C10...40User manual

Page 2: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

3Manual CORRIGO C-SERIES 2000.09

ContentsModel overview CORRIGO for ventilation systems 4Technical data 5Overview of inputs and outputs 6Installation 10Wiring Diagrams 11Description of inputs and outputs 15Using the CORRIGO menu system 19Logging in 21Configuration 23Controlling temperature 33Controlling pressure 34Controlling humidity 34Running mode 35Inputs 35Outputs 36Scheduler 38Alarm settings and lists 40Settings (other) 42Relay modules, accessories 44Commissioning protocol 46Configuration tables 48

Introduction

COORIGO is a completely new range of controllers which has been designed to beeasy to use and operate. The controllers have a display and built in panels foroperation and alarm on the front and are operated by means of clearly definedbuttons.The controllers have been designed for mounting on a DIN rail, in norm housing oron the front of a cabinet.The required functions are selected with the help of questions in normal script or bymeans of a code under the configuration menu depending on the type ofapplication.The controller has a year-base clock and automatic summer/winter timechangeover.The menu system works with different user-levels to show settings and to allowsettings to be altered. This means that non-technical staff can feel secure whileusing the system since it is impossible, on the lower user-levels, to programmeincorrect settings when checking operating status, parameter values, alarms etc.During normal operation, without pressing any buttons, the display also shows themost important operating statuses such as setpoint/current value, sequence-outputcontrol and time/date/version etc.We hope you will be satisfied with your CORRIGO and that it will provide you withsimpler and more economic running of your control systems.

Page 3: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

4Manual CORRIGO C-SERIES 2000.09

Overview - air handling models

There are four CORRIGO models for ventilation control each with certain differencesin control function and the number of outputs and types of input. These are suppliedeither with or without LON Works communication.

Temperature control

C10 Temperature control with up to three sequences.C10-LON With LON Works communication

Temperature and pressure control

C20 Temperature control with up to three sequences. Pressure control ofsupply air and exhaust air fans.

C20-LON With LON Works communication

Temperature and humidity control

C30 Temperature control with up to three sequences. Humidity controltwo sequences.

C30 LON With LON Works communication.

Temperature, humidity and pressure control

C40 Temperature control with up to three sequences. Humidity controltwo sequences. Pressure control supply air and exhaust air fans.

C40 LON With LON Works communication.

C10 C20 C30 C40• • • •

• •• •

7 7 7 73 5 4 6

10 8 10 86 6 4 4

2 2 4• • • •• • • •• • • •• • • •• •• • • •• • • •• • • •• • • •• • • •• • • •• • • •• •• • • •• • • •

Temperature controlPressure controlHumidity controlNumber of digital outputsNumber of analogue outputs (0...10 V)Number of digital inputsNumber of analogue inputs (PT1000)Number of analogue intputs (0...10 V)Run-time indication with yellow LEDsAlarm indication in text and red LEDsOne- or twospeed control of supply and exhaust air fansIndividual start and stop of supply and exhaust air fansEfficiency monitoringCooling recoveryAutomatic night cooling (free cooling)Periodic fire-damper exercising with alarm functionFilter alarm and pressure alarmActive frost protection with stand-by heating when the system is shut downAutomatic circulation pump control with periodic exercisingMemory (48 hour backup time in event of a power-failiure)External setpointCommunication (Lon-versions)Year-base clock

Page 4: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

5Manual CORRIGO C-SERIES 2000.09

Technical data

Supply voltage 24V AC +/- 15%Power consumption 3VAAmbient temperature 0...50 deg.C.Storage temperature -40...+50 deg.C.Ambient humidity Maximum 90% RHDimensions (w x h x d) 105 x 112 (incl.terminals) x 58 mm.Protection class IP20. Front mounting IP40Mounting On DIN-rail in a cabinet or standard housing.

On cabinet front using mounting kit FMCConnections Disconnectable terminal stripsTemp.sensor inputs PT1000Analogue inputs 0....10V DCDigital inputs Potential free closure.Digital outputs 0.5 A, 24 V AC triac outputsAnalogue outputs 0...10 V DC, 5 mA. Short-circuit protectedMemory Flash. All settings are stored in the event of power failure.

Real-time clock with 48 hour reserve running time.Display Background illumination. LCD, 2 rows of 16 charactersRunning indication 7 in number steady shining yellow LEDsAlarm indication 7 in number steady shining/flashing red LEDsAlarms Steady shining/flashing LED and relay output,

1A 24V DC/AC.The alarm output can be blocked to prevent unprioritisedalarms activating the alarm relay during the night orduring holidays.This product conforms with the requirements ofEuropean EMC standards CENELEC EN50081-1 andEN50082-1 and carries the CE mark.

Front mounting kitWhen mounting CORRIGO in a cabinet front use the FMk1 kit for easier mounting.The kit contains a front frame with see-through lid and an integrated mounting-rail.Protection class IP65.When mounting 2 CORRIGOs or one CORRIGO plus a relay unit next to each other inthe cabinet front use the FMk2 mounting kit. It contains the same items as FMK1above but in different dimensions.

Page 5: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

6Manual CORRIGO C-SERIES 2000.09

CORRIGO - C10

Analogue inputs - Temperature sensorsAI3 Exhaust air temperatureAI4 Extract air temperature or

External setpoint orExchanger return temperature (Liquid connectedexchanger).

AI5 Outdoor temperatureAI6 Supply air temperatureAI7 Room temperatureAI8 Frost protection temperature.

When frost protection function has beenselected orHigh temperature limit. When using an electricheater

Digital inputs - operation and alarm indicationAI1 Fan monitor or pressure switch Supply air fan.AI2 Fan monitor or pressure switch Exhaust air fan.DI1 Filter guard(s)DI2 Circulation pump monitor, heater circuitDI3 Input for alarm from chiller(s)DI4 Rotation sentinel or

ice build-up sentinel for heat exchangerDI5 Fire alarmDI6 External alarm,

external switches ”not in Auto position” orend-position indication for fire-damper (for fire-damper exercising).

DI7 Button or timer for extended running time (atsingle speed) / Extended running time highspeed for two- speed fan systems).

DI8 Button or timer for extended low speed runningtime (for two-speed fan systems).

6 analogue sensor inputs Pt100010 digital inputs3 analogue outputs 0....10V7 digital outputsThe controller has temperature control with up to three sequences, control DX-cooling,one- or two-speedoperation, heat exchanger efficiency calculation, cooling recovery function, night setback etc.

Analogue outputs - output signal 0...10 VAO1 Y1 - Heating, cooling or damperAO2 Y2 - Heating, plate exchanger, rotating

exchanger,liquid connected exchanger, damper or cooling

AO3 Y3 – Heating, cooling or not usedDigital outputsDO1 Control supply air fan or

Supply air fan high speed for two-speed fansDO2 Control exhaust air fan or

Exhaust air fan high speed for two-speed fansDO3 Control circulation pump or

Electric heating interlockDO4 Control chiller 1 (DX) or

Supply air fan low speed for two-speed fansDO5 Control chiller 2 (DX) or

Exhaust air fan low speed for two-speed fansDO6 Control external frost protection or

Fire damper exercisingDO7 Alarm output

Example of an applicationsuitable for controlling bythe C10 model.

Page 6: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

7Manual CORRIGO C-SERIES 2000.09

CORRIGO - C20

Analogue inputs - Pressure sensors 0....10VAI1 Pressure sensor, supply air fanAI2 Pressure sensor, exhaust air fanAnalogue inputs - Temperature sensorsAI3 Exhaust air temperatureAI4 Extract air temperature or

External setpoint orExchanger return temperature (Liquidconnected exchanger)

AI5 Outdoor temperatureAI6 Supply air temperatureAI7 Room temperatureAI8 Frost protection temperature

When frost protection function has beenselected orHigh temperature limit. When using an electricheater.

Digital inputs - operation and alarm indicationDI1 Filter guard(s)DI2 Circulation pump monitor, heater circuitDI3 Input for alarm from chiller(s)DI4 Rotation sentinel or

ice build-up sentinel for heat exchangerDI5 Fire alarmDI6 External alarm,

external switches ”not in Auto position” orend-position indication for fire-damper (for fire-damper exercising).

DI7 Button or timer for extended running time atnormal speed.

DI8 Button or timer for extended running time atreduced speed.

6 analogue sensor inputs Pt10002 analogue inputs 0....10 V8 digital inputs5 analogue outputs 0....10 V7 digital outputsThe controller has temperature control with up to three sequences, control of DX-cooling, pressure control ofsupply air fan and exhaust air fan, heat exchanger efficiency calculation, cooling recovery function, freecooling etc.

Analogue outputs - output signal 0...10 VAO1 Y1 - Heating, cooling or damperAO2 Y2 - Heating, plate exchanger, rotating

exchanger,liquid connected exchanger, damper orcooling

AO3 Y3 – Heating, cooling or not usedAO4 Pressure control signal for supply air fanAO5 Pressure control signal for exhaust air fanDigital outputsDO1 Activate supply air fanDO2 Activate exhaust air fanDO3 Control circulation pump or

Electric heating interlockDO4 Control chiller 1 (DX)DO5 Control chiller 2 (DX)DO6 Control external frost protection or

Fire damper exercisingDO7 Alarm output

Example of anapplication suitable forcontrolling by the C20model.

Page 7: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

8Manual CORRIGO C-SERIES 2000.09

CORRIGO - C30

Analogue inputs - Temperature sensorsAI3 Room humidity sensorAI4 Duct humidity sensor (limiting sensor in supply

air duct)Analogue inputs - Temperature sensorsAI5 Outdoor temperatureAI6 Supply air temperatureAI7 Room temperatureAI8 Frost protection temperature. When frost

protection function has been selected orHigh temperature limit (When using anelectric heater)

Digital inputs - operation and alarm indicationAI1 Fan monitor or pressure switch Supply air

fan.AI2 Fan monitor or pressure switch Exhaust air

fan.DI1 Filter guard(s)DI2 Circulation pump monitor, heater circuitDI3 Input for alarm from chiller(s)DI4 Rotation sentinel or

Ice build-up sentinel for heat exchangerDI5 Fire alarmDI6 External alarm,

external switches ”not in Auto position” orend-position indication for fire-damper (forfire-damper exercising).

DI7 Button or timer for extended running time (atsingle speed) / Extended running time highspeed for two- speed fan systems).

DI8 Button or timer for extended low speedrunning time (for two-speed fan systems).

4 analogue sensor inputs Pt10002 analogue 0...10V inputs10 digital inputs3 analogue outputs 0....10V7 digital outputsThe controller has temperature control with up to three sequences, humidity control (humidification,dehumidification or humidification in combination with dehumidification by using the cooling output, control ofDX-cooling,one- or two-speed operation, cooling recovery function, night setback etc).

Analogue outputs - output signal 0...10 VAO1 Y1 - Heating, cooling or damperAO2 Y2 - Heating, plate exchanger, rotating exchanger,

liquid connected exchanger, damper or coolingAO3 Y3 – Heating, cooling or not usedAO6 Humidification / DehumidificationDigital outputsDO1 Control supply air fan or

Supply air fan high speed for two-speed fansDO2 Control exhaust air fan or

Exhaust air fan high speed for two-speed fansDO3 Control circulation pump or

Electric heating interlockDO4 Control chiller 1 (DX) or

Supply air fan low speed for two-speed fansDO5 Control chiller 2 (DX) or

Exhaust air fan low speed for two-speed fansDO6 Control external frost protection or

Fire damper exercisingDO7 Alarm output

Example of an applicationsuitable for controlling bythe C30 model.

Page 8: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

9Manual CORRIGO C-SERIES 2000.09

Analogue outputs - output signal 0...10 VAO1 Y1 - Heating, cooling or damperAO2 Y2 - Heating, plate exchanger, rotating

exchanger,liquid connected exchanger, damper orcooling

AO3 Y3 – Heating, cooling or not usedAO4 Pressure control signal for supply air fanAO5 Pressure control signal for exhaust air fanAO6 Humidity controlDigital outputsDO1 Activate supply air fanDO2 Activate exhaust air fanDO3 Control circulation pump or

Electric heating interlockDO4 Control chiller 1 (DX)DO5 Control chiller 2 (DX)DO6 Control external frost protection or

Fire damper exercisingDO7 Alarm output

CORRIGO - C40

Overview4 analogue sensor inputs Pt10004 analogue inputs 0....10 V8 digital inputs6 analogue outputs 0....10 V7 digital outputsThe controller has temperature control with up to three sequences, humidity control, control of DX-cooling,pressure control of supply air fan and exhaust air fan, heat exchanger efficiency calculation, cooling recoveryfunction, free cooling etc.

Analogue inputs - Pressure sensors / Humiditysensors 0....10VAI1 Pressure sensor, supply air fanAI2 Pressure sensor, exhaust air fanAI3 Room humidity sensor (Main sensor)AI4 Duct humidity sensor (Limiting sensor)Analogue inputs - Temperature sensorsAI5 Outdoor temperatureAI6 Supply air temperatureAI7 Room temperatureAI8 Frost protection temperature. When frost

protection function has been selected orHigh temperature limit. When using an electricheater

DI Digital inputs - operation and alarm indicationDI1 Filter guard(s)DI2 Circulation pump monitor, heater circuitDI3 Input for alarm from chiller(s)DI4 Rotation sentinel or

Ice build-up sentinel for heat exchangerDI5 Fire alarmDI6 External alarm, external switches ”not in Auto

position” or end-position indication for fire-damper (for fire-damper exercising).

DI7 Button or timer for extended running time atnormal speed.

DI8 Button or timer for extended running time atreduced speed.

Example of anapplication suitable forcontrolling by the C40model.

Page 9: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

10Manual CORRIGO C-SERIES 2000.09

Installation

CORRIGO can be mounted in standard casing, on a DIN rail in a cabinet or in thefront of a cabinet.

Front mounting kitWhen CORRIGO is to be placed in a cabinet front mounting will be facilitated usingthe front mounting kit FMK1. The kit contains a front frame with see-through lid andan integrated mounting-rail.When placing two CORRIGOs or one CORRIGO and one relay unit RM6..-24/D next toeach other in the front of the cabinet use the FMCR mounting kit. It contains thesame parts as FMC above but they are of different dimensions.

Supply voltageThe controller is to be supplied with 24V AC. Terminal 43, system neutral, isinternally connected to terminal 41, signal neutral for the analogue outputs, andterminals 24, 27, 30 och 33, signal neutral for the analogue inputs.

InputsThe controller has common poles for signal neutral to transmitters (AI 1-8) and acommon pole for digital input signals.

Terminal 22 (common for digital input signals) is not the same as signal neutral fortransmitters ( terminals 24,27,30 and 33) and they must not be interconnected.Signal neutral terminals for transmitters (24,27,30 and 33) are, however, internallyconnected and connected to system neutral on terminal 43.

OutputsThe analogue outputs give 0...10 V DC. Signal neutral on terminal 41 is internallyconnected to system neutral on terminal 43.

Digital outputs are supplied in pairs with 24V AC on the terminals which are markedwith 24V AC in (terminals 6,9 and 12). Each output has an internal triac which gives24V AC. Terminals 6, 9 and 12 are also internally connected.

Service pinOn the LON-models the comissioning service pin is located behind a markedopening on the upper side of the CORRIGO.

AI1...AI8 analogue in

AO1... AO6 analogue out

Supply voltage 24 V AC

DO1...DO7 digital outputs

DI1...DI8 digital inputs

Important !

Service pin (LON models)

Display contrast setting

Page 10: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

11Manual CORRIGO C-SERIES 2000.09

Wiring diagram C10

Wiring example actuator

Control signal 0...10VSignal neutralSupply voltage 24 V ACSystem neutral (24 V AC)

AO1 Y1 0...10 V DCAO2 Y2 0...10 V DCAO3 Y3 0...10 V DCAO4AO5AO6M Neutral for AO1-AO3

24 V ACN System neutralGround

35363738394041

424344

Supply voltage

Page 11: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

12Manual CORRIGO C-SERIES 2000.09

Wiring example actuator

Wiring diagram C20

Signal 0...10VSignal neutralSupply voltage 24 V ACSystem neutral (24 V AC)

24 V ACN system neutralGround

35363738394041

424344

Supply voltage

AO1 Y1 0...10 V DCAO2 Y2 0...10 V DCAO3 Y3 0...10 V DCAO4 Supply air fan control 0...10 V DCAO5 Exhaust air fan control 0...10 V DCNot connectedM Neutral for AO1-AO5

Page 12: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

13Manual CORRIGO C-SERIES 2000.09

Wiring diagram C30

Wiring example actuator

12

3456789

10111213

141516171819202122

232425262728293031323334

35363738394041

424344

NetA LON-connector C30-LON onlyNetB LON-connector C30-LON only

DO7 Alarm outputDO7 Alarm outputDO6 Frost protection / Fire damper exercisingC5/6 24 V AC in DO5/DO6DO5 Control DX 2 DO4 Control DX 1 C3/4 24 V AC in DO3/DO4DO3 Control Circ. pump/ El. Heating interlockDO2 Activation Exhaust air fanC1/2 24 V AC in DO1/DO2DO1 Activation Supply air fan

DI8 Ext. running Reduced speedDI7 Ext. running Normal speed DI6 Fire damper indicationDI5 Fire alarmDI4 Rotation sentinelDI3 Alarm from chillersDI2 Circulation pump alarmDI1 Filter guardsDI+ Common supply DI1-DI8

AI1 Fan monitor Supply air fanM Signal neutralAI2 Fan monitor Exhaust air fanAI3 Room humidity sensorM Signal neutralAI4 Duct humidity sensor (limiting sensor)AI5 Outdoor temperature sensorM Signal neutralAI6 Supply air temperature sensorAI7 Room temperature sensorM Signal neutralAI8 Frost protection sensor

AO1 Y1 0...10 V DCAO2 Y2 0...10 V DCAO3 Y3 0...10 V DCNot connectedNot connectedAO6 Humidity control output 0...10 V DCM Neutral for AO1-AO3, AO6

24 V ACN Supply neutralGround

24 V AC

1A24 V AC/DC

0...10V

0...10V

-

-

+

+

Supply voltage

Control signal 0...10VSignal neutralSupply voltage 24 V ACSystem neutral (24 V AC)

AO1 Y1 0...10 V DCAO2 Y2 0...10 V DCAO3 Y3 0...10 V DCNot connectedNot connectedAO6 Humidity control output 0...10 V DCM Neutral for AO1-AO3, AO6

24 V ACSystem neutralGround

35363738394041

424344

Supply voltage

Page 13: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

14Manual CORRIGO C-SERIES 2000.09

Wiring example actuator

Wiring diagram C40

Control signal 0...10VSignal neutralSupply voltage 24 V ACSystem neutral (24 V AC)

AO1 Y1 0...10 V DCAO2 Y2 0...10 V DCAO3 Y3 0...10 V DCAO4 Supply air fan control 0...10 V DCAO5 Exhaust air fan control 0...10 V DCAO6 Humidity control output 0...10 V DCM Neutral for AO1-AO6

24 V ACSystem neutralGround

35363738394041

424344

Supply voltage

12

3456789

10111213

141516171819202122

232425262728293031323334

35363738394041

424344

Net A LON-connector C40-LON onlyNet B LON-connector C40-LON only

DO7 Alarm outputDO7 Alarm outputDO6 Frost protection / Fire damper exercisingC5/6 24 V AC in DO5/DO6DO5 Control DX 2 DO4 Control DX 1 C3/4 24 V AC in DO3/DO4DO3 Control Circ. pump / El. Heating InterlockDO2 Activation Exhaust air fanC1/2 24 V AC in DO1/DO2DO1 Activation Supply air fan

DI8 Ext. running Reduced speedDI7 Ext. running Normal speed DI6 Fire damper indicationDI5 Fire alarmDI4 Rotation sentinelDI3 Alarm from chillersDI2 Circulation pump alarmDI1 Filter guardsDI+ Common supply DI1-DI8

AI1 Fan monitor Supply air fanM Signal neutralAI2 Fan monitor Exhaust air fanAI3 Room humidity sensorM Signal neutralAI4 Duct humidity sensor (limiting sensor)AI5 Outdoor temperature sensorM Signal neutralAI6 Supply air temperature sensorAI7 Room temperature sensorM Signal neutralAI8 Frost protection sensor

AO1 Y1 0...10 V DCAO2 Y2 0...10 V DCAO3 Y3 0...10 V DCAO4 Supply air fan 0...10 V DCAO5 Exhaust air fan 0...10 V DCAO6 Humidity control output 0...10 V DCM Neutral for AO1...AO6

24 V ACN Supply neutralGround

24 V AC

1A24 V AC/DC

0...10V

0...10V-

+

+

0...10V

0...10V-

+

+

Supply voltage

Page 14: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

15Manual CORRIGO C-SERIES 2000.09

AI Analogue inCORRIGO has 8 analogue inputs, AI1...AI8The function of some of the inputs varies depending on the choice of model andconfiguration.PT1000 type temperature sensors must be used on those inputs that areconfigured as temperature inputs.In certain cases an AI-input may be used as a digital input. It must then beconnected to a voltage-free, closing contact.When active input signals are connected they must be 0...10 V DC.AI-inputs must always use the signal neutral of the AI terminal block as reference.(terminals 24, 27, 30 or 33).AI1 and AI2are used for connecting pressure switches/transmitters for monitoring and controlof the supply air and exhaust air fansNote: These signals control vital functions in the CORRIGO. They must always beconnected for correct control function.

C10 and C30Connect the inputs to pressure switches with voltage-free closing contacts,for example DTV, or to voltage-free closing contacts in the fan-motorrelays.

C20 and C40Connect the inputs to pressure transmitters with a 0...10V DC output, forexample DMD or DTL. Wiring, see example in the margin.The transmitter pressure range is set in the menu ”Settings”, see page 42.

AI3 och AI4C10 and C20AI3 Used for exhaust air temperature sensor, for example TG-K3/PT1000.AI4 Used for extract air temperature sensor or for minimum limiting sensor in

the heat exhanger circuit when using a liquid connected heat exchanger.(See page 28).These functions are mutually exclusive, only one of them may be chosen.

C30 and C40AI3 Used for room humidity transmitter, for example HRT.AI4 Used for duct humidity sensor (limiting sensor), for example HDT3200.

The sensors must have an output signal of 0...10 V DC corresponding to0...100% RH.Since neither of the supply voltage terminals is connected to the AI signalneutral it is necessary to make an external connection between the supplyvoltage pole chosen as G0 and the AI signal neutral.Note: If no limiting sensor is connected AI4 must be connected to signalneutral.

AI5...AI8AI5 Outdoor temperature sensor, for example TG-R6/PT1000.AI6 Supply air temperature sensor, for example TG-K3/PT1000.AI7 Room temperature sensor, for example TG-R5/PT1000.AI8 Frost protection sensor, for example TG-A1/PT1000 when the unit is

configures for water heating.Input for high temperature limiting switch when the controller is configuredfor electric heating. Connect to voltage-free closing contact. (See page 27)

Page 15: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

16Manual CORRIGO C-SERIES 2000.09

DI Digital inputsCORRIGO has 8 digital inputs, DI1...DI8 for activation of certain functions and input ofexternal alarm signals.These inputs may only be wired to voltage-free contacts.These inputs may only refer to the common DI pole on terminal 22.Terminal 22 does not have the same potential as other signal neutrals in theCORRIGO and may not be connected to any other terminals except the DI inputs.Each input can be individually set, either so that closed contact activates thefunction/alarm, or so that open contact activates the function/alarm. See undermenu ”Settings” page 43.

DI1 Input for filter monitor pressure switch(es).If there are several switches these should be wired in parallell.

DI2 Circulation pump indication.Must be wired when CORRIGO is configured for water heating.A stopped pump will force the controller to go into shut down mode.

DI3 Alarm from cooling machine(s).DI4 Rotation sentinel or ice build-up thermostat in plate exchanger.DI5 Fire alarm.DI6 External alarms or external switches not in ”Auto position” (used when

CORRIGO is used with relay module RM6H-24/D or fire damper end positionswitches (for fire damper exercising). Function depends on configurationsettings (see page 30).

DI7 Pushbutton or timer for extended running, single speed fan or high speedwhen using two-speed fans.

DI8 Pushbutton or timer for extended running, low speed when using two-speedfans.Simultaneous closure of both DI7 and DI8 will force the CORRIGO to shutdown.For installations with external switches for fan control, wire according to thefigures below. DI7 and DI8 should then be configured as for timer.See page 31. High speed

Low speed0Auto

DI7

DI8

2-speed fanssingle-speed fans

H0Auto

DI8

DI7

Important!

Page 16: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

17Manual CORRIGO C-SERIES 2000.09

AO Analogue outputsDepending on model, CORRIGO has 3...6 analogue outputs, AO1...AO6.Output signal 0...10 V DC, 5 mA. Short-circuit protected.These outputs should refer to terminal 41, signal neutral.Signal neutral G0, terminal 41, in the CORRIGO is internally connected to sytemneutral on terminal 43.It is therefore important that any actuators sharing the CORRIGO supply transformerare wired with their supply neutral connected to the same transformer pole as theCORRIGO terminal 43.AO1...AO3 is present in all models. These outputs comprise the temperature controlsequence. The output function is dependant on the configuration settings but theactuating order is always Y3 before Y2 before Y1 on increasing heatdemand.AO1 Y1 - Heating or mixing-dampers.AO2 Y2 - Heating, Plate exchanger, Rotating exchanger, liquid-connected

exchanger or cooling.AO3 Y3 - Heating, cooling.AO4 Output signal for supply-air fan speed control.

Models C20 and C40 only.AO5 Output signal for exhaust-fan speed control.

Models C20 and C40 only.AO6 Humidification, dehumidification

Models C30 and C40 only. Function, see page 34.

Page 17: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

18Manual CORRIGO C-SERIES 2000.09

DO Digital outputs

CORRIGO has 7 digital outputs DO1...DO7.DO7, alarm output is a voltage free closing relay contact. 1 A, 24 V AC/DC.The outputs DO1...DO6 are triac controlled, 0.5 A, 24 V AC. Short term 1 A.The triac outputs are paired to common supply terminals for 24 V AC.See figure in the margin.For handling higher voltages or currents, use relay modules RM6-24/D orRM6H-24/D that have been developed for this purpose.Some of the outputs have alternative functions depending on model and con-figuration. For example, this means that, in C10 and C30, DX cooling cannot becombined with control of two-speed fans.

DO1 Start supply-air fan (High speed for 2-speed fan in C10 and C30).DO2 Start exhaust-air fan (High speed for 2-speed fan in C10 and C30).DO3 Control of circulation pump or electric heating interlock.

Must be wired when water heater is used. Stopped pump will force theCORRIGO to shut-down mode.DO3 is normally used for control of the circulation pump. When using electricheating, this is not used. Instead it can often be useful with an output forelectric heating interlock, for example when a step-controller is used tocontrol the heater.Step-controllers often have step-up/step-down time delay functions.This can lead to heating output during the cool-down period or even after thesupply air fan has been shut down which will trip the heater high-limitthermostat.By wiring the heating relays via DO3 the heating output will be shut down assoon as CORRIGO switches from running mode to shutdown mode.When CORRIGO is configured for electric heating DO3 will be active duringnormal running mode and switched off in shut-down mode i.e. even duringthe cool-down period.

DO4 Control of chiller 1 (DX1) orStart supply-air fan, low speed for 2-speed control in C10 and C30.

DO5 Control of chiller 2 (DX2) orStart exhaust-air fan, low speed for 2-speed control in C10 and C30.

DO6 External frost protection interlock or fire damper exercising.Function see page 30, Function DI6/DO6.

DO7 Alarm output relay

567

24 V AC inDO5 out

DO6 out

Page 18: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

19Manual CORRIGO C-SERIES 2000.09

Buttons on the front

Arrow up – move upwards in the menu. In the ”Change” position thebutton is used to INCREASE the value indicated. When the button isheld in a depressed position the function is repeated.

Arrow down – move downwards in the menu. In the ”Change” mode thebutton is used to DECREASE the value indicated. When the button isheld in a depressed position the function is repeated.

This is used to stop an ongoing operation or to move one level upwardsin the menu. The Esc button is also used to move backwards in themenus which contain a number of values, thus it is possible to moveforwards with OK and backwards with Esc.

(enter). Is used to confirm an item in the menu. In the ”Change” modethe button is used to confirm a set value and/or to continue to the nextsetting. Help menus: Press OK and the controller will show anexplanatory text for the menu in question, provided that the menu is notin the ”Change” position.

Alarm – opens the alarm queue. Press this button and active and non-acknowledged alarms will be displayed in the menu window. The LEDfor alarms placed above the alarm button is lit when there are alarms inthe queue. If there are multiple alarms use � and � to move betweenthem. An alarm can be acknowledged by using OK. To abort, press Esc.

Change – Goes over to ”Change” mode. Use this button to changesomething in a menu, for example, a setpoint. You remain in the”Change” mode until you have confirmed the change by means of OKor aborted the operation by means of Esc. If the buttons are notactivated the controller will stop the operation automatically aftera minute or so.

Changing languageCORRIGO is supplied with the script in English. Apart from English, CORRIGO can alsobe set to show Swedish or Nowegian.The language selection function is activated by holding the � button depressedduring power up.The language menu is then shown:

To change language press ! again and the marker will show the current language.Select the desired language by using the arrow buttons. Press OK to acknowlege.When the language has been changed or if no change is to be made, press OKand the controller’s normal menu system will start up.

Esc

OK

Language/Språk English

Page 19: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

20Manual CORRIGO C-SERIES 2000.09

Information series - rolling display

During normal running when the buttons are not in use a series of menu pages isshown.The display alternates between a general display with product description andclock, setpoint/actual temperature, output status for the control outputs Y1,Y2 andY3 and setpoint, actual value and output status for supply air fan and exhaust airfan and sepoint and actual value for the humidity control.The initial display shows the product name, date and time.Program version number By pressing Esc when the gerneral display is active theproduct version number is displayed. For LON-models the 12 digit neuronID-number is also displayedThe information menu is started by leaving the main menu by means of Esc or byleaving the keyboard unused for a ten-minute period. First, the start window will beshown for 10 seconds and then the three displays shown above will alternate atthree-second intervals.

Main menuPress the OK button.The information menu will stop and the main menu will openimmediately.The main menu consists of a number of menu headings and what can be seen anddone is governed by the log-in level of the user, as described below.When the main menu is opened TEMP CONTROL is always displayed at the top ofthe display.

The arrow marker to the left of TEMP CONTROL means that this heading is mar-ked and pressing the OK button opens this menu and shows its submenus.Arrows at the right of the display indicate that there are headings above and belowthe text that is currently being displayed. Move by using the arrow buttons.The main menu has the following headings:

LoginConfiguration Only shown at user level 3Temp ControlPressure control Models C20 and C40 onlyHumidity control Models C30 and C40 onlyRunning modeAI Analogue inDI Digital inAO Analogue outDO Digital outSchedulerAlarm settings Only shown at user level 1 or higherSettings Only shown at user level 2 or higher

* CORRIGO C40 * Mo 990208 1012

Setpoint/Actual20,0°C / 20,0°C

Y1 / Y2 / Y3 0% / 45% / 0%

SF/Setp/Act/Out 275Pa/275Pa/70%

EF/Setp/Act/Out 250Pa/250Pa/60%

Setpoint/Actual50% RH / 48% RH

>Temp control �AI Analogue in �

Page 20: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

21Manual CORRIGO C-SERIES 2000.09

Alarms

When alarms are activated they are displayed in the alarm queue and also as ablinking red light on the display panel on the front of the controller. Certain alarmscannot be traced to one of the 7 LEDs on the panel and therefore have no separatealarm on the front. The alarm lamp above the alarm button always blinks red,however, in the event of an alarm.Alarm queueTo check the alarm queue press the alarm button �. The display will then showactive alarms, the date and time when the alarm became active and the alarmstatus.Alarm status

Blinking ”AL” indicates that the alarm is active and has not beenacknowledged.Steady ”AL” indicates that the alarm is active but has been acknowledged.Blinking ”OK” indicates that the alarm has aborted but has not beenacknowledged.

Acknowledging an alarmAlarms are acknowledged by means of the OK button which will remove the alarmfrom the alarm list. If the alarms are still active they will remain in the alarm list butthe blinking will be replaced by a steady ”AL” and a steady red light on the alarmsignals.

Arrows on the right-hand side show when there are more alarms in the queue.

LoginCORRIGO has four different login levels to prevent the user from inadvertentlychanging any settings.

0 Without logging in all of the most important parameters can be viewed suchas input and output status, alarms in the alarm queue, setpoints etc. Alarmscan also be acknowledged.

1 Main setpoint, time and date can be set. Outputs can be manually set andthe running mode can be set to manually on or off. Other parameters can beread off but not changed.

2 Gives access to most setpoints and running parameters such as outdoorcompensation, control alarm deviations, time delays etc.

3 The highest user level giving total access. Used by the commissioningengineer for system configuration.

Menu informationIf the user attempts to make changes that cannot be made or which lie outside hisuser level the controller will display the following information:

UnauthorisedMake new logon

No changes inthis menu

Alarm chillerAL 980925 14:20

Menu help textThere are extra help-text to most of the menu pages. By pressing the OK button(except when in ”Change mode”) the extra text will be displayed.

Page 21: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

22Manual CORRIGO C-SERIES 2000.09

To log in to another user level.Press � or � until the cursor arrow points at Login. Press OK.The login menu will be displayed.

To log in press � and a marker will be shown on the first digit. Press �� tochange the value.Press OK to move to the next digit. To return to the previous digit press Esc. Afterthe last digit the code is evaluated.The operation can be aborted by means of Esc.If an incorrect code is given an error message is displayed:

The correct code will result in an acknowledging message showing the login level.

After 2 seconds the system automatically returns to the main menu.

Factory set codes

The codes for the three user levels are factory set as follows

User level 1 1111User level 2 2222User level 3 3333

Changing codesThe codes for the three user levels can easily be changed in user level 3.Enter the login menu:

The arrow means that there are menus below, press the arrow until the code forlevel 1, 2 or 3 is displayed.

Change the code using �.The cursor will start on the first digit. Change using thearrow buttons. To move to the next digit press OK. To return to the previous digitpress Esc.By pressing OK after the last digit the code will be registered. To abort use Esc.DO NOT FORGET TO MEMORIZE THE NEW CODES or to write them down. Thisis especially important for user level 3. Should the code for level three be lost thesystem can be opened by means of a code number which can be obtained fromREGIN. This code number is time dependent.

Set your code 0000 Level:0

Incorrect code try again

Login ok Code:0

Set your code 0000 Level:3 �

Code for level1�1111 �

Code for level2�2222 �

Code for level3�3333 �

Important !

Page 22: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

23Manual CORRIGO C-SERIES 2000.09

ConfigurationConfiguration implies the commissioning setting of all the parameters in theCORRIGO. Parameters are set using script.Configuration codesThere is also the option of setting parameters by means of two configuration codes.This function is particularly useful and time-saving when a number of controllers areto be configured in the same way.The first thing to be shown when the configuration menu is opened is the setting ofthe control function.Using the arrow up button the two configuration codes will be displayed and thearrow down button will give the parameters of the other configurations in script.The code digits in the configuration code correspond to the script parameters belowin numerical sequence. This means that the first digit in CONFIG.CODE1determines which control function the controller is to work with. The second digitrefers to heater type etc.Before the corresponding selection in the script parameters there is a digit whichcorresponds to the code number in the configuration code. See the details below.Tables for configuration codeThere is also a special table to facilitate the choice of configuration code. This isalways supplied together with the CORRIGO instruction sheet.In the table all the configuration parameters are shown as well as the selectionsthat can be made. Basic selections are marked in bold type.By going through the parameters and filling in the figures beside the respectiveselections the configuration code can be obtained without difficulty. This can alsoact as a protocol of settings for CORRIGO.Automatic restart after changingWhen one or more parameters have been changed the controller will restart whenthe user leaves the configuration menu.

Control funct. �0 Suppl.air cnt�

Config code 1 �0011.1110.0000 �

Config code 2 �0100.010 �

A Control function0. Supply air control 01. Supply air control with outdoor temperature compensation 12. Room control with cascaded supply air temperature control 23. Room control with min/max limiting of supply air temp. 34. Room control, single sensor 45. Supply air control/Room control. Outdoor temp dependent 56. Not available for Corrigo C40 -

B Heater type0. Water heater 01. Electric heater 1

C Output Y10. Not active 01. Heating 12. Damper 23. Cooling 3

D Output Y20. Not active 01. Plate heat exchanger 12. Rotating heat exchanger 23. Not available for Corrigo C40 -4. Damper 45. Heating 56. Cooling 6

E Output Y30. Not active 01. Cooling 12. Heating 2

F Frost protection (Water heating only)0. Not active 01. Active on Y1 12. Active on Y2 23. Active on Y1 with automatic alarm reset 34. Active on Y2 with automatic alarm reset 4

G Shutdown mode (Water heating only. Requires outdoor sensor)0. No 01. Yes 1

H Pump stop (Water heating only. Requires outdoor sensor)0. No 01. Yes 1

I Function not available for Corrigo C40This code must always be set to 0 0

J DX-cooling0. No 01. 1-step 12. 2-step 23. 3-step binary 3

K Cooling recovery0. No 01. Yes 1

L Free cooling0. No 01. Yes 1

CONFIGURATION-CORRIGO C40 A B C D . E F G H . I J K LConfiguration code 1 . .

Page 23: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

24Manual CORRIGO C-SERIES 2000.09

Configuration settingsSome of the settings are only available on certain models. This because som of theinputs / outputs have different functions in different models.A. CONTROL FUNCTIONB. HEATER TYPEC. SEQUENCE Y1D. SEQUENCE Y2E. SEQUENCE Y3F. FROST PROTECTIONG. SHUTDOWN MODEH. PUMP STOPI. FUNCTION NOT AVAILABLE FOR CORRIGO C40J. ON/OFF-COOLINGK. COOL RECOVERYL. FREE COOLINGM. FUNCTION DI 6 / DO 6N. FIRE ALARMO. FUNCTION DI 7 / DI 8P. FUNCTION NOT AVAILABLE FOR CORRIGO C40Q. FUNCTION NOT AVAILABLE FOR CORRIGO C40R. DAYLIGHT SAVING TIMES. HUMIDITY CONTROLT. BASIC SETTING. Used to reset to factory values.

A. The first question concerns the controller’s control function.To change the parameter press �, the marker appears by the digit. Press � or �to change to another control function. The various functions are described below.When the correct function has been selected, press OK to store.Application examples – flow diagramsIn all the examples below for the various control situations, water heating has beendepicted with frost protection sensor, and electric heating with high temperaturelimiting/thermostat. All examples are drawn with rotating heat exchanger and watercooling. When configuring, the three output control sequences in CORRIGO are setindividually to suit the appropriate application .Supply air temperature controlThe supply-air temperature sensor (AI6) controls the sequences to reach setpoint.

Control funct. �0 Suppl.air cnt�

0. Supply airtemperaturecontrol

Frost protectionsensor

Page 24: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

25Manual CORRIGO C-SERIES 2000.09

Supply air control with outdoor temperature compensationThe temperature sensor Supply Air (AI6) controls the sequences to reach setpoint.The setpoint is compensated with respect to the temperature at outdoor tempera-ture sensor (AI5). Parameters are set in the menu ”Temp control” where menus foroutdoor compensation will become accessible when this selection is made.Outdoor temperature compensation can be set with two breaking points and twoend positions, see the section ”Temp control”.

Room temperature control with cascade control of the supply air temperatureThe temperature sensor Supply air (AI6) controls the sequence so that the setpointis reached in the same way as with supply air control. The setpoint for the supplyair temperature is determined by Room sensor (AI7) which, when heating isrequired, raises the setpoint for supply air according to the parameters set or,when cooling is required, lowers the setpoint.The cascade factor (by how much the setpoint should be changed on a one-degreedeviation from the set room-temperature) is set under ”Temp control”, see theappropriate section.N.B. Cascade control is a PI-control with settable I-time (Factory setting 10 minu-tes) and works with setpoints between set minimum and maximum limitation.(Current setpoint for supply air temperature is shown in the menu for cascadefactor).

1. Supply air tempera-ture control, outdoortemperaturecompensated.

Frost protectionsensor

Supply-air sensor

Room sensor

Frost protectionsensor

Supply-air sensor

2. Room temperaturecontrol, cascadeconnected.

Page 25: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

26Manual CORRIGO C-SERIES 2000.09

3. Room temperaturecontrol with min/maxlimiting

4. Room temperaturecontrol

5. Room/supply airtemperature control

Room-temperature control with min-/max limitation of supply-air temperatureThe room temperature sensor (AI7) controls the sequences so that the setpoint isreached.The supply-air temperature at the sensor (AI6) is kept within the set minimum andmaximum limits.

Room temperature control without supply air sensorThe temperature sensor Room (AI7) controls the sequences so that the setpoint isreached.

Supply air temperature control with outdoor temperature compensation orroom control with min/max limiting. Outdoor temperature dependent switch-overThe outdoor temperature sensor controls the change-over between supply aircontrol (winter) and room control (summer).1) The supply air sensor (AI6) controls the sequences to reach setpoint. The

setpoint is outdoor temperature compensated by means of the outdoor tempera-ture sensor (AI5). Parameters are set under the menu ”Temp. control”.

2) The room sensor (AI7) controls the sequences to reach setpoint. The supply airtemperature (AI6)can be min/max limited. Cooling is prevented from startingwhen the outdoor temperature is low. Parameters are set under ”Settings”.

Frost protectionsensor

Frost protectionsensor

Frost protectionsensor

Supply-air sensor

Supply-air sensor

Room sensor

Room sensor

Room sensor

Outdoor sensor

Page 26: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

27Manual CORRIGO C-SERIES 2000.09

Exhaust air temperature control with minimum/maximum limiting of thesupply air temperatureThe exhaust-air temperature sensor (AI3) controls the sequences to reach setpoint.The temperature at the supply-air sensor (AI6) is kept within the minimum/maxi-mum temperatures set.

B. Setting of heater type0. Water heating.1. Electric heating.

When electric heating has been selected input A18 is set for closingcontact from high temperature limit. The configuration parametersapplicable to water heated circuits: frost protection sensor, shutdownmode, pump stop, are not shown when electric heating is selected.

Wiring suggestion whenusing electric heating.High limit thermostat contactsdrawn unactivated

Frost- protectionsensor

Exhaust-air sensor

Supply-air sensor

6. Exhaust air tempcontrol with min/maxlimiting of the supplyair temperature

Heater type �0 Water heating�

High limitthermostat

Controlrelay

Relayelectric heating

Control voltage

Control voltage

3334 CORRIGO AI8

N.B.Not available for C30 andC40. This since AI3 is thenused as humidity input.

N.B. It is important that the high temperature limit switch is wired to dissconnect the powerto the heater via a relay to ensure that the heating is properly disconnected when the limitswitch is tripped.

Page 27: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

28Manual CORRIGO C-SERIES 2000.09

C. Output sequence Y10 When not in use1. AO1 Heating2. AO1 Damper3. AO1 Cooling

D. Output sequence Y20. When not in use1. AO2 Plate heat exchanger

Means that the output controls e.g. a damper actuator for the heatexchanger bypass duct.DefrostingIce-build up sensor is connected to DI4. On ice build-up the defrostingfunction is activated.-The heat exchanger is set to full bypass and the heating sequence worksprimarily when heating is required. If this is not sufficient to maintain thesetpoint the heat exchanger is permitted to go in with up to 30% of capa-city.-The fans continue operating. If the fans are of the two-speed type they willoperate at low speed while the defrosting function is active.-Defrosting will continue until the ice build-up sensor returns to normal, witha deactivation delay of 10 minutes. If defrosting still is active after 30minutes, the supply air fan will be shut off until the defrosting is completed.

2. AO2 Rot.Heat exchangerAlarm from the rotation sentinel is connected to input DI4.CORRIGO can be set to stop the fans on rotation sentinel alarm.Set under ”Settings”

3. AO2 Liquid connected heat exchangerThe valve is controlled in sequence andthe temperature in the circuit is minimumlimited via the sensor ”Return Exchanger”connected to AI4.

N.B. This function can not be used with theCORRIGO C30 or C40 since there is no inputfor a minimum limiting sensor.

4. AO2 Damper5. AO2 Heater6. AO2 Cooler

E. Sequence Y30. When not in use1. AO3 Cooling2. AO3 Heating

Sequence Y1 �1 AO1 Heating �

Sequence Y2 �1 AO2 Plateexch�

Sequence Y3 �1 AO3 Cooling �

The function of the outputs can be setindividually. The sequence order,however, is always the same: Atincreasing heat requirement Y3 isalways activated first, then Y2 andfinally Y1.

Exhaust air

Supply air

Extract air

Outdoor air

Liquid connected exchanger

Sensor Return ExchPump

Control valve,exchanger

Y1 Y2 Y3

Outputsignal

Temperature

Setpoint

Page 28: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

29Manual CORRIGO C-SERIES 2000.09

F. FROST PROTECTION0. Not active1. Y1 Y1 is forced open on frost risk2. Y2 Y2 is forced open on frost risk3. Y1 Aut Reset Y1 is forced open on frost risk. Automatic reset.4. Y2 Aut Reset Y2 is forced open on frost risk. Automatic reset.The alarm limit for the frost protection sentinel is set under ”Settings”. (Factorysetting is 7°C.) The system begins to override the output signal to the valvewhen the temperature is 5K higher than the alarm limit. This means that thetemperature when the output begins to be affected is 12°C for the factory settingof 7°C.

G. SHUTDOWN MODEControls the heating valve to maintain a preset temperature at the frostprotection sensor when the system is shut down.The function is only activated if the circulation pump output DO3 is active.0. No1. Yes

H. PUMP STOPThe circulation pump is stopped when there is no heating demand and theoutdoor temperature is above a preset temperature. The basic setting is +6°C.Activation delayed 15 minutes. Can be set under ”Settings”.Stopped pump is exercised 5 minutes a day at 12 noon.This function requires an outdoor temperature sensor.0. No1. Yes

I. EFFICIENCY MONITORING Not available for C30 and C40Heat exchanger efficiency is calculated and presented under AI analogue in, onthe last line.The function requires an outdoor sensor on AI5, an extract-air sensor on AI4and, either an exhaust-air sensor on AI3, or a room sensor on AI7. So, if theCORRIGO has been configured for an application with room sensor it is notnecessary to install an exhaust-air sensor. CORRIGO will automatically choose theroom temperature sensor if an exhaust-air sensor has not been installed.At efficiency values <50% and full output on Y2 the alarm ”low efficiency” isactivated.0. No1. Yes

Frostprotection�1 Y1 �

Shutdown mode �0 No �

Pump stop �0 No �

Extract airtemp

Exhaust airtemp

Outdoor temp

Efficiency mon.�0 No �

This function can not becombined with liquidconnected heatexchanger

TExhaust - TExtractη= TExhaus t- TOutdoor

Page 29: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

30Manual CORRIGO C-SERIES 2000.09

K. COOLING RECOVERYThe temperatures at the sensor Outdoor temp (AI5) and the Exhaust air sensor(AI3) are compared.If the exhaust air temperature is a preset number of degrees colder than theoutdoor temperature the heat exchanger or mixing dampers will be set formaximum recovery. A heat exchanger will be set to full capacity and dampers tomaximum recirculation.The value for minimum percentage outdoor air is set under the menu ”Settings”.0. No1. Yes

L. FREE COOLINGIf the night temperature at sensor Room (AI7) exceeds a preset temperature thesupply and exhaust air fans are started to give free cooling. Heating, heatexchange and cooling are not used during free cooling.When two-speed fans have been configured the fans run at high speed duringfree cooling.Other prerequisites are that the outside temperature exceeds the preset value(basic setting +10°C.) to prevent condensation and that the outside temperatureis a preset number of degrees lower than the room temperature (factory setting3K). If this condition is not met, no cooling run will take place.0. No1. Yes

M. FUNCTION INPUT DI6 OCH OUTPUT DO6These can be changed for various functions.0. External alarm + frost protection.

DI6 receives an external alarm. The alarm is presented in the alarm queueas ”External alarm”. DO6 is controlled to be on as long as the frost protectionis in the normal position.When the frost alarm is activated the output is deactivated. This function isused when external switches for manual operation of the fans is desired.

1. Auto + Frost protectionIn this position DI6 receives a signal that external switches are not in theauto position. It is used primarily when the relay module RM6H-24/D withexternal switches is connected to the controller. If any one of the switches isnot in the Auto position the alarm will be given after 5 minutes.

2. Fire damper exerciseDO6 is used to control fire dampers for exercising and testing.Exercising is carried out once every 24 hours at the time set under”Settings”. The basic setting is for 12 midnight.During the exercising the fans will be stopped even if free cooling is active.

Cool recovery �0 No �

Free Cooling �0 No �

Funct. DI6/DO6 �0 Ext.alarm+fro�

J. DX-COOLINGThe outputs DO4 and DO5 are used to control DX chillers in stages.0. No1. 1 stage2. 2 stages3. 3 stages binary

DX Cooling �0 No �

N.B.Can not be combinedwith control of 2-speedfans in models C10 andC30

Page 30: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

31Manual CORRIGO C-SERIES 2000.09

When exercising commences output DO6 isactivated. Then the controller will wait for thedamper’s end position contact to open the input DI6.If the contacts do not open within 5 minutes the alarmwill be given.After opening of the contacts has occured the control-ler will wait for the other set of contacts to closeindicating that all dampers have reached the closedposition. If the contacts do not close within 5 minutesthe alarm will be given.After closing on DI6 has occurred DO6 is deactivatedagain and the controller will wait for the contacts toopen again to input DI6. If the contacts do not openwithin 5 minutes the alarm will be given.After opening of the contacts has occured the control-ler will wait for the other set of contacts to closeindicating that all dampers have once again reachedthe fully open position. If the contacts do not closewithin 5 minutes the alarm will be given.

N. FIRE ALARMThe signal from the fire alarm or smoke detector is connected to DI5.This function is used to set if fans are to continue running or are to be stopped inthe event of alarm.0. Alarm only (the fans continue to run).1. Supply fan + Exhaust fan Stop2. Supply fan Stop3. Exhaust fan Stop

O. FUNCTION DI7 / DI8DI7 and DI8 are used for extended running when the scheduler is deactivated.For single speed fans DI7 is used for extended running.DI7 controls extendedrunning at normal speed while DI8 controls extended running at reduced speed.DI8 also has the following function at both low and high speed;If input DI8 is closed at the same time as DI7 is closed a stop signal will begiven. This function can be used, for example, when an external, commonManual-0-Auto switch is mounted in the cabinet.See wiring suggestion for this type of switch fig.1.When an external switch as in fig.1 is used FUNCTION DI7/8 must beconfigured as ”2 Timer”.

0. This function is not used1. Push button.

Instantaneous closure gives extended running for preset time.(Factory setting 0 min) .

2. TimerExtended running as long as the contact is closed.

Fire alarm �0 Alarm only �

Function DI7/8�0 --- �

Fig 2. Switch for unitwith two speed fans.

Fig 1. Switch for unit withsingle speed fans.

High speedLow speed0Auto

Damper 1Damper 2Damper 3

0° 90°DI6

Terminal22

Damper ..

DO6

DI6

High

HighLow

Low

max 5minutes

max 5minutes

DI7

DI8

Manual0Auto

DI7

DI8

Page 31: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

32Manual CORRIGO C-SERIES 2000.09

P. TWO-SPEED FANS (C10 and C30 only)Cannot be selected when DX-cooling has been configured.When two-speed fans are used the scheduler menu is automaticallycomplemented with periods for low speed running. See under ”Scheduler”.On startup the exhaust air fan will be started first, at low speed. After a presettime the supply air fan will start, at low speed.Should the scheduler or external switches/timer be set for high speed runningthe exhaust air fan will switch to high speed followed by the supply air fan.Highspeed is activated 1 second after low speed has been deactivated.When switching from high speed to low speed both fans are first switched off.After a retardation period of 10 seconds, low speed is activated for both fans.When free cooling is activated both fans run at high speed.The fans can be forced to low-speed at low outdoor temperatures. See underSettings0. No1. Yes

Q. EXTERNAL SETPOINT (C10 and C20 only)When external setpoint is to be used.Set point device TG-R4/Pt1000 is connected to AI4.This function cannot be combined with efficiency monitoring or liquid connectedheat exchanger.0 No1 Yes

R. DAYLIGHT SAVING TIMEThe timer takes account of the spring and autumn time changes that aregenerally implemented according to European rules.Spring: At 02.00 on the last Sunday in March the clock moves forward one hour.Autumn: At 03.00 on the last Sunday in October the clock moves backwardsone hour.If this function is not required set to ”0 No”.

0. No1. Yes

S. HUMIDITY CONTROL (C30 and C40 only)Output AO6 is used for controlling dehumidification, humidification orhumidification in combination with dehumidification by control of the outputAO1...AO3 which is configured as a cooling output.0. Humidification (AO6) / Dehumidification (by control of cooling output

AO1...AO3)1. Humidification (AO6)2. Dehumidification (AO6)

T. BASIC SETTINGUse this function to reset to factory settings. Press the ”change” button, choose”Yes” and confirm with OK.To abort at the ”change” stage, press Esc.All parameters and settings revert to the original factory settings if thecommand ”Basic Settings” is used.This command should only be used by the commissioning engineer.

Two speed fans �0 No �

External setp �0 No �

Daylight saving�1 Yes �

Humidity contr.�0 Humid/dehumid�

Basic setting �No �

N.B Important !

Page 32: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

33Manual CORRIGO C-SERIES 2000.09

Temperature control

In this menu you can look at and set most control values for the temperaturecontrol. See also menu branch ”Settings”.The control function that has been chosen and the selected login level willdetermine which of the following menus can be seen and which parameters can beset.The table shows all the menus and the control functions with which they are shown.

Table of control functions0. Supply air control1. Supply air control with outdoor temperature compensation2. Room temperature control with cascade function of supply air temperature3. Room temperature control with minimum/maximum limiting of supply air

temperature4. Room temperature control without supply air sensor5. Supply air control with outdoor compensation or room temperature control.

Change-over point is outdoor temperature dependent.6. Room temperature control with minimum/maximum limiting of supply air

temperature.

1. Setpoint/Actual temp. Control function 0,2,3,4.2. Calculated setpoint/Actual temp. Control function 1,5,6.3. Output % for Y1,Y2,Y3. Control function 0,1,2,3,4,5,6. If the output is not used this will be shown as —.4. Setpoint Supply air/Compensation. Control function 1,5.5. Setpoint/Actual value of supply air. Control function 2.6. Setpoint Room/Change-over temp. Control function 5.7. Minimum/Maximum limiting. Control function 2,3,5,6.8. P-band/I-time/Neutral zone. Control function 0,1,2,3,4,5,6.9. Room P-band/I-factor. Control function 5

These factors set the P-band and I-time for the room temperature controllerin control function 5. They are multiplication factors applied to theequivalent parameters set for supply air control in menu 8 above.

10. Cascade factor/I-time. Control function 2.11. Outdoor temperature compensation. Breakpoint 1. Control function 1,5.12. Outdoor temperature compensation. Breakpoint 2. Control function 1,5.13. Outdoor temperature compensation. Breakpoint 3. Control function 1,5.14. Outdoor temperature compensation. Breakpoint 4. Control function 1,5.

The breakpoints must be placed with 1 lowest and4 highest.For each point both the temperature andcompensation in degrees has to be set.

For temperatures lower than point 1 and higherthan point 4 the compensation is constant andequal to the value set for these points.

Setpoint/Actual� 20.0°C/20.0°C�

1

2 3

4

Setpoint

Outdoor temp

Page 33: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

34Manual CORRIGO C-SERIES 2000.09

Pressure control

In this menu you can look at and set most control values for the pressure control.See also menu branch ”Settings”.The control function that has been chosen and the selected login level willdetermine which of the following menus can be seen and which parameters can beset.The table shows all the menus and the control functions with which they are shown.

1 SF Setp/Act/Out. Setpoint/Actual pressure/output status for the supply airfan control signal. Setpoint can not be changed in this menu.

2. EF Setp/Act/Out. Setpoint/Actual pressure/output status for the exhaust airfan control signal. Setpoint can not be changed in this menu.

3. Setpoint SF/EF. Menu for setting the desired supply air and exhaust airpressures for normal air flow.

4. Reduced SF/EF. Menu for setting the desired supply air and exhaust airpressures for reduced air flow.

5. SF P/I/D. Control parameters P-Band, I-Time and D-Factor for the supplyair fan control.

6. EF P/I/D. Control parameters P-Band, I-Time and D-Factor for the exhaustair fan control.

7. Outdoor temperature compensation. Breakpoint 1.8. Outdoor temperature compensation. Breakpoint 2.9. Outdoor temperature compensation. Breakpoint 3.10. Outdoor temperature compensation. Breakpoint 4.

The breakpoints must be placed with 1lowest and 4 highest.For each point both the outdoor temperatureand compensation in Pa (+/-) has to be set.All breakpoints have factory set values thatcan easily be changed if necessary.For temperatures lower than point 1 andhigher than point 4 the compensation isconstant and equal to the value set for thesepoints.

SF Setp/Act/Out�200Pa/190Pa/90%�

Humidity control

In this menu all the parameters for the humidity control can be set and are dis-played.

1. Setpoint / Actual valueSetpoint and actual value for the room humidity sensor (main sensor).

2. Maximum limit / Actual valueSetpoint and actual value for the duct humidity sensor (limiting sensor).

3. Humidification / DehumidificationOutput status for humidification and dehumidification signals.

4. P-band / I-time.Humidity control control parameters.

C30 and C40 only

Setpoint/Actual� 55%RH/ 54%RH �

C20 and C40 only

1

2 34

Setpoint pressure

Outdoor temperature

Example, compensation curve

Page 34: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

35Manual CORRIGO C-SERIES 2000.09

Running mode

In this menu the unit’s running mode can be seen and set to manual control.On the left the display shows Auto/Manual and on the right the present runningmode.The running modes AUTO/NORMAL/REDUCED/OFF can be set. In the normalAUTO position the running mode is set by the scheduler or by input signals on DI7/DI8 for extended running.If the setting is not reset to AUTO mode within 15 seconds an alarm will beactivated.

AI Analogue inputs

In this menu the current input values on the analogue inputs are displayed.AI1 Supply-air fan pressure.

C10 and C30 display On or Off, C20 and C40 display the current pressure.AI2 Exhaust-air fan pressure.

C10 and C30 display On or Off, C20 and C40 display the current pressure.The inputs AI1 and AI2 must be wired to pressure transmitters (C20 andC40), pressure switches or other free contacts (C10 and C30) that areclosed when the fans are running since they control functions vital to therunning of CORRIGO.

AI3 Exhaust air temperature (C10 and C20) orRoom humidity sensor. (Main sensor) (C30 and C40).

AI4 Extract air temperature (C10 and C20) orDuct humidity sensor. (Limiting sensor) (C30 and C40).

AI5 Outdoor temperature sensorAI6 Supply air temperature sensorAI7 Room temperature sensorAI8 Frost protection sensor For water heating when frost protection has been

chosen orHigh temperature limit. When electric heating has been chosen.

Adjustment of sensor input valuesThe values displayed for the inputs AI1 to AI8 can be changed by +/- 2.0 units.Log in to user level 3, go the the applicable sensor input AI3 to AI8, press �.Adjust the display value using � or �. When completed, confirm using OK.Bear in mind that CORRIGO is always supplied with factory calibrated inputs. Thisapplies also to sensor inputs thus no adjustment is normally necessary.In rare cases where,for example, long sensor leads give incorrect readings,however, the option to make adjustments is available. Be sure to measure thetemperature at the sensor with a reliable and carefully calibrated measuringinstrument and to check that the temperature at the sensor is stable at the time ofmeasurement.Damping of sensor input valuesA damping factor can be set individually on any of the inputs if the readings showdisturbing fluctuations. Set under the menu ”Settings”. See page 43.Show min/max valuesShow Min/Max-temperatures for AI3...AI8. The lowest and highest valuesencountered since the last activation of the function are stored and will be displayedfor each input. To reset and start a new logging, press � and then confirm with OK.Both values will be set to the present input value.

Running mode �Auto / On �

Can be read withoutlogging in.Can be changed fromuser level 1 and higher.

Page 35: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

36Manual CORRIGO C-SERIES 2000.09

DI Digital inputsDI1 Filter guard (s) (Pressure switch monitoring the pressure drop across a filter)

If there are several filter guards they should be wired in parallelDI2 Run indication for water circulation pump

Must be connected when water heating is used. Pump standstill will preventthe system from running

DI3 Alarm input from chiller (-s)DI4 Rotation sentinel or heat exchanger ice build-up sentinelDI5 Fire alarmDI6 External alarm, external switches ”not in Auto position” or end position

switches in fire dampers (for fire damper exercising)DI7 Pushbutton or timer for extended running at normal speedDI8 Pushbutton or timer for extended running at reduced speed

AO Analogue outputsIn this menu the current configurations and outputs for the analogue outputs areshown. The outputs are shown both in V DC and in %.AO1 Y1 - Heating, cooling or mixing dampersAO2 Y2 - Heating, plate exchanger, rotating exchanger, liquid connected

exchanger or coolingAO3 Y3 - Heating or coolingAO4 Output signal for supply air fan pressure control (C20 and C40 only)AO5 Output signal for exhaust air fan pressure control (C20 and C40 only)AO6 HumidIfication or dehumidification (C30 and C40 only)

The outputs AO1....AO3 can also be set to -, indicating that they are not in use.

DO Digital outputsDO1 Start supply-air fan (High speed for 2-speed fan in C10 and C30).DO2 Start exhaust-air fan (High speed for 2-speed fan in C10 and C30).DO3 Control of circulation pump or electric heating interlock.

Must be wired when water heater is used. Stopped pump will force theCORRIGO to shut-down mode.

DO4 Control of chiller 1 (DX1) orStart supply-air fan, low speed for 2-speed control in C10 and C30.

DO5 Control of chiller 2 (DX2) orStart exhaust-air fan, low speed for 2-speed control in C10 and C30.

DO6 External frost protection interlock or fire damper exercising.Function see page 36, Function DI6/DO6.

DO7 Alarm output relay

Page 36: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

37Manual CORRIGO C-SERIES 2000.09

Setting outputs manually

Both digital and analogue outputs can be set to manual mode for testing and fortemporary running.

1. Analogue outputsTo set to manual mode press � and change to HAND using � or �.Then press OK and confirm, then change the output value using the arrowbuttons. Confirm the setting using OK.To revert to normal running mode press � again and change to AUTOusing � or �. Confirm using OK.If the setting is not reset to the AUTO mode within 15 seconds, an alarmwill be activated.

2. Digital outputsTo set to manual mode press � and change to the desired mode ON orOFF using � or � . Then press OK and confirm.To return to normal running mode press � again and change to AUTOusing � or �. Confirm using OK.If the setting is not reset to the AUTO mode within 15 seconds, an alarmwill be activated.

AO1 Heating �AUTO/ 50%/5.0 V�

DO1 SFAUTO OFF �

Page 37: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

38Manual CORRIGO C-SERIES 2000.09

SchedulerCORRIGO has a year-base clock. This means that a week-schedule, individualholidays and holiday periods for a full year can be set.

1. Clock Accessible from user level 1.Here weekday, date and time are set.

2. Scheduler period 1,2,3. Accessible from user level 2.

For setting week-schedule. CORRIGO has 3 setting periods for week-schedule.Select using � . Use � or � to determine whether or not the day displayedis to be included in the required week-schedule. When the first day has beenselected/rejected confirm the setting using OK. The marker will then move onto the next day which is set in the same way, using the arrow buttons andconfirming with OK. Move through all the settings in the menu using OK andselect those required.The letter H signifies Holiday. This is set by means of the date settings.Periods 2 and 3 are used if separate running times for other days arerequired.Example: The system is to be running Monday to Friday from 07.00 till 17:00and Saturday from 8.00 till 13.00.Do as follows: Set period 1 to: and period 2 to:

Using an external clockfunctionIf the CORRIGO is to be used with an external clock instead of the internal oneall periods must be set to zero according to the following example.

3. Reduced 1, 2, 33 periods for programming reduced speed running will be displayed.Setting and function as described above but for reduced speed running.If the set times for normal running and reduced speed running overlap,normal speed running will be chosen.

ClockTh 980925 14:25�

Period 1 08:00�MTWTF___ -17:00�

Period 1 07:00�MTWTF___ -17:00�

Period 1 08:00�_____S__ -13:00�

Period 1 00:00�________ -00:00�

Reduced1 17:00�MTWTF___ -18:30�

Page 38: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

39Manual CORRIGO C-SERIES 2000.09

Holiday 1 / 2 �980101 / 980101�

Holiday period �980101 - 980101�

4. Dates for holidays. Accessible from user level 2.A total of 10 individual holidays can be selected.Running time during a holiday is set by programming the day H into one ofthe three scheduler periods. If the system is to be closed down during aholiday no setting will be necessary for that holiday scheduler period.

5. Holiday periods. Accessible from level 2 and up.For longer holiday periods, e.g. the Christmas break, Summer holidays etc.the first and last dates of the period are set. Set the running times in the timeperiod 1,2, or 3 above for the days that the holiday programme is to apply. Ifthe system is to be closed down during a holiday no setting of scheduleperiod will be necessary.

Page 39: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

40Manual CORRIGO C-SERIES 2000.09

Alarm settings

Here all settings for the alarm system are set including alarm parameters, delays,suppression times etc.1. Temperature deviation alarm

Should the actual temperature differ from the setpoint by more than the setvalue an alarm will be activated after a set time.

2. Outdoor temperature range within which the temperature deviationalarm can be activatedTo prevent alarms when the outdoor temperature leads to conditions beyondthe system capacity.Example: If a system for supply air control does not have cooling an alarmwill be given when the outside temperature exceeds 20 to 25 degrees sincethe temperature cannot be reduced. To avoid a ”false” alarm the uppertemperature limit is set at 20 degrees in this case. The same is true at theother extreme. If the outside temperature should fall below the set tempera-ture a ”false” alarm can be avoided by setting the lowest outside tempera-ture limit to this temperature.N.B. This function is not available unless an outdoor sensor is connected toCORRIGO.

3. Pressure deviation alarm (C20 and C40 only)Should the actual pressure differ from the setpoint by more than the set valuean alarm will be activated after a set time.

4. Alarm suppression Supply air fanA fan pressure deviation alarm is suppressed by a set time to avoid thealarm stopping the fan during start up before the pressure has reached thenormal level.

5. Alarm suppression Exhaust air fanAs for supply air fan above

6. Alarm output suppressionThe alarm output relay can be blocked so that unprioritised alarms will onlybe forwarded during the set time and not during the night or weekends, forexample. Outside the set period only frost alarm, high temperature alarm andfire alarm will activate the alarm relay.Set the times in this menu when alarms are forwarded to the alarm relayoutput.Example: An alarm is only to activate the alarm output between 08.00 and17.00, Monday to Friday. The setting will be as follows:

N.B. Even if the alarm output is blocked the alarm will be registered andindicated by the red flashing alarm diode and the alarm list menus willfunction as normal.

Temp.dev. alarm�5.0K / 2 min �

Outd.Temp range� 20.0°C/-20.0°C�

Press.dev.alm �50 Pa / 2 min �

Alarm delay SF �30 sec �

Alarm delay EF �30 sec �

Alarm out 08:00�MTWTF___ -17:00�

Page 40: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

41Manual CORRIGO C-SERIES 2000.09

7. Stop on alarm from rotating heat exchangerAn alarm from a rotating heat exchanger can initiate a complete stop of theunit.This to prevent running at too low a temperature. Heat exchangermalfunction can also lead to unneccessarily high running costs which isavoided by stopping the unit when an alarm is indicated on input DI4.The function is only available if rotating heat exchanger has been configured.

Alarms -Overview

Operational failure Supply air fan AI1Operational failure Exhaust air fan AI2Operational failure, pump DI2 With water heaterFrost protection AI8 With water heaterHigh temperature limit AI8 With electric heaterFire alarm DI5Fire damper DI6Rotation sentinel, heat exchanger DI4Chiller DI3External alarm DI6 When DI6 is configured

for external alarmSensor failure AI3-AI8Temperature deviationPressure deviationOutput in manual modeManual running modeSwitch not in Auto mode DI6 When DI6 is configured

for this, external switch.

Stop Exch alarm�No

Page 41: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

42Manual CORRIGO C-SERIES 2000.09

SettingsThis menu contains various settings that are normally only set at the comissioningof the CORRIGO.Which alternatives are shown depends on the model and the configuration settings.1. Setpoint, frost protection function.

Only when water heating with frost protection has been configured.See alsopages 27 and 29.Factory setting 7°C. Range 0...60°C.

2. Setpoint shutdown control.Only when water heating with frost protection has been configured.See alsopages 27 and 29.Factory setting 25°C. Range 0...60°C.

3. Pump stop.Only when water heating has been configured. Outside temperature abovewhich the pump is permitted to stop with no heating requirement, i.e. output heatis less than 1%. Delay time for the pump can also be set.Factory setting 6°C. and 15 minutes. Range 0...20°C. and 0...60 min.

4. Supply air fan run on time for cooling electric heater.Only if electric heating has been configured.Factory setting 120 sec. Range 0...180 sec.

5. Supply air fan delay at normal start up. Period for which heat exchanger is to runat 100% at start up.Startup is normally done with only the exhaust-air fan running. With C20 andC40 the fan will be running at reduced flow. With C10 and C30 the fan will berunning at low speed it two-speed running has been configured, otherwise atnormal speed. After the set time the supply-air fan is started at reduced flowlevel(C20 and C40)/ low speed (C10 and C30) if two-speed running has beenconfigured. If the fans shall run at normal speed the exhaust-air fan will nowswitch to normal speed and 5 seconds later also the supply-air fan.If any of the temperature control outputs has been configured as heatexchanger, this output will at startup be set to 100%, that is to maximum heatexchange, for the set time. The other outputs will be held at 0 % output until thesupply-air fan is started. If a cooling demand is at hand, the cooling output willnot be activated until the exchanger startup period has run out.Factory setting 60 sec. and 90 sec. Range 0...180 sec. and 0...600 sec.

6. Extended running. When set for DI7/DI8 using pushbutton. See page 30.Sets required running time after using push button. The function is not additivei.e. multiple pressings of the button will not give longer running time.Factory setting 0 min. Range 0...180 min.

7. P-band Y2,Y3. Factor of P-band for Y1.Multiplication factor compared to the proportional band set for output Y1.Does not normally need setting. Option available for plants where controlenhancement for respective devices are different.Factory setting 0.5 / 0.5. Range 0...10 and 0...10

8. Minimum fresh air percentage when using mixing dampers on Y1 or Y2.See page 30.Factory setting 0%. Range 0...100%.

9. Free cooling. Lowest outdoor temperature and differential between room andoutside temperature. See page 30.Factory setting 10°C. and 3K. Range 0...30°C and 0...10K.

10.Free cooling. Setpoint for room temperature. See page 30.Factory setting 21°C. Range 0...30°C.

11.Cooling recovery. Differential outdoor temperature/room temperature.See page 30.Factory setting 2K. Range 0...60K.

Page 42: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

43Manual CORRIGO C-SERIES 2000.09

Diode Text Function yellow Function red1 SF Supply fan on SF error2 EF Exhaust fan on EF error3 Pump Pump on Pump error4 Y1 Output Y1 Over temp limit

Heating or frost protection5 Y2 Output Y2 Alarm

Exch Blinks on defrost Heat exchanger6 Y3 Cool Output Y3 Alarm chiller7 Filter --- Filter alarm

Alarm -- --- Alarm active

LED’sThe LEDs are connected to the functions of certain in- and outputs. Normal runningindication is yellow. A red LED signifies an error. From the text strip, cut out a partthat suits the programmed configuration. Insert the strip through the rectangular slotabove the text windows to the left of the LEDs.

12.DX cooling. Minimum on and off times. See page 30.Factory setting 5 min. and 5 min. Range 0...90 min and 0...90 min.

13.Lowered minimum limit by DX cooling. See page 30.For control configurations with minimum limiting of the supply-air temperature(control functions 2, 3, 5 and 6) the minimum limit temperature will be loweredby the set number of degrees when the cooling is activated. This is to reducethe risk of the minimum limit causing a premature stopping of the cooling.Factory setting 5 K. Range 0...15K.

14.DX cooling.Minimum outdoor temperature.Control function 5 only. At outdoor temperature lower than the set value the DX-cooling outputs will not be activated.Factory setting 12 K. Range 0...30°C.

15.Time for fire damper exercise.Factory setting 12 midnight. Can be set at any given time during the day ornight.

16.Min. temp and P-band for liquid connected exchangerFactory setting 2°C and 5K Range 0...10°C and 0...5K

17.Force low speed on fans when outdoor temp. is lower than set value.Factory setting Yes / -10 °C. Range Yes/No and -30...+10°C

18.Range SF/EF. Pressure range for SF and EF pressure transmittersFactory setting 500/500 Pa. Range 0....1000Pa

19.Damping factor, Analogue inputs AI1...AI8Factory setting 1. Range 1...10

20.Inversion of function for digital inputs DI1...DI8Factory setting +. (Closed contact activates function/alarm)

21.Show Min/Max-temperatures for AI3...AI8. The lowest and highest valuesencountered since the last activation of the function are stored and will bedisplayed for each input under the menu Analogue in.Factory setting No. Range Yes or No

Page 43: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

44Manual CORRIGO C-SERIES 2000.09

Relay modules for digital outputs

CORRIGO has digital outputs DO1 to DO6 carrying 24 V AC with up to 0.5 A.If higher voltage and/or capacity is required, relay module RM6-24/D orRM6H-24/D can be used.Model RM6-24/D contains 6 relays with change-over relays 10A / 230V AC.Model RM6H-24/D is as RM6-24/D but also has manual switches on the front,MANUAL-0-AUTO.When the relay module RM6H-24/D with manual switch is used in conjunction withCORRIGO, output DU6 must be configured for frost protection output and DI6 toreceive the alarm ”switch not in AUTO-mode”. The switch for DU6 on the relaymodule must always be in the AUTO mode.

Model RM6H-24/DModel RM6-24/D

Relay modules

RM6-24/DRelay unit intended for direct connection to CORRIGO

Supply voltage 24V AC +/- 15%Consumption 3VAAmbient temperature 0-50 deg.C.Storage temperature -40 - +50 deg.C.Ambient humidity Maximum 90% RHDimensions (w x h x d) 105 x 110 (incl.terminal) x 59 mmProtection class IP20, for front mounting IP40Mounting On a DIN-rail in a cabinet or normal housing.

On cabinet front using mounting kit FMC.Connections Disconnectable terminal stripsInputs 6 in number, 24V AC from digital outputs on CORRIGOOutputs 6 in number, potential free change-over contacts

10 A / 230 V AC.

RM6H-24/DRelay unit as above but with 6 Manual-0-Auto switches.The unit is 70 mm deep including the switches.

This product conforms with the requirements of Euro-pean EMC standards CENELEC EN 50081-1 and EN50082-1 and carries the CE mark.

This product conforms with the requirements ofEuropean LVD standards IEC 669-1 and IEC 669-2-1.

Page 44: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

45Manual CORRIGO C-SERIES 2000.09

Wiring diagrams for relay modules

112

58 105

232425262728293031

2221201918171615

DO3NONC

DO4NONC

DO5NONC

NCNO

DO2NCNO

DO1NCNO

32 DO6

1234567891011

DO1C1/2DO2DO3C3/4DO4DO5C5/6DO6

121314

24V~24V~

10A 250 V ~R

M6-24/D

1312111098765

DO1C1/2DO2DO3C3/4DO4DO5C5/6DO6

Corrigo

232425262728293031

2221201918171615

DO3NONC

DO4NONC

DO5NONC

NCNO

DO2NCNO

DO1NCNO

32 DO6

1234567891011

DO1C1/2DO2DO3C3/4DO4DO5C5/6DO6

121314

24V~24V~

10A 250 V ~

1312111098765

DO1C1/2DO2DO3C3/4DO4DO5C5/6DO6

Corrigo

1622

DI6DI+

AutoAuto

RM

6H-24/D

Page 45: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

46Manual CORRIGO C-SERIES 2000.09

Commissioning protocol

Configuration Factory setting Commissioning settingConfig.code 1 0011.1110.0000 ____._____._____Config.code 2 0100.010 ____._____A. CONTROL FUNCT. 0 Supply air control _______________B. HEATER TYPE 0 Water heater _______________C. SEQUENCE Y1 1 Heating _______________D. SEQUENCE Y2 1 Plate-exchanger _______________E. SEQUENCE Y3 1 Cooling _______________F. FROST PROTECTION 1 Y1 _______________G. SHUTDOWN MODE 1 Yes _______________H. PUMP STOP 0 No _______________I. EFF MONITORING 0 No _______________J. DX-COOLING 0 No _______________K. COOLING RECOVERY 0 No _______________L. FREE COOLING 0 No _______________M. FUNCT. DI6/DU6 0 Ext.alarm+frost prot. _______________N. FIRE ALARM 1 SF+EF Stop _______________O. FUNCTION DI7/DI8 0 --- _______________P. 2-SPEED FANS 0 No _______________Q. EXTERNAL SETPOINT 0 No _______________R. DAYLIGHT SAVING 1 Yes _______________S. HUMIDITY CONTROL 0 Humidif/Dehumidification _______________BASIC SETTING No Used to reset to factory settings

Control TempSetpoint / Actual 20.0 _______________Min.limit / Max.limit 10.0°C / 30.0°C ________ / _____PBand / Itime / Nz 20K / 60s / 2K _____/_____/____Room P/I Factor 0.5 / 2.0 _______________Casc.f / Itime 2.0 / --- _______________Setp.Room/ Outdoor temp 22.0 / 12.0 _______________Outdoor comp. point 1 -20°C / 0.0°C _______________Outdoor comp. point 2 20°C / 0.0°C _______________Outdoor comp. point 3 25°C / 0.0°C _______________Outdoor comp. point 4 30°C / 0.0°C _______________

Control PressureSetpoint SF/EF 300 / 300Pa ________ / _____Reduced SF/EF 200 / 200Pa ________ / _____SF P / I / D 200Pa / 60s / 0.0 _____/_____/____EF P / I / D 200Pa / 60s / 0.0 _____/_____/____Outdoor comp. point 1 -20°C / 0Pa _______________Outdoor comp. point 2 20°C / 0Pa _______________Outdoor comp. point 3 25°C / 0Pa _______________Outdoor comp. point 4 30°C / 0Pa _______________

Control HumiditySetpoint / Actual --- ________/______Max.limit / Actual 80%RH / --- _______ / ______PBand / Itime 40%RH / 60s _______/_______

Installation

System

Commiss. date Commiss. by Page 1

C10 and C20 only

C10 and C30 only

C10 and C20 only

C30 and C40 only

C20 and C40 only

C30 and C40 only

Page 46: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

47Manual CORRIGO C-SERIES 2000.09

Commissioning protocol

Scheduler Factory setting Commissioning settingPeriod 1 MTWTF 08:00-17:00 _______________Period 2 _______________Period 3 _______________Reduced speed 1 _______________Reduced speed 2 _______________Reduced speed 3 _______________Holidays 980101 _______________Alarm settings1. Temp deviation alarm 5K och 2 minutes ______________2. Outdoor temp interval within which

temp deviation alarm is active 20...-20°C _______________3. Pressure deviation alarm 50Pa / 2 minutes _______________4. Alarm delay, supply air fan 30 seconds _______________5. Alarm delay, exhaust air fan 30 seconds _______________6. Alarm output active Mo-Su 00:00 - 24:00 _______________7. Stop on exchanger alarm No _______________Settings1. Setpoint frost protection 7°C _______________2. Setpoint shut-down mode 25°C _______________3. Pump stop. Min outdoor temp, 6°C _______________

start- stop delay 15 minutes _______________4. Cool-down (electric heating) 120 seconds _______________5. Delay supply air fan 60 seconds _______________

time with 100% Exch. at start 90 seconds _______________6. Extended running.Pushbutton 0 minutes _______________7. P-band Y2,Y3. Factor 0,5 / 0,5 _______________8. Min outdoor air, mix. damper Y2 0 % _______________9. Free cooling. Min outdoor temp10°C _______________

difference outdoor/indoor 3 K _______________10.Free cooling. Setpoint room 21°C _______________11.Cooling recovery.

Diff outdoor-/exhaust air temp 2 K _______________12.DX-cooling. Min. on-/off-times 5 min. and 5 min. _______________13.DX-cooling. Lowered min.lim. 5 K _______________14.DX-cooling. Min. outdoor temp. 12°C _______________15.Starttime damper exercising. 00:00 _______________16.Min-temp and P-band, liquid conn. exch. 2°C and 5K _______________17.Force fan low speed

on low outdoor temp Yes / -10 °C _______________18.SF/EF pressure range 500/500 Pa _______________19.Damping factor AI1...AI8 1 _/ _/ _/ _/ _/ _/ _/_20.Function DI1...DI8 + _/ _/ _/ _/ _/ _/ _/_20.Show Min/Max-temp AI3...AI8 No _______________

Installation

System

Commiss. date Commiss. by Page 2

Page 47: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

48Manual CORRIGO C-SERIES 2000.09

CONFIGURATION- Corrigo C10 A B C D . E F G H . I J K LConfiguration code 1 . .

A Control function0. Supply air control 01. Supply air control with outdoor temperature compensation 12. Room control with cascaded supply air temperature control 23. Room control with min/max limiting of supply air temp. 34. Room control, single sensor 45. Supply air control/Room control. Outdoor temp dependent 56. Exhaust air control with min/max limit of supply air temp 6

B Heater type0. Water heater 01. Electric heater 1

C Output Y10. Not active 01. Heating 12. Damper 23. Cooling 3

D Output Y20. Not active 01. Plate heat exchanger 12. Rotating heat exchanger 23. Liquid connected heat exchanger 34. Damper 45. Heating 56. Cooling 6

E Output Y30. Not active 01. Cooling 12. Heating 2

F Frost protection (Water heating only)0. Not active 01. Active on Y1 12. Active on Y2 23. Active on Y1 with automatic alarm reset 34. Active on Y2 with automatic alarm reset 4

G Shutdown mode (Water heating only)0. No 01. Yes 1

H Pump stop (Water heating only. Requires outdoor sensor)0. No 01. Yes 1

I Efficiency monitoring0. No 01. Yes 1

J DX-cooling0. No 01. 1-step 12. 2-step 23. 3-step binary 3

K Cooling recovery0. No 01. Yes 1

L Free cooling0. No 01. Yes 1

Page 48: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

49Manual CORRIGO C-SERIES 2000.09

CONFIGURATION- Corrigo C10 M N O P . Q R SConfiguration code 2 . 0

M Function DI6/DO60. External alarm & frost protection 01. Auto position & frost protection 12. Fire damper exercising

N Fire alarm0. Alarm only 01. Alarm + supply air and exhaust air fans stop 12. Alarm + supply air fan stops 23. Alarm + exhaust air fan stops 3

O Function DI7/DI80. Not active 01. Pushbutton 12. Timer 2

P 2-speed fans (Can not be combined with DX-cooling)0. No 01. Yes 1

Q External setpoint0. No 01. Yes 1

R Daylight saving time0. No 01. Yes 1

S This function is not available for Corrigo C10The code must always be set to 0 0

Page 49: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

50Manual CORRIGO C-SERIES 2000.09

CONFIGURATION- Corrigo C20 A B C D . E F G H . I J K LConfiguration code 1 . .

A Control function0. Supply air control 01. Supply air control with outdoor temperature compensation 12. Room control with cascaded supply air temperature control 23. Room control with min/max limiting of supply air temp. 34. Room control, single sensor 45. Supply air control/Room control. Outdoor temp dependent 56. Exhaust air control with min/max limit of supply air temp 6

B Heater type0. Water heater 01. Electric heater 1

C Output Y10. Not active 01. Heating 12. Damper 23. Cooling 3

D Output Y20. Not active 01. Plate heat exchanger 12. Rotating heat exchanger 23. Liquid connected heat exchanger 34. Damper 45. Heating 56. Cooling 6

E Output Y30. Not active 01. Cooling 12. Heating 2

F Frost protection (Water heating only)0. Not active 01. Active on Y1 12. Active on Y2 23. Active on Y1 with automatic alarm reset 34. Active on Y2 with automatic alarm reset 4

G Shutdown mode (Water heating only. Requires outdoor sensor)0. No 01. Yes 1

H Pump stop (Water heating only. Requires outdoor sensor)0. No 01. Yes 1

I Efficiency monitoring0. No 01. Yes 1

J DX-cooling0. No 01. 1-step 12. 2-step 23. 3-step binary 3

K Cooling recovery0. No 01. Yes 1

L Free cooling0. No 01. Yes 1

Page 50: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

51Manual CORRIGO C-SERIES 2000.09

CONFIGURATION- Corrigo C20 M N O P . Q R SConfiguration code 2 0 . 0

M Function DI6/DO60. External alarm & frost protection 01. Auto position & frost protection 12. Fire damper exercising

N Fire alarm0. Alarm only 01. Alarm + supply air and exhaust air fans stop 12. Alarm + supply air fan stops 23. Alarm + exhaust air fan stops 3

O Function DI7/DI80. Not active 01. Pushbutton 12. Timer 2

P Function not available for Corrigo C20This code must always be set to 0 0

Q External setpoint0. No 01. Yes 1

R Daylight saving time0. No 01. Yes 1

S This function is not available for Corrigo C20The code must always be set to 0 0

Page 51: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

52Manual CORRIGO C-SERIES 2000.09

CONFIGURATION- Corrigo C30 A B C D . E F G H . I J K LConfiguration code 1 . . 0

A Control function0. Supply air control 01. Supply air control with outdoor temperature compensation 12. Room control with cascaded supply air temperature control 23. Room control with min/max limiting of supply air temp. 34. Room control, single sensor 45. Supply air control/Room control. Outdoor temp dependent 56. Not available for Corrigo C30 -

B Heater type0. Water heater 01. Electric heater 1

C Output Y10. Not active 01. Heating 12. Damper 23. Cooling 3

D Output Y20. Not active 01. Plate heat exchanger 12. Rotating heat exchanger 23. Not available for Corrigo C30 -4. Damper 45. Heating 56. Cooling 6

E Output Y30. Not active 01. Cooling 12. Heating 2

F Frost protection (Water heating only)0. Not active 01. Active on Y1 12. Active on Y2 23. Active on Y1 with automatic alarm reset 34. Active on Y2 with automatic alarm reset 4

G Shutdown mode (Water heating only. Requires outdoor sensor)0. No 01. Yes 1

H Pump stop (Water heating only. Requires outdoor sensor)0. No 01. Yes 1

I Function not available for Corrigo C30This code must always be set to 0 0

J DX-cooling0. No 01. 1-step 12. 2-step 23. 3-step binary 3

K Cooling recovery0. No 01. Yes 1

L Free cooling0. No 01. Yes 1

Page 52: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

53Manual CORRIGO C-SERIES 2000.09

CONFIGURATION- Corrigo C30 M N O P . Q R SConfiguration code 2 . 0

M Function DI6/DO60. External alarm & frost protection 01. Auto position & frost protection 12. Fire damper exercising

N Fire alarm0. Alarm only 01. Alarm + supply air and exhaust air fans stop 12. Alarm + supply air fan stops 23. Alarm + exhaust air fan stops 3

O Function DI7/DI80. Not active 01. Pushbutton 12. Timer 2

P 2-speed fans (Can not be combined with DX-cooling)0. No 01. Yes 1

Q Function not available for Corrigo C30This code must always be set to 0 0

R Daylight saving time0. No 01. Yes 1

S Humidity control0. Humidification / Dehumidification 01. Humidification 12. Dehumidification 2

Page 53: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

54Manual CORRIGO C-SERIES 2000.09

CONFIGURATION- Corrigo C40 A B C D . E F G H . I J K LConfiguration code 1 . . 0

A Control function0. Supply air control 01. Supply air control with outdoor temperature compensation 12. Room control with cascaded supply air temperature control 23. Room control with min/max limiting of supply air temp. 34. Room control, single sensor 45. Supply air control/Room control. Outdoor temp dependent 56. Not available for Corrigo C40 -

B Heater type0. Water heater 01. Electric heater 1

C Output Y10. Not active 01. Heating 12. Damper 23. Cooling 3

D Output Y20. Not active 01. Plate heat exchanger 12. Rotating heat exchanger 23. Not available for Corrigo C40 -4. Damper 45. Heating 56. Cooling 6

E Output Y30. Not active 01. Cooling 12. Heating 2

F Frost protection (Water heating only)0. Not active 01. Active on Y1 12. Active on Y2 23. Active on Y1 with automatic alarm reset 34. Active on Y2 with automatic alarm reset 4

G Shutdown mode (Water heating only. Requires outdoor sensor)0. No 01. Yes 1

H Pump stop (Water heating only. Requires outdoor sensor)0. No 01. Yes 1

I Function not available for Corrigo C40This code must always be set to 0 0

J DX-cooling0. No 01. 1-step 12. 2-step 23. 3-step binary 3

K Cooling recovery0. No 01. Yes 1

L Free cooling0. No 01. Yes 1

Page 54: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

55Manual CORRIGO C-SERIES 2000.09

CONFIGURATION- Corrigo C40 M N O P . Q R SConfiguration code 2 0 . 0

M Function DI6/DO60. External alarm & frost protection 01. Auto position & frost protection 12. Fire damper exercising

N Fire alarm0. Alarm only 01. Alarm + supply air and exhaust air fans stop 12. Alarm + supply air fan stops 23. Alarm + exhaust air fan stops 3

O Function DI7/DI80. Not active 01. Pushbutton 12. Timer 2

P Function not available for Corrigo C40This code must always be set to 0 0

Q Function not available for Corrigo C40This code must always be set to 0 0

R Daylight saving time0. No 01. Yes 1

S Humidity control0. Humidification / Dehumidification 01. Humidification 12. Dehumidification 2

Page 55: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

56Manual CORRIGO C-SERIES 2000.09

AAI Analogue inputs 15, 35Alarm settings 40Alarms 21Alarms -Overview 41AO Analogue outputs 17, 36Arrow-buttons 19Auto + Frost protection 30

BBasic setting 32Buttons on the front 19

CChanging codes 22Changing language 19Commissioning protocol 46Configuration 23Configuration codes 23Control function 24Cooling recovery 30

DDaylight saving time 32Defrosting 28DI Digital inputs 16, 36Display contrast setting 10DO Digital outputs 18, 36DX Cooling 30

EEfficiency monitoring 29Esc-button 19Extended running 16, 42External alarm + frost protection 30External clockf 38External setpoint 32

FFactory set codes 22Factory setting 32Fire alarm 31Fire damper exercise 30Free cooling 30Front mounting kit 5Frost protection 29Function DI6/DO6 30Function DI7 / DI8 31

HHigh limit thermostat 27Holiday periods 39Holidays 39Humidity control 32, 34

IInformation series 20Installation 10

LLanguage 19LED 43Liquid connected heat exchanger 28Login 21

MMain menu 20Manual operation 37Menu 20

AI Analogue inputs 35Alarm settings 40AO Analogue outputs 36DI Digital inputs 36DO Digital outputs 36Help text 21Humidity control 34Pressure control 34Running mode 35Scheduler 38Settings 42Temperature control 33

Menu information 21

Index

OOK-button 19Outdoor temp. compensation 33, 34Overview 4

PPencil-button 19Pressure control 34Pump stop 29

RRelay modules 44

Wiring diagrams 45RM6-24/D 44RM6H-24/D 44Running mode 35

SScheduler 38Sequence Y1 28Sequence Y2 28Sequence Y3 28Service pin 10Setting outputs manually 37Settings 42Shutdown mode 29

TTechnical data 5Temperature control 33Two-speed fans 32

VWiring diagram

C10 11C40 14

Page 56: 10.. - ran-klima.czran-klima.cz/docs/regulatory_vzt/c10-40-q.pdf · 4 Manual CORRIGO C-SERIES 2000.09 Overview - air handling models There are four C ORRIGO models for ventilation

AB Regin

I M P R O V I N G I N D O O R C L I M A T E C O N T R O L W O R L D W I D E

Phone: +65 747 82 33Fax: +65 747 92 33

Head office SwedenHemsida: www.regin.seE-mail: [email protected]

Phone: +46 31 720 02 10Fax: +46 31 94 01 46

Regional office Asia PacificWeb site: www.regin.com.sgE-mail: [email protected]

Regin´s business mission is to be a flexible, globalpartner providing first-rate products for indoor

climate control. Our products are designed forcreating a pleasant indoor climate while, at

the same time, utilizing energy in the mostcost-effective way possible. The productrange consists of Regin´s own productsas well as products from leadingmanufacturers.

Vår affärsidé är att vara din flexiblapartner som globalt erbjuder ledandeprodukter för reglering av inneklimat.Dessa bidrar till att skapa ett behagligt

inneklimat samtidigt som energin utnyttjaspå ett kostnadseffektivt sätt. Programmet

består av såväl egenutvecklade produkter somagenturprodukter från världsledande tillverkare.

Visit our web site to get moreinformation about our indoorclimate product range.

Besök vår hemsida för att läsamer om vårt övriga sortiment.

www.regin.sewww.regin.se