Power and productivity
for a better worldTM
AdvaBuild® Administrator User Guide
Version 3.7 SP2
AdvaBuild ®Administrator User Guide
Version 3.7 SP2
NOTICEThis document contains information about one or more ABB products and may include a description of or a reference to one or more standards that may be generally relevant to the ABB products. The presence of any such description of a standard or reference to a standard is not a representation that all of the ABB products referenced in this document support all of the features of the described or referenced standard. In order to determine the specific features supported by a particular ABB product, the reader should consult the product specifications for the particular ABB product.
ABB may have one or more patents or pending patent applications protecting the intellectual property in the ABB products described in this document.
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document.
Products described or referenced in this document are designed to be connected, and to communicate information and data via a secure network. It is the sole responsibility of the system/product owner to provide and continuously ensure a secure connection between the product and the system network and/or any other networks that may be connected.
The system/product owners must establish and maintain appropriate measures, including, but not limited to, the installation of firewalls, application of authentication measures, encryption of data, installation of antivirus programs, and so on, to protect the system, its products and networks, against security breaches, unauthorized access, interference, intrusion, leakage, and/or theft of data or information.
ABB Ltd and its affiliates are not liable for damages and/or losses related to such security breaches, any unauthorized access, interference, intrusion, leakage and/or theft of data or information.
ABB verifies the function of released products and updates. However system/product owners are ultimately responsible to ensure that any system update (including but not limited to code changes, configuration file changes, third-party software updates or patches, hardware change out, and so on) is compatible with the security measures implemented. The system/product owners must verify that the system and associated products function as expected in the environment they are deployed.
In no event shall ABB be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, nor shall ABB be liable for incidental or consequential damages arising from use of any software or hardware described in this document.
This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license. This product meets the requirements specified in EMC Directive 2014/30/EU and in Low Voltage Directive 2014/35/EU.
TRADEMARKSAll rights to copyrights, registered trademarks, and trademarks reside with their respective owners.
Copyright © 2001-2020 by ABB.All rights reserved.
Release:February 2020Document number:3BUR001977R3701 RevB
3BUR001977R3701 RevB 5
TABLE OF CONTENTS
About This BookGeneral ............................................................................................................................15Intended User...................................................................................................................15Document Conventions ...................................................................................................15Use of Warning, Caution, Information, and Tip ..............................................................16Terminology.....................................................................................................................16Related Documentation ...................................................................................................18
On-line Documentation........................................................................................20On-line Help.........................................................................................................20
Section 1 - IntroductionProduct Overview............................................................................................................21
System Services Software ....................................................................................22AdvaBuild Administration Software....................................................................23
AdvaBuild Administration Functions .................................................23Journal Administration Functions .......................................................23
Product Release History .......................................................................................24Prerequisites and Requirements ......................................................................................25
RTA PREREQUISITES .......................................................................................27External RTA Unit Requirements.........................................................................27NIC Card Configuration.......................................................................................27Changing the External RTA Unit Default IP Address ..........................................27
Licensing .........................................................................................................................28Client Licensing ...................................................................................................28Node licensing......................................................................................................29
Security Settings ..............................................................................................................29
Table of Contents
6 3BUR001977R3701 RevB
AdvaBuild User ................................................................................................... 29Client User ........................................................................................................... 30AdvaBuild Users Group....................................................................................... 30DCOM Settings.................................................................................................... 30
Section 2 - InstallationGeneral Information ........................................................................................................ 31Database Requirements ................................................................................................... 31Upgrading to AdvaBuild Version 3.7 SP2....................................................................... 32Installation Workflow...................................................................................................... 34Server Installation ........................................................................................................... 40
Install ABB 3rd Party Common Install ................................................................ 41Install ABB PAS - System Services..................................................................... 42Install Database Software for AdvaBuild (Oracle) .............................................. 43
Install Database Software for AdvaBuild ........................................... 43
Install RNRP Software........................................................................ 46Install ABB AdvaBuild ........................................................................................ 48Install ABB MOD 300 Engineering Displays...................................................... 54Install ABB Central Licensing System ................................................................ 56
Client Installation ............................................................................................................ 61ABB Common 3rd Party Install (Client) ............................................................. 61Install RNRP Software (Client) ........................................................................... 62Install ABB AdvaBuild (Client)........................................................................... 62Install ABB MOD 300 Engineering Displays (Client) ........................................ 63
Install Database Patch ..................................................................................................... 64Installing Documentation ................................................................................................ 65MOD 300/DCN Network Address and Time Synchronization Configuration for
Client/Server ........................................................................................................ 66Configure the MOD 300/DCN network address for the client/server 66
Set Windows to View Hidden Files and Folders............................................................. 69Viewing Project ZIP Files ............................................................................................... 69Add Client Users to Server ............................................................................................. 69
Table of Contents
3BUR001977R3701 RevB 73BUR001977R3701 RevB 7
Shutdown and Startup Procedures...................................................................................71Shutdown Procedures...........................................................................................71Startup Procedures ...............................................................................................72
Product Verification.........................................................................................................72
Section 3 - System AdministrationConsiderations .................................................................................................................73When To Use System Administration Tools....................................................................73
Administration Procedures for System Services .................................................73RTA Time Synchronization Configuration..........................................73Changing Control Network Parameters ..............................................73System Status ......................................................................................74Starting, Stopping, and Supervising Advant Software Processes .......74
Application Start-up ........................................................................................................74Administration Procedures for System Services .............................................................75
Time Synchronization Configuration...................................................................75Control Network Configuration ...........................................................................78Viewing System Status.........................................................................................78Process Administration Services ..........................................................................81
Process Administration Service Window ............................................81Start or Stop Processes ........................................................................82Reset Failed Processes ........................................................................84Refresh Process Information ...............................................................84Start or Stop the Process Administration Service ...............................84Close the Process Administration Service Window ............................84
Section 4 - AdvaBuild AdministrationConsiderations .................................................................................................................85Administration Procedures for AdvaBuild Applications .................................................85Starting the AdvaBuild Administration Component........................................................86
Changing the Default Server ................................................................................90Connecting to a Different Server .........................................................................90Changing the Journal Control Setting ..................................................................91
Table of Contents
8 3BUR001977R3701 RevB
Toggling the Display of the Tool Bar................................................................... 92Toggling the Display of the Status Bar ................................................................ 92Demanding a Refresh........................................................................................... 92Enabling/Disabling Timed Refresh...................................................................... 92Setting Refresh Rate ............................................................................................ 93Displaying Component Version Information ....................................................... 93Viewing Licenses ................................................................................................. 93
Managing Projects and Their Users ................................................................................ 94Concurrence Of Conflicting Administration Functions....................................... 95Inserting a New Project........................................................................................ 96
How to Handle an Incomplete Project ................................................ 98Deleting a Project................................................................................................. 99Enlarging the Size of a Project........................................................................... 102Saving a Project ................................................................................................. 103Loading a Project ............................................................................................... 110Inserting New Project Users .............................................................................. 117Deleting Project Users ....................................................................................... 118Changing Passwords .......................................................................................... 119
Changing Password for Admin User ................................................ 119Changing Password for Project User ................................................ 120
Viewing and Managing Log Files...................................................................... 122Opening the Log Files Window ........................................................ 123Sorting the Log Files......................................................................... 123Viewing a Selected Log File ............................................................. 124Refreshing the Log File List ............................................................. 125Deleting a Log File ........................................................................... 126Printing the Log File List.................................................................. 126Printing a Log File ............................................................................ 126Closing a Log File............................................................................. 127
Printing Project and User Data .......................................................................... 128Managing Journals for AdvaBuild Applications ........................................................... 128
Viewing the Journal ........................................................................................... 128
Table of Contents
3BUR001977R3701 RevB 93BUR001977R3701 RevB 9
Enabling/Disabling the Journal Function...........................................................131Toggling the Display of the Tool Bar.................................................................131Toggling the Display of the Status Bar ..............................................................131Demanding a Refresh.........................................................................................131Opening Journal for Another Project .................................................................131Saving Journal to an Archive File ......................................................................132Displaying an Archive File.................................................................................133Displaying Current Journal Data if Viewing Archive File .................................134Deleting Records from Journal without Archiving ............................................134Searching the Journal .........................................................................................135Querying the Journal ..........................................................................................135Printing the Journal ............................................................................................141Exiting the Journal .............................................................................................141
Managing Object Name Reuse ......................................................................................141Deny Reuse ........................................................................................................142Allow Reuse .......................................................................................................142How to Allow or Deny Object Name Reuse ......................................................143
Exiting the AdvaBuild Administration Component ......................................................145............................................................................................................................145
Section 5 - MaintenancePreventive Maintenance ................................................................................................147Hardware Indicators ......................................................................................................147Error Messages ..............................................................................................................147Fault Finding and User Repair ......................................................................................147Backup/Restore Procedures...........................................................................................148Software Removal .........................................................................................................148Software Repair or Modify............................................................................................149Changing AdvaBuild User Security Settings ................................................................149
............................................................................................................................150Changing AdvaBuild Machine Hostname .....................................................................150
Appendix A - Software License Entry
Table of Contents
10 3BUR001977R3701 RevB
Introduction ................................................................................................................... 151Machine ID Types ......................................................................................................... 152Obtaining Machine ID................................................................................................... 152
Obtaining the Ethernet Address ......................................................................... 153Obtaining the Machine ID from the Dongle ...................................................... 154
Requesting Software Keys ............................................................................................ 155Entering Licenses .......................................................................................................... 156Licensing Troubleshooting............................................................................................ 157
Locating the license file:.................................................................................... 157Unavailable Machine IDs .................................................................................. 157
Dongle .................................................................................... 157Ethernet .................................................................................... 158
Error Codes ........................................................................................................ 158
Appendix B - Data Model and Directory StructureEngineering Station Data Model ................................................................................... 161
ES_ADMIN Tablespace..................................................................................... 161ES_ADMIN Tablespace Creation..................................................... 164ADMIN Users................................................................................... 165Populating Admin Support Tables .................................................... 166Admin Package Creation .................................................................. 166
Project Tablespace.............................................................................................. 166Project Support Tables ...................................................................... 167Project Data Tables ........................................................................... 167PROJECT Table................................................................................ 170Project Data Validation ..................................................................... 170Oracle Constraints............................................................................. 170Default Values................................................................................... 171Triggers, Stored Procedures, and Packages ...................................... 171Project Users .................................................................................... 171Project Creation ................................................................................ 172
Project Data Directory Structure ................................................................................... 172
Table of Contents
3BUR001977R3701 RevB 113BUR001977R3701 RevB 11
Appendix C - Database Considerations for DCN ConnectionsGeneral Information ......................................................................................................173
PHYSICAL DEVICE........................................................................173AUTO START...................................................................................175SOFTWARE NAME.........................................................................175DO RATE ....................................................................................175SECONDARY DP, BACKUP ENABLE, BACKUP OVERRIDE, and
DEFAULT ENVIRONMENT ....................................175NODE TYPE ....................................................................................176
Appendix D - Windows SupportPLC Templates ATF File ...............................................................................................177Special Algorithm FCMs...............................................................................................177
Creating a Descriptor File ..................................................................................178Migrating a Descriptor File ................................................................................179Backing Up Special Algorithm Files..................................................................179Copy the Descriptor File to All 800xA for MOD 300 Connectivity Servers.....179
Objects Not Supported on Windows .............................................................................179
Appendix E - System Performance MonitoringIntroduction ...................................................................................................................181DCN Load Monitoring and Trending ............................................................................181
DCNLOAD Loop...............................................................................................181M0 or M1 Data Entry FCM ...............................................................................182
AC460 Controller Status Monitoring ............................................................................183Discussion: ....................................................................................184
Appendix F - PROM ChecksumsVersion 10.0/n and 14.n Multibus Node PROM Checksums - (7 June 2001) ...185
Advant DCN_DCN (D/D).................................................................185MULTIBUS, D/D (Obsolete) - Cat #6006PZ00032B.......................185SERIAL I/O - Cat #6007PZ000010A ...............................................186D/M ....................................................................................186
Table of Contents
12 3BUR001977R3701 RevB
D/F .................................................................................... 186MULTIBUS - (2M) Cat #6026PZ00004A........................................ 187SCSI DISK CONTROLLER ............................................................ 187VIDEO MODULE............................................................................ 188MODEL A CONTROLLER ............................................................. 188MODEL B,C,D CONTROLLER...................................................... 189SC_CONTROLLER ......................................................................... 189BMC .................................................................................... 189SC_BMC .................................................................................... 190
Advant Firmware .......................................................................................................... 191Firmware for DCN Interface Module ................................................................ 191
Firmware for Advant Controllers AC 460..................................................................... 191
Appendix G - Time SynchronizationIntroduction ................................................................................................................... 193Master System Timekeeper ........................................................................................... 193
Notification ........................................................................................................ 194Arbitration.......................................................................................................... 194
Clock Accuracy ............................................................................................................. 195Reverse Time Synchronization ..................................................................................... 195
Setting the Reverse Time Synchronization Variable.......................................... 196AdvaBuild Client/Server................................................................... 196800xA for MOD 300......................................................................... 196OPC Server for MOD 300 ................................................................ 196
Detecting Reverse Time Synchronization Mode ............................................... 196100ms Time Synchronization........................................................................................ 197Time Zone and Daylight Saving ................................................................................... 198Setting Time and Date ................................................................................................... 198
800xA Systems .................................................................................................. 198
Appendix H - Third Party LicensesIntroduction ................................................................................................................... 199Revision Control System (RCS) ................................................................................... 199
Table of Contents
3BUR001977R3701 RevB 133BUR001977R3701 RevB 13
Appendix I - Hardening, VirtualizationHardening ......................................................................................................................201Virtualization .................................................................................................................203
INDEX
Table of Contents
14 3BUR001977R3701 RevB
3BUR001977R3701 RevB 15
About This Book
GeneralThis instruction describes how to install and administer the AdvaBuild® suite of software products for the Windows Server 2016 and Windows 10 platform (hereafter referred to as AdvaBuild software). This instruction covers administration procedures for:
• Software installation.
• AdvaBuild administrative services (for instance, managing projects and users assigned to each project, etc.).
Use this section as a guide to the conventions and terminology used throughout this instruction.
Intended UserAs a prerequisite the user should know how to use and maintain the Microsoft® Windows operating system, as well as related hardware and software. In addition, Administrator privileges are required on the computer where the AdvaBuild software runs. When installing the Administration component of the AdvaBuild software, a check is performed to verify Administrator privileges. The installation is not allowed if this check determines that the person performing it does not have Administrator rights.
Document ConventionsMicrosoft Windows conventions are normally used for the standard presentation of material when entering text, key sequences, prompts, messages, menu items, screen elements, etc.
Use of Warning, Caution, Information, and Tip About This Book
16 3BUR001977R3701 RevB
Use of Warning, Caution, Information, and TipThis publication includes Warning, Caution, and Information where appropriate to point out safety related or other important information. It also includes Tip to point out useful hints to the reader. The corresponding symbols should be interpreted as follows:
Although Warning hazards are related to personal injury, and Caution hazards are associated with equipment or property damage, it should be understood that operation of damaged equipment could, under certain operational conditions, result in degraded process performance leading to personal injury or death. Therefore, comply fully with all Warning and Caution notices.
TerminologyThe following table includes terms and definitions that apply to the AdvaBuild suite of software products where the usage is different from commonly accepted industry standard definitions and definitions given in standard dictionaries such as Webster’s Dictionary of Computer Terms. Terms that uniquely apply to this instruction may be included here as part of this document.
Electrical warning indicates the presence of a hazard which could result in electrical shock.
Warning indicates the presence of a hazard which could result in personal injury.
Caution indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment/property.Information alerts the reader to pertinent facts and conditions.
Tip indicates advice on, for example, how to design your project or how to use a certain function.
Term Description
Advant OCS ABB Advant Open Control System
About This Book Terminology
3BUR001977R3701 RevB 17
Component Container for files performing a well-defined function. This is the smallest building block in the Advant OCS.
ES Engineering Station
Functional Subsystem Container for System Modules. Used to classify the System Modules into groups with associated functions.
MCB MOD Control Builder
MDI Multiple Document Interface
NAV Navigator
RTA, RTAB Real-time Accelerator Board. The RTAB is used with System Services and is required in the computer if it is being used as a client/server and connecting to the Advant OCS Control Network (MOD 300 DCN). RTAB refers to the original internally mounted PCI RTA card. The latest version of this interface to the DCN is an RTA unit mounted externally from the PC.
RTS Reverse time synchronization
System Module Container for components. Used to classify components into groups with similar functions.
TCB TCL Builder
TCL Taylor Control Language
TEB Templet Builder
TLB TLL Builder
TLL Taylor Ladder Logic
Term Description
Related Documentation About This Book
18 3BUR001977R3701 RevB
Related DocumentationTable 1 lists all documentation related to AdvaBuild.
Table 1. Related Documentation
Category Title Description
System Administration
Microsoft Windows Administrator’s Guide
Install, uninstall, administration, and registry of Windows operating system.
System Administration
AdvaBuild Release Notes Information regarding upgrades and changes that are not described in this instruction.
Basic Software
AdvaBuild Control Builder User’s Guide Consult this instruction for instructions on how to:• Operate the various builders
(Control and Templet Builders) to configure the MOD 300 database
• Compile, install, download, and decompile the database
• Transfer data between the various database configuration platforms
About This Book Related Documentation
3BUR001977R3701 RevB 19
Options AdvaBuild TCL Builder User’s Guide Describes how to generate and manage TCL programs via the TCL Builder.
Taylor Control Language (TCL) User’s Guide
Provides format and syntax rules, and other reference information for TCL. This instruction also provides instructions for using the TCL Catalog display to compile and link TCL sequences.
AdvaBuild TLL Builder User’s Guide Describes how to generate and manage TLL segment files via the TLL Builder.
Taylor Ladder Logic (TLL) User’s Guide Provides structure requirements and instruction information for TLL segment files.
AdvaBuild MOD 300 Engineering Displays Installation User Guide
Describes how to install the MOD 300 Engineering Displays software on the AdvaBuild Server and client PCs.
AdvaBuild MOD 300 Engineering Displays User Guide
Describes the operation and use of MOD 300 Engineering Displays
Virtual Installation
System 800xA Virtualization with VMware vSphere ESXi
Describes configuration and installation considerations for installing the product on a virtual machine.
External RTA Unit
System 800xA for MOD 300 RTA Unit PU410 and PU412 User's Guide
Includes technical data and describes installation considerations for the external RTA units.
800xA Network Configuration User Guide
Describes the 800xA network topology. May be needed if default IP address of the PU410 RTA unit must be changed. This document also provides information about RNRP and time synchronization in the 800xA System.
Table 1. Related Documentation (Continued)
Category Title Description
On-line Documentation About This Book
20 3BUR001977R3701 RevB
On-line DocumentationAll documentation is supplied in Adobe® reader (.pdf) format. Adobe Reader can be downloaded for free from (http://www.adobe.com) and is included with the AdvaBuild the 800xA Common Install delivered on the AdvaBuild release media. Windows must be set up to start Adobe Reader for .pdf files.
This instruction is available as on-line documentation on the AdvaBuild Installation release media. After installing the AdvaBuild documentation (and Adobe Reader if necessary), it can be accessed from the Windows Taskbar by choosing ABB Start Menu>ABB MOD 300>AdvaBuild>Documentation> Document. A contents file that links a searchable index is included. ABB Solutionsbank can also be subscribed to for on-line documentation.
On-line HelpHelp is included for MOD 300 Engineering Displays and MOD 300 Control Builder in an HTML compiled format. The help file is context sensitive to the field level for each AdvaBuild template and supports both F1 and What is This type help.
http://www.adobe.com
3BUR001977R3701 RevB 21
Section 1 Introduction
Product OverviewThe AdvaBuild software consists of a set of core software, plus optional software applications as summarized in Table 2 and Table 3. This instruction covers only the System Services and AdvaBuild Administration software (and Section 4, AdvaBuild Administration). Refer to the corresponding user’s guides listed in Related Documentation on page 18 for information regarding the other software applications listed in Table 2 and Table 3.
Table 2. AdvaBuild Software - Core Functionality
Application Description
System Services System Services along with an external RTA unit is required in the computer if it is being used as a client/server and is connected to the MOD 300 Control Network (MOD 300 DCN or eDCN). System Services software supports basic services including network communications, object handling, process supervision, and system messaging.
Administration The Administration software allows the Administrator to manage projects and the users assigned to each project, manage the journal, and manage object name reuse.
Control Builder The Control Builder software consists of 4 components: Navigator, Templet Builder, On-line Builder, and Journal. The first 3 components are used to view and define the MOD 300 database. The Journal is used to keep track of changes made to the database.
Oracle Dedicated Oracle installation packaged with AdvaBuild and included on the AdvaBuild Installation Media.
System Services Software Section 1 Introduction
22 3BUR001977R3701 RevB
System Services SoftwareThe System Services software has the following uses:
• Configuring the control network.• Configuring process startup.• Viewing system status.• Process Administration Services.• Viewing system messages.
Table 3. AdvaBuild Software Options
Application Description
TCL Builder The TCL Builder software is a TCL development package that provides the means to:• Edit TCL source and recipe files using either the standard tcleditor
provided with the TCL Builder or another text editor of your choice that runs on your station.
• Check syntax and view both the source and listing files in the same window.
• Manage files in a Revision Control System (RCS).• Transfer the files between different TCL development platforms (via
migration) in the Advant OCS.
TLL Builder The TLL Builder software is a ladder logic development package that provides the means to:• Edit TLL segment files using the standard TLL Editor provided with the
TLL Builder.• Check syntax.• Manage files in a Revision Control System (RCS).• Transfer the files between different TLL development platforms (via
migration) in the Advant OCS.
Section 1 Introduction AdvaBuild Administration Software
3BUR001977R3701 RevB 23
AdvaBuild Administration SoftwareThe AdvaBuild Administration software is used by the Administrator (Admin user) to manage projects and the users assigned to each project, manage journals that record the changes made to projects, and manage object name reuse.
AdvaBuild Administration Functions
The administration functions are used by the Admin user to:
• Insert projects.• Delete projects.• Enlarge projects.• Save projects.• Load projects.• Insert project users.• Delete project users.• Change user passwords.• View log files generated by the project and user administration functions.• Print project and user data.• Allow/deny the reuse of object names in the database.• Enable/disable journaling.
Journal Administration Functions
The journal administration functions allow the Admin user to:
• Enable/disable the journal function.• Open a journal for another project.• Save a journal to an archive file.• Display archive view of journal data.• Delete all records from a journal without archiving.• Search a journal.• Query a journal to narrow the scope of data displayed.• Print a journal.
Product Release History Section 1 Introduction
24 3BUR001977R3701 RevB
Product Release HistoryTable 4 lists the major milestones in the development of the AdvaBuild software. Refer to the release notes for incremental releases and patches.
Table 4. Release History
Version Description
3.7 SP2 Error corrections and documentation updates. Support for Windows Server 2016 and Windows 10 Enterprise 2016 LTSB. Removed support for all other Windows operating systems.Oracle passwords are now case sensitive.Removed support for SE46 Whitelisting Software.
3.7 SP1 Error corrections and documentation updates. Support for Windows 8.1 client installations.
3.7 For operation on Windows Server 2008 R2 SP1 (64-bit) for client/server installations and Windows Server 2008 SP2 for 32 bit client/server installations. Operation on Windows 7 SP1 Professional or Enterprise editions (32-bit or 64-bit) for client only installations. Installation on a virtual machine supported, error corrections and documentation updates are also included.
3.6 For operation on Windows Server 2008 SP2 (32-bit) for client/server installations and Windows 7 for client installations. Minor enhancements, error corrections and documentation updates.
3.5 SP1 Error corrections and documentation updates.
3.5 Combines AdvaBuild and MOD 300 Engineering products into one product DVD. Enhancements to both AdvaBuild and MOD 300 Engineering Displays. For Windows XP Professional SP3 and Windows Server 2003 SP2. Provides support for the PU410/412 External RTA Unit.
3.4 Initial release of all AdvaBuild software for the Windows XP Professional SP2 or Windows Server 2003 SP2 platform. Support for Oracle 10.2. All software is delivered on a single DVD.
Section 1 Introduction Prerequisites and Requirements
3BUR001977R3701 RevB 25
Prerequisites and RequirementsThe following hardware and software is required to support the basic AdvaBuild software (ABB PAS System Services, Administration, and Control Builder):
• AdvaBuild server installations require Windows Server 2016. AdvaBuild clients can be installed on Windows 10 Enterprise 2016 LTSB or Windows Server 2016.
– The Microsoft Windows operating system must be the U.S. English version.
3.3 Initial release of all AdvaBuild software for the Windows 2000 platform. Changes include AdvaBuild User security, expanded context sensitive help, faster install times, and license entry.
3.2 This release provides configuration support for Profibus devices and an enhanced compiler for faster compiles.
3.1 Initial release of the AdvaBuild TLL Builder software for the Windows NT platform.
3.0 Initial release of the AdvaBuild Control Builder, Templet Builder, On-line Builder, and TCL Builder software for the Windows NT platform.
ABB certifies 800xA software products for use on a variety of workstation and server products including Dell, HP, and Lenovo. Since AdvaBuild is an engineering tool that supports 800xA, it is recommended that AdvaBuild software also be installed on the 800xA certified server and workstation products. ABB recommends that the hardware chosen is certified to run the supported operating systems (Windows Server 2016, Windows 10 Enterprise 2016 LTSB).
The
The user installing software must be proficient in the Microsoft Operating System. There may be differences in accessing the Microsoft Operating System settings described in this and the following sections depending on the selected operating system. It is the responsibility of the user to consult Microsoft documentation and online help to accurately make the settings.
Table 4. Release History
Version Description
Prerequisites and Requirements Section 1 Introduction
26 3BUR001977R3701 RevB
– The hard drives must be NTFS partitioned.
– Regional and Language must be set to US English. Refer to Installation Workflow on page 35
– Windows Automatic Updates should be disabled, refer to Installation Workflow on page 36. ABB routinely tests the Microsoft updates and publishes document 3BUA001588 advising which updates can be applied.
– During the Windows operating system installation, be sure to select the correct time zone. If daylight saving time is used, check the box to enable Automatically adjust clock for daylight saving changes.
• The installation drive must be at least 100 GB for the installation of the operating system and AdvaBuild.
• PC RAM: Minimum 8GB, 16 GB recommended
• 19-inch minimum monitor is recommended.
• Valid static IP address. The software will not function properly without a valid static IP address. Do not use DHCP.
A dynamic IP address, using DHCP, is not supported because of client disconnects from servers. This is a known problem with DHCP and D/COM. If DHCP is chosen, there will be disconnect errors (the frequency or rate of errors experienced while using DHCP has not been tested). A refresh of the display might recover from the error. However, it may be necessary to exit and restart the application.
The following software must be installed before installing the AdvaBuild software:
• Client/Server Installations: Windows Server 2016.
• Client Installations: Windows 10 Enterprise 2016 LTSB
• Microsoft Internet Explorer 11
• McAfee VirusScan Enterprise
• Adobe Reader, is installed with 800xA Common Install.
Any additional hardware or software requirements for optional AdvaBuild applications are described in their respective user’s guides
Section 1 Introduction RTA PREREQUISITES
3BUR001977R3701 RevB 27
RTA PREREQUISITESThe ABB-PAS System Services software supplied with AdvaBuild includes drivers to support the external RTA unit (PU410/412).
External RTA Unit RequirementsThe PU410/412 external RTA unit uses standard NIC cards as the interface to the PC. Thus the RTA unit is not affected by PC hardware changes that revise supported hardware interface specifications as long as NIC card support is available.
Before you install AdvaBuild 3.7 SP2 and PAS on the AdvaBuild server PC review this AdvaBuild Administrator User Guide and the PU410/412 RTA Unit User Guide, 3BUA001442. The PC will need to be fitted with dual NIC cards for communication support between the AdvaBuild server PC and the RTA unit. Additionally the ABB product RNRP must be installed, see Install RNRP Software on page 46. RNRP will report on the health of the dual network connections between the PC and the RTA unit. The NIC card configuration and RNRP installation must be done prior to AdvaBuild and PAS installation.
NIC Card ConfigurationConfigure the NIC card IP addresses as described in PU410/412 RTA Unit User Guide, 3BUA001442. Configure these prior to installing the AdvaBuild software.
Changing the External RTA Unit Default IP AddressFor most installations the default RTA unit IP addresses may be used. In some 800xA RNRP installations in which network area 10 has already been configured for use, the RTA Unit IP addresses will need to be changed.
The procedure for changing the RTA Unit IP address is described in the PU410/PU412 RTA Unit User Guide. If it becomes necessary to change the default
During PAS software installation the external RTA unit PU410/412 drivers will be installed.
The IP addresses for the NIC card interface to the RTA unit must be included in the firewall exception list.
Licensing Section 1 Introduction
28 3BUR001977R3701 RevB
IP addresses, double click on the ManagementTool.exe file and follow the instructions in the PU410/PU412 RTA Unit User Guide. The ManagementTool.exe can be found at:
"C:\Program Files (x86)\ABB 800xA\SystemServices\DxBase\bin"
LicensingLicensing is enforced at the server. The license features available for AdvaBuild are:
• ABNTSU - Control Builder Clients.• ABNTSC - MOD 300 Subsystem nodes.• ABNTST - TCL Client option.• ABNTSL - TLL Client option.
The license features available for AdvaBuild MOD 300 Engineering Displays are:• ABMEDU - MOD 300 Engineering Displays Clients• ABMEDT - TCL client displays option• ABMEDL - TLL client displays option
Client LicensingClient licenses are regulated by quantity based on the number of Control Builders that can be connected to a server. The license is per user per machine. If a user has multiple Control Builders open at once on one machine, only one license is required.
TCL and TLL Builder licenses are options to the Control Builder license, not quantities. This means that the quantity associated with Control Builder is the implicit quantity for TCL Builder and for TLL Builder. If there are four Control Builder licenses and the TCL Builder option, it is possible to connect four TCL Builders to the server.
Checking for client licenses is done at the time of server connection. TCL and TLL Builders are able to operate in a client-only, disconnected state without requiring a license.
Utilities like project load, project save, cross reference, and multi-edit are not subject to license checking. Server operations like the compiler and decompiler are
Section 1 Introduction Node licensing
3BUR001977R3701 RevB 29
not subject to license checking. Any direct Oracle connections (e.g., SQL*Plus, SQL*Net, ODBC) are not subject to license checking.
Node licensingNode licensing refers to the number of MOD300 subsystems that can be configured by a CDP. Node licenses are regulated by quantity.
A node license is defined as a configured MOD300 subsystem. Specifically, the following template types are counted to determine the number of configured subsystems: AC410, AC460, CONSOLE, CONT_SS, DCN_DCN, ADVANT_D2D, GENERICD. Controller subsystems count as one node license. Controller cards are not counted.
Checking for node license is done at install time. If the number of configured subsystems exceeds the number of node licenses, the install will not be scheduled. Top down, area level, subsystem level, and node level installs are subject to license checking. Loop level installs are not subject to license checking.
Security SettingsIn versions previous to AdvaBuild 3.3, local/domain users had to have Windows administrative privileges on the server. This requirement was removed at AdvaBuild 3.4. Instead, an AdvaBuild administrative user is added during installation and is used to control allowed connections by the clients to the AdvaBuild server applications using DCOM. A client user still needs to be listed on the server; however, the user can be part of the Users Group.
AdvaBuild UserThe AdvaBuild user account is added during installation of the Control Builder Client/Server and assigned a password during the installation. This user is given membership in the Administrators and ORA_DBA groups. The ability to Log on Locally is granted in the security settings for Local Security Policy and should be restricted to this user and specified administrative users (not client users) to maintain the server security. The password can be changed by an administrative user from the Users and Passwords dialog and by executing SecuritySetup.exe in AdvaBuild\Install\DCOM. If there is a failure to connect, check the Event Viewer for a Logon failure: ... message and see if it was password related.
Client User Section 1 Introduction
30 3BUR001977R3701 RevB
Client UserEvery client user needs to be added as a user on the server. Client users have their own access privileges and do not require the administration rights of the AdvaBuild user account. The client user can be part of a domain or workgroup. The domain user must be part of the domain and a member of the Users group on the server.
In the Local Security Settings / Local Policies / Security Options, the policy Network access: Sharing and security model for local accounts must be set to Classic - local users authenticate as themselves if the user is not running on a domain. This security option allows the same username and password authentication to work in the absence of a domain. It needs to be set on both the client and server.
AdvaBuild Users GroupThe AdvaBuild Users group was added with the release of AdvaBuild 3.4. The client user must be a member of this group on the server computer to be able to connect to AdvaBuild.
DCOM SettingsSecurity settings are now enforced independently and the AdvaBuild user becomes the specified user account for process administration using DCOM on the server (see the Identity tab on DCOM application properties). Additionally, custom access permissions are enforced (see the Security tab) and the following names are allowed access: INTERACTIVE, NETWORK and SYSTEM. There is no need to change or verify these settings.
Never create a user name that is the same as the host name of the machine (the full computer name). This will cause a licensing error message when trying to use the program.
3BUR001977R3701 RevB 31
Section 2 Installation
General InformationThis section describes the installation of new AdvaBuild client/server and client PCs, and also details the information to be saved and recorded when upgrading existing AdvaBuild installations.
This section describes how to install the ABB Common 3rd Party software, ABB PAS - System Services, Database software for AdvaBuild (Oracle), RNRP, ABB AdvaBuild, ABB MOD 300 Engineering Displays, ABB Central Licensing System, and AdvaBuild documentation (including installation of Adobe Reader). All of these applications are delivered on the release media.
Database RequirementsComputers with AdvaBuild software connected to the Distributed Control Network (DCN or eDCN) via the external RTA unit must be represented in the MOD 300 database by a GENERICD object. The GENERICD object establishes the computer as an Advant OCS node in the MOD 300 database.
The GENERICD database object is inserted into the MOD 300 database hierarchy and its object attributes are defined via the AdvaBuild Templet Builder as described in the AdvaBuild Control Builder User’s Guide. Refer also to Appendix C, Database Considerations for DCN Connections for guidelines.
Upgrading to AdvaBuild Version 3.7 SP2 Section 2 Installation
32 3BUR001977R3701 RevB
Upgrading to AdvaBuild Version 3.7 SP2
Perform the following when upgrading from previous versions of AdvaBuild:
1. Record the project name, number and database size associated with each project listed in the upper portion of the Main AdvaBuild Administration Window (Figure 47).
2. Save all existing projects as described in Saving a Project, and place the resulting zip files on a secure media other than the hard drive of the computer being upgraded.
3. If there is a customized memory pools file, save the resulting pu412_pools.x file (located in C:\Program Files\ABB Industrial IT\ System Services\MODBase\pu412load) on a secure media other than the hard drive of the computer being upgraded.
4. Record and save the information in the Communications Settings dialog.
a. Select: Start > Control Panel > Administrative Tools > PAS > Process Administration. This launches the ABB PAS Service Message dialog.
b. Click Yes to run the configuration utility and launch the Communication Settings dialog shown in Figure 1.
c. Record and save the values shown in the dialog.
5. Record the settings for RTA Time Synchronization, REVERSED_SYNC_MODE. See section RTA Time Synchronization Configuration. Whenever PAS is installed or reinstalled, the REVERSE_SYNC_MODE will be set to the default value of '0', disabled.Record the settings for RTA Time Synchronization, REVERSED_SYNC_MODE. See section RTA Time Synchronization Configuration. Whenever PAS is installed or reinstalled, the REVERSE_SYNC_MODE will be set to the default value of '0', disabled.
AdvaBuild 3.7 SP2 server supports a new operating system and a new version of Oracle which will require a full re-installation of the Windows operating system when upgrading from earlier versions.
The OMF shared memory should always be set to the default 128 MB.
Section 2 Installation Upgrading to AdvaBuild Version 3.7 SP2
3BUR001977R3701 RevB 33
6. Install the software according to Installation Workflow.
7. After the software for AdvaBuild has been installed, create a project for each project saved in Step 2 using the corresponding project number recorded in Step 1. Refer to Inserting a New Project for instructions on how to create or insert a project.
8. Load the projects saved in Step 2. Refer to Loading a Project for instructions on how to load a project.
Figure 1. Communications Settings dialog
The AdvaBuild client PC upgrade requires a new operating system installation. This will be a full re-installation of the Windows operating system. Client PC’s do not contain any AdvaBuild data that requires backup nor does any AdvaBuild software need to be un-installed/removed.
Installation Workflow Section 2 Installation
34 3BUR001977R3701 RevB
9. If memory pools were customized, load the pu412_pools.x file saved in Step 3 into the directory shown below:
C:\Program Files (x86)\ABB 800xA\SystemServices\MODBase\pu412load.
10. Reboot the computer.
Installation WorkflowThe following is a high level procedure. It includes references to other installation procedures.
1. The external RTA unit is required if the PC will be used as a client/server and will be connected to the MOD 300 Control Network (MOD 300 DCN or eDCN). Refer to External RTA Unit Requirements in Section 1. If the RTA is not required, skip that part of the installation procedure.
Refer to Prerequisites and Requirements and verify that the computer can support the applications being installed.
After loading a project saved using AdvaBuild 3.6 or earlier, be sure to apply the database patch as described in the information note at the beginning of the Loading a Project section.
A static IP address is required for the LAN Internet Protocol (TCP/IP). Do not use DHCP. This product will not work correctly without a static IP address.
Section 2 Installation Installation Workflow
3BUR001977R3701 RevB 35
2. Load Microsoft Windows Server 2016 (client/server) or Windows 10 Enterprise 2016 LTSB (client).
3. The Regional and Language options must be set to English (United States)
a. Open Windows Control Panel.
b. Click Clock, Language and Region.
c. Click Language and verify English is enabled. If it is not click Add a language and select English from the menu and click Add. Select English from the list and click Options. Click Make this the primary language and click OK.
d. Click Change date, time or number formats.e. Click Additional settings... f. Verify that the value in the Decimal symbol field drop-down list is a dot
(.). If it is not, change it to a dot (.) and click Apply and then OK.
Installation restrictions with 800xA:
AdvaBuild Server: 800xA software must not be installed on the AdvaBuild server PC. Combining 800xA software and the AdvaBuild server on one PC may impair the operation of each application. However, it is possible to combine on one machine using virtual installations. See the 800xA Server Node Virtualization User Guide. If using a virtual installation, the RTA must be the PU410/PU412 external unit form factor.
AdvaBuild Client: If installing AdvaBuild engineering client and 800xA client software on the same PC, install the 800xA client software first. The ABB Common Install software included with the 800xA client software install procedure does not need to be installed a second time when installing the AdvaBuild client software.
MOD 300 Engineering Displays: MOD 300 Engineering Displays clients must not be installed on the same PC as 800xA clients. Since the displays have common code, installing on the same PC may cause conflicts.When installing the Windows operating system, the logged on user must have Administrator privileges to load software. The user name must be defined local to the computer where the software is installed. Do not use a domain-defined user name.
Installation Workflow Section 2 Installation
36 3BUR001977R3701 RevB
g. Click the Administrative tab.
h. Click Change system locale to launch the Regional and Language Settings dialog box.
i. Verify that the value in the Current system locale drop-down list is English (United States). If it is not, change it to English (United States) and click OK to return to the Administrative tab of the Regional and Language Options dialog box.
j. Click Copy Settings...k. Enable the Welcome screen and system accounts and New User
Accounts check boxes and click OK.l. Click OK to exit the Regional and Language Options dialog box.
m. Close Windows Control Panel.
4. Disable Windows Automatic Update.
The Windows Automatic Update feature must be disabled.
a. Click on the Windows icon in the lower left hand corner of the screen.b. Click on the Settings icon.
c. Click on Update & security.
d. Under the Update settings section, click on Advanced options.e. Select the Defer feature updates option.
5. Verify that Internet Explorer 11 is installed.
6. Make a disk image of the computer and all of its application data before installing the following application software.
7. Exit all Windows applications.
If a message box appears asking: Would you like to apply your regional and language changes?, click Apply
If the computer already has a newer version of the third-party software that is being installed, the installation wizard will advise that the target is newer than the source. If the target is a released version (not a Beta version), then select No to keep the newer software.
Section 2 Installation Installation Workflow
3BUR001977R3701 RevB 37
8. Enable virus protection.
9. Enable Windows Firewall before installing the software.
10. The software installed depends on whether the computer is being used as a client or a client/server (Table 5). Be sure to have valid AdvaBuild licenses.
Enable Windows Firewall before installing the software. If Windows firewall is enabled after installing the software, AdvaBuild software applications will not work unless the DCOM security setup is run as described under Changing AdvaBuild User Security Settings.
If the AdvaBuild installation is in a domain, log out from the local Administratorprivileged user and re-login as a user defined in the Domain Admins group.If the AdvaBuild installation is in a workgroup, continue the installation procedure as the logged on Admin user defined on the local PC. Do not use a domain defined user name.
Table 5. Software to Install
Software Client/Server Client
ABB Common 3rd Party Install
X X
ABB PAS System Services X
Database Software - Oracle X
RNRP X X
ABB AdvaBuild X X
ABB MOD 300 Engineering Displays
X X
ABB Central Licensing System1
X
AdvaBuild documentation X X
NOTE:1. After installing the license software, enter the software licenses on
the client/server as described in Appendix A, Software License Entry.
Installation Workflow Section 2 Installation
38 3BUR001977R3701 RevB
a. Install ABB Common Install software. Refer to Install ABB 3rd Party Common Install for server or ABB Common 3rd Party Install (Client) for client.
b. Install ABB PAS System Services software. Refer to Install ABB PAS - System Services.
c. Install Database Software - Oracle. Refer to Install Database Software for AdvaBuild (Oracle).
d. Install RNRP software. Refer to Install RNRP Software for server or Install RNRP Software (Client) for client.
e. Install ABB AdvaBuild software. Refer to Install ABB AdvaBuild for server or Install ABB AdvaBuild (Client) for client.
f. Optionally install ABB ABB MOD 300 Engineering Display software. Refer to Install ABB MOD 300 Engineering Displays for server or Install ABB MOD 300 Engineering Displays (Client) for client.
g. Install ABB Central Licensing System software. Refer to Install ABB Central Licensing System.
h. Enter the software licenses as described in Appendix A, Software License Entry.
i. Install the AdvaBuild documentation according to Installing Documentation. The on-line help (F1) file provides a link to these files in its Related Documentation section.
11. Configure the MOD 300/DCN network addresses as described in MOD 300/DCN Network Address and Time Synchronization Configuration for Client/Server.
12. Enable viewing of hidden folders described in Set Windows to View Hidden Files and Folders.
Windows must be completely reloaded on a clean partition to guarantee removal of all Oracle references if any Oracle software currently exists on the computer on which the AdvaBuild software will be installed. Conflicts can exist between the Oracle software included with the AdvaBuild software and residual Oracle settings found in the Windows environment. These conflicts can prohibit a successful installation of the AdvaBuild software.
Section 2 Installation Installation Workflow
3BUR001977R3701 RevB 39
13. Add client users to the AdvaBuild server as described in Add Client Users to Server.
14. Shutdown and restart the AdvaBuild server as described in Shutdown and Startup Procedures.
Server Installation Section 2 Installation
40 3BUR001977R3701 RevB
Server InstallationDouble-click on the Launcher.exe file in the Installation Media and select Server Installation to display the AdvaBuild Server Installation window (Figure 2).
Follow the steps below to install the required server software in the order listed starting with ABB Common Install, and ending with Licensing.
Windows must be completely reloaded on a clean partition to guarantee removal of all Oracle references if any Oracle software currently exists on the computer on which the AdvaBuild software will be installed. Conflicts can exist between the Oracle software included with the AdvaBuild software and residual Oracle settings found in the Windows environment. These conflicts can prohibit a successful installation of the AdvaBuild software.
Figure 2. AdvaBuild Server Installation Window
Section 2 Installation Install ABB 3rd Party Common Install
3BUR001977R3701 RevB 41
Install ABB 3rd Party Common Install1. From the AdvaBuild Server Installation window (Figure 2), select Install ABB
Common 3rd Party Install.
2. The ABB 800xA Common 3rd Party Install dialog will be displayed (Figure 3). Select Next>.
3. Select Install.
4. Select Finish when installation completes.
Figure 3. ABB 800xA Common 3rd Party Install Dialog
Install ABB PAS - System Services Section 2 Installation
42 3BUR001977R3701 RevB
Install ABB PAS - System Services1. From the AdvaBuild Server Installation window (Figure 2), select Install ABB
PAS – System Services.
2. An ABB PAS - System Services Install dialog will be displayed (Figure 4). Select the radio button for MOD300 For AdvaBuild, then click Install Now.
3. When installation completes, click Finish.
Figure 4. ABB PAS - System Services Install Dialog
Section 2 Installation Install Database Software for AdvaBuild (Oracle)
3BUR001977R3701 RevB 43
Install Database Software for AdvaBuild (Oracle)
Before installing Oracle, check to make sure the LOCAL Environment Variable is not present. It is it present, it must be deleted. To check for, and delete if necessary, the LOCAL Environment Variable:
1. Open Windows Control Panel.
2. Double-click System to open the System Properties dialog.
3. Select the Advanced tab.4. Click Environment Variables to open the Environment Variables dialog.
5. Look for the LOCAL variable in the System Variables list.
6. Delete the LOCAL variable if it is present.
Install Database Software for AdvaBuild
1. From the AdvaBuild Server Installation window (Figure 2), select Install Database Software for AdvaBuild.
2. An Oracle Installer Wizard window will be displayed (Figure 5). Leave all selections at their defaults and select Install.
3. An Install Oracle dialog will be displayed (Figure 6). Select Yes.
If installing in a domain, the logged in user must be defined in the Domain Admins group before installing Oracle.
If the LOCAL Environment Variable is present, it must be deleted.
Install Database Software for AdvaBuild (Oracle) Section 2 Installation
44 3BUR001977R3701 RevB
Figure 5. Oracle Installer Wizard
Figure 6. Install Oracle Dialog
Section 2 Installation Install Database Software for AdvaBuild (Oracle)
3BUR001977R3701 RevB 45
4. An Oracle Universal Installer console window will be displayed containing text related to the installation (Figure 7). This will repeat twice and is non-interactive; no user action is required.
Installation may take several hours depending on system resources. Progress can be monitored on the Oracle Installer Wizard window (Figure 8).
Figure 7. Oracle Universal Installer console window
Figure 8. Oracle Installer Wizard - Installation Progress
Install RNRP Software Section 2 Installation
46 3BUR001977R3701 RevB
5. When installation is complete, click the Finish button in the Oracle Installer Wizard window (Figure 9).
Install RNRP SoftwareThe RNRP default install is all that is required for support of the external RTA unit. When configured in an 800xA system or if you desire to install RNRP on other non-800xA PCs review the RNRP discussion in the PU410/412 RTA Unit User Guide and the 800xA Automation System Network Design and Configuration User Guide. If custom configuration is needed, see the System 800xA Network Configuration User Guide, 3BSE034463.
1. From the AdvaBuild Server Installation window (Figure 2), select Install RNRP Software.
Figure 9. Oracle Installer Wizard - Installation Complete
Section 2 Installation Install RNRP Software
3BUR001977R3701 RevB 47
2. An ABB 800xA RNRP Install Wizard window will be displayed (Figure 10). Click Next>.
3. A License Agreement dialog is displayed (Figure 11). Review the license agreement text. To accept the agreement and continue with installation, select “I accept the terms in the license agreement” and click Next>.
Figure 10. ABB 800xA RNRP Install Wizard
Figure 11. ABB 800xA RNRP License Agreement Dialog
Install ABB AdvaBuild Section 2 Installation
48 3BUR001977R3701 RevB
4. Click Install.
5. When the installation completes, click Finish.
Install ABB AdvaBuild1. From the AdvaBuild Server Installation window (Figure 2), select Install ABB
AdvaBuild.2. An ABB AdvaBuild Installshield Wizard window will be displayed
(Figure 12). Click Next>.
3. A License Agreement dialog is displayed (Figure 13). Review the license agreement text. To accept the agreement and continue with installation, select “I accept the terms in the license agreement” and click Next>.
Figure 12. ABB AdvaBuild Installshield Wizard Window
Section 2 Installation Install ABB AdvaBuild
3BUR001977R3701 RevB 49
4. A Custom Setup window will be displayed (Figure 14). Keep default settings click Next>.
Figure 13. ABB AdvaBuild License Agreement Dialog
Figure 14. ABB AdvaBuild Custom Setup Window
Install ABB AdvaBuild Section 2 Installation
50 3BUR001977R3701 RevB
5. Click Install.
6. A few minutes into the installation, a separate AdvaBuild Security Setup window will be displayed (Figure 15) and a blinking icon will appear in the taskbar (Figure 16). This window may be displayed under the Installshield Wizard window. Select the Security Setup window and then click Next>.
7. An AdvaBuild Users Group window will be displayed (Figure 17). If this is a domain installation, select the “Find or create this group in the current domain” check box. Leave the group name as the default and click Next>.
Figure 15. AdvaBuild Security Setup Window
Figure 16. Installation Taskbar Icon
Section 2 Installation Install ABB AdvaBuild
3BUR001977R3701 RevB 51
8. An AdvaBuild User window will be displayed (Figure 18). Leave the default Username as “AdvaBuild”, enter a password in the Password and Confirm password fields, and click Next>.
Figure 17. AdvaBuild Users Group Window
Figure 18. AdvaBuild User Window
Install ABB AdvaBuild Section 2 Installation
52 3BUR001977R3701 RevB
9. Select Next> on the next 3 windows that are displayed.
10. Select Finish.11. An AdvaBuild Installation window will now appear (Figure 19). If this
window does not appear, hover over the task bar and click to bring up the hidden dialog. Click Install.
12. When completed, click Finish on the AdvaBuild Installation window (Figure 20).
Figure 19. AdvaBuild Installation Window
Section 2 Installation Install ABB AdvaBuild
3BUR001977R3701 RevB 53
13. Click Finish on the Installation Wizard window (Figure 21).
Figure 20. AdvaBuild Installation - Finish
Figure 21. AdvaBuild Installation Wizard - Finish
Install ABB MOD 300 Engineering Displays Section 2 Installation
54 3BUR001977R3701 RevB
Install ABB MOD 300 Engineering Displays1. From the AdvaBuild Server Installation window (Figure 2), select Install ABB
MOD 300 Engineering Displays.
2. A MOD 300 Engineering Displays Setup window will be displayed(Figure 22). Select the Client and Server Installation Type, then click Install Now.
3. A few minutes into the installation, a separate window will be displayed and a blinking icon will appear in the taskbar (Figure 16). This window may be displayed under the installation wizard window. Select this window and then click Next>.
4. A MOD 300 Engineering Display Group Settings window will be displayed (Figure 23). If this is a domain installation, select the “Find or create this group in the current domain” check box. Leave the group name as the default and select Next>.
Figure 22. MOD 300 Engineering Displays Setup Window
Section 2 Installation Install ABB MOD 300 Engineering Displays
3BUR001977R3701 RevB 55
5. A MOD 300 User Settings window will be displayed (Figure 24). Keep the Username as “AdvaBuild” and enter a password in the Password and Confirm password fields. Then click Next>.
Figure 23. MOD 300 Engineering Displays Group Settings Window
Figure 24. MOD 300 Engineering Displays User Settings Window
Install ABB Central Licensing System Section 2 Installation
56 3BUR001977R3701 RevB
6. Select Next> on the next two windows that are displayed.
7. Select Finish.8. A MOD 300 Engineering Displays Setup Complete window will be displayed
(Figure 25). Click Finish.
Install ABB Central Licensing System1. From the AdvaBuild Server Installation window (Figure 2), select Install ABB
Central Licensing. 2. An ABB Central Licensing System InstallShield Wizard will be displayed
(Figure 26). Click Next>.
3. A License Agreement dialog is displayed. Review the license agreement text. To accept the agreement and continue with installation, select Yes.
4. A Choose Destination Location window will be displayed (Figure 27). Keep the default installation directory and click Next>.
Figure 25. MOD 300 Engineering Displays Setup Complete Window
Section 2 Installation Install ABB Central Licensing System
3BUR001977R3701 RevB 57
Figure 26. ABB Central Licensing System InstallShield Wizard
Figure 27. ABB Central Licensing Choose Destination Location Window
Install ABB Central Licensing System Section 2 Installation
58 3BUR001977R3701 RevB
5. A Setup Type window is displayed (Figure 28). Select Standalone and click Next>.
6. A Select Program Folder window is displayed (Figure 29). Leave Program Folder at the default and click Next>.
7. A Local Client Component (LCC) Username and Password window is displayed (Figure 30). Enter a Username and Password for an account that is in the Administrators Group. Enter the same Password in the Confirm field, then click Next>.
8. A Start Copy Files window is displayed (Figure 31). Click Install.
9. Click Finish.10. Restart the computer.
11. Refer to Appendix A, Software License Entry and install the licenses.
Figure 28. ABB Central Licensing Setup Type Window
Section 2 Installation Install ABB Central Licensing System
3BUR001977R3701 RevB 59
Figure 29. ABB Central Licensing Program Folder Window
Figure 30. ABB Central Licensing Local Client Component (LCC) Username and Password Window
Install ABB Central Licensing System Section 2 Installation
60 3BUR001977R3701 RevB
Figure 31. ABB Central Licensing Start Copy Files Window
Section 2 Installation Client Installation
3BUR001977R3701 RevB 61
Client InstallationDouble-click on the Launcher.exe file in the Installation Media and select Client Installation to display the AdvaBuild Client Installation window (Figure 32).
ABB Common 3rd Party Install (Client)1. From the AdvaBuild Client Installation window (Figure 32), select Install
ABB Common 3rd Party Install.
2. The ABB 800xA Common 3rd Party Install dialog will be displayed (Figure 3). Select Next>.
3. Select Install.
4. Select Finish when installation completes.
Figure 32. AdvaBuild Client Installation Window
Install RNRP Software (Client) Section 2 Installation
62 3BUR001977R3701 RevB
Install RNRP Software (Client)The RNRP default install is all that is required for support of the external RTA unit. When configured in an 800xA system or if you desire to install RNRP on other non-800xA PCs review the RNRP discussion in the PU410/412 RTA Unit User Guide and the 800xA Automation System Network Design and Configuration User Guide. If custom configuration is needed, see the System 800xA Network Configuration User Guide, 3BSE034463.
1. From the AdvaBuild Client Installation window (Figure 32), select Install RNRP Software.
2. An ABB 800xA RNRP Install Wizard window will be displayed (Figure 10). Click Next>.
3. A License Agreement dialog is displayed (Figure 11). Review the license agreement text. To accept the agreement and continue with installation, select “I accept the terms in the license agreement” and click Next>
4. Click Install.5. When the installation completes, click Finish.
Install ABB AdvaBuild (Client)1. From the AdvaBuild Client Installation window (Figure 32), select Install
ABB AdvaBuild.
2. An ABB AdvaBuild Installshield Wizard window will be displayed (Figure 12). Click Next>.
3. A License Agreement dialog is displayed (Figure 13). Review the license agreement text. To accept the agreement and continue with installation, select “I accept the terms in the license agreement” and click Next>.
4. A Warning dialog will be displayed indicating the server feature will be disabled (Figure 33). Click OK.
Section 2 Installation Install ABB MOD 300 Engineering Displays (Client)
3BUR001977R3701 RevB 63
5. A Custom Setup window will be displayed (Figure 14). Keep default settings click Next>.
6. Click Install.
7. Click Finish on the Installation Wizard window (Figure 21).
Install ABB MOD 300 Engineering Displays (Client)1. From the AdvaBuild Client Installation window (Figure 32), select Install
ABB MOD 300 Engineering Displays.
2. A MOD 300 Engineering Displays Setup window will be displayed (Figure 22). Select the Client Installation Type, then click Install Now.
3. Select Finish.
Figure 33. AdvaBuild Warning Dialog
Install Database Patch Section 2 Installation
64 3BUR001977R3701 RevB
Install Database Patch
1. Double-click on the Launcher.exe file in the Installation Media and select Existing Project Patch to display the Existing Project Patch installation screen (Figure 34).
2. Select Install Database Patch for Existing Projects.
Figure 34. Patch Installation Screen
3. In command window enter database username at prompt, hit Enter (Figure 35).
Figure 35. Command Window
4. In command window enter database password at prompt, hit Enter (Figure 35).
If installing in a domain, the logged in user must be defined in the Domain Admins group before installing Oracle.
Section 2 Installation Installing Documentation
3BUR001977R3701 RevB 65
5. When prompted hit any key to exit command window.
Installing DocumentationInstalling the AdvaBuild documentation provides local access to all relevant reference information. In addition, the help file used by the application supports links to the Adobe Reader files in the Related Documentation section. The documentation is also accessible directly from the AdvaBuild Installation Media.
To install the AdvaBuild documentation,
1. Double-click on the Launcher.exe file in the Installation Media and select Documentation to display the AdvaBuild Documentation Installation window.
2. Select Install PDF Documentation to Disk.
3. A Welcome to the Installshield wizard for AdvaBuild Documentation dialog appears. Click Next>.
4. A License Agreement dialog is displayed. Review the license agreement text. To accept the agreement and continue with installation, select “I accept the terms in the license agreement” and click Next>.
5. A Destination Folder dialog is displayed. Click Next> to select the default folder.
6. A Ready to Install the Program dialog appears. Click Install to start the installation.
7. Click Finish when the InstallShield Wizard Complete dialog appears. To access the installed AdvaBuild documentation, select Start > All Programs > ABB Industrial IT > Control IT > AdvaBuild > Documentation > Document.
The Software License Agreement dialog is opened if Adobe Reader is opened for the first time. Click on Accept to close the Software License Agreement dialog and view the document.
MOD 300/DCN Network Address and Time Synchronization Configuration for Client/Server Section
66 3BUR001977R3701 RevB
MOD 300/DCN Network Address and Time Synchronization Configuration for Client/Server
Configure the Time Synchronization value REVERSED_SYNCH_MODE as required, see the section Time Synchronization Configuration.
Configure the MOD 300/DCN network address for the client/server
1. Select ABB Start Menu>ABB System 800xA>PAS Management>PAS Control. This opens the Process Administration Service Window Figure 37.
2. Click on the Advanced Button.
3. Click on the Comm Settings button4. This opens the Communication Settings dialog shown in Figure 36.
5. If this is a reinstallation, the message Would you like to revert back to saved settings? appears. Click Yes to use the settings saved before reinstallation and continue with Step 9. Otherwise, continue with Step 6.
6. Select MOD300 in the Control Network frame of the Communication Settings dialog.
7. Enter the MOD 300/DCN Network Address information in the Network Address frame of the Communication Settings dialog as described in Step a through Step d.
a. Enter a decimal value for the address of the computer on the DCN in the DCN Address field. Addresses with lower order hexadecimal values of one are reserved for client/server nodes used as a configuration/data processor (CDP). Refer to Table 6 for valid address numbers.
b. Enter the network address number of the connected media (must match other nodes connected to the same media) in the E-DCN Network Address 1 and E-DCN Network Address 2 fields. The addresses must not be the same. The default numbers are acceptable.
Section 2 Installation MOD 300/DCN Network Address and Time Synchronization Configuration for
3BUR001977R3701 RevB 67
c. Click OK and the Comstacks Tool dialog opens. This is a notification that the settings specified in the Communication Settings dialog have been saved and the computer must be restarted for the changes to the communication settings to take effect.
d. Click OK to close the dialog. The computer will be restarted in Step 10.
8. Check the OMF Shared Memory value. It should be 128 MB, if not, enter 128.
9. Verify, from the Process Administration Service dialog (Figure 37), that all processes are started before proceeding to Step 10.When the process state for all processes listed in the Process Administration Service dialog is Started, click Close to close the window.
Figure 36. Communication Settings dialog
MOD 300/DCN Network Address and Time Synchronization Configuration for Client/Server Section
68 3BUR001977R3701 RevB
10. Restart the computer.
Table 6. DCN Addresses for Nodes with Configurator Software
Address (Hex)
Decimal Equivalent
Address (Hex)
Decimal Equivalent
01 1 81 129
11 17 91 145
21 33 A1 161
31 49 B1 177
41 65 C1 193
51 81 D1 209
61 97 E1 225
71 113 F1 241
Figure 37. Process Administration Service dialog
Section 2 Installation Set Windows to View Hidden Files and Folders
3BUR001977R3701 RevB 69
Set Windows to View Hidden Files and FoldersIn Windows Explorer the setting to view hidden files is needed in order to view folders where AdvaBuild data is stored.
In Windows Explorer Select Tools>Folder Options. In the Folder Options window select the View tab.
• Uncheck: Hide extension for known file types.•