Installation Guide

3RU Splice and Patch Panel

Series

Page 2: 3RU Splice and Patch Panel - aflhyperscale.com

2 © AFL Hyperscale. All rights reservedSeries

Safety Precautions

Laser Precautions

Warning: The laser light used to transmit information over optical fiber cables can cause severe eye damage. Because this light is invisible, it will not cause the iris of the eye to contract involuntarily as when

viewing a bright visible light, and no pain is felt as the retina is burned.

Never look into the end of a fiber or connector which may have a laser coupled to it. Should accidental eye exposure to laser light be suspected, arrange for an eye examination immediately.

General Precautions

Personnel must be thoroughly familiarized with all applicable Occupational Health and Safety (OH&S) regulations, local regulations, and your company safety practices and policies.

Warning: To reduce the chance of accidental injury:

Before work begins, all personnel must be thoroughly familiar with the operation of all equipment and procedures to be used during the installation.

Before use, all equipment, especially safety gear, must be inspected and tested for proper operation. Replace and repair as necessary.

U-Series 3RU Splice and Patch Panel

Before installing or adjusting this product, please read these instructions carefully. Please keep this guide for future reference.

Page 3: 3RU Splice and Patch Panel - aflhyperscale.com

3

U-Series 3RU Splice and Patch Panel

© AFL Hyperscale. All rights reservedSeries

Component Overview

01

02

07

06

05

04

03

Page 4: 3RU Splice and Patch Panel - aflhyperscale.com

4 © AFL Hyperscale. All rights reservedSeries

In the Box

Item Number

ItemLC

QtySC

Qty

01U-Series 3RU Splice and

Patch Panel1 1

02U-Series Patch Adapter Plate

12 12

03 Patch Cable Management 1 1

04 Brush Strip 2 2

05 Rear Cover 1 1

06Internal Fiber Slack

Management1 1

07 Front Door Assembly 1 1

08 M6 Cage Nut + Screw 4 4

0912f Ribbon Splice

Protector24 12

10Cable Tie

Black 300mm x 4.5mm10 10

11500mm Length of Ø32mm

Conduit1 1

12 Ribbon Pigtail 12 12

13 Hose Clip Ø11-16mm 2 2

(01) U-Series 3RU Splice and Patch Panel

(04) Brush Strip

Cross-Head + Flat-Head Screwdriver

(07) Front Door Assembly

(10) Cable Tie Black 300mm x 4.5mm

(02) U-Series Patch Adapter Plate

(05) Rear Cover

(08) M6 Cage Nut + Screw

(11) 500mm Length of Ø32mm Conduit

(13) Hose Clip Ø11-16mm

(03) Patch Cable Management

(06) Internal Fiber Slack Management

(09) 12f Ribbon Splice Protector

(12) Ribbon Pigtail

What You Will Need Related Products

FVP Pre-Terminated Replacement Cassette

250 μm WTC with SWR®

One-Click® Cleaner

D-LC, Duplex LC

U-Series 3456f & 6912f

Breakout Box

Page 5: 3RU Splice and Patch Panel - aflhyperscale.com

5

U-Series 3RU Splice and Patch Panel

© AFL Hyperscale. All rights reservedSeries

Installation Procedure

Turn the quick release fasteners anti-clockwise to remove the rear cover (05).

4Attach the front door assembly (07) as shown.3

Insert the cage nut screws (08) with a screwdriver.

2Insert cage nuts (08) in the positions shown above on both the left- and right-hand sides of the rack.

1

3U

2U

Page 6: 3RU Splice and Patch Panel - aflhyperscale.com

6 © AFL Hyperscale. All rights reservedSeries

Route the conduit (11) into the panel and cable tie (10) it to the internal bracket as shown above.

8Push conduit (11) up and over the cable jacket and cable tie (10) the conduit to the bracket.

7

Remove the brush strip (14), tie off the cable using the hose clip (13) and flat head screwdriver - ensure the jacket strip point is as shown.

6

Installation Procedure

Slide the hose clip (13) and conduit (11) (cut to 150mm) over the cable, and strip 1m of cable jacket in accordance with the cable manufacturers’ guidelines.

5

1m

(ap

pro

x.)

150m

m (

ap

pro

x.) Jacket strip point

Page 7: 3RU Splice and Patch Panel - aflhyperscale.com

7

U-Series 3RU Splice and Patch Panel

© AFL Hyperscale. All rights reservedSeries

Inbound fiberPre-installed

ribbon pigtails

Ensure the fiber is routed around these managers before cutting to the maximum length

Installation Procedure

Re-fit the rear cover and secure with a quarter turn of the fasteners - they will click when they are closed.

12Re-dress the fiber into the panel, clipping the splice protectors into the holders. Use the dotted line route for re-spliced fibers.

11

Undress the fiber from all the managers and splice according to splice schedule and cable manufacturers’ guidelines (approx. 700mm of slack available).

10Dress the fiber into the panel as per the green route, cut both inbound and pre-installed fiber to length.

9

Inbound fiberPre-installed

ribbon pigtails

Page 8: 3RU Splice and Patch Panel - aflhyperscale.com

8 © AFL Hyperscale. All rights reservedSeries

LC Fiber Map

SC Fiber Map

Po

siti

on

Nu

mb

er

1

2

3

4

5

6

7

8

9

10

11

12

13

Po

sition

Nu

mb

er

14

15

16

17

18

19

20

21

22

23

24

PositionNumber

Fiber/Tubing Color

1 Blue

2 Orange

3 Green

4 Brown

5 Grey

6 White

7 Red

8 Black

9 Yellow

10 Purple

11 Pink

12 Aqua

Position Number

Fiber/Tubing Color

13 Orange

14 Blue

15 Brown

16 Green

17 White

18 Grey

19 Black

20 Red

21 Purple

22 Yellow

23 Aqua

24 Pink

1 2 3 4 5 6 7 8 9 10 11 12Adapter Plate Numbers

Adapter Plate Numbers

Adapter Keyway Up

Po

siti

on

Nu

mb

er

1

3

5

7

9

11

2

Po

sition

Nu

mb

er

4

6

8

10

12

Position Number Fiber/Tubing Color

1 Blue

2 Orange

3 Green

4 Brown

5 Grey

6 White

7 Red

8 Black

9 Yellow

10 Purple

11 Pink

12 Aqua

1 2 3 4 5 6 7 8 9 10 11 12

Page 9: 3RU Splice and Patch Panel - aflhyperscale.com

9

U-Series 3RU Splice and Patch Panel

© AFL Hyperscale. All rights reservedSeries

Notes

Page 10: 3RU Splice and Patch Panel - aflhyperscale.com

10 © AFL Hyperscale. All rights reservedSeries

Notes

Page 11: 3RU Splice and Patch Panel - aflhyperscale.com

11

U-Series 3RU Splice and Patch Panel

© AFL Hyperscale. All rights reservedSeries

Notes

Page 12: 3RU Splice and Patch Panel - aflhyperscale.com

Thank you for choosing AFL Hyperscale

AFLHS3RUSPP270820

www.aflhyperscale.com

AFL Hyperscale reserves the right to make changes in this Installation Guide at any time without notice