Asset: DISTRICT #18 CEC - BROOKLYN, 1106 EAST 95 STREET, New York, 11236
Inspection Id Inspection Type Time In Last Edited
SA : K818 Architectural - Senior 2019-12-03 12:51 PM 2019-12-03 6:13 PM
AA : K818 Architectural - Associate 2019-12-03 12:42 PM 2019-12-03 6:36 PM
Asset Data
Question Answer
Was the building fully accessible for inspection Yes
Principal(s) Information
Principal Name Beverly Wilkins (Superintendent)
Organization Community School District 18 - Brooklyn
Did you meet with this Principal? Yes
Did this Principal provide feedback? Yes
Summary of Principal's Feedback The Superintendent's comments are as follows: 1. There are leaks fromthe roofs and walls into several rooms. The roofing needs to bereplaced. 2. The heating throughout the building is inconsistent andneeds to be replaced with a new system.
Principal Name Audrey Isaacs (Supervising Attorney)
Organization Brooklyn Staten Island Office of Student Suspension Hearings -Brooklyn
Did you meet with this Principal? Yes
Did this Principal provide feedback? Yes
Summary of Principal's Feedback The Supervising Attorney's comments are as follows: 1. There areongoing leaks from the roofs and walls into many rooms that need tobe repaired. 2. The boiler heating plant needs to be upgraded.
Custodian Peter Meehan
Fireman John Jaskowiak
Building Square Footage 16,000
Comments on the Area Entire Building Leased
Comments on the Stories (Floors) plus Basements 2+B
Comments on the Number of Classrooms 0
Comments on the Year Built 1950
Student Population 0
Staff Population 28
Weather Fair
Facade Photo
Corner of Conklin Avenue and East 95thStreet - West view
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 1 of 57
Main Entrance Photo
Facade A - East 95th Street
Roof Photo
Roof 1 - Northeast view
Have any Systems/Major Building Components been upgraded? Yes
Systems: Limited Window repairs
Year: 2019
Systems: Bulkhead Roofing and Masonry repairs, Roofing, Parapetand Exterior Masonry repairs, Roofing replacement atelevator
Year: 2016
Systems: Roofing, Parapet and Coping repairs
Year: 2012
Systems: Roofing replacement (re-roofing)
Year: 2001
Systems: Complete renovation for conversion to DOE use includingWindows and Exterior Guards replacement
Year: 1996
Have there been any New Building Additions? No
Tandem Schools? No
Leased Space? Yes
Year Leased 1996
Inspection Full Inspection
Priority Condition
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 2 of 57
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are all floors of the building accessible through compliant means? Yes
Accessible classrooms exists on each floor? Yes
Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes
If the following spaces exist, are they ALL accessible? Art Room, Auditorium,Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs
Yes
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings Yes Yes
Interior Routes
Corridor and Lobby H/C Lifts No No
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies Yes
Interior Elevators Yes Yes
Interior Lobby Doors and Hardware Yes
Interior Ramps No
Rooms & Spaces
Art Rooms No
Auditorium No
Cafeteria No
Classrooms No
Computer Rooms No
Gymnasium No
Library No
Main Office Room 110, 2nd Floor Yes Yes
Multi-purpose Room Basement Yes Yes No Yes
Nurse's Room No
Pool No
Science Lab No
Toilet Rooms (Boys) No
Toilet Rooms (Girls) No
Toilet Rooms (Staff) Basement, 1st Floor Yes Yes
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 3 of 57
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Inspected
InspectedInstance on AW1
Instance Condition 2 - Between Good and Fair
Instance Quantity 1
Instance Quantity Uom EACH
Deficiency AREAWAY STAIRS: DETERIORATEDTREADS/RISERS/NOSINGS
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 4 of 57
Question Response
EXTERIOR
AREAWAY
Deficiency Photo1
AW1
Violations No violations recorded.
Deficiency AREAWAY WALLS: CRACKS AND SPALLING
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
AW1
Violations No violations recorded.
AWNINGS AND CANOPIES Inspected
Condition 4 - Between Fair and Poor
Deficiency CONCRETE: MAJOR CRACKS/SPALLING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 5 of 57
Question Response
EXTERIOR
AWNINGS AND CANOPIES
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade D
Violations No violations recorded.
Deficiency METAL: DETERIORATION/DAMAGED/MISSING PIECES
Roof Plan reference
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 6 of 57
Question Response
EXTERIOR
AWNINGS AND CANOPIES
Deficiency Photo1
Facade B
Violations No violations recorded.
Deficiency METAL: WATER PENETRATION
Roof Plan reference
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
CHIMNEY Inspected
Material Type(s) Masonry, Metal
Condition 3 - Fair
Deficiency BRICK: MINOR CRACKS AND SPALLING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 7 of 57
Question Response
EXTERIOR
CHIMNEY
Roof Plan reference
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action RESTITCH
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 CH
Violations No violations recorded.
Deficiency BRICK: OPEN JOINTS
Roof Plan reference
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 8 of 57
Question Response
EXTERIOR
CHIMNEY
Deficiency Photo1
Roof 1 CH
Violations No violations recorded.
COPING Inspected
Condition 2 - Between Good and Fair
Deficiency TERRA COTTA: OPEN TRANSVERSE JOINTS WITH DAMAGEDCAULKING
Roof Plan reference
Deficiency Quantity 20
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 Facade E
Violations No violations recorded.
CORNICE Does not Exist
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 4 - Between Fair and Poor
Deficiency ROLL-UP DOOR: DETERIORATED DOOR AND FRAME -MINOR DETERIORATION
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 9 of 57
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency METAL: DETERIORATED DOOR AND FRAME - MINORDETERIORATION
Roof Plan reference
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 10 of 57
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Deficiency Photo1
Facade B
Violations No violations recorded.
Deficiency METAL CLAD: DETERIORATED DOOR - MAJORDETERIORATION
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade D
Violations No violations recorded.
DOOR HARDWARE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency STEEL: MINOR RUSTING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 11 of 57
Question Response
EXTERIOR
DOORS
LINTELS
Roof Plan reference
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade G
Violations No violations recorded.
TRANSOM/SIDE LIGHT Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
EXTERIOR WALLS Inspected
Material Type(s) Masonry, Concrete
Replacement Quantity 8,000
Replacement Uom S.F.
InspectedInstance on All Facades
Instance Condition 5 - Poor
Instance Quantity 8,000
Instance Quantity Uom S.F.
Deficiency BRICK: MINOR CRACKS AND SPALLING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 12 of 57
Question Response
EXTERIOR
EXTERIOR WALLS
Roof Plan reference
Elevation
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action RESTITCH
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade E
Violations No violations recorded.
Deficiency BRICK: OPEN JOINTS
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 13 of 57
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Deficiency Quantity 300
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade D
Violations No violations recorded.
Deficiency BRICK: OPEN JOINTS
Roof Plan reference
Elevation
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPOINT
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 14 of 57
Question Response
EXTERIOR
EXTERIOR WALLS
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade E
Violations No violations recorded.
Deficiency BRICK: CRACKS/DISPLACED/SPALLED BRICK AT BUILDINGCORNERS
Roof Plan reference
Elevation
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REMOVE AND REBUILD
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 15 of 57
Question Response
EXTERIOR
EXTERIOR WALLS
Facade A
Violations No violations recorded.
Deficiency STONE: CHIPPED/SPALLED/BROKEN PIECES
Roof Plan reference
Elevation
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency CAST IN PLACE / PRE-CAST CONCRETE: MINOR CRACKS,SPALLED, DETERIORATED REBAR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 16 of 57
Question Response
EXTERIOR
EXTERIOR WALLS
Roof Plan reference
Elevation
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency BRICK: MASONRY SILLS - OPEN JOINTS
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 17 of 57
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade D
Violations No violations recorded.
Deficiency BRICK: DETERIORATED MASONRY SILLS
Roof Plan reference
Elevation
Deficiency Quantity 30
Quantity Uom L.F.
Potential Action REPAIR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 18 of 57
Question Response
EXTERIOR
EXTERIOR WALLS
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade G
Violations No violations recorded.
Deficiency BRICK: WATER INFILTRATION IN INSTRUCTIONAL SPACE
Roof Plan reference
Elevation
Deficiency Quantity 900
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 19 of 57
Question Response
EXTERIOR
EXTERIOR WALLS
Facade A - Toilet Room by Room 108 shown, Facade A - Rooms104, 116, 201, 204, 205, 207, Facade F - North Stair/2, Facade G -Corridor by Room 207 similar
Violations No violations recorded.
Deficiency GLASS BLOCK: WATER INFILTRATION IN INSTRUCTIONALSPACE
Roof Plan reference
Elevation
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Facade G - 2nd Floor Corridor by Roof Door
Violations No violations recorded.
EXTERIOR SOFFITS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOADING DOCK Does not Exist
LOUVER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
PARAPETS Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 20 of 57
Question Response
EXTERIOR
PARAPETS
Material Type(s) Masonry
Replacement Quantity 2,200
Replacement Uom C.F.
InspectedInstance on All Facades
Instance Condition 4 - Between Fair and Poor
Instance Quantity 2,200
Instance Quantity Uom C.F.
Deficiency BRICK: MAJOR DETERIORATION/CRACKS
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REMOVE AND REBUILD
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 Facade G
Violations No violations recorded.
Deficiency BRICK: MINOR CRACKS, SPALLING
Roof Plan reference
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 21 of 57
Question Response
EXTERIOR
PARAPETS
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 Facade D
Violations No violations recorded.
Deficiency BRICK: OPEN JOINTS
Roof Plan reference
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 Facade G
Violations No violations recorded.
Deficiency BRICK: OPEN JOINTS
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 22 of 57
Question Response
EXTERIOR
PARAPETS
Roof Plan reference
Deficiency Quantity 1,500
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 Facade D
Violations No violations recorded.
PLAZA DECK Does not Exist
ROOF Inspected
Roofing Inspected
Replacement Quantity 6,600
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Does not Exist
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF BARRIER Does not Exist
ROOF CAGE Does not Exist
ROOF FENCE Does not Exist
ROOFING Inspected
InspectedInstance on Built-Up: Roofs 1, 2
Instance Condition 5 - Poor
Instance Quantity 6,400
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2001
Source of Installation Custodial Staff
Deficiency BUILT-UP: ROOFING: DELAMINATION
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 23 of 57
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Roof Plan reference
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 2
Violations No violations recorded.
Deficiency BUILT-UP: ROOFING: LOSS OF GRAVEL
Roof Plan reference
Deficiency Quantity 1,500
Quantity Uom S.F.
Potential Action INSTALL NEW GRAVEL
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 24 of 57
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Deficiency Photo1
Roof 2
Violations No violations recorded.
Deficiency BUILT-UP: FLASHING: FLASHING OPEN JOINTS
Roof Plan reference
Deficiency Quantity 50
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 Facade F
Violations No violations recorded.
Deficiency BUILT-UP: FLASHING: BASE FLASHING DETERIORATED
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 25 of 57
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Roof Plan reference
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REMOVE AND REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 Facade G
Violations No violations recorded.
Deficiency BUILT-UP: ROOFING: MAJOR ACTIVE ROOF LEAKS ININSTRUCTIONAL SPACE
Roof Plan reference
Deficiency Quantity 500
Quantity Uom S.F.
Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 26 of 57
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Deficiency Photo1
Roof 1 - Room 201 shown, Roof 1 - Room 208, North Stair/2,Corridor by Room 207, Roof 2 - Room 102 similar
Violations No violations recorded.
InspectedInstance on Modified Bitumen: Roof 3
Instance Condition 1 - Good
Instance Quantity 200
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2016
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
ROOFING DRAINS Inspected
Condition 4 - Between Fair and Poor
Deficiency DETERIORATED
Roof Plan reference
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 27 of 57
Question Response
EXTERIOR
ROOF
Roofing Inspected
ROOFING DRAINS
Deficiency Photo1
Roof 1
Violations No violations recorded.
Specialties Inspected
BULKHEAD/PENTHOUSE Inspected
Condition 5 - Poor
Deficiency BULKHEAD/PENTHOUSE WALLS/EXTERIOR: OPEN JOINTS
Roof Plan reference
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 BH
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE WALLS/EXTERIOR:CRACKS/SPALLING - MINOR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 28 of 57
Question Response
EXTERIOR
ROOF
Specialties Inspected
BULKHEAD/PENTHOUSE
Roof Plan reference
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 BH
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE WALLS/EXTERIOR:CRACKS/SPALLING - MAJOR
Roof Plan reference
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 29 of 57
Question Response
EXTERIOR
ROOF
Specialties
BULKHEAD/PENTHOUSE
Deficiency Photo1
Roof 1 BH
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: PLASTERCRACKS/SPALLING
Roof Plan reference
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 BH
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE WALLS/EXTERIOR: WATERINFILTRATION
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 30 of 57
Question Response
EXTERIOR
ROOF
Specialties
BULKHEAD/PENTHOUSE
Roof Plan reference
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 BH
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE ROOF: MINOR LEAKAGE
Roof Plan reference
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 31 of 57
Question Response
EXTERIOR
ROOF
Specialties
BULKHEAD/PENTHOUSE
Deficiency Photo1
Roof 1 BH
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE CEILING: PLASTERDAMAGED/DETERIORATED
Roof Plan reference
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 BH
Violations No violations recorded.
Deficiency BULKHEAD/PENTHOUSE DOORS: DETERIORATED DOOR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 32 of 57
Question Response
EXTERIOR
ROOF
Specialties
BULKHEAD/PENTHOUSE
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE DOOR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 BH
Violations No violations recorded.
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
DUNNAGE STEEL Does not Exist
SKYLIGHT/ROOF VENT Does not Exist
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Inspected
Condition 5 - Poor
Deficiency BRICK: DETERIORATED JOINTS AT COPING STONES
Roof Plan reference
Deficiency Quantity 15
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 33 of 57
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency BRICK: DETERIORATED COPING STONE
Roof Plan reference
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency BRICK: CRACKS/SPALLING - MAJOR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 34 of 57
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Roof Plan reference
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
RAILINGS Inspected
Condition 3 - Fair
Deficiency RUST - MINOR
Roof Plan reference
Deficiency Quantity 80
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency RUST - MAJOR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 35 of 57
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
RAILINGS
Roof Plan reference
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
STAIRS/RAMPS Inspected
Condition 3 - Fair
Deficiency STONE: OPEN JOINTS
Roof Plan reference
Deficiency Quantity 20
Quantity Uom L.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 36 of 57
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency CONCRETE: CRACKS/SPALLING - MINOR
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade D
Violations No violations recorded.
Deficiency METAL: RUST - MINOR
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 37 of 57
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Roof Plan reference
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade F
Violations No violations recorded.
WINDOWS Inspected
Replacement Quantity 2,000
Replacement Uom S.F.
EXTERIOR GUARDS Inspected
Condition 3 - Fair
Deficiency DETERIORATED/TORN-OUT/MISSING
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 38 of 57
Question Response
EXTERIOR
WINDOWS
EXTERIOR GUARDS
Elevation
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency STEEL: MINOR RUSTING
Roof Plan reference
Elevation
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 39 of 57
Question Response
EXTERIOR
WINDOWS
LINTELS
Deficiency Quantity 50
Quantity Uom L.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
WINDOWS Inspected
Material Type(s) Aluminum
InspectedInstance on Aluminum - Other: All Facades
Instance Condition 3 - Fair
Instance Quantity 2,000
Instance Quantity Uom S.F.
Installation Year 1996
Source of Installation Custodial Staff
Deficiency ALUMINUM - OTHER: BROKEN PANE
Roof Plan reference
Elevation
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action MAINTENANCE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 40 of 57
Question Response
EXTERIOR
WINDOWS
WINDOWS
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 2 - Between Good and Fair
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING
Deficiency Location/Instance Basement
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Boiler Room
Violations No violations recorded.
FLOOR STRUCTURE Inspected
Condition 3 - Fair
Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS
Deficiency Location/Instance Basement
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 41 of 57
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE
Deficiency Photo1
Boiler Room
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Concrete
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
VAULTS-BUNKERS Inspected
Foundation Walls Inspected
Condition 2 - Between Good and Fair
Deficiency CRACKS, SPALLING
Deficiency Location/Instance Basement
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Ash Hoist Vault
Violations No violations recorded.
Slab Structure Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Vault/Ash Hoist Doors and Framing Inspected
Condition 5 - Poor
Deficiency WATER INFILTRATION
Deficiency Location/Instance Basement
Deficiency Quantity 10
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 42 of 57
Question Response
INTERIOR
STRUCTURAL
VAULTS-BUNKERS
Vault/Ash Hoist Doors and Framing
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Ash Hoist Vault
Violations No violations recorded.
Deficiency DETERIORATED/DAMAGED VAULT/ASH HOIST DOORS ANDFRAMING
Deficiency Location/Instance Basement
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Ash Hoist Vault
Violations No violations recorded.
AUDITORIUM Does not Exist
CAFETERIA Does not Exist
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK
Deficiency Location/Instance Rooms 102, 104, 116
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 43 of 57
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Deficiency Photo1
Room 102
Violations No violations recorded.
Deficiency ACOUSTIC TILES: DAMAGED/MISSING - ACTIVE LEAK
Deficiency Location/Instance Rooms 101, 201, Corridor near Room 207
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Room 201
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency METAL: MISSING DOOR
Deficiency Location/Instance Rooms 102, 103, 104, door by Room 113
Deficiency Quantity 4
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 44 of 57
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Door(s)
Room 104
Violations No violations recorded.
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Room 206
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 206
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency TERRAZZO: CRACKS
Deficiency Location/Instance In the Lobby
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
In the Lobby
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Room 202, 204, by Elevator/Basement
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 45 of 57
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Deficiency Photo1
Room 202
Violations No violations recorded.
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Room 101, Corridor near Rooms 202, 212, by the old Kitchen
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 212
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency GYPSUM BOARD: DETERIORATED
Deficiency Location/Instance Corridor near Rooms 102, 104, 106, 107
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 46 of 57
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls
Corridor near Room 102
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK
Deficiency Location/Instance Rooms 201, 204, 205, 207, 208, corridor by Room 207, 2nd Floorcorridor by roof door
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor by Room 207
Violations No violations recorded.
Specialties Does not Exist
GYMNASIUM Does not Exist
INTERIOR DOOR HARDWARE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Does not Exist
KITCHEN Does not Exist
LIBRARY Does not Exist
LOCKER ROOM Does not Exist
MULTI-PURPOSE ROOM Inspected
InspectedInstance on Basement
Ceiling
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency ACOUSTIC TILES: DAMAGED/MISSING
Deficiency Location/Instance Near the closet
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 47 of 57
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Ceiling
Deficiency Photo1
Near the closet
Violations No violations recorded.
Door(s)
InspectedInstance on Basement
Condition 3 - Fair
Deficiency METAL: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Main Entrance
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Main Entrance
Violations No violations recorded.
Fixed Equipment
Does not ExistInstance on Basement
Floor Finish
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Near the closet, by Main Entrance, in Exit Vestibule
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 48 of 57
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Floor Finish
Deficiency Photo1
In the Exit Vestibule
Violations No violations recorded.
Sliding-folding Partition
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage
Does not ExistInstance on Basement
Walls
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on Basement
SCIENCE DEMO ROOM Does not Exist
SCIENCE LAB Does not Exist
SCIENCE PREP ROOM Does not Exist
SHOWER ROOM Does not Exist
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? No
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK
Deficiency Location/Instance North Stair/2
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 49 of 57
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Ceiling Inspected
North Stair/2
Violations No violations recorded.
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Partition Does not Exist
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs and Landings Inspected
Condition 2 - Between Good and Fair
Deficiency STONE: BROKEN/MISSING
Deficiency Location/Instance South Stair/1
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
South Stair/1
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK
Deficiency Location/Instance North Stair/2
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 50 of 57
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR Inspected
Walls Inspected
North Stair/2
Violations No violations recorded.
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK
Deficiency Location/Instance Unisex toilet by Room 108
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Unisex toilet by Room 108
Violations No violations recorded.
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 5 - Poor
Deficiency RUST - MAJOR
Deficiency Location/Instance Women, Men toilet in the Basement
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 51 of 57
Question Response
INTERIOR
TOILET ROOMS - STAFF Inspected
Stalls Inspected
Women toilet in the Basement
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency GYPSUM BOARD: DETERIORATED
Deficiency Location/Instance Men toilet in the Basement
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Men toilet in the Basement
Violations No violations recorded.
TOILET ROOMS - STUDENTS Does not Exist
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Does not Exist
Drainage System for Asphalt Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Concrete Covering Does not Exist
Drainage System for Soil Does not Exist
DRINKING FOUNTAINS Does not Exist
FENCES Inspected
Condition 3 - Fair
Deficiency CONCRETE CURB: DAMAGED/DETERIORATED
Deficiency Location/Instance E.95th Street, Conklin Avenue
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 52 of 57
Question Response
SITE
FENCES
Deficiency Photo1
E.95th Street
Violations No violations recorded.
Deficiency WROUGHT IRON: DAMAGED/DETERIORATED
Deficiency Location/Instance E.95th Street
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
E.95th Street
Violations No violations recorded.
Deficiency WROUGHT IRON: MISSING SECTIONS
Deficiency Location/Instance E.95th Street
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
E.95th Street
Violations No violations recorded.
Deficiency CHAIN LINK: DAMAGED POST/RAIL
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 53 of 57
Question Response
SITE
FENCES
Deficiency Location/Instance In the Parking Lot
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
In the Parking Lot
Violations No violations recorded.
Deficiency CHAIN LINK: DAMAGED/DETERIORATED
Deficiency Location/Instance In the Parking Lot
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
In the Parking Lot
Violations No violations recorded.
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Inspected
Gravel Exists? No
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance In the Parking Lot
Deficiency Quantity 300
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 54 of 57
Question Response
SITE
PAVING
Student Non-Use
Concrete
Purpose of Action LEVEL 2
Deficiency Photo1
In the Parking Lot
Violations No violations recorded.
Pavers Does not Exist
Student Use Does not Exist
Site Sidewalks & Walkways Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance E.95th Street
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
E.95th Street
Violations No violations recorded.
Pavers Does not Exist
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED CURBS
Deficiency Location/Instance E.95th Street, Conklin Avenue
Deficiency Quantity 40
Quantity Uom L.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 55 of 57
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 4
Deficiency Photo1
E.95th Street
Violations 56016
Deficiency HEAVING
Deficiency Location/Instance Conklin Avenue
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Conklin Avenue
Violations 56016
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance E.95th Street, Conklin Avenue
Deficiency Quantity 225
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 4
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 56 of 57
Question Response
SITE
PAVING
DOT Sidewalk
Concrete Inspected
Deficiency Photo1
E.95th Street
Violations 56016
Pavers Does not Exist
PLAYGROUNDS Does not Exist
PLAYING SURFACE Does not Exist
RETAINING WALLS Does not Exist
SEATING Does not Exist
SITE WALLS (NOT RETAINING WALLS) Does not Exist
STAIRS/RAMPS: EXTERIOR Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K818
PB/A&W Print Date: 9/14/2020Page 57 of 57
Recommended