13
Adding GE WTG Models to WECC Approved Dynamic Model Library WECC MVWG Meeting June 2014 Eric Bakie

Adding GE WTG Models to WECC Approved Dynamic Model Library WECC MVWG Meeting June 2014 Eric Bakie

Embed Size (px)

Citation preview

Page 1: Adding GE WTG Models to WECC Approved Dynamic Model Library WECC MVWG Meeting June 2014 Eric Bakie

Adding GE WTG Models to WECC Approved Dynamic Model Library

WECC MVWG Meeting

June 2014

Eric Bakie

Page 2: Adding GE WTG Models to WECC Approved Dynamic Model Library WECC MVWG Meeting June 2014 Eric Bakie

2

Agenda

• Review of GE WTG models in WECC MDF and WECC Cases

• Discussion of Adding GE WTG models to WECC Approved Model Library

Page 3: Adding GE WTG Models to WECC Approved Dynamic Model Library WECC MVWG Meeting June 2014 Eric Bakie

3

Background – SRWG Representation LogCase Rep Log Number of unapproved models

in WECC Basecase dataModels

Screened

13hs2a April 2013 54 motor1

14hps1a July 2013 50 svcwsc

14hs4a Nov 2013 46

14ls1a March 2014 40

20hw1 June 2014 40

Case Number of gens records

Number of gens records with Turbine Type Data blank or set

to unknown

24hs1 4,277 2,369

• Next Focus Area – GE WTG Dynamic Records

Page 4: Adding GE WTG Models to WECC Approved Dynamic Model Library WECC MVWG Meeting June 2014 Eric Bakie

4

Questions Asked

• Why are GE WTG Models not on the Approved Model List?

• How many GE WTG records are already in the WECC MDF?– How many records represent GE Wind Turbines?– How many records represent non-GE Wind Turbines?– How many records represent solar projects?

• Can the GE WTG models be added to the Approved Model List?

Page 5: Adding GE WTG Models to WECC Approved Dynamic Model Library WECC MVWG Meeting June 2014 Eric Bakie

5

Criteria for Adding Models to WECC Approved Model List

• Model documented and tested• Model available in all three programs• Justification that the model is needed

Page 6: Adding GE WTG Models to WECC Approved Dynamic Model Library WECC MVWG Meeting June 2014 Eric Bakie

6

GE WTG Model Benchmarking Documentation

Images: GE Energy

Page 7: Adding GE WTG Models to WECC Approved Dynamic Model Library WECC MVWG Meeting June 2014 Eric Bakie

7

GE WTG Model Status

• GE WTG Models have been implemented in all three programs– GE PSLF– PSS/E– PowerWorld

– GE has indicated that their preference would be to represent GE WTGs with the dynamic models GE developed

Page 8: Adding GE WTG Models to WECC Approved Dynamic Model Library WECC MVWG Meeting June 2014 Eric Bakie

8

Model Records in WECC Cases

Model 14hs4a 14hsp1a 14hw2a 14lw1a 14ls1a 15hw3a 15lw2a 24hs1sa MDF

gewtg 76 56 56 55 77 73 71 112 133

exwtge 42 33 32 32 47 48 49 55 70

ewtgfc 16 10 10 10 17 18 17 21 30

wndtge 32 28 27 27 32 32 33 48 54

• A conversion routine to transfer GE WTG models to Phase 2 Generic Models is not available at this time

• Inclusion of GE WTG models on the approved model list could reduce the number of models that would need to be converted to Phase 2 Generic Wind Models

Page 9: Adding GE WTG Models to WECC Approved Dynamic Model Library WECC MVWG Meeting June 2014 Eric Bakie

9

More Detailed Review ofWECC MDF GE WTG Records

UnidentifiableGeneration

Type

gewtg model only

Est. Solar

Type 3 Type 4

48 32 44 42 4

575V/690V(GE1.5/1.6/2.5)

<575V/690V >690V>100kV(BES)

32 42 52 7

• Review suggests that approximately 50 of 133 records are most likely being used to represent Type 3 and Type 4 WTGs

Page 10: Adding GE WTG Models to WECC Approved Dynamic Model Library WECC MVWG Meeting June 2014 Eric Bakie

10

Discussion Topics

• Adding GE WTG models could potentially reduce the need to convert about 50 records– Does this justify adding the GE WTG models?– Could create the possibility of records not getting reviewed and updated– Increases difficulty of tracking Phase 2 implementation

• Not adding the models provides opportunity to start fresh by replacing all wind/solar model records with the new Phase 2 Generic Wind/Solar Models– Improves the chance of developing better modeling representation– Easier to track Phase 2 implementation

Page 11: Adding GE WTG Models to WECC Approved Dynamic Model Library WECC MVWG Meeting June 2014 Eric Bakie

11

Modeling of GE Wind Turbine-Generators for Grid Studies Guide

• Can a revised GE guide be published that also includes using the Phase 2 Generic Wind Models for modeling GE Wind Turbines with recommended modeling data?

Page 12: Adding GE WTG Models to WECC Approved Dynamic Model Library WECC MVWG Meeting June 2014 Eric Bakie

12

Motion

• Add GE WTG models to the WECC Approved model library for use to represent GE Wind Turbines Only– Type 3 (DFAG - GE 1.5MW, 1.6MW, 3.6MW)– Type 4 (Full Converter - GE Multi-Megawatt 2.5 MW)

Page 13: Adding GE WTG Models to WECC Approved Dynamic Model Library WECC MVWG Meeting June 2014 Eric Bakie

13

Questions

Eric Bakie, P.E.SYSTEM PLANNING ENGINEERIdaho Power | System Planning (208) 388-5677 [email protected]