Asset: DISTRICT #18 CEC - BROOKLYN, 1106 EAST 95 STREET, New York, 11236 Inspection Id Inspection Type Time In Last Edited SA : K818 Architectural - Senior 2019-12-03 12:51 PM 2019-12-03 6:13 PM AA : K818 Architectural - Associate 2019-12-03 12:42 PM 2019-12-03 6:36 PM Asset Data Question Answer Was the building fully accessible for inspection Yes Principal(s) Information Principal Name Beverly Wilkins (Superintendent) Organization Community School District 18 - Brooklyn Did you meet with this Principal? Yes Did this Principal provide feedback? Yes Summary of Principal's Feedback The Superintendent's comments are as follows: 1. There are leaks from the roofs and walls into several rooms. The roofing needs to be replaced. 2. The heating throughout the building is inconsistent and needs to be replaced with a new system. Principal Name Audrey Isaacs (Supervising Attorney) Organization Brooklyn Staten Island Office of Student Suspension Hearings - Brooklyn Did you meet with this Principal? Yes Did this Principal provide feedback? Yes Summary of Principal's Feedback The Supervising Attorney's comments are as follows: 1. There are ongoing leaks from the roofs and walls into many rooms that need to be repaired. 2. The boiler heating plant needs to be upgraded. Custodian Peter Meehan Fireman John Jaskowiak Building Square Footage 16,000 Comments on the Area Entire Building Leased Comments on the Stories (Floors) plus Basements 2+B Comments on the Number of Classrooms 0 Comments on the Year Built 1950 Student Population 0 Staff Population 28 Weather Fair Facade Photo Corner of Conklin Avenue and East 95th Street - West view NYC Department of Education Architectural Inspection Building Condition Assessment Survey 2019 - 2020 K818 PB/A&W Print Date: 9/14/2020 Page 1 of 57

NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Asset: DISTRICT #18 CEC - BROOKLYN, 1106 EAST 95 STREET, New York, 11236

Inspection Id Inspection Type Time In Last Edited

SA : K818 Architectural - Senior 2019-12-03 12:51 PM 2019-12-03 6:13 PM

AA : K818 Architectural - Associate 2019-12-03 12:42 PM 2019-12-03 6:36 PM

Asset Data

Question Answer

Was the building fully accessible for inspection Yes

Principal(s) Information

Principal Name Beverly Wilkins (Superintendent)

Organization Community School District 18 - Brooklyn

Did you meet with this Principal? Yes

Did this Principal provide feedback? Yes

Summary of Principal's Feedback The Superintendent's comments are as follows: 1. There are leaks fromthe roofs and walls into several rooms. The roofing needs to bereplaced. 2. The heating throughout the building is inconsistent andneeds to be replaced with a new system.

Principal Name Audrey Isaacs (Supervising Attorney)

Organization Brooklyn Staten Island Office of Student Suspension Hearings -Brooklyn

Did you meet with this Principal? Yes

Did this Principal provide feedback? Yes

Summary of Principal's Feedback The Supervising Attorney's comments are as follows: 1. There areongoing leaks from the roofs and walls into many rooms that need tobe repaired. 2. The boiler heating plant needs to be upgraded.

Custodian Peter Meehan

Fireman John Jaskowiak

Building Square Footage 16,000

Comments on the Area Entire Building Leased

Comments on the Stories (Floors) plus Basements 2+B

Comments on the Number of Classrooms 0

Comments on the Year Built 1950

Student Population 0

Staff Population 28

Weather Fair

Facade Photo

Corner of Conklin Avenue and East 95thStreet - West view

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 1 of 57

Page 2: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Main Entrance Photo

Facade A - East 95th Street

Roof Photo

Roof 1 - Northeast view

Have any Systems/Major Building Components been upgraded? Yes

Systems: Limited Window repairs

Year: 2019

Systems: Bulkhead Roofing and Masonry repairs, Roofing, Parapetand Exterior Masonry repairs, Roofing replacement atelevator

Year: 2016

Systems: Roofing, Parapet and Coping repairs

Year: 2012

Systems: Roofing replacement (re-roofing)

Year: 2001

Systems: Complete renovation for conversion to DOE use includingWindows and Exterior Guards replacement

Year: 1996

Have there been any New Building Additions? No

Tandem Schools? No

Leased Space? Yes

Year Leased 1996

Inspection Full Inspection

Priority Condition

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 2 of 57

Page 3: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

PriorityCondition ExistLast Year?

PriorityCategory

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Structural Engineer Required

StructuralCondition Type

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Accessibility

Accessibility Status Question Response

Is the primary or secondary entrance on an accessible route? Yes

Is the building a multi-story building? Yes

Are all floors of the building accessible through compliant means? Yes

Accessible classrooms exists on each floor? Yes

Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes

If the following spaces exist, are they ALL accessible? Art Room, Auditorium,Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs

Yes

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

Exterior Entrances & Exits Yes

Exterior H/C Lifts No No

Exterior Ramps and Railings Yes Yes

Interior Routes

Corridor and Lobby H/C Lifts No No

Interior Corridor Doors and Hardware Yes Yes

Interior Corridors and Lobbies Yes

Interior Elevators Yes Yes

Interior Lobby Doors and Hardware Yes

Interior Ramps No

Rooms & Spaces

Art Rooms No

Auditorium No

Cafeteria No

Classrooms No

Computer Rooms No

Gymnasium No

Library No

Main Office Room 110, 2nd Floor Yes Yes

Multi-purpose Room Basement Yes Yes No Yes

Nurse's Room No

Pool No

Science Lab No

Toilet Rooms (Boys) No

Toilet Rooms (Girls) No

Toilet Rooms (Staff) Basement, 1st Floor Yes Yes

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 3 of 57

Page 4: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

Building Template

Inspection

Question Response

Architectural

EXTERIOR Inspected

AREAWAY Inspected

InspectedInstance on AW1

Instance Condition 2 - Between Good and Fair

Instance Quantity 1

Instance Quantity Uom EACH

Deficiency AREAWAY STAIRS: DETERIORATEDTREADS/RISERS/NOSINGS

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 4 of 57

Page 5: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

AREAWAY

Deficiency Photo1

AW1

Violations No violations recorded.

Deficiency AREAWAY WALLS: CRACKS AND SPALLING

Roof Plan reference

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

AW1

Violations No violations recorded.

AWNINGS AND CANOPIES Inspected

Condition 4 - Between Fair and Poor

Deficiency CONCRETE: MAJOR CRACKS/SPALLING

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 5 of 57

Page 6: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

AWNINGS AND CANOPIES

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade D

Violations No violations recorded.

Deficiency METAL: DETERIORATION/DAMAGED/MISSING PIECES

Roof Plan reference

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 6 of 57

Page 7: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

AWNINGS AND CANOPIES

Deficiency Photo1

Facade B

Violations No violations recorded.

Deficiency METAL: WATER PENETRATION

Roof Plan reference

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Facade B

Violations No violations recorded.

CHIMNEY Inspected

Material Type(s) Masonry, Metal

Condition 3 - Fair

Deficiency BRICK: MINOR CRACKS AND SPALLING

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 7 of 57

Page 8: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

CHIMNEY

Roof Plan reference

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action RESTITCH

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 CH

Violations No violations recorded.

Deficiency BRICK: OPEN JOINTS

Roof Plan reference

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 8 of 57

Page 9: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

CHIMNEY

Deficiency Photo1

Roof 1 CH

Violations No violations recorded.

COPING Inspected

Condition 2 - Between Good and Fair

Deficiency TERRA COTTA: OPEN TRANSVERSE JOINTS WITH DAMAGEDCAULKING

Roof Plan reference

Deficiency Quantity 20

Quantity Uom L.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 Facade E

Violations No violations recorded.

CORNICE Does not Exist

DOORS Inspected

DOORS AND FRAMES Inspected

Condition 4 - Between Fair and Poor

Deficiency ROLL-UP DOOR: DETERIORATED DOOR AND FRAME -MINOR DETERIORATION

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 9 of 57

Page 10: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

Deficiency METAL: DETERIORATED DOOR AND FRAME - MINORDETERIORATION

Roof Plan reference

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 10 of 57

Page 11: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES

Deficiency Photo1

Facade B

Violations No violations recorded.

Deficiency METAL CLAD: DETERIORATED DOOR - MAJORDETERIORATION

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade D

Violations No violations recorded.

DOOR HARDWARE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency STEEL: MINOR RUSTING

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 11 of 57

Page 12: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

DOORS

LINTELS

Roof Plan reference

Deficiency Quantity 10

Quantity Uom L.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade G

Violations No violations recorded.

TRANSOM/SIDE LIGHT Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

EXTERIOR WALLS Inspected

Material Type(s) Masonry, Concrete

Replacement Quantity 8,000

Replacement Uom S.F.

InspectedInstance on All Facades

Instance Condition 5 - Poor

Instance Quantity 8,000

Instance Quantity Uom S.F.

Deficiency BRICK: MINOR CRACKS AND SPALLING

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 12 of 57

Page 13: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

EXTERIOR WALLS

Roof Plan reference

Elevation

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action RESTITCH

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade E

Violations No violations recorded.

Deficiency BRICK: OPEN JOINTS

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 13 of 57

Page 14: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

EXTERIOR WALLS

Elevation

Deficiency Quantity 300

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade D

Violations No violations recorded.

Deficiency BRICK: OPEN JOINTS

Roof Plan reference

Elevation

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPOINT

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 14 of 57

Page 15: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

EXTERIOR WALLS

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade E

Violations No violations recorded.

Deficiency BRICK: CRACKS/DISPLACED/SPALLED BRICK AT BUILDINGCORNERS

Roof Plan reference

Elevation

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REMOVE AND REBUILD

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 15 of 57

Page 16: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

EXTERIOR WALLS

Facade A

Violations No violations recorded.

Deficiency STONE: CHIPPED/SPALLED/BROKEN PIECES

Roof Plan reference

Elevation

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

Deficiency CAST IN PLACE / PRE-CAST CONCRETE: MINOR CRACKS,SPALLED, DETERIORATED REBAR

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 16 of 57

Page 17: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

EXTERIOR WALLS

Roof Plan reference

Elevation

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

Deficiency BRICK: MASONRY SILLS - OPEN JOINTS

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 17 of 57

Page 18: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

EXTERIOR WALLS

Elevation

Deficiency Quantity 10

Quantity Uom L.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade D

Violations No violations recorded.

Deficiency BRICK: DETERIORATED MASONRY SILLS

Roof Plan reference

Elevation

Deficiency Quantity 30

Quantity Uom L.F.

Potential Action REPAIR

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 18 of 57

Page 19: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

EXTERIOR WALLS

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade G

Violations No violations recorded.

Deficiency BRICK: WATER INFILTRATION IN INSTRUCTIONAL SPACE

Roof Plan reference

Elevation

Deficiency Quantity 900

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 19 of 57

Page 20: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

EXTERIOR WALLS

Facade A - Toilet Room by Room 108 shown, Facade A - Rooms104, 116, 201, 204, 205, 207, Facade F - North Stair/2, Facade G -Corridor by Room 207 similar

Violations No violations recorded.

Deficiency GLASS BLOCK: WATER INFILTRATION IN INSTRUCTIONALSPACE

Roof Plan reference

Elevation

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Facade G - 2nd Floor Corridor by Roof Door

Violations No violations recorded.

EXTERIOR SOFFITS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LOADING DOCK Does not Exist

LOUVER Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

PARAPETS Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 20 of 57

Page 21: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

PARAPETS

Material Type(s) Masonry

Replacement Quantity 2,200

Replacement Uom C.F.

InspectedInstance on All Facades

Instance Condition 4 - Between Fair and Poor

Instance Quantity 2,200

Instance Quantity Uom C.F.

Deficiency BRICK: MAJOR DETERIORATION/CRACKS

Roof Plan reference

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REMOVE AND REBUILD

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 Facade G

Violations No violations recorded.

Deficiency BRICK: MINOR CRACKS, SPALLING

Roof Plan reference

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPAIR

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 21 of 57

Page 22: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

PARAPETS

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 Facade D

Violations No violations recorded.

Deficiency BRICK: OPEN JOINTS

Roof Plan reference

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 Facade G

Violations No violations recorded.

Deficiency BRICK: OPEN JOINTS

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 22 of 57

Page 23: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

PARAPETS

Roof Plan reference

Deficiency Quantity 1,500

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 Facade D

Violations No violations recorded.

PLAZA DECK Does not Exist

ROOF Inspected

Roofing Inspected

Replacement Quantity 6,600

Replacement Uom S.F.

ROOF HATCH/SMOKE HATCH Does not Exist

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF BARRIER Does not Exist

ROOF CAGE Does not Exist

ROOF FENCE Does not Exist

ROOFING Inspected

InspectedInstance on Built-Up: Roofs 1, 2

Instance Condition 5 - Poor

Instance Quantity 6,400

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 2001

Source of Installation Custodial Staff

Deficiency BUILT-UP: ROOFING: DELAMINATION

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 23 of 57

Page 24: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

ROOF

Roofing

ROOFING

Roof Plan reference

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 2

Violations No violations recorded.

Deficiency BUILT-UP: ROOFING: LOSS OF GRAVEL

Roof Plan reference

Deficiency Quantity 1,500

Quantity Uom S.F.

Potential Action INSTALL NEW GRAVEL

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 24 of 57

Page 25: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

ROOF

Roofing

ROOFING

Deficiency Photo1

Roof 2

Violations No violations recorded.

Deficiency BUILT-UP: FLASHING: FLASHING OPEN JOINTS

Roof Plan reference

Deficiency Quantity 50

Quantity Uom L.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 Facade F

Violations No violations recorded.

Deficiency BUILT-UP: FLASHING: BASE FLASHING DETERIORATED

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 25 of 57

Page 26: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

ROOF

Roofing

ROOFING

Roof Plan reference

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REMOVE AND REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 Facade G

Violations No violations recorded.

Deficiency BUILT-UP: ROOFING: MAJOR ACTIVE ROOF LEAKS ININSTRUCTIONAL SPACE

Roof Plan reference

Deficiency Quantity 500

Quantity Uom S.F.

Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 26 of 57

Page 27: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

ROOF

Roofing

ROOFING

Deficiency Photo1

Roof 1 - Room 201 shown, Roof 1 - Room 208, North Stair/2,Corridor by Room 207, Roof 2 - Room 102 similar

Violations No violations recorded.

InspectedInstance on Modified Bitumen: Roof 3

Instance Condition 1 - Good

Instance Quantity 200

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 2016

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

ROOFING DRAINS Inspected

Condition 4 - Between Fair and Poor

Deficiency DETERIORATED

Roof Plan reference

Deficiency Quantity 2

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 27 of 57

Page 28: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

ROOF

Roofing Inspected

ROOFING DRAINS

Deficiency Photo1

Roof 1

Violations No violations recorded.

Specialties Inspected

BULKHEAD/PENTHOUSE Inspected

Condition 5 - Poor

Deficiency BULKHEAD/PENTHOUSE WALLS/EXTERIOR: OPEN JOINTS

Roof Plan reference

Deficiency Quantity 60

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 BH

Violations No violations recorded.

Deficiency BULKHEAD/PENTHOUSE WALLS/EXTERIOR:CRACKS/SPALLING - MINOR

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 28 of 57

Page 29: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

ROOF

Specialties Inspected

BULKHEAD/PENTHOUSE

Roof Plan reference

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 BH

Violations No violations recorded.

Deficiency BULKHEAD/PENTHOUSE WALLS/EXTERIOR:CRACKS/SPALLING - MAJOR

Roof Plan reference

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 29 of 57

Page 30: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

ROOF

Specialties

BULKHEAD/PENTHOUSE

Deficiency Photo1

Roof 1 BH

Violations No violations recorded.

Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: PLASTERCRACKS/SPALLING

Roof Plan reference

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 BH

Violations No violations recorded.

Deficiency BULKHEAD/PENTHOUSE WALLS/EXTERIOR: WATERINFILTRATION

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 30 of 57

Page 31: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

ROOF

Specialties

BULKHEAD/PENTHOUSE

Roof Plan reference

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 BH

Violations No violations recorded.

Deficiency BULKHEAD/PENTHOUSE ROOF: MINOR LEAKAGE

Roof Plan reference

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 31 of 57

Page 32: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

ROOF

Specialties

BULKHEAD/PENTHOUSE

Deficiency Photo1

Roof 1 BH

Violations No violations recorded.

Deficiency BULKHEAD/PENTHOUSE CEILING: PLASTERDAMAGED/DETERIORATED

Roof Plan reference

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 BH

Violations No violations recorded.

Deficiency BULKHEAD/PENTHOUSE DOORS: DETERIORATED DOOR

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 32 of 57

Page 33: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

ROOF

Specialties

BULKHEAD/PENTHOUSE

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE DOOR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 BH

Violations No violations recorded.

CUPOLA/ SPIRES/ TOWERS Does not Exist

DORMER Does not Exist

DUNNAGE STEEL Does not Exist

SKYLIGHT/ROOF VENT Does not Exist

ROOF/GRAVITY TANK Does not Exist

STAIRS/RAMPS: EXTERIOR Inspected

BUILDING CHEEK/FLANK WALLS Inspected

Condition 5 - Poor

Deficiency BRICK: DETERIORATED JOINTS AT COPING STONES

Roof Plan reference

Deficiency Quantity 15

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 33 of 57

Page 34: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

BUILDING CHEEK/FLANK WALLS

Quantity Uom L.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

Deficiency BRICK: DETERIORATED COPING STONE

Roof Plan reference

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

Deficiency BRICK: CRACKS/SPALLING - MAJOR

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 34 of 57

Page 35: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

BUILDING CHEEK/FLANK WALLS

Roof Plan reference

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

RAILINGS Inspected

Condition 3 - Fair

Deficiency RUST - MINOR

Roof Plan reference

Deficiency Quantity 80

Quantity Uom L.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

Deficiency RUST - MAJOR

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 35 of 57

Page 36: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

RAILINGS

Roof Plan reference

Deficiency Quantity 10

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

STAIRS/RAMPS Inspected

Condition 3 - Fair

Deficiency STONE: OPEN JOINTS

Roof Plan reference

Deficiency Quantity 20

Quantity Uom L.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 36 of 57

Page 37: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

STAIRS/RAMPS

Deficiency Photo1

Facade A

Violations No violations recorded.

Deficiency CONCRETE: CRACKS/SPALLING - MINOR

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade D

Violations No violations recorded.

Deficiency METAL: RUST - MINOR

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 37 of 57

Page 38: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

STAIRS/RAMPS

Roof Plan reference

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPAINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade F

Violations No violations recorded.

WINDOWS Inspected

Replacement Quantity 2,000

Replacement Uom S.F.

EXTERIOR GUARDS Inspected

Condition 3 - Fair

Deficiency DETERIORATED/TORN-OUT/MISSING

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 38 of 57

Page 39: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

WINDOWS

EXTERIOR GUARDS

Elevation

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency STEEL: MINOR RUSTING

Roof Plan reference

Elevation

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 39 of 57

Page 40: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

WINDOWS

LINTELS

Deficiency Quantity 50

Quantity Uom L.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

WINDOWS Inspected

Material Type(s) Aluminum

InspectedInstance on Aluminum - Other: All Facades

Instance Condition 3 - Fair

Instance Quantity 2,000

Instance Quantity Uom S.F.

Installation Year 1996

Source of Installation Custodial Staff

Deficiency ALUMINUM - OTHER: BROKEN PANE

Roof Plan reference

Elevation

Deficiency Quantity 60

Quantity Uom S.F.

Potential Action MAINTENANCE

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 40 of 57

Page 41: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

EXTERIOR

WINDOWS

WINDOWS

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

INTERIOR Inspected

POOLS Does not Exist

STRUCTURAL Inspected

COLUMNS/BEAMS/BEARING WALLS Inspected

Condition 2 - Between Good and Fair

Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING

Deficiency Location/Instance Basement

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Boiler Room

Violations No violations recorded.

FLOOR STRUCTURE Inspected

Condition 3 - Fair

Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS

Deficiency Location/Instance Basement

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 41 of 57

Page 42: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

INTERIOR

STRUCTURAL

FLOOR STRUCTURE

Deficiency Photo1

Boiler Room

Violations No violations recorded.

FOUNDATION WALLS Inspected

Material Type(s) Concrete

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF STRUCTURE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

VAULTS-BUNKERS Inspected

Foundation Walls Inspected

Condition 2 - Between Good and Fair

Deficiency CRACKS, SPALLING

Deficiency Location/Instance Basement

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Ash Hoist Vault

Violations No violations recorded.

Slab Structure Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Vault/Ash Hoist Doors and Framing Inspected

Condition 5 - Poor

Deficiency WATER INFILTRATION

Deficiency Location/Instance Basement

Deficiency Quantity 10

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 42 of 57

Page 43: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

INTERIOR

STRUCTURAL

VAULTS-BUNKERS

Vault/Ash Hoist Doors and Framing

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Ash Hoist Vault

Violations No violations recorded.

Deficiency DETERIORATED/DAMAGED VAULT/ASH HOIST DOORS ANDFRAMING

Deficiency Location/Instance Basement

Deficiency Quantity 2

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Ash Hoist Vault

Violations No violations recorded.

AUDITORIUM Does not Exist

CAFETERIA Does not Exist

CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK

Deficiency Location/Instance Rooms 102, 104, 116

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 43 of 57

Page 44: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Ceiling

Deficiency Photo1

Room 102

Violations No violations recorded.

Deficiency ACOUSTIC TILES: DAMAGED/MISSING - ACTIVE LEAK

Deficiency Location/Instance Rooms 101, 201, Corridor near Room 207

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Room 201

Violations No violations recorded.

Door(s) Inspected

Condition 5 - Poor

Deficiency METAL: MISSING DOOR

Deficiency Location/Instance Rooms 102, 103, 104, door by Room 113

Deficiency Quantity 4

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 44 of 57

Page 45: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Door(s)

Room 104

Violations No violations recorded.

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Room 206

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 206

Violations No violations recorded.

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency TERRAZZO: CRACKS

Deficiency Location/Instance In the Lobby

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

In the Lobby

Violations No violations recorded.

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Room 202, 204, by Elevator/Basement

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 45 of 57

Page 46: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Floor Finish

Deficiency Photo1

Room 202

Violations No violations recorded.

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Room 101, Corridor near Rooms 202, 212, by the old Kitchen

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Room 212

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency GYPSUM BOARD: DETERIORATED

Deficiency Location/Instance Corridor near Rooms 102, 104, 106, 107

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 46 of 57

Page 47: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Walls

Corridor near Room 102

Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK

Deficiency Location/Instance Rooms 201, 204, 205, 207, 208, corridor by Room 207, 2nd Floorcorridor by roof door

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor by Room 207

Violations No violations recorded.

Specialties Does not Exist

GYMNASIUM Does not Exist

INTERIOR DOOR HARDWARE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

INTERIOR GUARDS Does not Exist

KITCHEN Does not Exist

LIBRARY Does not Exist

LOCKER ROOM Does not Exist

MULTI-PURPOSE ROOM Inspected

InspectedInstance on Basement

Ceiling

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency ACOUSTIC TILES: DAMAGED/MISSING

Deficiency Location/Instance Near the closet

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 47 of 57

Page 48: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

INTERIOR

MULTI-PURPOSE ROOM

Ceiling

Deficiency Photo1

Near the closet

Violations No violations recorded.

Door(s)

InspectedInstance on Basement

Condition 3 - Fair

Deficiency METAL: DETERIORATED DOOR AND FRAME

Deficiency Location/Instance Main Entrance

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Main Entrance

Violations No violations recorded.

Fixed Equipment

Does not ExistInstance on Basement

Floor Finish

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Near the closet, by Main Entrance, in Exit Vestibule

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 48 of 57

Page 49: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

INTERIOR

MULTI-PURPOSE ROOM

Floor Finish

Deficiency Photo1

In the Exit Vestibule

Violations No violations recorded.

Sliding-folding Partition

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stage

Does not ExistInstance on Basement

Walls

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

Does not ExistInstance on Basement

SCIENCE DEMO ROOM Does not Exist

SCIENCE LAB Does not Exist

SCIENCE PREP ROOM Does not Exist

SHOWER ROOM Does not Exist

STAIRS/RAMPS: INTERIOR Inspected

Do Letter Stair Signs Exist? No

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK

Deficiency Location/Instance North Stair/2

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 49 of 57

Page 50: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Ceiling Inspected

North Stair/2

Violations No violations recorded.

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Partition Does not Exist

Railings Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stairs and Landings Inspected

Condition 2 - Between Good and Fair

Deficiency STONE: BROKEN/MISSING

Deficiency Location/Instance South Stair/1

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

South Stair/1

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK

Deficiency Location/Instance North Stair/2

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 50 of 57

Page 51: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR Inspected

Walls Inspected

North Stair/2

Violations No violations recorded.

TOILET ROOMS - STAFF Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK

Deficiency Location/Instance Unisex toilet by Room 108

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Unisex toilet by Room 108

Violations No violations recorded.

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stalls Inspected

Condition 5 - Poor

Deficiency RUST - MAJOR

Deficiency Location/Instance Women, Men toilet in the Basement

Deficiency Quantity 2

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 51 of 57

Page 52: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

INTERIOR

TOILET ROOMS - STAFF Inspected

Stalls Inspected

Women toilet in the Basement

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency GYPSUM BOARD: DETERIORATED

Deficiency Location/Instance Men toilet in the Basement

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Men toilet in the Basement

Violations No violations recorded.

TOILET ROOMS - STUDENTS Does not Exist

LIFE SAFETY Inspected

F.D. HOLDING AREA Does not Exist

STEEL STAIRS Does not Exist

SITE Inspected

CONTAINERIZATION Does not Exist

Drainage System for Asphalt Does not Exist

Drainage System for Concrete Inspected

Catch Basins/Manhole - Surrounded by concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Concrete Covering Does not Exist

Drainage System for Soil Does not Exist

DRINKING FOUNTAINS Does not Exist

FENCES Inspected

Condition 3 - Fair

Deficiency CONCRETE CURB: DAMAGED/DETERIORATED

Deficiency Location/Instance E.95th Street, Conklin Avenue

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 52 of 57

Page 53: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

SITE

FENCES

Deficiency Photo1

E.95th Street

Violations No violations recorded.

Deficiency WROUGHT IRON: DAMAGED/DETERIORATED

Deficiency Location/Instance E.95th Street

Deficiency Quantity 80

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

E.95th Street

Violations No violations recorded.

Deficiency WROUGHT IRON: MISSING SECTIONS

Deficiency Location/Instance E.95th Street

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

E.95th Street

Violations No violations recorded.

Deficiency CHAIN LINK: DAMAGED POST/RAIL

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 53 of 57

Page 54: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

SITE

FENCES

Deficiency Location/Instance In the Parking Lot

Deficiency Quantity 10

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

In the Parking Lot

Violations No violations recorded.

Deficiency CHAIN LINK: DAMAGED/DETERIORATED

Deficiency Location/Instance In the Parking Lot

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

In the Parking Lot

Violations No violations recorded.

IRRIGATION SYSTEM Does not Exist

PAVING Inspected

Student Non-Use Inspected

Gravel Exists? No

Asphalt Does not Exist

Concrete Inspected

Condition 3 - Fair

Deficiency CRACKS - MAJOR

Deficiency Location/Instance In the Parking Lot

Deficiency Quantity 300

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 54 of 57

Page 55: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

SITE

PAVING

Student Non-Use

Concrete

Purpose of Action LEVEL 2

Deficiency Photo1

In the Parking Lot

Violations No violations recorded.

Pavers Does not Exist

Student Use Does not Exist

Site Sidewalks & Walkways Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 3 - Fair

Deficiency CRACKS - MAJOR

Deficiency Location/Instance E.95th Street

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

E.95th Street

Violations No violations recorded.

Pavers Does not Exist

DOT Sidewalk Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 3 - Fair

Deficiency DAMAGED CURBS

Deficiency Location/Instance E.95th Street, Conklin Avenue

Deficiency Quantity 40

Quantity Uom L.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 55 of 57

Page 56: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

SITE

PAVING

DOT Sidewalk

Concrete

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 4

Deficiency Photo1

E.95th Street

Violations 56016

Deficiency HEAVING

Deficiency Location/Instance Conklin Avenue

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Conklin Avenue

Violations 56016

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance E.95th Street, Conklin Avenue

Deficiency Quantity 225

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 4

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818

PB/A&W Print Date: 9/14/2020Page 56 of 57

Page 57: NYC Department of EducationYear: 2016 Systems: Exterior Walls repointing; Bulkhead Walls, Chimney and Parapets repointing Year: 2015 Systems: Partial Roofing, Parapets and Coping repairs

Question Response

SITE

PAVING

DOT Sidewalk

Concrete Inspected

Deficiency Photo1

E.95th Street

Violations 56016

Pavers Does not Exist

PLAYGROUNDS Does not Exist

PLAYING SURFACE Does not Exist

RETAINING WALLS Does not Exist

SEATING Does not Exist

SITE WALLS (NOT RETAINING WALLS) Does not Exist

STAIRS/RAMPS: EXTERIOR Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K818