Trends in the World and Israeli Green Data Centers (2008)
Shahar Geiger MaorVP & Senior Analyst
Your Text hereYour Text here
2
The Data Center’s Situation
Operational costs are soaring and more pollution is emitted
More cooling is needed
Servers are heating up
floor space is running out
More racks and more servers
Greater need for computing resources
All Rights Reserved @STKI Moshav Bnei Zion, Israel +972 9 74 444 74 www.stki.info
Typical DC has annual energy costs per square foot 15-40 times that of typical office
buildings
Your Text hereYour Text here
3
STKI Survey 2008:
Agree54%
Disagree43%
No Opinion3%
New\refurbish Data Center will be built within next 2 years?
All Rights Reserved @STKI Moshav Bnei Zion, Israel +972 9 74 444 74 www.stki.info
Your Text hereYour Text here
4
Cooling50%
Hardware Electricity
30%
UPS18%
Lighting2%
Data Center Power Usage Allocations
The Data Center’s Situation -Key Figures
All Rights Reserved @STKI Moshav Bnei Zion, Israel +972 9 74 444 74 www.stki.info
Source: Computer Economics
Your Text hereYour Text here
5
Electricity Use by End Use (USA)
2000-2006
All Rights Reserved @STKI Moshav Bnei Zion, Israel +972 9 74 444 74 www.stki.info
(Source: EPA)
Your Text hereYour Text here
6
Electricity Use Trends -ASHRAE
All Rights Reserved @STKI Moshav Bnei Zion, Israel +972 9 74 444 74 www.stki.info
Your Text hereYour Text here
7
AFCON Predictions (2006)
By 2010, more than half of all data centers will have to
relocate to new facilities or outsource some applications
Over the next five years power failures and limits on power
availability will halt data center operations at more than
90% of all companies
By 2010, nearly 70% of all data centers will utilize some
form of grid computing or other virtual processing
Within the next five years, 1/4 of all data centers will
experience a business disruption serious enough to affect
the entire company’s ability to continue business-as-usual
Your Text hereYour Text here
8
Metrics (by The Green Grid)
Power Usage Effectiveness (PUE):
PUE = Total Facility Power ÷ IT Equipment Power
and its reciprocal, the DCiE is defined as:
DCiE = 1÷ PUE = (IT Equipment Power ÷ Total Facility Power) x 100%
Average DC: PUE = 2.0-3.0
Best practice DC = 1.3-1.6
State of Art DC = 1.2
Your Text hereYour Text here
9
EPA Report to Congress
Your Text hereYour Text here
10
SVLG Demonstration
Your Text hereYour Text here
11
Combinations of IT and Site Data Center Types
Your Text hereYour Text here
12
SVLG Demonstration vs. EPA Estimates
Your Text hereYour Text here
13
The Data Center’s Situation: Practical
Solutions
Assessments and Thermal Modeling
Green servers and storage devices
Advanced cooling methods
Data Center arrangements (e.g.: Hot Aisles/Cold Aisles)
Virtualization, Consolidation
All Rights Reserved @STKI Moshav Bnei Zion, Israel +972 9 74 444 74 www.stki.info
Your Text hereYour Text here
14
Practical Solutions for the Data
Center: Thermal Modeling
•Locate Hot Spots
•Recommend new policy
All Rights Reserved @STKI Moshav Bnei Zion, Israel +972 9 74 444 74 www.stki.info
Your Text hereYour Text here
15
The Data Center’s Situation: Practical
Solutions
Assessments and Thermal Modeling
Green servers and storage devices
Advanced cooling methods
Data Center arrangements (e.g.: Hot Aisles/Cold Aisles)
Virtualization, Consolidation
All Rights Reserved @STKI Moshav Bnei Zion, Israel +972 9 74 444 74 www.stki.info
Your Text hereYour Text here
16
Energy Star: EPA Report to Congress
What is it?
Other alternatives
SPEC (Standard Performance Evaluation
Corporation)
EPEAT (Electronic Product Environmental
Assessment Tool),
RoHS, EcoLabel
Encouraging energy efficiency by vendors
All Rights Reserved @STKI Moshav Bnei Zion, Israel +972 9 74 444 74 www.stki.info
Your Text hereYour Text here
17
Energy Calculations:
Rack -Fully
Configured
(kW)
Power cost
per hour
(0.45
₪/kWh)
Power
Cost per
Year
Including
cooling costs
(1:1)
Typical Blade #1
7U High16.2 KW 7.3 ₪ 63,948 ₪ 127,896 ₪
Typical Blade #2
7U High14.7 KW 6.6 ₪ 57,816 ₪ 115,632 ₪
Typical Blade #3
3U High14.2 KW 6.4 ₪ 56,064 ₪ 112,128 ₪
Typical Blade #4
3U High11.16 KW 5 ₪ 43,800 ₪ 87,600 ₪
All Rights Reserved @STKI Moshav Bnei Zion, Israel +972 9 74 444 74 www.stki.info
Your Text hereYour Text here
18
The Data Center’s Situation: Practical
Solutions
Assessments and Thermal Modeling
Green servers and storage devices
Advanced cooling methods
Data Center arrangements (e.g.: Hot Aisles/Cold Aisles)
Virtualization, Consolidation
All Rights Reserved @STKI Moshav Bnei Zion, Israel +972 9 74 444 74 www.stki.info
Your Text hereYour Text here
19
Practical Solutions for the Data
Center: Advanced cooling methods
Routine Checkup:
Clean Raised floor
Utilize proper spacing of cold/hot aisles
Limit maximum cooling unit throw
Seal all cable cutouts in the raised floor
Upgrading:
Rack Cooling
• Air Cooling
• Liquid Cooling
Closer cooling systems -higher average temp. possible
All Rights Reserved @STKI Moshav Bnei Zion, Israel +972 9 74 444 74 www.stki.info
Your Text hereYour Text here
20
The Data Center’s Situation: Practical
Solutions
Assessments and Thermal Modeling
Green servers and storage devices
Advanced cooling methods
Data Center arrangements (e.g.: Hot Aisles/Cold Aisles)
Virtualization, Consolidation
All Rights Reserved @STKI Moshav Bnei Zion, Israel +972 9 74 444 74 www.stki.info
Your Text hereYour Text here
21
Practical Solutions for the Data Center:
Consolidation by organization size
Source: Computer Economics 2007
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
ROI TCO
Small
Medium
Large
% of reported positive ROI
% of Consolidation same as budget
IT spending per user at organizations with single data centers to those with multipledata centers
$5,000
$6,000
$7,000
$8,000
Multi DC Single DC
Small
Medium
Large
All Rights Reserved @STKI Moshav Bnei Zion, Israel +972 9 74 444 74 www.stki.info
Your Text hereYour Text here
22
STKI Survey 2008:
0%
10%
20%
30%
40%
50%
60%
70%
Negotiate better prices from
vendors
Consolidation of servers, storage
and desktops
Standartization of technologies
Group Purchasing
Four best ways to cut IT operational costs:
All Rights Reserved @STKI Moshav Bnei Zion, Israel +972 9 74 444 74 www.stki.info
Your Text hereYour Text here
23
Energy Saving –World Trends
Source: SearchDataCenter.com 2007
All Rights Reserved @STKI Moshav Bnei Zion, Israel +972 9 74 444 74 www.stki.info
Your Text hereYour Text here
24
Renewable Energy –World Trends
All Rights Reserved @STKI Moshav Bnei Zion, Israel +972 9 74 444 74 www.stki.info
Your Text hereYour Text here
25
Renewable Energy –World Trends
All Rights Reserved @STKI Moshav Bnei Zion, Israel +972 9 74 444 74 www.stki.info
Your Text hereYour Text here
26
Renewable Energy –World Trends
Denmark: 20% of total energy use is from wind turbines
Iceland: 50% of total energy use is from geothermal
sources
Israel: 3% of total energy use is from solar energy (water
heating)
Brazil: fuels 50% of its vehicles using bio-ethanol
All Rights Reserved @STKI Moshav Bnei Zion, Israel +972 9 74 444 74 www.stki.info
Your Text hereYour Text here
27
Thermal Energy Storage
Extra-Pak Ice Coils are used in thermal energy storage for
buildings 30,000 square feet or larger, industrial process
cooling, and data centers
The design and layout of the elliptical, galvanized steel
coils increase the amount of ice that can be stored in a
given area
Low temperature cooling water (1°C/34°F) supplied to
an existing building loop can add 20% more cooling
capacity
All Rights Reserved @STKI Moshav Bnei Zion, Israel +972 9 74 444 74 www.stki.info
Your Text hereYour Text here
28
Thermal Energy Storage -Projects
Matam –Haifa (55,000 m2): Design –IES, investment: 1$M,
estimated savings: 150,000$ year
Israel Building –Carmiel (20,000 m2): Design –Articom,
investment: 680,000 ₪, estimated savings: 39,000 ₪ a
year
Most common in office and public buildings
No activity in Israeli IT –few pilots so far.
Drawbacks:
• Lack of experienced support
• Not reliable enough
All Rights Reserved @STKI Moshav Bnei Zion, Israel +972 9 74 444 74 www.stki.info
Shahar Geiger MaorVP & Senior Analyst
Your Text hereYour Text here
30
EPEAT program
EPEAT evaluates electronic products in relation to 51
total environmental criteria, identified in the Criteria
Table below and contained in IEEE 1680 -– 23 required
criteria and 28 optional criteria
Meets all 23 required criteria
Meets all 23 required criteria plus at least 50% of the
optional criteria
Meets all 23 required criteria plus at least 75% of the
optional criteria
back
Your Text hereYour Text here
31
RoHS Directive and Eco-Label
The RoHS Directive stands for "the restriction of the use
of certain hazardous substances in electrical and
electronic equipment“
Eco-Label: a voluntary scheme designed to encourage
businesses to market products and services that are
kinder to the environment and for European consumers -
including public and private purchasers - to easily
identify them