    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | JGroff@coj.net  

TheCityofJacksonvilleinordertooptimizefireandrescueoperationcommunicationsonscenesoffireandotheremergenciesandtocomplywiththeFloridaFirePreventionCodeNFPA1Chapter11.10asmodifiedbyFloridaStatute633.202(18)willrequireminimumradiosignalstrengthlevelsforcommunicationsforallnewandexistingbuildings.(Seebelowforcode,statutorylanguage,andDeclaratoryStatement). NFPA1Chapter11.1011.10Two‐WayRadioCommunicationEnhancementSystems11.10.1Inallnewandexistingbuildings,minimumradiosignalstrengthforfiredepartmentcommunicationsshallbemaintainedataleveldeterminedbytheAHJ.TheleveldeterminedtobeacceptableintheCityofJacksonvillewillbeasstipulatedintheInternationalFireCodeSection510.4.1Thebuildingshallbeconsideredtohaveacceptableemergencyresponderradiocoveragewhensignalstrengthmeasurementsin95%ofallgeneralareasofthebuildingand99%incriticalareasincludingelevators(measuredattheprimaryrecallfloor),stairshaftsandFireCommandCenterswheretheminimumsignalstrengthof‐95dBmshallbereceivablewithinthebuilding.FS633.202 FloridaFirePreventionCode:(18)Theauthorityhavingjurisdictionshalldeterminetheminimumradiosignalstrengthforfiredepartmentcommunicationsinallnewhigh‐riseandexistinghigh‐risebuildings.Existingbuildingsarenotrequiredtocomplywithminimumradiostrengthforfiredepartmentcommunicationsandtwo‐wayradiosystemenhancementcommunicationsasrequiredbytheFloridaFirePreventionCodeuntilJanuary1,2022.However,byDecember31,2019,anexistingbuildingthatisnotincompliancewiththerequirementsforminimumradiostrengthforfiredepartmentcommunicationsmustapplyforanappropriatepermitfortherequiredinstallationwiththelocalgovernmentagencyhavingjurisdictionandmustdemonstratethatthebuildingwillbecomecompliantbyJanuary1,2022.ExistingapartmentbuildingsarenotrequiredtocomplyuntilJanuary1,2025.However,existingapartmentbuildingsarerequiredtoapplyfortheappropriatepermitfortherequiredcommunicationsinstallationbyDecember31,2022.

City of Jacksonville 

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | JGroff@coj.net  

NoticeofDeclaratoryStatement

NOTICEISHEREBYGIVENthatDepartmentofFinancialServiceshasissuedanorder disposing of the petition for declaratory statement filed by Charles B.Parks, Chief Fire CodeOfficial ofBroward County on February 02, 2018.Thefollowingisasummaryoftheagency'sdispositionofthepetition:TheAmendedPetition requests a determination as towhether Section 633.202(18), FloridaStatutes,prohibitstheenforcementofNFPA1,section11.10,inbuildingsunder75 feet in height. The Department concludes section 633.202(18), FloridaStatutes,doesnotapplytotheenforcementofNFPA1,section11.10,inbuildingsunder75feetinheight.Sowhatdoesthatallmean?

Allnewandexistingbuildingsbelowrequiredthresholdmustcomply.Ifradiosignalstrengthaftersignalsurveyisfoundtobebelowacceptablethreshold,aBDAsystemwillberequired.

ExistingHigh‐risesmustcomplybyJan1,2022howeverapermitforsaidbuildingsmustbepulledbyDec.31,2019.

ExistingapartmentbuildingsarenotrequiredtocomplyuntilJanuary1,2025.However,existingapartmentbuildingsarerequiredtoapplyfortheappropriatepermitfortherequiredcommunicationsinstallationbyDecember31,2022.

Asperthe69ADec.statement(forclarification)allotherbuildingsnotmeetingminimumsignalstrengthsasdeterminedbyaradiosurveyperformedbyaFCClicensedentityaredeemednon‐compliantandwillberequiredtoinstallaBDA.TheCityofJacksonvillehasdeterminedthatthoseoccupancieswillbeallowedtoshowcompliancebyapplyingfortheappropriatepermitfortherequiredcommunicationsinstallationbyDecember31,2022withinstallationcompletednolaterthanJan1,2025.Allnewconstructionbuildingwillberequiredtocomplyaspartoftheirpermittingprocess.

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | JGroff@coj.net  

BuildingSurveyRequirements:

ThecityofJacksonvilleutilizesa28channelMotorola800MhzLinearsimulcastP25radiosystem.Wehave4availablecontrolchannelstransmittingintherangeof855.2100Mhzand856.000Mhz.Oursystemfrequencyrangeis807.000Mhz.to816.00Mhz.forBaseRXand854.900Mhz.to861.000Mhz.forBaseTX.

Ourcontrolchannelsareasfollows:

Wearecurrentlyusechannel4asprimary.

Oncethebuildingissubstantiallycompleteoranexistingbuildingissuspectedofhavingcomplianceissues,aqualifiedFCCGrollicensedvendorwillperformthesignalsurveytocheckthecurrentradiosignallevelsinsidethebuilding.

VendorwillmeasuretheincomingsignallevelsbymonitoringtheAHJradiorepeatertalk‐outfrequency.VendorshallnotifyCityofJacksonvilleRadioShopandgetapprovalforthetesting.StevenHaynerRadioSystemsEngineer(904)904‐255‐7418/Email:SHayner@coj.net

Ifthemeasurementsshowthatthelevelsareabovetherequiredthreshold,thevendorwillthanprepareareportstatingbuildingisincompliancesignedbyFCCLicenseewithtestingdataattached.PassingsurveyresultswillbesubmittedtotheOfficeofFirePlansreviewforarchivalpurposes.Iflevelsarebelowtherequiredthreshold,aBDAwillberequired.

1 855.9875 810.9875

2 855.9625 810.9625

3 855.4875 810.4875

4 855.2125 810.2125

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | JGroff@coj.net  

TechnicalInformationforBDAdesign:Systemshallcomplyandmeetthefollowingrequirements:

FloridaAdministrationCode:61G15‐33.005DesignofCommunicationSystemsFloridaStateStatues:TitleXXXVII,Insurance–Chapter633.202and633.551,FirePreventionandControlFloridaFirePreventionCode(FFPC)SixthEdition;69A‐60.005NFPA1.11.10Two–WayCommunicationNFPA1221,2016Edition,Standardfortheinstallation,Maintenance,andUseofEmergencyServicesCommunicationSystemsNFPA72,2013Edition,NationalFireAlarmCode;Chapt.10Section6;Chapt.24;Sections24.5.2.21through24.5.2.2.3FloridaBuildingCode(FBC)2017SixthEditionNFPA70,2014Edition,NationalElectricalCode

RetrofitBDAsystemswillrequireabuildingpermitthroughTheCityofJacksonville’sBuildingDepartmentduetotheratedenclosurerequirements.Newconstructionbuildingsthatareabletoshowenclosuresonnewconstructionbuildingplanswillbeabletopullanassociatedfirepermitinlieuofbuildingpermit.AdditionalassociatedelectricalandfirepermitsmayberequiredforelectricalandfirealarmworkrelatedtoBDA.

Licenserequirementforinstallation:ECCertifiedElectricalContractor,EFCertifiedAlarmSystemContractorI,EYRegisteredAlarmSystemContractor1,ESCertifiedTwo‐WayRadioCommunicationsEnhancementSystemSpecialtyalongwithFCCGrolLicense.

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | JGroff@coj.net  

Frequenciesrequired:Systemfrequencyrangeis807.000Mhz.to816.00Mhz.forBaseRXand854.900Mhz.to861.000Mhz.forBaseTX

Locationofradiositesforpublicsafetyradioenhancementsystem:

1.) HoganRoad8675HoganRd.2.) YellowWater2015YellowWaterRd.3.) LloydRd.2630LloydRd.4.) Greenland14247OldSt.AugustineRd.5.) JaxBeach95010thStreetSouth6.) Firestone6878FirestoneRd.7.) SJRPP11201NewBerlinRd.8.) CenterPark2797KernanRd.S9.) JEAPlaza21W.ChurchSt.

Listofspecificallyapprovedsystemcomponents:Allsystemcomponentsshallbedesigned,installed,tested,inspected,andmaintainedinaccordancewiththemanufacturers’publishedinstructionsandtherequirementsofSection9.6.ofNFPA12212016.

Ratingrequirements:

Risercoaxialcables(AntennadonorCabletoBDAheadend)shallberatedasrisercablesandroutedthrougha2‐hour–ratedenclosure.

Thefeederandrisercoaxialcables(FromBDAHeadendtoantennasorremotes)shallberatedasplenumcablesthatmatchthebuilding’sfireratingandpathwaysurvivability.See12212016TIA16‐2

Theconnectionbetweentheriserandfeedercoaxialcablesshallbe

madewithinanenclosurematchingthebuilding’sfireratingandpathwaysurvivability,andpassageofthefeedercableinandoutoftheenclosureshallbefire‐stoppedtothebuilding’sfireratingandpathwaysurvivability.See12212016TIA16‐2

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | JGroff@coj.net  

PathwaySurvivabilityRequirements:

PathwaysurvivabilityrequirementswillbebasedoffcurrentlyadoptededitionofNFPA72.

Forsystemsemployingrelocationorpartialevacuation,Level2orLevel3pathwaysurvivabilityshallberequired.Forsystemsthatdonotemployrelocationorpartialevacuation,aLevel1,Level2,orLevel3pathwaysurvivabilityshallberequired.

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | JGroff@coj.net  

PathwaySurvivabilityLevelsDefined:

PathwaySurvivabilityLevel1:PathwaysurvivabilityLevel1shallconsistofpathwaysinbuildingsthatarefullyprotectedbyanautomaticsprinklersysteminaccordancewithNFPA13,StandardfortheInstallationofSprinklerSystems,withanyinterconnectingconductors,cables,orotherphysicalpathwaysinstalledinmetalraceways.

PathwaySurvivabilityLevel2:PathwaysurvivabilityLevel2shallconsistofoneormoreofthefollowing:(1)2‐hourfire‐ratedcircuitintegrity(CI)cable(2)2‐hourfire‐ratedcablesystem[electricalcircuitprotectivesystem(s)](3)2‐hourfire‐ratedenclosureorprotectedarea(4)2‐hourperformancealternativesapprovedbytheauthorityhavingjurisdiction.PathwaySurvivabilityLevel3PathwaysurvivabilityLevel3shallconsistofpathwaysinbuildingsthatarefullyprotectedbyanautomaticsprinklersysteminaccordancewithNFPA13,StandardfortheInstallationofSprinklerSystems,andoneormoreofthefollowing:(1)2‐hourfire‐ratedcircuitintegrity(CI)cable(2)2‐hourfire‐ratedcablesystem[electricalcircuitprotectivesystem(s)](3)2‐hourfire‐ratedenclosureorprotectedarea(4)2‐hourperformancealternativesapprovedbytheauthorityhavingjurisdictionisapathwayinbuildingsthatarefullyprotectedbyautomaticsprinklersystemandcablesareinstalledinmetalraceways.RadioCoverageRequirements: Criticalareastoincludefirecommandcenters,firepumprooms,exitstairs,

exitpassageways,elevatorlobbies,standpipecabinets,sprinklersectionalvalvelocations,andotherareasdeemedcriticalbytheauthorityhavingjurisdiction,shallbeprovidedwith99%floorarearadiocoverage.

Generalbuildingareasshallbeprovidedwith95%floorarearadio

coverage.

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | JGroff@coj.net  

SignalStrengthRequirements:

Minimuminboundsignalstrengthof−95dBmshallbeprovidedthroughoutthecoverageareawithaninboundsignallevelofDAQ3.0

Minimumoutboundsignalstrengthof−95dBmatthedonorsiteshallbeprovided

fromthecoverageareawithanoutboundsignallevelofDAQ3.0

IsolationRequirements: Isolationshallbemaintainedbetweenthedonorantennaandallinside

antennastoaminimumof20dBunderalloperatingconditions.

MaximumacceptablepropagationDelay:

15Microseconds.

FrequencyChanges:

Systemsshallbeupgradeabletoallowforinstanceswherethejurisdictionchangesoraddssystemfrequenciestomaintainradiosystemcoverageasitwasoriginallydesigned.

ComponentEnclosureRequirements:

Allrepeater,transmitter,receiver,signalboostercomponents,externalfilters,andbatterysystemcomponentsshallbecontainedinaNEMA4‐orNEMA4X‐typeenclosure(s).

ComponentRequirements:

RFemittingdevicesandcablingusedintheinstallationofthepublicsafetytwo‐wayradiocommunicationsenhancementsystemsshallbeapprovedbytheAHJ,andallRFemittingdevicesshallhavethecertificationofthe

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | JGroff@coj.net  

Radiolicensingauthorityandbesuitableforpublicsafetyusepriorto

installation.

RFemittingdevicesshallmeetthefollowingrequirementsinadditiontoanyotherrequirementsdeterminedbytheAHJ:

(1)RFemittingdevicesshallhavethecertificationoftheradiolicensingauthoritypriortoinstallation.(2)AllRFemittingdevicesshallbecompatiblewithbothanaloganddigitalcommunications,asrequiredtobeusedbytheradiolicensingauthorityandtheAHJ,simultaneouslyatthetimeofinstallation.

PowerSupplies:

AtleasttwoindependentandreliablepowersuppliesshallbeprovidedforallRFemittingdevicesandanyothercomponentsofthesystem:oneprimaryandonesecondary.

TheprimarypowersourceshallbesuppliedfromadedicatedbranchcircuitandcomplywithNFPA72.

Thesecondarypowersourceshallconsistofoneofthefollowing:Astoragebatterydedicatedtothesystemwith12hoursof100percentsystemoperationcapacity

Analternativepowersourceof12hoursat100percentsystemoperationcapacityasapprovedbytheAHJ

SystemMonitoringRequirements:

Thesystemshallincludeautomaticsupervisorysignalsformalfunctionsofthetwo‐wayradiocommunicationsenhancementsystemsthatareannunciatedbythefirealarmsysteminaccordancewithNFPA72,andshallcomplywiththefollowing:

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | JGroff@coj.net  

MonitoringforintegrityofthesystemshallcomplywithNFPA72,Chapter10.

Systemsupervisorysignalsshallincludethefollowing:

(a)Donorantennamalfunction(b)ActiveRFemittingdevicefailure(c)Low‐batterycapacityindicationwhen70percentofthe12‐houroperatingcapacityhasbeendepleted(d)Systemcomponentfailure.PowersupplysupervisorysignalsshallincludethefollowingforeachRFemittingdeviceandsystemcomponent:(a)Lossofnormalacpower(b)Failureofbatterycharger

Thecommunicationslinkbetweenthefirealarmsystemandthetwo‐wayradiocommunicationsenhancementsystemmustbemonitoredforintegrity.

DedicatedPanelrequirements:

AdedicatedmonitoringpanelshallbeprovidedwithinthefirecommandcentertoannunciatethestatusofallRFemittingdevicesandsystemcomponentlocations.ThemonitoringpanelshallprovidevisualandlabeledindicationsofthefollowingforeachsystemcomponentandRFemittingdevice:(a)Normalacpower(b)Lossofnormalacpower(c)Batterychargerfailure(d)Lowbatterycapacity(to70percentdepletion)(e)Donorantennamalfunction(f)ActiveRFemittingdevicemalfunction(g)Systemcomponentmalfunction.Thecommunicationslinkbetweenthededicatedmonitoringpanelandthetwo‐wayradiocommunicationsenhancementsystemmustbemonitoredforintegrity.

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | JGroff@coj.net  

ConvergedSystems:

RadioenhancementsystemsBDAandDAScanshareantennasandcablingaslongasbothcomplywithalltherequirementsintheaforementionedtechnicalinformationforBDAdesignaspreviouslylisted.

Planssubmittalminimumrequirements:

Buildingownerandaddress(FAC61G6) CopyofthecontractwiththeownerorGC(FBC118.1.4) SignatureandsealoftheEngineerofRecordwithexperienceandtraining

inelectricalengineering.Thename,PEnumber,businessname,CAnumber,address,andcontactinformationshallbeshownontheplans.(NFPA72‐10.5)(FAC118.1.4)(61G15‐30.003(2)

Applicablecodesandeditiondates(61g15‐30.003(1b) Buildingdescriptionshowingbuildingconstruction,buildingoccupancy,

totalsquarefootage,numberoffloors,totalheightofbuilding(FAC61G15) Floorplansshowingdevicelocations,fire‐ratedenclosures,conduitruns,

andpropagationmodeling,etc.Propagation(heat)mapdrawingsshallincludethefollowing(FBC118.2.1.4):☐IndoorPredictionLegend☐MaterialsLegend☐PictogramLegend☐CablesLegend☐CalculationsLegend☐NumberofChannels☐Frequencies☐Predictivepropagationonfloorplans☐Nameofcertifieddesignerandcompany

Riserplansforsystems(FAC61G15) Specificationswithmanufacturer’spartsnumbers(FAC61G15) Details,includingfirewallpenetration,etc.(FAC61G15) Manufacturer’sspecificationsforequipment(FAC61G15) Antennaandsurgeprotectordetail(FAC61G15) Notesonplansshallstate(FBC118.4.2.2):“Thesystemshallneverbe

energizedfortestingoroperationuntilwritten,oronsite,approvalisobtainedfromtheFCCLicenseHolder.”

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | JGroff@coj.net  

TheBDAenclosureshallbepaintedredandasignshallshowpermit

number,vendornameandtelephonenumber.(FBC118.2.1.8) Pathwaysurvivabilitylevelshallbe1,2,or3.Level1:Allcoaxialcables

shallbeinmetalconduit.(NFPA72‐12.4) Radiocoverageshallbeaminimumof99%incriticalareasand95%in

generalbuildingareas.(NFPA72‐24.5.2.2)☐16. Signalstrengthinboundshallbeaminimumof‐95dBm.Signalstrength

outboundshallbeaminimumof‐95dBm.(NFPA72‐24.5.2.3)Note:asignalstrengthoflessthan‐90dBmasshownontheplanshasahighprobabilityoffailingthefinalinspectionofDAQ3.0minimum.SeeNFPA72‐14.4.10.3TestProcedures;Recommend‐90dBm.

Isolationshallbeaminimumof15dBmabovethesignalboostergainunderalloperatingconditions.(NFPA72‐24.5.2.3.3)Note:NFPA1221(2016)requiresaminimumof20dBm.Anylowervaluemayresultintheprobabilityoffailingthefinalinspection.☐

Systemradiofrequencies:systemshallbecapableoftransmittingallpublicsafetyradiofrequenciesusedbytheFCCAHJ.(NFPA72‐24.5.2.4)

Frequencychanges.Systemshallbecapableofupgrading.(NFPA72‐24.5.2.4.2)BCRCESGuidelinesPart2ADLRDraftEdition2019‐07‐202A.82A.1.4NFPA72(2013)PlanReview‐FCCLicenseHolder(cont.)

SystemComponents:ComponentsshallbeapprovedandcompatiblewiththePublicSafetyRadioSystem.(NFPA72‐24.5.2.5)Showthepropagationdelay.SignalBoostersshallhaveFCCCertification.Powersuppliesshallhaveatleasttwoindependentsupplies.Batteryshallprovidetwelve(12)hourminimumoperationalruntime.

SystemMonitoring:(NFPA72‐24.5.2.6.1)Thefirealarmsystemshallmonitorthefollowingitemsasaminimum:(1)Integrityofthecircuitmonitoringsignalbooster(s)andpowersupply(ies)shallcomplywithNFPA72‐24.10.6.9andNFPA72‐12.6.(2)Systemandsignalboostersupervisorysignalsshallincludethefollowing:(a)Antennamalfunction(b)Signalboosterfailure(c)Low‐batterycapacityindicationwhen70percentofthe12‐houroperatingcapacityhasbeendepleted.(3)Powersupplysignalsshallincludethefollowingforeachsignalbooster:(a)LossofnormalACpower(b)Failureofbatterycharger

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | JGroff@coj.net  

DedicatedPanel(annunciatorpanel)(NFPA72‐24.5.2.6.2)(1)NormalACpower(2)Signalboostertrouble(3)LossofnormalACpower(4)Failureofbatterycharger(5)Lowbatterycapacity

TechnicalCriteria(NFPA72‐24.5.2.7)(1)Frequenciesrequired(2)Locationofeffectiveradiatedpower(ERP)oftheFCCAHJradiosite(3)Maximumpropagationdelay(30microseconds)(4)Listofspecificallyapprovedcomponents(5)Othersupporttechnicalinformationasneeded.

Note:Theelevatorcodedoesnotallowtheelevatorshafttobeusedforcoaxialcablerisers.(ASMEA17.1.2.)AvarianceshallbeobtainedfromtheStateElevatorInspectionServicesSectionatpermittingpriortoanyworkinsideanelevatorshaftorelevatormachineroom.Thevarianceshallbetoinstalloneormoreantenna(s)intheelevatorshaft(s).(ASMEA17.1)