A4351S09 12 Cooling Loads

Embed Size (px)

Citation preview

  • 8/13/2019 A4351S09 12 Cooling Loads

    1/49

    Environmental Controls I/IG

    Lecture 12

    Cooling Loads

    Cooling Degree Hours

    Energy Performance Ratings

    Annual Fuel Consumption

  • 8/13/2019 A4351S09 12 Cooling Loads

    2/49

    Cooling LoadsComputed for worstcase scenario:

    Late summer afternoonat outdoor design dry

    bulb temperature

    Include:

    Insolation from sun

    Heat gain from people,

    lights, and equipment Infiltration in residential

    buildings

    Ventilation innonresidential buildings

    SR-3

  • 8/13/2019 A4351S09 12 Cooling Loads

    3/49

    Summer Design Conditions

    Design Dry Bulb Temperature

    Mean Daily Range

    S: p. 1496, T.B1

  • 8/13/2019 A4351S09 12 Cooling Loads

    4/49

    Determine Design Equivalent

    Temperature Difference (DETD)Construction type

    Outdoor design temperature

    Mean daily range

    L: 0-16FM: 16-25FH: 25+F

    S: p. 1613, T.F.5

  • 8/13/2019 A4351S09 12 Cooling Loads

    5/49

    Determine Envelope U-values

    Calculate R and then find U for wallsand roofs.

    Note: this method ignores floors, doors,and window U-values

  • 8/13/2019 A4351S09 12 Cooling Loads

    6/49

    Determine DCLF

    Glazing Type

    Design Temperature

    Shading

    Orientation

    S: p. 1615, T.5.6

  • 8/13/2019 A4351S09 12 Cooling Loads

    7/49

    Determine Area Quantities

    Perform area takeoffs forall building envelopesurfaces on each facade:

    gross wall area

    window area

    door area

    net wall area4

    Elevation

    4

    12

    100

    8

    1200 sf

    64 sf

    368 sf

    768 sf

    -

    -

  • 8/13/2019 A4351S09 12 Cooling Loads

    8/49

    Infiltration

    S: p. 1617, T.F.7

  • 8/13/2019 A4351S09 12 Cooling Loads

    9/49

    Ventilation Analysis

    Non-residential buildings use ventilation to providefresh air and to offset infiltration effects.

    ASHRAE Standard 62-2001 (S: p. 1598, T.E.25)

    Estimates the number of people/1000 sf of usage type

    Prescribes minimum ventilation/person for usage type

  • 8/13/2019 A4351S09 12 Cooling Loads

    10/49

    ASHRAE 62-2001

    Defines space occupancy and ventilation loads

    S: p. 1598, T.E.25

  • 8/13/2019 A4351S09 12 Cooling Loads

    11/49

    VentilationSensible CLF

    S: 1617, T.F.7

  • 8/13/2019 A4351S09 12 Cooling Loads

    12/49

    People Sensible Gain

    Determine number of people

    Activity level

    S: p. 1617, T.F.8

  • 8/13/2019 A4351S09 12 Cooling Loads

    13/49

    Lights

    Determine wattage of lighting/square foot

    ASHRAE 90.1 prescriptive levels

    Count fixture loads and add together

    Note: add 15% for ballasts where applicable

    (e.g., fluorescent lights)

  • 8/13/2019 A4351S09 12 Cooling Loads

    14/49

  • 8/13/2019 A4351S09 12 Cooling Loads

    15/49

    Equipment

    Use manufacturers data or otherreferences to obtain heat gain data.

    Standby mode

    Copiers

    Monitors

    Printers CPU

    energy star

    S: p. 1618, T.F.9

  • 8/13/2019 A4351S09 12 Cooling Loads

    16/49

    Latent Load

    Not calculated separately:

    Apply a factor as a percentage of the totalsensible cooling load

    Dry climates: 20%Moist/Humid climates: 30%

  • 8/13/2019 A4351S09 12 Cooling Loads

    17/49

    Cooling Load Example Problem

    Building: Office Building

    Location: Salt Lake City

    Building: 200 x 100 (2 stories, 12-6 each)

    Uwall= 0.054 Btuh/sf-F

    Uroof= 0.025 Btuh/sf-F

  • 8/13/2019 A4351S09 12 Cooling Loads

    18/49

    Cooling Load Example ProblemDetermine Building Envelope Areas (SF)

    Building: 200 x 100 (2 stories, 12-6 each)

    N E S WGross Wall 5,000 2,500 5,000 2,500

    Windows 1,000 500 2,000 500

    Doors 20 20 50 20Net Wall 3,980 1,980 2,950 1,980

    Roof/Floor Slab 20,000

  • 8/13/2019 A4351S09 12 Cooling Loads

    19/49

    Determine Design Equivalent

    Temperature Difference (DETD)Roof Construction type: Light color, vented, ceilingDesign temperature: 95F

    Mean daily range: 32F

    L: 0-16FM: 16-25FH: 25+F

    DETD=31.0F

    S: p. 1613, T.F.5

  • 8/13/2019 A4351S09 12 Cooling Loads

    20/49

    Cooling LoadsInsert roof values

    SR-3

    0.025 20,000 31.0 15,500 15,500

  • 8/13/2019 A4351S09 12 Cooling Loads

    21/49

    Determine Design Equivalent

    Temperature Difference (DETD)Wall Construction type (see given)Design temperature: 95F

    Mean daily range: 32F

    L: 0-16FM: 16-25F

    H: 25+F

    DETD=11.3F

    S: p. 1613, T.F.5

  • 8/13/2019 A4351S09 12 Cooling Loads

    22/49

    Cooling LoadsInsert roof values

    Insert wall values

    SR-3

    0.025 20,000 31.0 15,500 15,500

    N 0.054 3,980 11.3 2.429

    E 0.054 1,980 11.3 1.208S 0.054 2,950 11.3 1,800W 0.054 1,980 11.3 1,208 6,645

  • 8/13/2019 A4351S09 12 Cooling Loads

    23/49

    Glazing Type

    Design Temperature

    Shading

    Orientation

    Determine Window DCLF

    S: p.

    1615,T.F.6

  • 8/13/2019 A4351S09 12 Cooling Loads

    24/49

    Cooling LoadsInsert roof values

    Insert wall values

    Insert glass values

    SR-3

    0.025 20,000 31.0 15,500 15,500

    N 0.054 3,980 11.3 2.429

    E 0.054 1,980 11.3 1.208S 0.054 2,950 11.3 1,800W 0.054 1,980 11.3 1,208 6,645

    N 1,000 14 14,000E 500 35 17,500S 2,000 20 40,000W 500 35 17,500

    89,000

  • 8/13/2019 A4351S09 12 Cooling Loads

    25/49

    ASHRAE 62-2001

    Defines space occupancy and ventilation loads

    S: p. 1598, T.E.25

  • 8/13/2019 A4351S09 12 Cooling Loads

    26/49

    Ventilation Load Sensible

    40,000 sf x 5people/1,000sf = 200 people

    200 people x 17 cfm/person = 3,400 cfm

  • 8/13/2019 A4351S09 12 Cooling Loads

    27/49

    Ventilation Load Sensible CLF

    Design Temperature: 95F

    Commercial Building: Ventilation

    S: p. 1617, T.F.7

  • 8/13/2019 A4351S09 12 Cooling Loads

    28/49

    Cooling LoadsInsert roof values

    Insert wall values

    Insert glass values

    Insert outdoor airvalues

    SR-3

    0.025 20,000 31.0 15,500 15,500

    N 0.054 3,980 11.3 2.429

    E 0.054 1,980 11.3 1.208S 0.054 2,950 11.3 1,800W 0.054 1,980 11.3 1,208 6,645

    N 1,000 14 14,000E 500 35 17,500S 2,000 20 40,000W 500 35 17,500

    89,000

    N/A N/A N/A

    3,400 22.0 74,800 74,800

  • 8/13/2019 A4351S09 12 Cooling Loads

    29/49

    People Sensible Gain

    Determine number of people: 280

    Activity level: moderately active office work

    S: p. 1617, T.F.8

  • 8/13/2019 A4351S09 12 Cooling Loads

    30/49

    Cooling LoadsInsert roof values

    Insert wall values

    Insert glass values

    Insert outdoor airvalues

    Insert people values

    SR-3

    0.025 20,000 31.0 15,500 15,500

    N 0.054 3,980 11.3 2.429

    E 0.054 1,980 11.3 1.208S 0.054 2,950 11.3 1,800W 0.054 1,980 11.3 1,208 6,645

    N 1,000 14 14,000E 500 35 17,500S 2,000 20 40,000W 500 35 17,500

    89,000

    N/A N/A N/A

    3,400 22.0 74,800 74,800

    200 250 50,000

  • 8/13/2019 A4351S09 12 Cooling Loads

    31/49

    Lighting Load

    Lighting load: 1.5 w/sf

    Equipment load: 0.5 w/sf

  • 8/13/2019 A4351S09 12 Cooling Loads

    32/49

    Cooling LoadsInsert roof values

    Insert wall values

    Insert glass values

    Insert outdoor airvalues

    Insert people values

    Insert lighting values

    Insert equipmentvalues SR-3

    0.025 20,000 31.0 15,500 15,500

    N 0.054 3,980 11.3 2.429

    E 0.054 1,980 11.3 1.208S 0.054 2,950 11.3 1,800W 0.054 1,980 11.3 1,208 6,645

    N 1,000 14 14,000E 500 35 17,500S 2,000 20 40,000W 500 35 17,500

    89,000

    N/A N/A N/A

    3,400 22.0 74,800 74,800

    200 250 50,000

    40,000 1.5 204,780

    40,000 0.5 68,260 323,040

  • 8/13/2019 A4351S09 12 Cooling Loads

    33/49

    Cooling LoadsSensible Heat Gain:

    508985 Btuh

    Latent Heat Gain (20%):

    101,797 Btuh

    Total Heat Gain:

    610,782Btuh

    or

    50.9 Tons

    Tons=Q/12,000 SR-3

    0.025 20,000 31.0 15,500 15,500

    N 0.054 3,980 11.3 2.429

    E 0.054 1,980 11.3 1.208S 0.054 2,950 11.3 1,800W 0.054 1,980 11.3 1,208 6,645

    N 1,000 14 14,000E 500 35 17,500S 2,000 20 40,000W 500 35 17,500

    89,000

    N/A N/A N/A

    3,400 22.0 74,800 74,800

    200 250 50,000

    40,000 1.5 204,780

    40,000 0.5 68,260 323,040

    508,985

    101,797

    610,78250.9

    2.5

    1.1

    14.6

    16.783.3

    52.8

    12.3

    100.0

  • 8/13/2019 A4351S09 12 Cooling Loads

    34/49

    Cooling Degree Hours

  • 8/13/2019 A4351S09 12 Cooling Loads

    35/49

    Cooling Degree Hours

    Relative indicator of warmth

    S: p. 1496, T.B.1

  • 8/13/2019 A4351S09 12 Cooling Loads

    36/49

    Cooling Degree Hours

    Balance Point Temperature (BPT):temperature above which cooling is needed

    CDH(BPT)= ODBT-BPT

    If temperature (ODBT)=91F

    CDH74 =ODBT-74=91-74

    =17 cooling degree-hours

  • 8/13/2019 A4351S09 12 Cooling Loads

    37/49

    Energy Performance Ratings

  • 8/13/2019 A4351S09 12 Cooling Loads

    38/49

  • 8/13/2019 A4351S09 12 Cooling Loads

    39/49

    Annual Fuel Consumption

  • 8/13/2019 A4351S09 12 Cooling Loads

    40/49

    Annual Fuel Usage (E)

    E= UA xCDH(BPT)

    SEER

    where:

    UA: cooling load/F

    CDH(BPT): degree hours for balance point

    SEER: seasonal energy efficiency rating

  • 8/13/2019 A4351S09 12 Cooling Loads

    41/49

    Calculating UA

    QTotal= UA xT

    UA= QTotal/T

    From earlier example:

    QTotal= Btuh

    T= 95-75=20F

    UA=610782/20= 30,539 Btuh/F

  • 8/13/2019 A4351S09 12 Cooling Loads

    42/49

    Annual Fuel Usage Example

    Compare two systems to determine what

    is the expected annual electrical usage for

    an apartment in Salt Lake City if its peakcooling load is 12,000 Btuh?

    UA=Q/T

    UA=12,000/20= 600 Btuh/F

  • 8/13/2019 A4351S09 12 Cooling Loads

    43/49

    Determine SEER

    Obtain SEER from manufacturers data or

    Convert COP to SEER

    SEER: 5-15

    For this example:

    SEER1=6.8SEER2=10.2

  • 8/13/2019 A4351S09 12 Cooling Loads

    44/49

    Annual Fuel Usage Electricity

    E= UA x CDH74

    SEER

    E1 =(600)(9,898)/(6.8)

    =873,353 wh/yr

    =873 kwh/yr

    If electricity is $0.0735/kwh, then

    annual cost = $64

  • 8/13/2019 A4351S09 12 Cooling Loads

    45/49

    Annual Fuel Usage Electricity

    E= UA x CDH74

    SEER

    E2 =(600)(9,898)/(10.2)

    =582,235 wh/yr

    =582 kwh/yr

    If electricity is $0.0735/kwh, then

    annual cost = $43

  • 8/13/2019 A4351S09 12 Cooling Loads

    46/49

    Simple Payback Analysis

  • 8/13/2019 A4351S09 12 Cooling Loads

    47/49

  • 8/13/2019 A4351S09 12 Cooling Loads

    48/49

    Simple Payback

    Cooling SystemCost ComparisonFirst Annual Incremental Incremental Simple

    Cost Fuel Cost First Cost Annual Savings Payback($) ($/yr) ($) ($/yr) (yrs)

    System 1 500 64 --- --- ---

    System 2 600 43 100 21 4.8

    Payback exceeds 3 years, select system 1

    Other factors?

  • 8/13/2019 A4351S09 12 Cooling Loads

    49/49