooled condensers. Unit and system reliability depends on properly and completely
acknowledging these considerations. Consult your local Trane sales engineer if your applicationvaries from these guidelines.
Setting the Unit
A base or foundation is not required if the selected unit location is level and strong enough to
support the operating weight. Refer to the Weights section for the weight of individual units.
Isolation and Sound Emission
The most effective method of noise isolation is proper unit location. Units should be placed away
from noise sensitive areas. Structurally transmitted noise can be reduced with the use of spring
isolators and they are recommended for acoustically sensitive applications. Flexible electrical
conduit, for maximum isolation effectiveness, will reduce sound transmitted through electrical
conduit.
State and local codes on sound emissions should always be considered. Since the environment in
which a sound source is located affects sound pressure, unit placement must be carefully
evaluated.
Servicing
Recommended minimum space envelopes for servicing are located in the Dimensional Data
section and serve as guidelines for providing adequate clearance. The minimum space envelopes
also allow for control panel door swing and routine maintenance requirements.
Unit Location
Unobstructed flow of condenser air is essential to maintaining capacity and operating efficiency.
When determining unit placement, careful consideration must be given to assure a sufficient flow
of air across the condenser heat transfer surface. Two detrimental conditions are possible and must
be avoided: Warm air recirculation and coil starvation.
Warm air recirculation occurs when discharge air from the condenser fans is recycled back at thecondenser coil inlet. Coil starvation occurs when free airflow to the condenser is restricted.
Both warm air recirculation and coil starvation cause reductions in unit efficiency and capacity
because of the higher head pressures associated with them. In more severe cases, nuisance unit
shutdowns will result from excessive head pressures.
Cross winds, those perpendicular to the condenser, tend to aid efficient operation in warmer
ambient conditions. However, they tend to be detrimental to operation in lower ambients or when
hot gas bypass is used due to the accompanying loss of adequate head pressure. As a result, it is
advisable to protect air-cooled condensers from continuous direct winds exceeding 10 miles per
hour.
Debris, trash, supplies, etc., should not be allowed to accumulate in the vicinity of the air-cooled
condenser. Supply air movement may draw debris into the condenser coil, blocking spaces
between coil fins and causing coil starvation. Special consideration should be given to low ambient
units. Condenser coils and fan discharge must be kept free of snow or other obstructions to permit
adequate airflow for satisfactory unit operation.
Clearance
Vertical condenser air discharge must be unobstructed. While it is difficult to predict the degree of
warm air recirculation, a unit installed with a ceiling or other obstruction above it will lose capacity
and the maximum ambient operation will be reduced. Nuisance high head pressure tripouts may
also occur.
The inlet to the coil must also be unobstructed. A unit installed closer than the minimum
recommended distance to a wall or other vertical riser may experience a combination of coil
7/25/2019 Trane Air Cooled Condenser
6/32
6 ACDS-PRC003-EN
Application Considerations
starvation and warm air recirculation, resulting in unit capacity and efficiency reductions, as well
as possible excessive head pressures. The recommended lateral distances are listed in the
Dimensional Data section.
Voltage
Nominal voltage is the nameplate rating voltage. The actual range of line voltages at which the
equipment can satisfactorily operate is given below:
200/230-volt units ship from the factory set for operation in the 180 through 220-volt range. By
changing leads on unit transformers, the unit will operate in the 208 through 254-volt range.
Effects of Altitude
The tables in the Performance Data section are for use at sea level. At elevations substantially
above sea level, the decreased air density will decrease condenser capacity. Refer to the
Performance Adjustment Factors section to correct performance at other altitudes.
Ambient Limitations
Trane condensers are designed for year-around applications in ambients from 0F through 115F.
For operation below 0 F or above 115 F, contact the local Trane sales office.
Start-up and operation of Trane condensers at lower ambient temperatures require that sufficient
head pressure be maintained for proper operation. Minimum operating ambient temperatures for
standard unit selections and units with hot gas bypass are shown in the General Data section.
These temperatures are based on still conditions (winds not exceeding five mph.) Greater wind
velocities will result in a drop in head pressure, therefore, increasing the minimum starting andoperating ambient temperatures.
Units with the low ambient option are capable of starting and operating in ambients down to 0F,
10F with hot gas bypass. Optional low ambient units use a condenser fan damper arrangement
that controls condenser capacity by modulating in response to head pressure.
Maximum cataloged ambient temperature operation of a standard condenser is 115F. Operation
at design ambients above 115F can result in excessive head pressures. For operation above 115F,
contact the local Trane sales office.
Table 1. Voltage range
Nominal Voltage Voltage Utilization Range
200/230 180-220 or 208-254
460 416-508
575 520-635
7/25/2019 Trane Air Cooled Condenser
7/32
ACDS-PRC003-EN 7
20 to 60 Ton Model
NomenclatureDigit 1 Unit Type
C = Condenser
Digit 2 Condenser
A = Air-Cooled
Digit 3 Airflow
U = Upflow
Digit 4 Development
Sequence
J = Third
Digit s 5,6,7 Nominal Capacity
C20 = 20 Tons
C25 = 25 TonsC30 = 30 Tons
C40 = 40 TonsC50 = 50 TonsC60 = 60 Tons
Digit 8 Power Supply
G = 200/230/60/3 XL4 = 460/60/3 XL5 = 575/60/3 XL
Digit 9 Condenser Circuit
1 = Single (20-30 Ton)2 = Dual (40-60 Ton)
Digit 10 Design Sequence
* = Factory Assigned
Digit 11 Ambient Control0 = Standard1 = 0 F
Digit 12 Agency Approval
0 = None3 = cULus
Digits 13, 14 Miscellaneous
J = Corrosion Protected CondenserCoil1 = Spring Isolators2 = Rubber Isolators
Note: The service digit for each modelnumber contains 14 digits; all 14digits must be referenced.
80 to 120 Ton Model
NomenclatureDigit 1 Unit Type
C = Condenser
Digit 2 Condenser
A = Air-Cooled
Digit 3 Airflow
U = Upflow
Digit 4 Development
Sequence
J = Third
Digits 5,6,7 Nominal Capacity
C80 = 80 Tons
D10 = 100 TonsD12 = 120 Tons
Digit 8 Power Supply
F = 230/60/34 = 460/60/35 = 575/60/3E = 200/60/3
Digit 9 Condenser Circuit
2 = Dual Circuit
Digit 10 Design Sequence
A = First
Digit 11 Ambient Control
0 = Standard1 = 0F
Digit 12 Agency Approval
0 = None2 = CSA3 = cULus
Digits 13, 14 Miscellaneous
J = Corrosion Protected CondenserCoil1 = Spring Isolators
Note: The service digit for each modelnumber contains 14 digits; all 14digits must be referenced.
Model Number Descriptions
7/25/2019 Trane Air Cooled Condenser
8/32
8 ACDS-PRC003-EN
General Data
Table 2. General data
20 Ton 25 Ton 30 Ton 40 Ton 50 Ton 60 Ton 80 Ton 100 Ton 120 Ton
Model Number CAUJC-20 CAUJC-25 CAUJ-C30 CAUJ-C40 CAUJ-C50 CAUJ-C60 CAUJ-C80 CAUJ-D10 CAUJ-D12
Gross Heat Rejection
(MBh)(a) 350 402 456 635 819 1002 1269 1639 2004
Condenser Fan Data
Quantity/Fan Dia. Type 2/26"/Prop 3/26"/Prop 3/26"/Prop 4/26"/Prop 6/26"/Prop 6/26"/Prop 8/26"/Prop 12/26"/Prop 12/26"/Prop
Fan Drive Type Direct Direct Direct Direct Direct Direct Direct Direct Direct
No. of Motors/HP Each 2/1.0 3/1.0 3/1.0 4/1.0 6/1.0 6/1.0 8/1.0 12/1.0 12/1.0
Nominal Total CFM 14600 20700 20700 26790 36890 40490 56490 73890 76280
Condenser Coil Data
Number of Coils/Size
(Inches)2/42x71 2/42x71 2/42x71 2/59x71 2/51x96 2/64x96 4/59x71 4/51x96 4/64x96
Size (ft2
) 41.4 41.4 41.4 58.2 68.0 85.4 116.4 136 170.7Rows/Fin per ft 1/276 1/276 1/276 1/240 1/240 1/240 1/240 1/240 1/240
Condenser Storage
Capacity (lbs)(b)18.7 18.7 18.7 23.5 25.0 31.5 47.1 50.0 62.9
Type Microchannel
Refrigerant Data(c)
No. Refrigerant Circuits 1 1 1 2 2 2 2 2 2
Refrigerant Type R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A
Refrigerant OperatingCharge (Lbs.)(d)
11.9 11.8 11.8 22.7 23.4 26.4 57.1 59.1 65.3
Minimum Outdoor Air Temperature for Mechanical Cooling
Standard Ambient
Operating Range (F)40-125 40-125 40-125 40-125 40-125 40-125 40-125 40-125 40-125
Low Ambient Option (F) 0 0 0 0 0 0 0 0 0
(a) Gross Heat Rejection is at a 30 F ITD (Initial Temperature Difference) between condensing temperature and ambient air entering condenser (includesthe effect of subcooling).
(b)At conditions of 95 ambient, condenser is 95 percent full(c) Condensing units are shipping with nitrogen holding charge only.(d)Operating charge is for condensing unit only, and does not include charge for low side or interconnecting lines.
7/25/2019 Trane Air Cooled Condenser
9/32
ACDS-PRC003-EN 9
Selection Procedures
When manually matching condensers with compressors, performance cross plotting becomes
necessary. The following procedure should be used to determine the correct condenser.
1. Determine the total cooling load. Make a prelimary compressor selection based on theexpected evaporator SST and condensing temperature.
2. Select compressors from manufacturer's data to meet the load at the evaporator SST (for chiller
low suction applications contact Trane applications) -
a. Remove the subcooling effect from the compressor performance at two or more compressor
capacity points. R-410A capacity increases 0.75% for every degree of subcooling (0.75% x
15F = 11.25%). So if compressor performance is at 15F subcooling, divide capacity by 1.1125
to get capacity at 0F subcooling. Plot these two points (SCT vs. compressor tons a 0F
subcooling) as shown in the selection example (Figure 1, p. 11).
b. Select a condenser fromFigure 3, p. 13(CAUJ-D10 assumed for this example) and read two
condenser only heat rejection points. Divide the condenser heat rejection by the compressor
N factor (Table 6, p. 11) to convert from heat rejection to net capacity (Net Tons Less
Subcooling). The N factor equals the ratio of compressor heat rejection divided bycompressor capacity at 0F subcooling. Plot these two points (SCT vs. Net Tons at 0F
subcooling) as shown in Figure 1, p. 11selection example.
Example:
Given- Total cooling load = 101 tons (1212 Mbh)
Design outdoor temperature = 95F
Assume- Evaporator SST = 45F (used in this example - application dependent)
Condenser SCT between 115F and 125F (20-30F ITD SCT-ambient)
Table 3. Compressor capacity with subcooling
(Qty 2) CSHN611 Trane R-410A Trio Scrolls Performance data includes 15F subcooling
SST SCT Tons Mbh
45 115 110 1320
45 125 103 1236
Notes:1. SST = Saturated Suction Temperature2. SCT = Saturated Condensing Temperature
Table 4. Compressor capacity with subcooling removed(Qty 2) CSHN611 Trane R-410A Trio Scrolls
Capacity
15F subcooling 0F subcooling
SST(a)
(a) SST = Saturated Suction Temperature
SCT(b)
(b)SCT = Saturated Condensing Temperature
Tons Mbh Tons Mbh
45 115 110 1320 98.9 1187
45 125 103 1236 92.6 1111
7/25/2019 Trane Air Cooled Condenser
10/32
10 ACDS-PRC003-EN
Selection Procedures
c. As shown on Figure 1, p. 11, draw a line though the points representing the compressor
capacity at 0F subcooling. Next, draw a line through the points representing condenser net
capacity less subcooling.
d. At the point of intersection of the compressor and condenser lines draw dashed lines to the
left and bottom margins as shown in Figure 1, p. 11. The end points of these lines will show
a resultant gross capacity of 92 tons at 126.1F condensing temperature.
e. From Figure 2, p. 12calculate the percent increase in total heat rejection due to subcooling,
and multiply by the N factor (see Table 6, p. 11) to get the percent increase in net capacity
due to subcooling.
Example:
At 95Fambient and 126.1Fcondensing temperature Figure 2, p. 12shows there is a 7.8%
increase in total heat rejection due to subcooling. Table 6shows a 1.34 N factor by linear
interpolation. This yields a system capacity of 92tons x (1 + 7.8% x 1.34) = 102tons.
f. If necessary use the values in Table 7, p. 12to adjust the system capacity for altitude.
g. Compare this result with the design capacity and condensing temperature.
The required cooling load is 101 tons, therefore, the CAUJ-D10 is the proper selection.
Repeat the process steps B through G as necessary to achieve the most economic condenser
selection.Note: Note that evaporator selection must also meet performance requirements. For this
example, the evaporator needs to provide at least 105 tons at 45SST. A conservative
estimate for liquid temperature entering the evaporator is the SCT minus the design
subcooling (125.1 - 15F = 110.1F for the example above). Contact Trane Applications if
excessive refrigerant line lengths or pressure drops are required.
Table 5. Condenser net capacity Mbh (less subcooling)
Assumed TF ITD
(SCT - ambient)
Ambient,
F SCT, F
Cond only heat
rejection, Mbh N factor
Net capacity less subcooling
Mbh Tons
20 95 115 938 1.27 739 61.5
30 95 125 1418 1.33 1066 88.8
Notes:1. ITD = Initial Temperature Difference2. SCT = Saturated Condensing Temperature3. N Factor = Compressor Efficiency Ratio
7/25/2019 Trane Air Cooled Condenser
11/32
ACDS-PRC003-EN 11
Selection Procedures
Table 6. N factor - Trane R-410A scroll compressors
Sat condtemp, F
Saturated suction temperature, F
30 35 40 45 50
110 1.33 1.30 1.27 1.24 1.22
115 1.36 1.33 1.30 1.27 1.25
120 1.40 1.36 1.33 1.30 1.27
125 1.45 1.40 1.37 1.33 1.30
130 1.50 1.45 1.41 1.37 1.34
135 1.57 1.51 1.46 1.41 1.37
140 1.64 1.57 1.51 1.46 1.42
145 1.73 1.65 1.58 1.53 1.48
Figure 1. Selection example
7/25/2019 Trane Air Cooled Condenser
12/32
12 ACDS-PRC003-EN
Performance Adjustment Factors
Figure 2. Condenser heat rejection increase due to subcooling (R-410A)
Table 7. Altitude correction multiplier for cooling capacity -- air-cooled condenser
Altitude (Ft) 2,000 4,000 6,000 8,000 10,000
Correction Multiplier 0.977 0.949 0.917 0.881 0.843
7/25/2019 Trane Air Cooled Condenser
13/32
ACDS-PRC003-EN 13
Performance Data
Figure 3. Condenser heat rejection (R-410A), 20-120 ton
C20
C30
C40
C80
C50
D10
D12
C60
C25
100
300
500
700
900
1100
1300
1500
1700
1900
2100
2300
2500
15 20 25 30 35 40 45
CondenserOnlyHeatRejection(MBH)
Temperature Difference, F
(CondensingTemp- EnteringAir Temp)
7/25/2019 Trane Air Cooled Condenser
14/32
14 ACDS-PRC003-EN
Electrical Data
Table 8. Electrical data
Unit Characteristics Condenser Fan Motor
Nominal
Tons Model No.
Electrical
Characteristics
Allowable
Voltage
Range
Minimum
Circuit
Ampacity
(3),(5)
Maximum
Fuse
Size
(2),(5)
No./HP
(1)
FLA
(Ea.)
(1)
LRA
(Ea.)
(1)
KW
(Ea.)
(1),(4)
20
CAUJ-C20G
CAUJ-C204
CAUJ-C205
200-230/60/3
460/60/3
575/60/3
180-220/208-254
416-508
520-635
9.2
4.1
3.2
15
15
15
2/1.0
2/1.0
2/1.0
4.1
1.8
1.4
20.7
9.0
7.2
0.9
0.9
0.9
25
CAUJ-C25G
CAUJ-C254
CAUJ-C255
200-230/60/3
460/60/3
575/60/3
180-220/208-254
416-508
520-635
13.3
5.9
4.6
20
15
15
3/1.0
3/1.0
3/1.0
4.1
1.8
1.4
20.7
9.0
7.2
0.9
0.9
0.9
30
CAUJ-C30G
CAUJ-C304
CAUJ-C305
200-230/60/3
460/60/3
575/60/3
180-220/208-254
416-508
520-635
13.3
5.9
4.6
20
15
15
3/1.0
3/1.0
3/1.0
4.1
1.8
1.4
20.7
9.0
7.2
0.9
0.9
0.9
40CAUJ-C40GCAUJ-C404
CAUJ-C405
200-230/60/3460/60/3
575/60/3
180-220/208-254416-508
520-635
17.47.7
6.0
2015
15
4/1.04/1.0
4/1.0
4.11.8
1.4
20.79.0
7.2
0.90.9
0.9
50
CAUJ-C50G
CAUJ-C504
CAUJ-C505
200-230/60/3
460/60/3
575/60/3
180-220/208-254
416-508
520-635
25.6
11.3
8.8
30
15
15
6/1.0
6/1.0
6/1.0
4.1
1.8
1.4
20.7
9.0
7.2
0.9
0.9
0.9
60
CAUJ-C60G
CAUJ-C604
CAUJ-C605
200-230/60/3
460/60/3
575/60/3
180-220/208-254
416-508
520-635
25.6
11.3
8.8
30
15
15
6/1.0
6/1.0
6/1.0
4.1
1.8
1.4
20.7
9.0
7.2
0.9
0.9
0.9
80
CAUJ-C80E
CAUJ-C80F
CAUJ-C804
CAUJ-C805
200/60/3
230/60/3
460/60/3
575/60/3
180-220
208-254
416-508
520-635
34
34
15
12
40
40
20
15
8/1.0
8/1.0
8/1.0
8/1.0
4.1
4.1
1.8
1.4
20.7
20.7
9.0
7.2
0.9
0.9
0.9
0.9
100
CAUJ-D10E
CAUJ-D10F
CAUJ-D104
CAUJ-D105
200/60/3
230/60/3
460/60/3
575/60/3
180-220
208-254
416-508
520-635
50
50
22
17
60
60
25
20
12/1.0
12/1.0
12/1.0
12/1.0
4.1
4.1
1.8
1.4
20.7
20.7
9.0
7.2
0.9
0.9
0.9
0.9
120
CAUJ-D12E
CAUJ-D12F
CAUJ-D124
CAUJ-D125
200/60/3
230/60/3
460/60/3
575/60/3
180-220
208-254
416-508
520-635
50
50
22
17
60
60
25
20
12/1.0
12/1.01
12/1.0
12/1.0
4.1
4.1
1.8
1.4
20.7
20.7
9.0
7.2
0.9
0.9
0.9
0.9
Notes:1. Electric information is for each individual motor.2. Maximum fuse size is permitted by NEC 440-22 is 300 percent of one motor RLA plus the RLA of the remaining motors.3. Minimum circuit ampacity equals 125 percent of the RLA of one motor plus the RLA of the remaining motors.4. All Kw values taken at conditions of 45F saturated suction temperature at the compressor and 95F ambient.5. Local codes may take precedence.
7/25/2019 Trane Air Cooled Condenser
15/32
ACDS-PRC003-EN 15
Dimensional Data
Figure 4. 20-ton air-cooled condenser
4" CONDUIT
MAIN POWER1 3/4" KO LOW
VOLTAGE (30V MAX.)
37 11/16"
3 3/8"
CONTROL PANEL
35 13/16"
31 1/4"
29 1/4"
4 1/2"
2 5/8"
5 5/16"
5 3/8"
3 3/8"
1/2" X 4 KO (115V)
1/2" X 2 KO (115V)
4 3/8"
6 1/8"
88 5/16"
74 1/4"
60"
11 1/2"
18"
1 1/4" x 4 1/2"
SLOT FOR 115
VOLT CONTROL
4" LINE
VOLTAGE
ACCESS
78" 5 3/16"
1 13/16"
LOW AMBIENT
DAMPER (SEE NOTE 2)
FAN GRILLE
FAN GRILLE
CONTROL PANEL
(SEE DETAIL A)
26 13/16"
CONTROL BOX BOTTOM
(SEE DETAIL A)
13"
6 1/4"
57 5/8"
1 1/4"
8"
72 1/2"
3/4" X 4 MTG HOLES
DOOR 43 1/4" W/
180 DEG SWING
2 1
4 3
NOTES:1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES.
2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT .
DETAIL A
CONTROL BOX BOTTOM
7/25/2019 Trane Air Cooled Condenser
16/32
16 ACDS-PRC003-EN
Dimensional Data
Figure 5. 20-ton air-cooled condenser (connections)
VOLTAGE ACCESS
CONTROL PANEL
7/8" O.D.
LIQUID LINE
8 1/16"13"
42"
S C A L E
1 , 0 0 0
34 1/2"
5 7/16"5 3/4"
LIQUID LINE
DISCHARGE LINE
COIL
1 3/8" O.D.
DISCHARGE LINE
CONTROL PANEL SIDE
CONTROL
PANEL SIDE
PLAN VIEW OF UNITCONNECTION DRAWING
CONNECTION DRAWING
CONTROL PANEL SIDE VIEW OF UNIT
ISOMETRIC DRAWING
ORIENTATION VIEW OF UNIT
NOTES:
1. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH
INSTALLER DOCUMENTS BEFORE INSTALLATION
7/25/2019 Trane Air Cooled Condenser
17/32
ACDS-PRC003-EN 17
Dimensional Data
Figure 6. 25- and 30-ton air-cooled condenser
1/2" X 4 KO (115V)
1 3/4" KO LOW
VOLTAGE (30V MAX.)
1/2" X 2 KO (115V)
CONTROL PANEL
4 1/2"
3 3/8"
5 3/8"2 5/8"
37 11/16"
35 13/16"
5 5/16"3 3/8"
31 1/4"
29 1/4" 4" CONDUIT
MAIN POWER1.6
CONTROL BOX BOTTOM
(SEE DETAIL A)
FAN GRILLE
LOW AMBIENT
DAMPER (SEE NOTE 2)FAN GRILLE
4" LINE
VOLTAGE ACCESS
1 1/4" x 4 1/2"
SLOT FOR 115
VOLT CONTROL
88 1/2"
60 1/8"
74 1/4"
18"11 1/2"
88 5/16"
78"
4 3/8"
6 1/8" 5 3/16"
1 13/16"
13"
6 1/4"
CONTROL PANEL
(SEE DETAIL A)
27 1/4"
57 5/8"
1 1/4"
8"
72 1/2"
DOOR 43 1/4" W/
180 DEG SWING
2 1
34
3/4" X 4 MTG HOLES
CONTROL BOX BOTTOM
DETAIL A
NOTES:1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES.
2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT .
7/25/2019 Trane Air Cooled Condenser
18/32
18 ACDS-PRC003-EN
Dimensional Data
Figure 7. 25- and 30-ton air-cooled condenser (connections)
CONTROL PANEL
VOLTAGE ACCESS
SCALE1.000
SCALE1,000
34 1/2"42"
8 1/16"13"
7/8" O.D. LIQUID LINE
1 3/8" O.D.DISCHARGE LINE
5 3/4" 5 7/16"
COIL
LIQUID LINEDISCHARGE LINE
ORIENTATION VIEW OF UNIT
ISOMETRIC DRAWING
CONTROL PANEL SIDE VIEW OF UNIT
CONNECTION DRAWING
CONNECTION DRAWING
PLAN VIEW OF UNIT
CONTROL
PANEL SIDE
CONTROL
PANEL SIDE NOTES:1. VERIFYWEIGHT, CONNECTION, ANDALL DIMENSION WITH
INSTALLER DOCUMENTS BEFORE INSTALLATION
7/25/2019 Trane Air Cooled Condenser
19/32
ACDS-PRC003-EN 19
Dimensional Data
Figure 8. 40-ton air-cooled condenser
29 1/4"
31 1/4"
35 13/16"
37 11/16"
3 3/8"
3 3/8"5 5/16"
2 5/8" 5 3/8"
1 3/4" KO LOW
VOLTAGE (30V MAX.)
1/2" X 2 KO (115V)
1/2" X 4 KO (115V)
4 1/2"
4" CONDUIT
MAIN POWER
CONTROL PANEL
88 9/16"
88 5/16"
22 1/2"16"
4 3/8"
6 1/8"5 3/16"
1 15/16"
88 5/16"
79 1/4"
13"
LOW AMBIENT
DAMPER (SEE NOTE 2)
FAN GRILLE
FAN GRILLE
1 1/4" x 4 1/2"
SLOT FOR 115
VOLT CONTROL
4" LINE
VOLTAGE ACCESS
CONTROL PANEL
(SEE DETAIL A)
6 1/4"
32 3/16"
BOTTOM OF CONTROL
BOX (SEE DETAIL A)
DOOR 43 1/4" W/
180 DEG SWING
2
3
6
8"
36 1/8"
36 1/8"
1 1/4"
1
4
5
3/4" X 6
MTG HOLES
85 5/8"
DETAIL A
BOTTOM OF CONTROL BOX
NOTES:1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES.
2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT .
7/25/2019 Trane Air Cooled Condenser
20/32
20 ACDS-PRC003-EN
Dimensional Data
Figure 9. 40-ton air-cooled condenser (connections)
VOLTAGE
ACCESS
1 3/8" O.D.
DISCHARGE
LIQUID LINE
S C A LE1, 000
5 11/16" 5 7/16"
27 7/16"
2 7/8"
41 7/8"
27"
10 1/2"
27 7/16"
49 1/2"
27"
1 3/8" O.D.
DISCHARGE
7/8" O.D. LIQUID LINE
DISCHARGE
7/8"O.D. LIQUID LINE
CONTROL
PANEL
ORIENTATION VIEW OF UNIT
ISOMETRIC DRAWING
CONTROL PANEL SIDE VIEW OF UNIT
CONNECTION DRAWING
CONNECTION DRAWING
PLAN VIEW OF UNIT
CONTROL PANELSIDE
CONTROL
PANELSIDE
NOTES:1. VERIFYWEIGHT, CONNECTION, ANDALL DIMENSION WITH
INSTALLER DOCUMENTS BEFORE INSTALLATION
7/25/2019 Trane Air Cooled Condenser
21/32
ACDS-PRC003-EN 21
Dimensional Data
Figure 10. 50-ton air-cooled condenser
29 1/4"
31 1/4"
35 13/16"
37 11/16"
3 3/8"
3 3/8"5 5/16"
2 5/8" 5 3/8"
1 3/4" KO LOW
VOLTAGE (30V MAX.)
1/2" X 2 KO (115V)
1/2" X 4 KO (115V)
4 1/2"
4" CONDUIT
MAIN POWER
CONTROL PANEL
88 5/16"
113 13/16"
103 1/2"
16"22 1/2"
79 1/4"
1 15/16"
FAN GRILLE
LOW AMBIENT
DAMPER (SEE NOTE 2)FAN GRILLE
1 1/4" x 4 1/2"
SLOT FOR 115VOLT CONTROL
4" LINE
VOLTAGE
ACCESS
BOTTOM OF CONTROL
BOX (SEE DETAIL A)
13"6 1/4"
32 1/4"
CONTROL PANEL
(SEE DETAIL A)
DOOR 43 1/4" W/
180 DEG SWING
8 1/8"
48 7/8"
48 7/8"
85 5/8"
3/4" X 6
MTG HOLES
12
34
56
DETAIL A
BOTTOM OF CONTROL BOX
NOTES:
1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES.
2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT .
7/25/2019 Trane Air Cooled Condenser
22/32
22 ACDS-PRC003-EN
Dimensional Data
Figure 11. 50-ton air-cooled condenser (connections)
Note List - 97075
CONTROL
PANEL
VOLTAGE
ACCESS
SC ALE 1, 00 0
SCALE1,000
10 13/16"
74 7/16"
10 13/16"
67 3/8"
27 7/16"
61 3/16"
27 7/16"
61 3/16"
5 7/16"5 11/16"
LIQUID LINE
1 3/8" O.D.
DISCHARGELINE
1 3/8" O.D.
DISCHARGE LINE
7/8"O.D.
LIQUID LINE
7/8"O.D.
LIQUID LINE
ORIENTATION VIEW OF UNIT
ISOMETRIC DRAWING
CONTROL PANEL SIDE VIEW OF UNIT
CONNECTION DRAWING
CONNECTION DRAWING
PLAN VIEW OF UNIT
CONTROL
PANELSIDE
CONTROLPANEL SIDE
NOTES:
1. VERIFYWEIGHT, CONNECTION, AND ALLDIMENSION WITH
INSTALLER DOCUMENTS BEFORE INSTALLATION
7/25/2019 Trane Air Cooled Condenser
23/32
ACDS-PRC003-EN 23
Dimensional Data
Figure 12. 60-ton air-cooled condenser
29 1/4"
31 1/4"
35 13/16"
37 11/16"
3 3/8"
3 3/8"5 5/16"
2 5/8" 5 3/8"
1 3/4" KO LOW
VOLTAGE (30V MAX.)
1/2" X 2 KO (115V)
1/2" X 4 KO (115V)
4 1/2"
4" CONDUIT
MAIN POWER
CONTROL PANEL
FAN GRILLE
4" LINE
VOLTAGE
ACCESS
1 1/4" x 4 1/2"
SLOT FOR 115
VOLT CONTROL
FAN GRILLE
CONTROL PANEL
(SEE DETAIL A)
1 15/16"
103 1/2" 5 3/16"
113 13/16"
22 1/2"16"
79 1/4"
114"
88 5/16"
13"
LOW AMBIENT
DAMPER (SEE NOTE 2)
32 3/16"
BOTTOM OF CONTROLBOX (SEE DETAIL A)
6 1/4"
3/4" X 6
MTG HOLES
DOOR 43 1/4" W/
180 DEG SWING
8 1/8"
48 7/8"
48 7/8"
85 5/8"
2 1
34
6 5
NOTES:
1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES.
2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT .
BOTTOM OF CONTROL BOX
DETAIL A
7/25/2019 Trane Air Cooled Condenser
24/32
24 ACDS-PRC003-EN
Dimensional Data
Figure 13. 60-ton air-cooled condenser (connections)
VOLTAGE
ACCESS
CONTROL
PANEL
SCALE
1,000
10 13/16"
74 7/16"
10 13/16"
67 3/8"
27 7/16"
61 3/16"
27 7/16"
61 3/16"
LIQUID LINE
1 3/8" O.D.DISCHARGELINE
1 3/8" O.D.
DISCHARGE LINE
7/8"O.D.
LIQUID LINE
S CA LE 1,000
5 11/16" 5 7/16"
7/8" O.D.
LIQUID LINE
CONTROL PANEL SIDE VIEW OF UNIT
CONNECTION DRAWING
CONNECTION DRAWING
PLAN VIEW OF UNIT
ORIENTATION VIEW OF UNIT
ISOMETRIC DRAWING
CONTROL
PANEL SIDE
CONTROL
PANEL SIDE
NOTES:
1. VERIFYWEIGHT, CONNECTION, ANDALL DIMENSION WITH
INSTALLER DOCUMENTS BEFORE INSTALLATION
7/25/2019 Trane Air Cooled Condenser
25/32
ACDS-PRC003-EN 25
Dimensional Data
Figure 14. 80-ton air-cooled condenser
1 13/16"
176 7/16"
83 1/8"
30 1/4" 30 1/8"
83 1/4"
88 5/16"
176 11/16"
FAN GRILLE
1 1/4"x 4 1/2"
SLOT FOR115
VOLT CONTROL
4" LINE
VOLTAGE
ACCESS
FAN GRILLE
79 1/4"
7"
9"
14"
LOW AMBIENTDAMPER(SEE NOTE 2)
6 1/4"13"
16 5/16"
BOTTOM OF CONTROLBOX(SEE DETAILA)
CONTROL PANEL
(SEE DETAILA)
2 1/4"x 1 1/4"24 VOLTAGE
CONTROL WIRING
3/4"X 8
MTG HOLES
DOOR43 1/4"W/
180 DEGSWING1 1/4"
8"
72 1/8"
16"
72 1/8"
85 5/8"
12
4 3
6 5
8 7
291/4"
31 1/4"
35 13/16"
37 11/16"
3 3/8"
3 3/8"5 5/16"
2 5/8" 5 3/8"
1 3/4"KO LOW
VOLTAGE (30VMAX.)
1/2"X 2 KO(115V)
1/2"X 4 KO(115V)
4 1/2"
4" CONDUIT
MAIN POWER
CONTROL PANEL
DIMENSIONAL DETAIL
DETAIL A
NOTES:1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES.2. LOW AMBIENT DAMPERONLYCOMESWITH SELECTEDUNIT .
7/25/2019 Trane Air Cooled Condenser
26/32
26 ACDS-PRC003-EN
Dimensional Data
Figure 15. 80-ton air-cooled condenser (connections)
VOLTAGE
ACCESS
C
ONTROL
PANEL
DISCHARGELINEC
OIL
LIQUIDLINE
11/8"O
.D.
LIQUIDLINE
15/8"DISCHARGELINE
SCALE1,000
59/16"
75/
16"
1369/16"
483/8"
35/16"
35/16"
2
111/16"
191/16"
141/16"
ISOMETRICDRAW
ING
ORIENTATIONVIEW
OFUNIT
PLANVIEW
OFUNIT
CONNECTIONDRAWING
CONNECTIONDRAWING
CONTROLPANELSIDEVIEW
OFUNIT
CONTROL
PANELSIDE
CONTROL
PANELSIDE
7/25/2019 Trane Air Cooled Condenser
27/32
ACDS-PRC003-EN 27
Dimensional Data
Figure 16. 100- and 120-ton air-cooled condenser
1 15/16"
108 11/16"
20 1/16"
5 3/16"
108 5/8"
5 1/8"
20 1/16"
79 1/4"
7"
14"
9"
88 5/16"
FAN GRILLE
CONTROL PANEL
(SEE DETAIL A)
4" LINE
VOLTAGE ACCESS
1 1/4" x 4 1/2"
SLOT FOR 115
VOLT CONTROL
FAN GRILLE
LOW AMBIENT
DAMPER (SEE NOTE 2)
BOTTOM OF CONTROL
BOX (SEE DETAIL A)
16 3/16"
2 1/4" x 1 1/4" 24 VOLTAGE
CONTROL WIRING6 1/4"
13"
3/4" X 8
MTG HOLES
DOOR 43 1/4" W/180 DEG SWING
8"
1 1/4"
97 5/8"
16"
97 5/8"
85 13/16"
29 1/4"
31 1/4"
35 13/16"
37 11/16"
3 3/8"
3 3/8"5 5/16"
2 5/8" 5 3/8"
1 3/4" KO LOW
VOLTAGE (30V MAX.)
1/2" X 2 KO (115V)
1/2" X 4 KO (115V)
4 1/2"
4" CONDUIT
MAIN POWER
CONTROL PANEL
DIMENSIONAL DETAIL
DETAIL A
NOTES:
1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES.
2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT .
7/25/2019 Trane Air Cooled Condenser
28/32
28 ACDS-PRC003-EN
Dimensional Data
Figure 17. 100- and 120-ton air-cooled condenser (connections)
VOLTAGE
ACCESS
CONTR
OL
PANEL
COIL
SCALE
1,000
75/16"
DISCHARGELINE
LIQUID
LINE
59/16"
901/8"
162"
45/16"
41/4"
181/16"
131/16"
213/8"
11/8"O
.D.
LIQUIDLINE
ISOMETRICDRAWING
ORIENTATIONVIEW
OFUNIT
PLANVIEW
OFUNIT
CONNECTIONDRAWING
CONNECTIONDRAWING
CONTROLPANE
LSIDEVIEW
OFUNIT
CONTROL
PANELSIDE
CONTROL
PANELSIDE
7/25/2019 Trane Air Cooled Condenser
29/32
ACDS-PRC003-EN 29
Weights
Table 9. 20 to 120 ton weights
Tons Model
Operating
Weight
Weight on isolator mounting location (lbs.)
Loc. 1 Loc. 2 Loc 3. Loc 4. Loc. 5 Loc. 6 Loc. 7 Loc. 8
20 CAUJC20 1188 296.3 340.8 358.8 192.1 --- --- --- ---
25 CAUJC25 1238 357.1 300.2 318.8 261.9 --- --- --- ---
30 CAUJC30 1236 360.9 302.0 316.0 257.1 --- --- --- ---
40 CAUJC40 1808 385.9 212.5 181.7 441.8 377.2 208.3 --- ---
50 CAUJC50 2120 239.4 211.3 367.5 339.4 495.5 466.6 --- ---
60 CAUJC60 2136 238.8 210.9 370.2 342.2 501.6 472.8 --- ---
80 CAUJC80 3212 513.5 474.4 459.6 200.2 452.1 196.7 561.6 354.0
100 CAUJC100 3960 636.7 402.1 610.1 383.6 605.8 380.5 579.2 361.9
120 CAUJC120 4451 687.8 461.8 667.7 447.8 664.4 445.5 644.4 431.5
Figure 18. Air-cooled condensing units
1
2
3
4
5
6
7
8
Control
Panel
X
Y
1
2
3
4
5
6
Control
Panel
X
Y
Control
Panel
1
2
3
4
X
Y
20-30 Ton 40-60 Ton
80-120 Ton
7/25/2019 Trane Air Cooled Condenser
30/32
30 ACDS-PRC003-EN
Weights
Table 10. Isolator mounting locations
Mounting Location
Unit
Size 1 2 3 4 5 6 7 8
20/25/30 X 8 8 6' 8 1/8 6' 8 1/8 - - - -
Y 4' 10 3/4 1 1/4 4' 10 3/4 1 1/4 - - - -
40 X 8 8 3' 8 1/8 3' 8 1/8 6' 8 1/4 6' 8 1/4 - -
Y 7' 3 1/8 1 1/4 7' 3 1/8 1 1/4 7' 3 1/8 1 1/4 - -
50/60 X 8 8 4' 8 7/8 4' 8 7/8 8' 9 3/4 8' 9 3/4 - -
Y 7' 3 1/8 1 1/4 7' 3 1/8 1 1/4 7' 3 1/8 1 1/4 - -
80 X 8 8 6' 8 1/8 6' 8 1/8 9' 1/8 9' 1/8 14' 1/4 14' 1/4"
Y 7' 3 1/8 1 1/4 7' 3 1/8 1 1/4 7' 3 1/8 1 1/4 7' 3 1/8 1 1/4"
100/120 X 8 8 8' 9 5/8 8' 9 5/8 10' 1 5/8 10' 1 5/8 18' 3 1/4 18' 3 1/4
Y 7' 3 1/8 1 1/4 7' 3 1/8 1 1/4 7' 3 1/8 1 1/4 7' 3 1/8 1 1/4"
7/25/2019 Trane Air Cooled Condenser
31/32
ACDS-PRC003-EN 31
Mechanical Specifications
General
Factory-assembled and wired air cooled condensing unit. Units are constructed of 14-gaugewelded galvanized steel frame with 14 and 16-gauge galvanized steel panels and access doors. Unit
surface is phosphatized and finished with an air-dry paint. This air-dry paint finish is durable
enough to withstand a 1000-consecutive-hour salt spray application in accordance with standard
ASTM B117.
Refrigeration Circuits and Control
The 20 to 30 ton units are single circuit. The 40 to 120 ton units are dual circuited. All the necessary
controls to run the unit fans are provided. The control panel contains fan motor contactors, terminal
point connection for compressor interlock and 115 volt control power transformer. Standard units
will operate from 40 - 115F. All units shipped with factory installed liquid line service valves.
Condenser Coils and Fans
Condenser coils shall be pressure tested and have all aluminum Microchannel design. Direct drive
condenser fan motors have permanently lubricated ball bearings and thermal overload protection.
Low Ambient Operation
Standard ambient control allows operation down to 40F with cycling of condenser fans. Optional
low ambient allows operation down to 0F with external damper assembly for head pressure
control. Refer to Options section for details.
Options
Low Ambient Control
Low ambient allows operation down to 0F through the use of fan cycling and head pressure
control dampers. The control consists of a heavy gauge damper assembly that is modulated by an
actuator. The actuator is controlled by a low ambient control module. All components are factory-
mounted for both production and Packed Stock Plus units.
Corrosion Protected Condenser Coil
Condenser coil protection shall consist of a corrosion resistent coating that will withstand ASTM
B117 Salt Spray test for 1000 hours and ASTM G85 A2 Cyclic Acidified Salt Fog test for 2400 hours.
This coating shall be added after coil construction cover all tubes, headers and fin edges, therefore
providing optimal protection in more corrosive environments.
Spring Isolation Package
Spring isolators reduce transmission of noise and vibration to building structure, equipment, and
adjacent spaces. Isolators consist of a cast, spring loaded, telescoping housing as the isolation
medium. Mountings include built-in leveling bolts, resilient inserts that act as centering guides, and
ribbed neoprene acoustical pads bonded to the bottom of the isolator. The kit includes instructions
for field installation.
Neoprene-in-shear Isolation PackageNeoprene isolators reduce transmission of noise and vibration to building structure, equipment,
and adjacent spaces. Isolators have a steel plate and base completely imbedded in neoprene.
Mountings have a 1/4-inch deflection. The kit includes instructions for field installation. Available
on 20 to 60-ton units only.
7/25/2019 Trane Air Cooled Condenser
32/32
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the
leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad
portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more
information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.