133

 · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document
Page 2:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 3:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 4:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 5:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 6:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document
Page 7:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

• °

• °

• °

• °

Page 8:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

° °

•72 hours < 5 minutes

30°C/hr

Page 9:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-3

(4.1.1.1)

[69] The packaged equipment shall not sustain

any damage or deteriorate in functional

performance after it has been exposed to the

environment described in Table 4-1.

Page 10:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 11:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

CR4-20 [151] If a delay occurs between power turn-on

and full operational capacity of the equipment,

that equilibration time shall be recorded and

reported. Both the equilibration at room

temperature (25°C/770°F) and cold test

temperature shall be reported

Page 12:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

• °

Page 13:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

° °

°

° °

96 Hours

≈ 100 Hours

Page 14:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-4

(4.1.1.2)

[71] The packaged equipment shall not sustain

any damage or deteriorate in functional

performance after it has been exposed to the

environment described in Table 4-2.

Page 15:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 16:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

• °

• °

• °

• °

• °

Page 17:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

° °

•< 5 minutes

72 hours

30°C/hr

Page 18:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-5

(4.1.1.3)

[70] The packaged equipment shall not sustain

any damage or deteriorate in functional

performance after it has been exposed to the

environment described in Table 4-3.

Page 19:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 20:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document
Page 21:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

°

• °

Page 22:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

°

°

°

°

° °

°

°

°

°

° °

Page 23:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

°

°

°

°

° °

°

°

°

°

° °

Page 24:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Issue 4 Operational Temperature/Humidity

-20

0

20

40

60

80

100

0 20 40 60 80 100 120 140 160

Tem

p (

C)

/%R

H

Time (Hours)

Temperature HumidityTOH=50, 55, 60 or 650COr 60 above TOH

Page 25:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Operational Temp/Humidity Class 2

-50

-30

-10

10

30

50

70

90

0 5 10 15 20 25 30 35 40

Tem

p (

C )

/Hu

mid

ity

%R

H

Time (Hours )

Temperature Humidity

Repeat 4 times for a total of 5

Page 26:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Operational Temp/Humidity Class 3 & 4

-50

-30

-10

10

30

50

70

90

0 10 20 30 40 50

Tem

p (

C )

/Hu

mid

ity

%R

H

Time (Hours)

Temperature HumidityClass 4 can be +460C + Solar load

Repeat 4 times for a total of 5

Page 27:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-6

(4.1.2)

[72] The equipment shall not sustain any damage

or deterioration of functional performance during

its operating life when operated within the

conditions of Table 4-4.

Page 28:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

o ° °

o ° °

o ° °

o ° °

o ° °

Page 29:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 30:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

o

Page 31:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

°

°

Page 32:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 33:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

0

20

40

60

80

100

120

0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0

kP

a/T

em

p C

time (hrs)

Altitude (kPa) Temperature

TAH TAM

Shelf level Objective Test

Page 34:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-7

(4.1.3)

[74] All equipment shall be functional when

installed at elevations between 61 m (200 ft)

below sea level and 1,829 m (6,000 ft) above sea

level at aisle-ambient temperatures of 40°C.

R4-8

(4.1.3)

[136] All equipment shall be functional when

installed at elevations between 1,829 m (6,000 ft)

and 3,960 m (13,000 ft) above sea level, at aisle-

ambient temperatures of 30°C.

R4-9

(4.1.3)

[75] The manufacturer shall provide special

requirements for installations above 1,829 m

(6,000 ft) in the product documentation, if

needed.

Page 35:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

O4-10

(4.1.3)

[137] All equipment shall be functional when

installed at elevations between 61 m (200 ft)

below sea level and 1,829 m (6,000 ft) above sea

level at aisle-ambient temperatures of 50C.

O4-11

(4.1.3)

[76] All equipment shall be functional when

installed at elevations between 1,829 m (6,000 ft)

and 3,960 m (13,000 ft) above sea level, at aisle-

ambient temperatures of 40C.

Page 36:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 37:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

0

10

20

30

40

50

60

70

0 2 4 6 8 10 12 14

tem

per

atu

re (C

)

Time (hours)

TML

Page 38:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-12

(4.1.4)

[153] Equipment response to temperatures up to

10°C above the short-term high temperature

extreme of Table 4-4 shall be determined. Report

the threshold temperature for deterioration of

functional performance and/or equipment

shutdown.

Page 39:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-13

(4.1.5)

[154] Equipment cooled by forced convection

shall not sustain damage or deterioration of

functional performance when operated with any

single fan failure at 40°C equipment aisle air

temperature for a short-term of up to 96 hours

Note: No humidity required

Page 40:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 41:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document
Page 42:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-28

(4.1.6)

[77] The maximum heat release and method of

cooling (e.g., natural convection, forced-air fans)

shall be documented for all equipment.

• For circuit-packs, document the rate of heat

release in Watts (W)

• For floor-mounted equipment, document the

rate of heat release in Watts, as well as the

rate of heat dissipation in W/ft2 of floor area

• For equipment shelves, document the rate of

heat release in Watts, as well as the rate of

heat dissipation in W/m2 per meter or W/ft2

per foot of frame vertical height used

Page 43:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

O4-29

(4.1.6)

[78] Equipment rate of heat dissipation should

not exceed the values presented in Table 4-5

Heat Dissipation greater than these objectives

must be clearly identified in product

documentation along with a note indicating that

special equipment room cooling may be

required. The heat-dissipation objectives for an

individual frame are based upon overall system

heat dissipation that does not exceed the system

values that Table 4-5 Provide.

Page 44:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 45:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-31

(4.1.6)

[195] Equipment shall be tested to the applicable

ATIS-0600015.2009 Energy Efficiency for

Telecommunications Equipment: methodology

for Measurement and Reporting-General

Requirements standard, or other specification

identified by the service provider. The results

shall be provided to the service provider.

Page 46:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

• ° ± °

• ±

± ±

± ±

Page 47:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

• ° ± °

Page 48:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document
Page 49:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

O4-32

(4.1.7)

[79] It is an objective that equipment surfaces that face

aisles or surfaces where normal maintenance functions

are anticipated should not exceed 48°C (118°F) when

equipment is operating in a room with an air

temperature of 23°C (73°F). Passive equipment,

wherein no heat is generated, are exempt for testing.

R4-33

(4.1.7)

[159] It is a requirement that equipment surfaces that

face aisles or surfaces where normal maintenance

functions are anticipated shall conform to the

temperature limits established in Table 4-6

“temperature Limits of Touchable Surfaces” when the

equipment is operating in a room with ambient air

temperature of 23°C (73°F). Passive equipment,

wherein no heat is generated, are exempt for testing.

Page 50:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document
Page 51:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 52:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document
Page 53:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-34

(4.1.8)

[160] Air Cooled equipment shall utilize only

rear-aisle exhaust (EC Class X-R1, X-R2, X-R3

or a combination of these)

Note: Where approved by exception, top exhaust

(EC Class X-T) airflow equipment may be

deployed in support of specialized airflow

requirements.

Page 54:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document
Page 55:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 56:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document
Page 57:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 58:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

• °

Page 59:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

0

1

2

3

4

5

6

7

8

9

10

0 50 100 150 200 250 300

Met

han

e F

low

L/m

in

Time (secs)

29 cm

20 CM

15 CM

10 cm

Page 60:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

=

=

Page 61:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

=

=

Page 62:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

=

=

Page 63:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Airflow

SLIIM

Page 64:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 65:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 66:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 67:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-57

(4.2.3.1)

[90] All Materials, components, and interconnect wire

and cable used within equipment assemblies shall meet

the requirements of ANSI T1.307-2007, Fire Resistance

Criteria- Ignitability for Equipment Assemblies, Ancillary

Non-Metallic Apparatus, and Fire Spread Requirements

for Wire and Cable Section 4.1

Components contained within a small metal fire enclosure

do not present a risk of self-ignition due to lack of oxygen

and lack of potential for fire spread R4-57 [90] does not

apply to materials and components within an enclosure of

0.005 m3 (305 in3) or less, Consisting totally of metal and

having no intentional ventilation openings, Interfaces

entering or leaving a fire enclosure are not considered

intentional ventilation openings if they pass from the

enclosure with minima clearance.

Page 68:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-58

(4.2.3.1)

[202] Components and materials exposed or outside of

the fire enclosure shall conform to R4-57 [90]

Page 69:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-59

(4.2.3.1)

[91] Mechanical components (examples include circuit

boards, backplanes, connectors, and plastic covers, labels,

and handles) shall either:

• Rated SC 0, SC1, SC-TC 0, or SC-TC 1, or

• Formed of materials that, in the minimum thickness

as used in the component, are rated UL 94 V-0 or

better, as determined by ANSI/UL 94-2006, Test for

Flammability of Plastic Components for Parts in

Devices and Appliance, or

• Formed of materials that, in the minimum thickness

as used in the component, are rated UL 94 V-1 or

better, and have an oxygen index of 28% or greater as

determined by ASTM D2863, Standard Test Method

or Measuring the Minimum Oxygen Concentration to

Support Candle-Like Combustion of Plastics (Oxygen

Index), or

continued…

Page 70:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-59

(4.2.3.1)

[91] Mechanical components (examples include circuit

boards, backplanes, connectors, and plastic covers, labels,

and handles) shall either:

• Conforming to the needle flame test of ANSI T1.307-

2007, Section 5.1, or

• Conforming to the in-situ needle flame test of ANSI

T1.307-2007, Section 5.2, or

• Conforming to the Telcordia needle flame test of GR-

63-CORE Section 5.2.4.1

• Conforming to the Telcordia in-situ needle flame test

of GR-63-CORE Section 5.2.4.2

Page 71:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-60

(4.2.3.1)

[92] Small discrete structural components, grouped in

close proximity, as described in the second paragraph or

R4-59 [91], shall be tested to the needle flame test as

described in ANSI T1.307-2007, Section 5.2 or the

Telcordia needle flame test of GR-63-CORE Section

5.2.4 “Telcordia Needle Flame Test” The ignition of one

component by the test flame shall not ignite any adjacent

components

R4-61

(4.2.3.1)

[93] Foamed polymers shall meet the HF-1 requirements

of ANSI/UL 94-2006

Note: Foamed polymers air filter assemblies must also

meet the fire-spread requirements of GR-63-CORE

Section 4.5 “Airborne Contaminants.”

Page 72:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-62

(4.2.3.1)

[95] Insulating tapes shall meet the flammability

requirements of UL 510-2005, Standard for Polyvinyl

Chloride, Polyethylene and Rubber Insulating Tape.

R4-63

(4.2.3.1)

[96] Sleeving and tubing flammability shall meet the

VW-1 requirements of ANSI/UL 1441-2005 Coated

Electrical Sleeving

R4-64

(4.2.3.1)

[203] The flammability of miscellaneous sleeving and

tubing used for mechanical and protection of optical

fibers shell meet R4-59 [91] or R4-60 [92], or the VW-1

requirements when tested to the flammability test

methods of ANSI/UL 1441-2005 Coated Electrical

Sleeving

R4-64 is a new requirement

Page 73:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-65

(4.2.3.1)

[97] Discrete electronic components shall be either:

• Conforming to the needle flame test of ANSI T1.307-

2007, Section 5.1, or

• Conforming to the in-situ needle flame test of ANSI

T1.307-2007, Section 5.2, or

• Conforming to the Telcordia needle flame test of GR-

63-CORE Section 5.2.4.1

• Conforming to the Telcordia in-situ needle flame test of

GR-63-CORE Section 5.2.4.2, or

• Rated SC 0, SC1, SC-TC 0, or SC-TC 1, or

• Formed of materials that, in the minimum thickness as

used in the component, are rated UL 94 V-0 or better, as

determined by ANSI/UL 94-2006, or

• Formed of materials that, in the minimum thickness as

used in the component, are rated UL 94 V-1 or better,

and have an oxygen index of 28% or greater as

determined by ASTM D2863-10

Page 74:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document
Page 75:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document
Page 76:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 77:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 78:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document
Page 79:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 80:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-80

(4.3.1.1)

[107] The packaged equipment shall not sustain

any physical damage or deteriorate in functional

performance when subjected to free-fall shocks

to to surfaces, edges, and corners at levels

expected during shipping and handling (Readers

may refer to Table 5-7 “Category A Container

Packaged Equipment Shock” criteria)

Page 81:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-81

(4.3.1.2)

[108] The packaged equipment shall not sustain

any physical damage or deteriorate in functional

performance when subjected to free-fall shocks

to the normal rest surface at level expected

during shipping and handling

Page 82:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 83:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 84:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 85:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 86:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-82

(4.3.2)

[109] The unpackaged equipment shall not

sustain physical damage or deteriorate in

functional performance when subjected to shock

levels expected during installation activities.

Minor Cosmetic damage is allowed

Page 87:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 88:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document
Page 89:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 90:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document
Page 91:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-83

(4.4.1.2)

[110] All equipment shall be constructed to sustain the

waveform testing of Section 5.4.1 “Earthquake Test

Methods” without permanent structural or mechanical

damage.

R4-84

(4.4.1.2)

[111] Frame-level equipment shall be constructed so that

during the waveform testing of Section 5.4.1,

“Earthquake Test Methods” the maximum single-

amplitude deflection at the top of the framework, relative

to the base, does not exceed 75 mm (3 in).

R4-85

(4.4.1.2)

[112] Frame-level equipment shall have a natural

mechanical frequency greater than 2.0 Hz as determined

by the swept sine survey of Section 5.4.1, “Earthquake

Test Methods”

Page 92:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

O4-86

(4.4.1.2)

[113] Frame-level equipment should have a natural

mechanical frequency greater than 6.0 Hz as determined

by the swept sine survey of Section 5.4.1 “Earthquake

Test Methods.”

Page 93:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-87

(4.4.1.3)

[114] All equipment shall be constructed to meet

applicable functionality requirements immediately before

and after each axis of waveform testing of Section 5.4.1.

“Earthquake Test Methods.” The equipment shall sustain

operation without replacement of components, manual

rebooting, or human intervention.

O4-88

(4.4.1.3)

[115] All equipment should be constructed to meet

applicable functionality requirements continuously during

waveform testing of Section 5.4.1. “Earthquake Test

Methods.” These functionality criteria shall demonstrate

that the equipment has sustained operation without loss of

service during the testing.

Page 94:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

O4-89

(4.4.2)

[116] Framework should be of welded construction.

R4-90

(4.4.2)

[117] Framework shall be constructed for base mounting

to the floor without auxiliary support or bracing from the

building walls or ceilings.

O4-91

(4.4.2)

[118] For framework used in earthquake risk zones, the

static pull testing procedures of Section 5.4.1.4 “Static

Test Procedure” should be followed, meeting these

objectives:

• The maximum single amplitude deflection at the top

of the framework should not exceed 75 mm (3 in).

• The top of the framework should return to its original

position, within 6 mm (0.24 in) when the load is

removed.

The framework should sustain no permanent structural

damage during static framework testing.

Page 95:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 96:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document
Page 97:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Control

Test Direction

Input

Dummy Weight

Test Sample

23 kg

Top MountMiddle MountBottom Mount

Page 98:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Control

Test Direction

Input

Dummy Weight

Test Sample

23 kg

Top Mount

Page 99:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Control

Test Direction

Input

Test Sample

Middle Mount

Page 100:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Control

Test Direction

Input

Test Sample

Bottom Mount

Page 101:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-92

(4.4.2)

[119] Concrete expansion anchors used to base mount

framework to the floor shall meet the following

requirements:

• Maximum embedded depth of 90 mm (3.5 in)

• Maximum bolt diameter of 13 mm (0.5 in)

O4-93

(4.4.2)

[120] Concrete expansion anchors used to base mount

framework to the floor should be suitable for

earthquake (dynamic) applications, as specified by the

manufacturer.

O4-94

(4.4.3)

[121] Concrete expansion anchors should use steel

construction to minimize creep.

R4-95

(4.4.3)

[175] Fastening systems used for wall-mounted

equipment shall withstand a force of 3 times the

weight of the equipment applied to the equipment in

any direction.

Page 102:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 103:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 104:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document
Page 105:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

0.01

0.1

1

5 50

g’s

Frequency (Hz)

Issue 4

Page 106:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

0.001

0.01

0.1

1

5 50

m2/s

ec3

Frequency (Hz)

Issue 4

Page 107:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-96

(4.4.4.2)

[122] All equipment shall be constructed to

sustain the office vibration testing of Section

5.4.2 “Office Vibration Test Procedure.”

without permanent structural or mechanical

damage.

R4-97

(4.4.4.3)

[123] All equipment shall be constructed to meet

applicable functionality requirements

continuously during each axis of the office

vibration testing of Section 5.4.2“Office

Vibration Test Procedure.” The equipment shall

sustain operation without replacement of

components, manual rebooting, or human

intervention.

Page 108:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

0.001

0.01

0.1

1

5 50

m2/s

ec3

Frequency (Hz)

Issue 4 Class 3.2

Page 109:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 110:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document
Page 111:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 112:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

0.0001

0.001

0.01

0.1

1

5 50 500

g2/H

z

Frequency (Hz)

Page 113:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-98

(4.4.5.1)

[124] Equipment shall not sustain any physical

damage or deteriorate in functional performance

when subjected to vibration expected during

transportation.

Page 114:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 115:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document
Page 116:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 117:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

±

±

Page 118:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-99

(4.5.1)

[125] It is a requirement that equipment intended

for installation in controlled environmental space

or sealed OSP cabinets operate reliably for its

intended service life within the average yearly

levels of contamination listed in Table 2-4

“Indoor Contaminant Levels.” Conformance to

this requirement for reactive gases and

hygroscopic fine particulate can be demonstrated

through the test methods given in Section 2.11.1

“Gaseous Contamination Levels.”

Minor word change for OSP cabinet

Page 119:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-100

(4.5.1)

[127] It is a requirement that equipment intended

to function in outdoor air, such as cabinets

installed on pads or poles, ventilated with little or

no filtration, should operate reliably for the

intended service life at the contaminant levels

listed n Table 2-3 “Outdoor Contaminant

Levels.” Conformance to this requirement for

reactive gases and hygroscopic fine particulate

can be demonstrated through the test methods

given in Section 5.5 “Airborne Contaminants

Tests Methods.”

Page 120:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 121:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Ώ

Page 122:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

1.00000E+03

1.00000E+04

1.00000E+05

1.00000E+06

1.00000E+07

1.00000E+08

1.00000E+09

40% 45% 50% 55% 60% 65% 70% 75% 80% 85%

Resis

tan

ce

%RH

Coupon 1 Front row-left Coupon 2 Front row-middle Coupon 3 Front row-right

Coupon 4 2nd row left Coupon 5 2nd row right Average

Page 123:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

1.00000E+03

1.00000E+04

1.00000E+05

1.00000E+06

1.00000E+07

1.00000E+08

1.00000E+09

40% 45% 50% 55% 60% 65% 70% 75% 80% 85%

Resis

tan

ce

%RH

Coupon 1 Front row-left Coupon 2 Front row-middle Coupon 3 Front row-right

Coupon 4 2nd row left Coupon 5 2nd row right Average

Page 124:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

0

10

20

30

40

50

60

70

80

0 1 2 3 4 5 6

Temp RHt

Page 125:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 126:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document
Page 127:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

• °° °

Page 128:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document
Page 129:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

R4-101

(4.6)

[128] Under normal operation, equipment shall

not produce declared A-weighted sound power

level (LWAd) above the limits shown in Table 4-8

Location LWAd Temp (C)

Telecomm.

Room78 27

Power

room83 27

R4-102

(4.6)

[177] The sound power level produced while

operating at maximum fan speed shall be

measured and provided

Page 130:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

Page 131:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

o

o

o

• °

Page 132:  · • For floor-mounted equipment, document the rate of heat release in Watts, as well as the rate of heat dissipation in W/ft2 of floor area • For equipment shelves, document

o