1. ALL STEEL PLATES, SHAPES, AND ITEMS SHALL BE
GALVANIZED PER SPECIFICATION SECTION 05 05 35
AND PAINTED PER SPECIFICATION SECTION 09 90 00.
2. REFER TO SPECIFICATION 46 41 11 FOR COMPLETE
MIXER MFR SCOPE OF SUPPLY.
3. CLEAN, POLISH AND SEAL TERRAZZO FLOOR PER
SPECIFICATION 09 66 13. EXTENTS OF CLEANING
SHOWN ON S04.
4. SEE DEMOLITION NOTES ON S01 FOR DUST CONTROL
REQUIREMENTS.
5. ALL DIMENSIONS TO BE FIELD VERIFIED.
NICHOLE M.
SAJDAK
ENGINEER
No.
50704
J. COOK
A. ALVAREZ
M01
RAPID MIX BUILDING - DEMOLITION AND
PROPOSED PLAN
N. SAJDAK
HGFEDCBA
1
2
3
4
A B C D E F G H
4
3
2
1
APPRDESCRIPTIONS / REVISIONS CHK'D
DRAWN BY:
CHECKED BY:
APPROVED BY:
DATE
DESIGNED BY: SEAL / STAMP
DRAWING No.
GLWA CIP No.
GLWA CONTRACT No.
RANGESECTION MAP SECTIONTOWN
MDEQ PERMIT No.
Q QQ
FACILITY
PROJECT TITLE
DRAWING TITLE
FIRM NAME
HAZEN AND SAWYER
3031 W. GRAND BLVD., SUITE 622
DETROIT, MICHIGAN 48202N.SAJDAK
SPRINGWELLS WATER TREATMENT PLANT
REPLACEMENT OF 1958 PROCESS TRAIN
RAPID MIX UNITS GLWA-CON-251
917
NMSREGULATORY REVIEW NMS 8/2017
W-179056
NMSBID DOCUMENTS NMS 12/2017
PROPOSED - PLAN AT EL 134.501/4" = 1'-0"
DEMOLITION - PLAN AT EL 134.501/4" = 1'-0"
7'-3" 7'-3"6'-9" 7'-3"
CHECKERED
C.I.
MANHOLE
COVER, TYPCHECKERED
C.I. COVER,
TYP
OLD MOTOR
CONTROL CENTER.
NEW MCC LOCATED
ON 2ND FLOOR.
REFER TO
CONTRACT SP-563
SERVICE SINK
7'-
6"
6'-
6"
7'-3" 7'-3"6'-9" 7'-3"
ABANDONED MOTOR
CONTROL CENTER.
MCC-09-03 AND
MCC-09-04 LOCATED
ON 2ND FLOOR
UNDER CONTRACT
SP-563
SERVICE SINK
7'-
6"
6'-
6"
STEEL BASE
PLATE, TYP
CM02
CM02
RAPID MIXER
RM-2A
RAPID
MIXER
RM-1B
RAPID MIXER
RM-1A
RM-2B
RM-2A
RM-1BRM-1A
MANHOLE STEPS AND GRAB BARS,
SEE STRUCTURAL DRAWINGS, TYP
OF 6 LOCATIONS
RE-USE LOCAL NON-FUSIBLE
DISCONNECT SWITCH AND CONTROL
STATION TO REMAIN, TYP.
EXISTING CHEMICAL FEED PIPING.
CONTRACTOR TO FIELD VERIFY
DIMENSIONS AND LOCATION IN FIELD.
REMOVE EXISTING
6"Hx8"W CURB TO
EXTENTS SHOWN TO
TOP OF SLAB EL
134.33, TYP OF FOUR
LOCATIONS
AM02
AM02
4"
TYP
5'-
0"
TYP
4"
TYP
4"
TYP
5'-0"
TYP
4"
TYP
8"
TYP
8"
TYP
8"
TYP
8"
TYP
B
B
B
B
CC
A
AA
A
REMOVE MANHOLE STEPS AND GRAB BARS. SEE STRUCTURAL DRAWINGS FOR
DETAILS.
REMOVE AND DEMOLISH RAPID MIX EQUIPMENT, BASE PLATE, CURB, GRANOLITHIC
LINER AND GROUT TO TOP OF CONCRETE EL. 134.33. CURB AND GROUT SHALL BE
DEMOLISHED AROUND FULL PERIMETER. DEMOLISH ELECTRICAL TO DISCONNECT
SWITCH.
DEMOLISH EXISTING CHEMICAL FEED PIPING TO EXISTING FLANGE. SEE SECTIONS
A AND B SHEET M02.
PROTECT ALL FLOORS AND STAIRS DURING CONSTRUCTION. SEE
SPECIFICATION 01 50 00, TEMPORARY FACILITIES.
A
B
C
RAPID
MIXER
RM-2B
REMOVE EXISTING
VERTICAL RISER PIPE AND
MANHOLE COVER. REPLACE
WITH NEW MANHOLE
COVER, SEE STRUCTURAL
DRAWINGS
RE-USE LOCAL NON-FUSIBLE
DISCONNECT SWITCH AND CONTROL
STATION TO REMAIN, TYP.
D
CL OF EXISTING
66" Ø BFV
CL OF EXISTING
66" Ø BFV
CL OF EX
66" Ø BFV
CL OF EX
66" Ø BFV
MAIN ACCESS
DOOR
23'-
9"
15'-
0"
5'-
6"
14'-9" 14'-0" 14'-9"
BM02
NEW MANHOLE
COVER, SEE
STRUCTURAL
DRAWINGS
NEW CONCRETE CURB
WITH TERRAZZO
FINISH. SEE
SPECIFICATION 09 66 13
COAT MH COVERS AND
FRAMES. TYP OF 7
3'-
10"
9'-
2"
NMSADDENDUM NO. 1 NMS 01/20181
EL 113.50
A AB B C
EL 127.50
EL 134.50 EL 134.33
EL 134.50
A AB B C
EL 134.33
EL 134.50
NOTES:
1. CONTRACTOR TO FIELD VERIFY LOCATION FORMOUNTING OF NEW CHEMICAL PIPING ANDDIFFUSER. ALL HARDWARE SHALL BE PAINTED HOTDIPPED GALVANIZED STEEL.
2. PROVIDE FRP BEAMS TO ACCOMMODATE PIPESUPPORTS. ALL ANCHORS, BOLTS, ANDHARDWARE ASSOCIATED WITH FRP BEAMS SHALLBE PAINTED HOT DIPPED GALVANIZED STEEL. SEESPECIFICATION 40 05 13.02 FOR PIPE SUPPORTSPACING REQUIREMENTS. SEE SPECIFICATIONSECTION 40 05 13.02-2.01.E.8.
3. NOTE THAT EXISTING BEAMS MAY BE PRESENTWITHIN THE RAPID MIX CHAMBERS. CONTRACTORMAY REQUEST TO USE EXISTING BEAMS TOACCOMMODATE REQUIRED PIPE SUPPORTS. SEESPECIFICATION SECTION 40 05 13.02-2.01.E.8.a.
4. SEE STANDARD DETAIL 1509411/ D01 FOR ALL PIPESUPPORTS.
5. ALL STEEL PLATES, SHAPES, AND ITEMS SHALL BEGALVANIZED PER SPECIFICATION SECTION 05 0535 AND PAINTED PER SPECIFICATION SECTION09 90 00.
6. REFER TO SPECIFICATION 46 41 11 FOR COMPLETEMIXER MFR SCOPE OF SUPPLY.
7. JET CLEAN TUBERCULATED SUCTION LINE.
NICHOLE M.
SAJDAK
ENGINEER
No.
50704
J. COOK
A. ALVAREZ
M02RAPID MIX BUILDING SECTIONS
N. SAJDAK
HGFEDCBA
1
2
3
4
A B C D E F G H
4
3
2
1
APPRDESCRIPTIONS / REVISIONS CHK'D
DRAWN BY:
CHECKED BY:
APPROVED BY:
DATE
DESIGNED BY: SEAL / STAMP
DRAWING No.
GLWA CIP No.
GLWA CONTRACT No.
RANGESECTION MAP SECTIONTOWN
MDEQ PERMIT No.
Q QQ
FACILITY
PROJECT TITLE
DRAWING TITLE
FIRM NAME
HAZEN AND SAWYER
3031 W. GRAND BLVD., SUITE 622DETROIT, MICHIGAN 48202
N.SAJDAK
SPRINGWELLS WATER TREATMENT PLANT
REPLACEMENT OF 1958 PROCESS TRAIN
RAPID MIX UNITS GLWA-CON-251
917
NMSREGULATORY REVIEW NMS 8/2017
W-179056
NMSBID DOCUMENTS NMS 12/2017
SECTION C1/4" = 1'-0" M01
STEEL BASE PLATE, DESIGNBY MANUFACTURER, TYP
RM-2A RM-2B
EAST 96" RAWWATER CONDUIT CL
4'-
9"
Ø66"
7'-
0"
Ø66"
3'-10"5'-4"
SUPPORT PEDESTAL, DESIGNBY MANUFACTURER TYP
BASE PLATE STIFFENERS,
DESIGN BY MANUFACTURER
INSTALL NEW 2 1/2" FLANGED
SCH 80 PVC PIPING. INSTALL IN 3SECTIONS. SEE NOTE 1.
INLET FLOW TARGET
BAFFLE WALL (SEE
STRUCTURAL DRAWINGS).
REMOVE BASEPLATE
AND DEMO CURB, TYP
REMOVE 4"Wx2"H TERRAZO FINISH ANDGROUT TOPPING TO EXTENTS SHOWN DOWN
TO TOS EL 134.33, AROUND FULL PERIMETER
OF CONCRETE CURB, SEE DETAIL 1/M02 FORORIGINAL GROUT TOPPING AND FINISHDETAIL, TYP
REMOVE 8"Wx6"H CONCRETE CURB TO EXTENTSSHOWN TO TOP OF CONCRETE EL 134.33, SEE
DETAIL 1/M02 FOR ORIGINAL CURB DETAIL, TYP
DEMO EXISTING ALUMFEED PIPING TO EX.
FLANGE. FIELD VERIFYLOCATION
SECTION A1/4" = 1'-0" M01
8" PVC CASING
PROVIDE FLANGE CONNECTION FROM
2 1/2" PVC TO 2 1/2" FLANGED
INJECTOR
APPROX. AREA OBSTRUCTED
BY OPEN 96" Ø BUTTERFLY
VALVE, SEE NOTE 3/S04
DEMOLITION PROPOSED
DEMOLITION NOTES:
1. REMOVE RAPID MIX EQUIPMENT. SEE KEYNOTE BSHEET M01.
2. EQUIPMENT NOT SHOWN IN SECTION FOR CLARITY.
FRP BEAM FOR PIPE SUPPORT,
SEE NOTES 2 AND 3/M02, TYP
96" Ø BFV, STEM AND
ACTUATOR (APPROX)
12'-
0"
6'-
0"
24"x24"x9" SUMP (TYP 2)
BOOSTER PUMP SUCTION
(APPROX. LOCATION)SEE NOTE 7.
CONNECT NEW ALUM PIPING
TO EXISTING FLANGE
DETAIL 1NTS M01
SECTION BN.T.S M01
DEMOLITION
FLANGED
CONNECTION (TYP)
FLUSHINGCONNECTION
TO CHAMBER
RH-2A
CONCRETE AND TERRAZZOCOATED PEDESTAL
EL. 113.5
EL. 130.33
NMSADDENDUM NO. 1 NMS 01/20181
A
4 3 2 1
AB
B
C
NOTES:
1. PROVIDE #5@32" OC VERTICAL ADHESIVE DOWELS AND AT WALL ENDS ABUTTING CONCRETE IN NEW 8" CMU BAFFLE WALL. DOWELS SHALL EXTEND FULL HEIGHT OF WALL INTO BOND BEAM. ADHESIVE DOWELS SHALL HAVE 6" MINIMUM EMBEDMENT INTO EXISTING CONCRETE SLAB. PROVIDE HEAVY DUTY CONTINUOUS GALVANIZED METAL WIRE TRUSS AT 16" OC FOR HORIZONTAL REINFORCING AT JOINTS. MASONRY BAFFLE WALLSSHALL BE COATED PER NOTE 1/S05.
2. TOP COURSE OF CMU WALL SHALL BE FULLY GROUTED BOND BEAM WITH 2-#5 BARS. BOND BEAMS SHALL BE ANCHORED INTO CONCRETE WALLS WITH 2-#5 HORIZONTAL ADHESIVE DOWELS, SIDE OF CMU WALL THAT PERPENDICULARLY ABUTS CONCRETE WALL (2 LOCATIONS TOTAL). ADHESIVE DOWELS SHALL HAVE 6" MINIMUM EMBEDMENT INTO EXISTING CONCRETE WALL. ADHESIVE DOWELS SHALL LAP A MINIMUM OF 45" WITHBOND BEAM BARS. PROVIDE 3/4"Ø GALVANIZED, PAINTED ADHESIVE ANCHORS (MIN EMBED = 6") AT THREE EQUALLY SPACED LOCATIONS ALONG HEIGHT OF WALL IN FULLY GROUTED LAST COURSE ON SIDE OF WALL ADJACENT TO CONCRETE WALL CORNER (2 LOCATIONS TOTAL, 6 ANCHORS TOTAL).
3. FIELD VERIFY THAT LOCATION OF NEW CMU BAFFLE WALL DOES NOT INTERFERE WITH OPENING AND CLOSING OPERATIONS OF 96"Ø AND 66"Ø BUTTERFLY VALVES. WALL SHALL BE LOCATED SO THAT THERE IS A MINIMUM OF 6" CLEARANCE BETWEEN BAFFLE WALL AND CLOSEST ELEMENT OF BUTTERFLY VALVES WHEN VALVES ARE OPEN, CLOSED, OR ANY POSITION IN BETWEEN.
4. FIELD VERIFY ALL DIMENSIONS AND ELEVATIONS.
5. REMOVE AND REPLACE EXISTING MANHOLE STEPS AND GRAB BARS. GRAB BARS SHALL BE PROVIDED AT FIVE OF THE SIX MANHOLE STEP LOCATIONS. MANHOLE STEPS SHALL BE CONSTRUCTED OF GRADE 60 STEEL REINFORCING ROD (MIN. 1/2-INCH) AND COMPLETELY ENCAPSULATED WITH A WEAR RESISTANT AND CHEMICAL RESISTANT PLASTIC. MANHOLE STEPS SHALL BE PER STANDARD DETAIL 0260008/D02. EACH MANHOLE STEPSHALL HAVE A MINIMUM VERTICAL LOAD RESISTANCE OF 800 POUNDS AND A MINIMUM PULL-OUT RESISTANCE OF 400 POUNDS. MANHOLE STEPS SHALL HAVE 14-INCH MINIMUM TREAD WIDTH AND SHALL BE PLACED AT A MAXIMUM SPACING OF 16-INCHES ON CENTER. CONTRACTOR SHALL COORDINATE LOCATION OF MANHOLE STEPS AROUND EXISTING MANHOLE STEPS ANCHORS. CONTRACTOR SHALL ASSUME EXISTING MANHOLESTEPS ARE AT 16" ON CENTER FOR BID PURPOSES. CONTRACTOR SHALL SUBMIT PROPOSED MANHOLE STEPS AND ANCHORAGE TO ENGINEER FOR APPROVAL. SEE DEMOLITION NOTE D-3/S01 FOR ANCHORAGE REMOVAL REQUIREMENTS. VERIFY REQUIRED QUANTITY OF MANHOLE STEPS PRIOR TO ORDERING.
6. SEE MECHANICAL DRAWINGS FOR EXISTING CONCRETE CURB AND GROUT DEMOLITION.
7. ALL STEEL PLATES, SHAPES, AND ITEMS SHALL BE GALVANIZED PER SPECIFICATION SECTION 05 05 35 AND PAINTED PER SPECIFICATIONS SECTION 09 90 00.
8. EXISTING AND NEW MANHOLE LIDS AND FRAMES SHALL BE CLEANED AND PREPARED FOR PAINTING PER SPECIFICATION SECTION 09 90 00. AFTER SURFACES HAVE BEEN PREPARED, MANHOLE LIDS AND FRAMES SHALL BE PAINTED. ALL WORK AND MATERIALS SHALL BE PER SPECIFICATION SECTION 09 90 00. PAINT COLOR SHALL BE SELECTED BY OWNER.
9. PORTLAND CEMENT TERRAZZO FINISH SHALL BE PROVIDED ON ALL EXPOSED SIDES AND TOPS OF NEW CONCRETE CURBS. TRANSITION BETWEEN NEW TERRAZZO FINISH ON SIDE OF NEW CONCRETE CURB AND EXISTING TERRAZZO FINISH ON TOP OF EXISTING FLOOR SLAB SHALL BE AS RECOMMENDED BY TERRAZZO MANUFACTURER AND CONTRACTOR. METAL STRIP USED AT TRANSITION SHALL ONLY BE ALLOWED IF APPROVED BYOWNER. SUBMIT TERRAZZO TRANSITION DETAILS AND COLORING TO OWNER AND ENGINEER FOR APPROVAL. TERRAZZO FINISH SHALL BE 1/2" THICK. SEE SPECIFICATION 09 66 13 FOR ADDITIONAL REQUIREMENTS.
10. NEW MANHOLE COVER SHALL BE CHECKERED CAST IRON BY NEENAH FOUNDRY OR EQUAL. MANHOLE COVER SHALL MATCH OR BE SIMILAR TO OTHER MANHOLE COVERS IN STRUCTURE. CONTRACTOR SHALL FIELD VERIFY SIZE OF REQUIRED MANHOLE COVER DIAMETER. MANHOLE COVER SHALL BE RATED FOR 300 PSF LIVE LOAD. MANHOLE COVER SHALL BE SUITABLE FOR 20 PSI INTERNAL PRESSURE. MANHOLE COVER SHALL INCLUDEWATERTIGHT GASKETING, PATTERNS, LETTERING, AND PICKHOLES. CONTACT SURFACES SHALL BE MACHINED TO PREVENT ROCKING. MANHOLE COVER SHALL SIT FLUSH WITH SURROUNDING FINISHED SURFACE. CONTRACTOR SHALL SUBMIT MANHOLE SUBMITTAL INDICATING WATERTIGHT GASKET, PATTERNS, LETTERING, AND PICKHOLE LOCATIONS TO ENGINEER AND OWNER FOR APPROVAL PRIOR TO FABRICATION.
K. FICKER
K. FICKER
S04RAPID MIX BUILDING - TOP AND BOTTOM PLANS
W. LEADBITTER
HGFEDCBA
1
2
3
4
A B C D E F G H
4
3
2
1
APPRDESCRIPTIONS / REVISIONS CHK'D
DRAWN BY:
CHECKED BY:
APPROVED BY:
DATE
DESIGNED BY: SEAL / STAMP
DRAWING No.
GLWA CIP No.
GLWA CONTRACT No.
RANGESECTION MAP SECTIONTOWN
MDEQ PERMIT No.
Q QQ
FACILITY
PROJECT TITLE
DRAWING TITLE
FIRM NAME
HAZEN AND SAWYER
3031 W. GRAND BLVD., SUITE 622DETROIT, MICHIGAN 48202
N.SAJDAK
SPRINGWELLS WATER TREATMENT PLANT
REPLACEMENT OF 1958 PROCESS TRAIN
RAPID MIX UNITS GLWA-CON-251
917
NMSREGULATORY REVIEW NMS 8/2017
W-179056
NMSBID DOCUMENTS NMS 12/2017
PLAN AT EL 113.501/4" = 1'-0"
8" CMU WALL, SEE NOTES
1, 2, AND 3/S04, TYP
10'-8" 10'-8"
12'-
4"
13'-0" 16" 12'-8"
5'-
0"
13'-0"
4'-
6"
13'-
0"
16"
17'-
8"
8"
5'-
6"
4"
CONCRETE PROTECTIVELINER COATING, SEE
NOTES 1, 2, AND 3/S05,TYP
AS05
AS05
BS05
BS05 8
"
PLAN AT EL 134.501/4" = 1'-0"
STEEL BASE PLATE ANDSTIFFENERS, SEE NOTES 5 AND
7/S05, TYP OF FOUR LOCATIONS
W8
W8
W8
W8
W8
EXISTING W8, SEE
NOTE 4/S05, TYP
EXISTING MANHOLE
FRAME AND LID, SEE
NOTE 8/S04 TYP
AS05
AS05
BS05
BS05
MANHOLE STEPS,
SEE NOTE 5/S04,
TYP OF 6LOCATIONS
MANHOLE STEPS,
SEE NOTE 5/S04, TYP
OF 6 LOCATIONS
18"
12"Wx6"H
TYP
SEE NOTE 6/S04
APPROXIMATE CL
LOCATION OF 66"ØBUTTERFLY VALVE,
SEE NOTE 3/S04
APPROXIMATE LOCATION OF
96"Ø BUTTERFLY VALVE, SEE
NOTE 3/S04, TYP
APPROXIMATE OPERATING
OUTLINE OF 96"Ø BUTTERFLY
VALVE, SEE NOTE 3/S04, TYP
3S02 TYP
3/4"Ø ADHESIVE
ANCHOR, SEE
NOTE 2/S04ADHESIVE DOWELIN BOND BEAM, SEE
NOTE 2/S04, TYP
TERRAZZO FLOORING ON CONCRETE
CURB, SEE NOTE 9/S04, TYP
EXISTINGCONCRETE WEIR
WALL BELOW, TYP
EXISTING24"Wx24"Lx9"D SUMP,
TYP OF TWO LOCATIONS
20'-
6"
15'-
0"
5'-
6"
14'-9" 14'-0" 14'-9"
2'-
6"
TYP
9'-9"
TYP12"
TYP
4'-4 1/2"
TYP
4'-4 1/2"
TYP
66" BUTTERFLYVALVEACTUATOR
STEMPENETRATION,
TYP OF TWOLOCATIONS
EXISTING STEEL PLATE IN
AREA OF 96" BUTTERFLY VALVESTEM SHALL REMAIN, TYP
LIMITS OF EXISTING TERRAZZO FLOOR
TO BE CLEANED PER NOTE 3/M01,
LIMITS SHALL INCLUDE ALL EXISTINGTERRAZZO FLOORS WITH FFE 134.50
WITHIN HATCHED LINE WORK AREA
WILLIAM G.
LEADBITTER
ENGINEER
No.
65802
REMOVE EXISTING VERTICALPIPE RISER AND MANHOLE
COVER, REPLACE WITH NEWMANHOLE COVER, SEE NOTES
8 AND10/S04
NMSADDENDUM NO. 1 NMS 01/20181
A AB B C 4 3 2 1
CORNER
EXISTING PIPE OR SLEEVE
PIPE PENETRATION
LINER COATINGSYSTEM
CONCRETE SUBSTRATE
LINER COATING SYSTEM, TYP
CONCRETESUBSTRATE, TYP
1" DEEP MIN GROOVE,TYP
TERMINATION
LINER COATING SYSTEM
1" DEEP MIN GROOVE
CONCRETESUBSTRATE
2" RADIUS CORNER W/45° CANT AT CORNER
1 1/2" THICK CHEMICALRESISTANT NON-SAG CAULKINGMATERIAL AROUND PIPE,APPROVED BY COATINGMANUFACTURER
1/4
"
TERMINATION AT ANCHOR
LINER COATING SYSTEM
CONCRETE SUBSTRATE
ANCHOR PER DRAWINGS
1/4" THICK CHEMICALRESISTANT NON-SAG CAULKINGMATERIAL AROUND ANCHOR,APPROVED BY COATINGMANUFACTURER
NOTES:
1. COAT INTERIOR SURFACES OF RAPID MIX BASINSTO EXTENTS SHOWN WITH PROTECTIVE CONCRETELINER COATING. INTERIOR SURFACES SHALLINCLUDE ALL WALL SURFACES BETWEENELEVATIONS 112.75 AND 134.33 AND UNDERSIDEOF ELEVATED SLABS. STOP THE COATING 6"BELOW TOP OF COMPONENT AT LOCATIONSWHERE COATING DOES NOT EXTEND ONTOADJACENT COMPONENT OR EXTEND OVER TOP OFWALL. STOP COATING 6" ABOVE BASE SLABALONG ALL COATED WALLS. TERMINATE COATINGINTO SAWCUT JOINTS PER COATINGMANUFACTURER'S RECOMMENDATIONS ANDDETAIL 2/S05. SEE COATING NOTES ON S05.REFER TO SPECIFICATION SECTION 09 96 35 FORLINER COATING REQUIREMENTS. ALL SIDES,INCLUDING TOP, OF CMU AND CONCRETE BAFFLEWALLS SHALL BE COATED.
2. PROVIDE A 2" 45° CANT COVE AT ALL 90° ANGLESBETWEEN ADJACENT WALLS AND WALLS ANDSLABS.
3. ANY ELEMENTS THAT REQUIRE TEMPORARYREMOVAL OR DEMOLITION FOR INSTALLATION OFNEW CONSTRUCTION SHALL BE RESTORED TOTHEIR ORIGINAL CONDITION UPON COMPLETIONOF ALL NEW CONSTRUCTION.
4. EXISTING GALVANIZED AND PAINTED STEELW8x21 BEAMS, CONNECTION ANGLES, ANDASSOCIATED HARDWARE (ANCHORS, BOLTS,WASHERS, NUTS, ETC.) SHALL BE CLEANED ANDPREPARED FOR PAINTING PER SPECIFICATIONSECTION 09 90 00. SURFACE PREPARATION SHALLBE PERFORMED IN A WAY SO THAT GALVANIZEDCOATING BELOW EXISTING PAINT IS NOTDAMAGED OR REMOVED. AFTER SURFACES HAVEBEEN PREPARED, ALL EXPOSED BEAM SURFACESSHALL BE PAINTED. ALL WORK AND MATERIALSSHALL BE PER SPECIFICATION SECTION 09 90 00.PAINT SHALL MATCH COLOR OF EXISTING PAINT.
5. DESIGN SHALL BE BY EQUIPMENT MANUFACTURER.REFER TO SPECIFICATION SECTION 46 41 11 FORCOMPLETE MIXER MANUFACTURER SCOPE OFSUPPLY.
6. FIELD VERIFY ALL DIMENSIONS AND ELEVATIONS.
7. ALL STEEL PLATES, SHAPES, AND ITEMS SHALL BEGALVANIZED PER SPECIFICATION SECTION 05 0535 AND PAINTED PER SPECIFICATION SECTION 0990 00.
8. GASKET SHALL BE MEDIUM/INDUSTRIAL GRADENEOPRENE, DUROMETER HARDNESS 55 (SHORE A).
K. FICKER
K. FICKER
S05RAPID MIX BUILDING - SECTIONS AND DETAILS
W. LEADBITTER
HGFEDCBA
1
2
3
4
A B C D E F G H
4
3
2
1
APPRDESCRIPTIONS / REVISIONS CHK'D
DRAWN BY:
CHECKED BY:
APPROVED BY:
DATE
DESIGNED BY: SEAL / STAMP
DRAWING No.
GLWA CIP No.
GLWA CONTRACT No.
RANGESECTION MAP SECTIONTOWN
MDEQ PERMIT No.
Q QQ
FACILITY
PROJECT TITLE
DRAWING TITLE
FIRM NAME
HAZEN AND SAWYER
3031 W. GRAND BLVD., SUITE 622DETROIT, MICHIGAN 48202
N.SAJDAK
SPRINGWELLS WATER TREATMENT PLANT
REPLACEMENT OF 1958 PROCESS TRAIN
RAPID MIX UNITS GLWA-CON-251
917
NMSREGULATORY REVIEW NMS 8/2017
W-179056
NMSBID DOCUMENTS NMS 12/2017
8" CMU WALL, SEE NOTES
1, 2, AND 3/S04, TYP
±
8" CMU, SEE NOTES 1 AND 3/S04
#5@32" OC VERTICAL ADHESIVE
DOWELS AND AT WALL ENDS,MIN EMBED = 6", SEE NOTE
1/S04
BOND BEAM W/ 2-#5
BARS, SEE NOTE 2/S04
EXISTING CONCRETE SLAB
CONCRETE PROTECTIVE
LINER COATING, SEE NOTES
1, 2, AND 3/S05, TYP
SECTION A1/4" = 1'-0" S04
1S05
DETAIL 11" = 1'-0" S05
SECTION B1/4" = 1'-0" S04
STEEL BASE PLATE,
SEE NOTE 5/S05, TYP
STEEL BASE PLATE,
SEE NOTE 5/S05, TYP
CONCRETE PROTECTIVELINER COATING, SEE NOTES
1, 2, AND 3/S05, TYP
DETAIL 21 1/2" = 1'-0"
LINER COATING DETAILS
S05
COATING NOTES:
1. DETAILS FOR ALL PROPOSED TERMINATION POINTS OF THE LINER COATINGSYSTEM SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL.
2. ALL TERMINATION POINTS OF THE LINER COATING SYSTEM SHALL BE INSTALLEDPER MANUFACTURER'S RECOMMENDATION DETAILS.
3. REPAIR/SURFACER FILL COAT PORTION OF CONCRETE PROTECTIVE COATINGSYSTEM NOT SHOWN.
EXISTING W8x21,
SEE NOTE 4/S05
EXISTING W8x21,
SEE NOTE 4/S05
STEEL BASE PLATE STIFFENER,
SEE NOTE 5/S05, TYP
STEEL BASE PLATESTIFFENER, SEE
NOTE 5/S05, TYP
APPROXIMATE OUTLINE OF
96" Ø BUTTERFLY VAVLE,
SEE NOTE 3/S04
APPROXIMATE LOCATION
OF 66"Ø BUTTERFLY
VALVE, SEE NOTE 3/S04
TYP
12"Wx6"H
TYP
12"Wx6"H
MANHOLE STEPS, SEE
NOTE 5/S04
MANHOLE STEP GRAB
BAR, SEE NOTE 5/S04
EXISTING MANHOLE FRAME
AND LID, SEE NOTE 8/S04, TYP
APPROXIMATE LOCATION
OF 66"Ø BUTTERFLY VALVE
APPROXIMATE AREA
OBSTRUCTED BY OPEN
96" Ø BUTTERFLY
VALVE, SEE NOTE 3/S04
ELEVATED FLOOR
SLAB, TYP
ELEVATED FLOOR
SLAB, TYP
TERRAZZO FINISH ON
CONCRETE CURB, SEE
NOTE 9/S04, TYP
TOP OF EXISTING CONCRETE
WEIR WALL BEYOND 127.50
6'Hx12'-8"W MIXED WATERCONDUIT OPENING BEYOND
TERRAZZO FINISH ON CONCRETE
CURB, SEE NOTE 9/S04, TYP
1/2"x4" 4-SIDED GASKET,
SEE NOTE 8/S05, TYP
1/2"x4" 4-SIDED
GASKET, SEE
NOTE 8/S05, TYP
EXISTING CONCRETEWEIR WALL
EXISTING CONCRETEWEIR WALL
WEIR WALLWEIR WALL
5'-0"
MIN
WILLIAM G.
LEADBITTER
ENGINEER
No.
65802
NMSADDENDUM NO. 1 NMS 01/20181