1

Low Voltage Power Low Voltage Power Supply SpecificationSupply Specification

DCS Workshop 8 Sept 03DCS Workshop 8 Sept 03L.JirdenL.Jirden

Page 2: 1 Low Voltage Power Supply Specification DCS Workshop 8 Sept 03 L.Jirden

2

Electrical CharacteristicsElectrical Characteristics

AC Input 230 VAC +- 10%, 50 HZ +- 6%, PF >0.9

DC Output Modular design

LV PS2 – 7 V, 125 A

8 outputs/crate

LV PS2 – 7 V, 25 A

12 outputs/crate

24h stability < 5mV or 0.1%

6m stability < 20mV or 0.5%

Noise & ripple < 10mV p to p

Page 3: 1 Low Voltage Power Supply Specification DCS Workshop 8 Sept 03 L.Jirden

3

Mechanical CharacteristicsMechanical CharacteristicsTYPICAL RACK LAYOUT

4U

1U

4U

1U

4U

VENTILATOR & CONTR.

HEAT EXCHANGER

LV PS

LV PS

HEAT EXCHANGER

LV PS

FRONT VIEW

LV PS

LV PS

SPACE

FOR

CABLES

600 mm

300 mm

SIDE VIEW

Page 4: 1 Low Voltage Power Supply Specification DCS Workshop 8 Sept 03 L.Jirden

4

Monitoring & ControlMonitoring & Control

LVPS 1LOCAL PANEL

PVSS

OPC CL

OPC SRV

PCI “Kvaser”

LVPS 16LOCAL PANELLVPS 1

LOCAL PANEL

ethernet

CANbusMin 4 per PC

Min 16 per bus

Provided by manufacturer External

interlock

Page 5: 1 Low Voltage Power Supply Specification DCS Workshop 8 Sept 03 L.Jirden

5

POWER ON/OFF SCHEME 1POWER ON/OFF SCHEME 1

DC POWER MODULES

CANI/F

AC/DC

CANbus

HAZEMEYER

LV POWER SUPPLY

RACK POWER DISTRIBUTION STRIP

LOCAL SWITCH

220V AC

Page 6: 1 Low Voltage Power Supply Specification DCS Workshop 8 Sept 03 L.Jirden

6

POWER ON/OFF SCHEME 2POWER ON/OFF SCHEME 2

DC POWER MODULES

CANI/F

AC/DC

CANbus

HAZEMEYER

LV POWER SUPPLY

RACK POWER DISTRIBUTION STRIP

220V AC

POWER

Page 7: 1 Low Voltage Power Supply Specification DCS Workshop 8 Sept 03 L.Jirden

7

POWER ON/OFF SCHEME 3POWER ON/OFF SCHEME 3

DC POWER MODULES

CANI/F

AC/DC

CANbus

HAZEMEYER

LV POWER SUPPLY

RACK POWER DISTRIBUTION STRIP

LOCAL SWITCH

220V AC

REMOTE CONTROL

Page 8: 1 Low Voltage Power Supply Specification DCS Workshop 8 Sept 03 L.Jirden

8

REMOTE MONITORING AND REMOTE MONITORING AND CONTROL FUNCTIONSCONTROL FUNCTIONS

VOLTAGES MON CON Individual channels ESS

CURRENTS MON 12 bit resolution ESS

RAMPING RATE MON CON Individual channels DES

TEMPERATURE MON Sensor above power circuits ESS

OVER-CURRENT TRIP OFF VALUE

MON CON Individual channels ESS

FAN STATUS MON Out of limit warning ESS

OVER-VOLTAGE MON Individual channels DES

OVER-CURRENT MON Individual channels ESS

OVER-TEMP MON Out of limit warning ESS

MON = MONITOR

CON = CONTROL

ESS = ESSENTIAL

DES = DESIREDFUNCTIONS/PARAM

Page 9: 1 Low Voltage Power Supply Specification DCS Workshop 8 Sept 03 L.Jirden

9

REMOTE MONITORING AND REMOTE MONITORING AND CONTROL FUNCTIONSCONTROL FUNCTIONS

DC TRIP OFF MON Individual channels

Global DC power

ESS

ESS

RESET DC TRIP OFF CON Individual channels

Global DC power

ESS

ESS

DC POWER ON/OFF MON CON Individual channels

Global DC power

ESS

ESS

AC POWER ON/OFF MON CON using external power?? DES

PS HEALTH MON Summary status DES

LOCAL CONTROL MON Remote control locked out ESS

PS RESET CON System reset (tbs)?? ESS

MON = MONITOR

CON = CONTROL

ESS = ESSENTIAL

DES = DESIREDFUNCTIONS/PARAM

Page 10: 1 Low Voltage Power Supply Specification DCS Workshop 8 Sept 03 L.Jirden

10

GROUP MANAGEMENTGROUP MANAGEMENT

VOLTAGES CON Groups of channels (perf ??) ESS

DC POWER ON/OFF CON Groups of channels ESS

RAMPING RATE MON CON Groups of channels DES

OVER-CURRENT TRIP OFF VALUE

MON CON Groups of channels DES

MON = MONITOR

CON = CONTROL

ESS = ESSENTIAL

DES = DESIREDFUNCTIONS/PARAM

THE POSSIBILITY TO CONFIGURE AND PERFORM FUNCTIONS ON GROUPS OF CHANNELS WITHIN A CRATE

Page 11: 1 Low Voltage Power Supply Specification DCS Workshop 8 Sept 03 L.Jirden

11

OPC SERVEROPC SERVER

General Compliance with OPC standards No effect on PS output due to failure of remote control Restart of OPC remotely Not send set points automatically at startup – read from

device PS shall maintain its set points during PS power failure? Genuine device and cache access Interactive list of device functions

Page 12: 1 Low Voltage Power Supply Specification DCS Workshop 8 Sept 03 L.Jirden

12

OPC SERVEROPC SERVER

Maintenance To support future versions of Windows and OPC

standards To support future versions of PS firmware

Configuration Allow appropriate management of the fieldbus Human readable configuration file (such as XML) Obtain actual configuration by scanning Setting of ranges for analog values and setting of the

dead band

Page 13: 1 Low Voltage Power Supply Specification DCS Workshop 8 Sept 03 L.Jirden

13

OPC SERVEROPC SERVER

Performance Change in Device to OPC: max 10 sec at full bus load

max 1 sec for a single PS

Device cache to OPC client: max 3 sec for all parameters Write from OPC to device: max 1 sec Interlock to start ramp-down: max 5 ms

Page 14: 1 Low Voltage Power Supply Specification DCS Workshop 8 Sept 03 L.Jirden

14

Cooling Forced air

Environment Radiation < 0.01 Gy < 108 n/cm2

Magnetic Field < 80 Gauss

Construction Halogen free material

Safety regulations CE certification

Reliability MTBF > 90 000 hours

Page 15: 1 Low Voltage Power Supply Specification DCS Workshop 8 Sept 03 L.Jirden

15

Quality assurance Production tests

Functional tests Load tests

Documentation User’s guide Reference manual Test and calibration reports

Page 16: 1 Low Voltage Power Supply Specification DCS Workshop 8 Sept 03 L.Jirden

16

QuestionsQuestions

Who wishes to use the spec? For Wiener, CAEN, Arem Pro, other? Individual or common purchasing? When? Adapt spec for HV supplies as well?