RF Tests of Chemical Additives for Water Cooled Loads 2008 Fifth CW and High Average Power RF Workshop Karen Young Luke Amer Gerald Bolme Caroline Bolton Karen Young, Luke Amer , Gerald Bolme, Caroline Bolton, John Lyles, Phillip Torrez AOT-RFE Group Los Alamos National Laboratory Operated by Los Alamos National Security, LLC for NNSA LA-UR-08-1733 1

RF Tests of Chemical Additives for Water Cooled Loads...Background – Evaporative Cooling TowersEvaporative Cooling Towers At LANSCE some 9 inch ((22.922.9 ccm)m) coacoaxialxial l

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: RF Tests of Chemical Additives for Water Cooled Loads...Background – Evaporative Cooling TowersEvaporative Cooling Towers At LANSCE some 9 inch ((22.922.9 ccm)m) coacoaxialxial l

RF Tests of Chemical Additives for Water Cooled Loads

2008 Fifth CW and High Average Power RF Workshop

Karen Young Luke Amer Gerald Bolme Caroline BoltonKaren Young, Luke Amer, Gerald Bolme, Caroline Bolton,

John Lyles, Phillip Torrez

AOT-RFE Groupp

Los Alamos National Laboratory

Operated by Los Alamos National Security, LLC for NNSA

LA-UR-08-1733

1

Page 2: RF Tests of Chemical Additives for Water Cooled Loads...Background – Evaporative Cooling TowersEvaporative Cooling Towers At LANSCE some 9 inch ((22.922.9 ccm)m) coacoaxialxial l

AcknowledgementsAcknowledgements

This work is based on the work done at DESY from the following paper:M Ebert F R Ullrich “Glycol Substitute for High Power RF Water Loads” Particle AcceleratorM. Ebert, F.R.Ullrich, Glycol Substitute for High Power RF Water Loads , Particle Accelerator

Conference, Knoxville, TN, 2005

The authors would like to thank Brent W. Chettle, owner and founder of ,WEST, Inc. of Santa Fe Springs, CA.• Brent has been extremely helpful during these tests and was a consultant for this

project.H d l d th h i l WEST C 441 f ifi li ti• He developed the chemical WEST C-441 for our specific application.

Operated by Los Alamos National Security, LLC for NNSA 2

Page 3: RF Tests of Chemical Additives for Water Cooled Loads...Background – Evaporative Cooling TowersEvaporative Cooling Towers At LANSCE some 9 inch ((22.922.9 ccm)m) coacoaxialxial l

O tliOutline

BackgroundEnvironmental ConsiderationsExperimental SetupExperimental Results ConclusionsNew Water System Design

Operated by Los Alamos National Security, LLC for NNSA 3

Page 4: RF Tests of Chemical Additives for Water Cooled Loads...Background – Evaporative Cooling TowersEvaporative Cooling Towers At LANSCE some 9 inch ((22.922.9 ccm)m) coacoaxialxial l

Background Why can’t we use DI water?Background – Why can’t we use DI water?

Deminerallized water with a low resistivity can be d i RF l d b t th i d l th f th l dused in RF loads, but the required length of the load

is many wavelengths long. This type of load is used in SPS at 200 MHz.

Ebert and Ullrich measured:• The attenuation constant of pure water is about 17 p

dB/meter at 500 MHz at 25 Deg C.• The attenuation constant of a 30% glycol and 70 %

water mixture is about 30 dB/meter at 500 MHz at 25water mixture is about 30 dB/meter at 500 MHz at 25 Deg C.

Operated by Los Alamos National Security, LLC for NNSA 4

Page 5: RF Tests of Chemical Additives for Water Cooled Loads...Background – Evaporative Cooling TowersEvaporative Cooling Towers At LANSCE some 9 inch ((22.922.9 ccm)m) coacoaxialxial l

Background Evaporative Cooling TowersBackground – Evaporative Cooling Towers

At LANSCE some 9 inch (22.9 cm) coaxial loads (22.9 cm) coaxial loads were cooled with water that circulates through an evaporative cooling tower. These loads are 3 MW peak power and 300 kW average power loads.This water contains many

t i t f thcontaminants from the environment because it is openly exposed to air at the cooling tower.

Operated by Los Alamos National Security, LLC for NNSA 5

Page 6: RF Tests of Chemical Additives for Water Cooled Loads...Background – Evaporative Cooling TowersEvaporative Cooling Towers At LANSCE some 9 inch ((22.922.9 ccm)m) coacoaxialxial l

Background Sludge Buildup in RF ComponentsBackground – Sludge Buildup in RF Components

The containments from the cooling tower ionized the gwater and made it a good RF absorber.The disadvantage is that this water is very dirty and awater is very dirty and a “sludge” builds up in the RF equipment. The RF equipment has to beThe RF equipment has to be cleaned every two years. The cleanings are time consuming and the cleaning abrasives can potentiallyabrasives can potentially damage the components.

Sludge in the 201 MHz Coaxial Load

Operated by Los Alamos National Security, LLC for NNSA 6

Page 7: RF Tests of Chemical Additives for Water Cooled Loads...Background – Evaporative Cooling TowersEvaporative Cooling Towers At LANSCE some 9 inch ((22.922.9 ccm)m) coacoaxialxial l

Background AlternativesBackground - Alternatives

70 % water and 30% glycol mixture has been used in loads. but The water glycol mixture can be difficult and expensive to dispose ofbut…The water glycol mixture can be difficult and expensive to dispose of because environmental regulations.

Water ionized by from the evaporative cooling tower has been used in loads. but This water builds up a sludge in the RF equipment that needs to bebut…This water builds up a sludge in the RF equipment that needs to be cleaned every two years.

A 30% soda water mixture has been used in loads by Continental Electronics.

but…This water can be difficult to dispose off.

DI water has been used in loads. but…The attenuation constant of DI water is low, so the required length of the load is very long at 201 MHz. The return loss is high.

So in 2003 Ebert and Ullrich found an alternative, Corrshield MD4151.

Operated by Los Alamos National Security, LLC for NNSA 7

Page 8: RF Tests of Chemical Additives for Water Cooled Loads...Background – Evaporative Cooling TowersEvaporative Cooling Towers At LANSCE some 9 inch ((22.922.9 ccm)m) coacoaxialxial l

Background Corrshield MD 4151Background - Corrshield MD 4151Ebert and Ullrich found that < 0.1% of Corrshield mixed into DI water resulted in a better RF absorption than a 30% glycol 70% water mixturewater mixture. Corrshield MD4151:• Made by GE-Betz • A sodium molybdate based corrosion inhibitor developed• A sodium molybdate based corrosion inhibitor developed

for closed loop hot water systems. • <25% sodium molybdate• 0.5 – 2.0% sodium-hydroxidey• Contains Benzotriazole (BZT), a corrosion inhibitor for

yellow metals, principally copper.In 2004 at DESY, they replaced the cooling water with a 0.4% C hi ld i t DI tCorrshield into DI water. They found that the optimal dosage for a minimum change in the attenuation constant with respect to temperature is 0.12% Corrshield

Operated by Los Alamos National Security, LLC for NNSA

Corrshield.

8

Page 9: RF Tests of Chemical Additives for Water Cooled Loads...Background – Evaporative Cooling TowersEvaporative Cooling Towers At LANSCE some 9 inch ((22.922.9 ccm)m) coacoaxialxial l

Environmental ConsiderationsEnvironmental ConsiderationsIn the summer of 2007, we began looking for an alternative to the cooling tower water for our 201 MHz test stand load. Based, on Eberts and Ullrich’s work with Corrshield, we began by testing Corrshield. Our local GE representative said that Corrshield MD5141 was only available in Europe and that the American equivalent is Corrshield MD401American equivalent is Corrshield MD401. A sample of 0.1% Corrshield MD401 into DI water barely passed our environment test to pour into the sanitary drain. A sample of 0 5% Corrshield MD401 failed the en ironmentalA sample of 0.5% Corrshield MD401 failed the environmental tests to dispose of into the sanitary drain.

Operated by Los Alamos National Security, LLC for NNSA 9

Page 10: RF Tests of Chemical Additives for Water Cooled Loads...Background – Evaporative Cooling TowersEvaporative Cooling Towers At LANSCE some 9 inch ((22.922.9 ccm)m) coacoaxialxial l

Environmental ConsiderationsEnvironmental ConsiderationsThe 0.5% Corrshield sample flunked the Waste Acceptance Criteria because it was killing the “good” bacteria in the sanitary sewer system. The 0.1% just barley passed.We suspect that benzotriazole (BZT), a component in Corrshield, is causing the toxicity. Brent Chettle, WEST, Inc. developed a chemical, WEST C-441 for us that would be a good RF absorber and that was able to pass our environmental tests. WEST C-441:• 20% Sodium Nitrite (NaNO2) based solution• buffered to a slightly alkaline pH with sodium silicatebuffered to a slightly alkaline pH with sodium silicate• contains a Telomer polymeric copper corrosion inhibitor in lieu

of BZT

Operated by Los Alamos National Security, LLC for NNSA 10

Page 11: RF Tests of Chemical Additives for Water Cooled Loads...Background – Evaporative Cooling TowersEvaporative Cooling Towers At LANSCE some 9 inch ((22.922.9 ccm)m) coacoaxialxial l

Sanitary Waste System Waste Acceptance Criteria (SWS WAC)(SWS WAC)

Sample pH CODChemical

MTX Screen

MTX EC50

Microtox

TSSTotal

TDSTotal

Overall ResultC e ca

Oxygen Demmand

Microtox

(% Effect)

c oto

(% Concentration)

otaSuspended Solids

(mg/l)

otaDisolved Solids

(mg/l)

SWS WAC 5 5 11 < 500 <= 50% > 25% < 300 < 1000SWS WAC

Requirement

5.5-11 < 500 <= 50% > 25% < 300 < 1000

0.1% wt. Corrshield

10.2 41 50 44 .95 309 PassCorrshield

0.5% wt. Corrshield

11.15 163 74 10.81 <2 1532 Fail

0.1% wt.

WEST C-441

9.43 59 25 Not Required 2 225 Pass

Operated by Los Alamos National Security, LLC for NNSA 11

Page 12: RF Tests of Chemical Additives for Water Cooled Loads...Background – Evaporative Cooling TowersEvaporative Cooling Towers At LANSCE some 9 inch ((22.922.9 ccm)m) coacoaxialxial l

Experimental Set Up for Low Power TestsExperimental Set Up for Low Power Tests

Operated by Los Alamos National Security, LLC for NNSA 12

Page 13: RF Tests of Chemical Additives for Water Cooled Loads...Background – Evaporative Cooling TowersEvaporative Cooling Towers At LANSCE some 9 inch ((22.922.9 ccm)m) coacoaxialxial l

Experimental SetupExperimental Setup

We measured the return loss of both Corrshield MD401 and WEST C 441 while varying theMD401 and WEST C-441 while varying the concentration and the temperature at 201.25 MHz and the harmonics. W i d th t t f 55 D F (13 D C)We varied the temperature from 55 Deg F (13 Deg C) to 130 Deg F (54 Deg C).We varied the concentration from 0% to 0.1% by yweight. With the Corrshield MD401, we were limited to 0.1% because of the Waste Acceptance Criteria test results.

Operated by Los Alamos National Security, LLC for NNSA 13

Page 14: RF Tests of Chemical Additives for Water Cooled Loads...Background – Evaporative Cooling TowersEvaporative Cooling Towers At LANSCE some 9 inch ((22.922.9 ccm)m) coacoaxialxial l

Experimental SetupExperimental Setup

RF Load Water Inlet and Outlets

Operated by Los Alamos National Security, LLC for NNSA

Network Analyzer and RF Load

14

Page 15: RF Tests of Chemical Additives for Water Cooled Loads...Background – Evaporative Cooling TowersEvaporative Cooling Towers At LANSCE some 9 inch ((22.922.9 ccm)m) coacoaxialxial l

Experimental SetupExperimental SetupA HACH spectrometer DR-2010 was used to measure the concentration by weight of theconcentration by weight of the chemical additive.To measure the concentration of Corrshield MD401, the amount of molybdate in partsamount of molybdate in parts per million was measured and then scaled to the ratio of molybdate to Corrshield MD401.To measure the concentration of West C-441, the amount of nitrite was measured and then scaled to the ratio of nitrite to West C-441.The holding tank, a “chili cooker”, was used to heat and cool the water.

Holding tank with heater element, flow meter and pump

Operated by Los Alamos National Security, LLC for NNSA

cool the water.

15

Page 16: RF Tests of Chemical Additives for Water Cooled Loads...Background – Evaporative Cooling TowersEvaporative Cooling Towers At LANSCE some 9 inch ((22.922.9 ccm)m) coacoaxialxial l

Experimental ResultsExperimental ResultsReturn Loss versus Temperature at 201.25 MHz

for DI Water With Chemical Additives

8

The RF performance of Corrshield MD401 and WEST C 441 i

-14

-12

-10

-8

CS = Corrshield MD401West = West C-441

WEST C-441 is very similar.

A good RF match (> 25

-20

-18

-16os

s (d

B)

CS 0%CS 0.04%CS 0 07%

Concentration by Weight:

g (dB) at all temperatures was obtained at concentrations of 0 04% or greater

-28

-26

-24

-22

Ret

urn

Lo

CS 0.07%CS 0.08%CS 0.10%West 0%West 0.02%West 0.04%West 0.06%

0.04% or greater.

The RF match was better at lower

-34

-32

-30West 0.08%West 0.1%temperatures, but is

still acceptable at higher temperatures.

Operated by Los Alamos National Security, LLC for NNSA

-3655 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135

Temperature (Degrees F)

16

Page 17: RF Tests of Chemical Additives for Water Cooled Loads...Background – Evaporative Cooling TowersEvaporative Cooling Towers At LANSCE some 9 inch ((22.922.9 ccm)m) coacoaxialxial l

Experimental ResultsExperimental ResultsWe operate at 201.25 MHz so the data at this frequency is shown. Data was also taken at the frequencies where harmonic power is often seen (402.5 MHz, 603.75 MHz and 805 MHz). The data had the best return loss at 201.25 MHz. At the higher frequencies, the return loss tended to have more fluctuations withthe return loss tended to have more fluctuations with temperature. The return loss of the DI water with no chemical varied with temperature between –20 dB and –8db and was not acceptable. With as little as 0.02% concentration of WEST C-441 the return loss became sufficient. Between 0.02% and 0.04%, it improved significantly. With both chemicals, between 0.04% and 0.1%, the reflection coefficient increased, but only by a small amount.

Operated by Los Alamos National Security, LLC for NNSA 17

Page 18: RF Tests of Chemical Additives for Water Cooled Loads...Background – Evaporative Cooling TowersEvaporative Cooling Towers At LANSCE some 9 inch ((22.922.9 ccm)m) coacoaxialxial l

ConclusionsConclusionsWe will proceed by using 0.1% of WEST C-441. We did not test WEST C-441 at concentrations above 0 1% b ld t t t C hi ld MD401 t0.1% because we could not test Corrshield MD401 at concentrations above 0.1%.Next summer, we will repeat these tests for WEST C-, p S441 at concentrations from 0.1% to 1% to see if the RF performance is still good. We would like to be able to use optimal concentrationWe would like to be able to use optimal concentration of WEST C-441 for corrosion inhibition, if possible. Fair corrosion protection is 0.35%, and excellent corrosion protection is > .6%.pWe installed a new closed loop system to be able to use WEST C-441 in our loads and avoid the issues that come with the cooling tower water

Operated by Los Alamos National Security, LLC for NNSA

that come with the cooling tower water.

18

Page 19: RF Tests of Chemical Additives for Water Cooled Loads...Background – Evaporative Cooling TowersEvaporative Cooling Towers At LANSCE some 9 inch ((22.922.9 ccm)m) coacoaxialxial l

New Ionized Water SystemNew Ionized Water System

A new closed loop water system was installed forsystem was installed for the 201 RF test stand.It is isolated from the cooling tower water by the heat exchangers.

The water systems contains a “shot feeder” so we canfeeder so we can easily add the WEST C-441 and take samples to measure

Operated by Los Alamos National Security, LLC for NNSA

samples to measure the concentration.

19

Page 20: RF Tests of Chemical Additives for Water Cooled Loads...Background – Evaporative Cooling TowersEvaporative Cooling Towers At LANSCE some 9 inch ((22.922.9 ccm)m) coacoaxialxial l

New ETL Water SystemsNew ETL Water Systems

Operated by Los Alamos National Security, LLC for NNSA 20