BDA Survey and Installation Requirements 214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | [email protected] The City of Jacksonville in order to optimize fire and rescue operation communications on scenes of fire and other emergencies and to comply with the Florida Fire Prevention Code NFPA 1 Chapter 11.10 as modified by Florida Statute 633.202 (18) will require minimum radio signal strength levels for communications for all new and existing buildings. (See below for code, statutory language, and Declaratory Statement). NFPA 1 Chapter 11.10 11.10 TwoWay Radio Communication Enhancement Systems 11.10.1 In all new and existing buildings, minimum radio signal strength for fire department communications shall be maintained at a level determined by the AHJ. The level determined to be acceptable in the City of Jacksonville will be as stipulated in the International Fire Code Section 510.4.1 The building shall be considered to have acceptable emergency responder radio coverage when signal strength measurements in 95% of all general areas of the building and 99% in critical areas including elevators (measured at the primary recall floor), stair shafts and Fire Command Centers where the minimum signal strength of 95 dBm shall be receivable within the building. FS 633.202 Florida Fire Prevention Code: (18) The authority having jurisdiction shall determine the minimum radio signal strength for fire department communications in all new highrise and existing highrise buildings. Existing buildings are not required to comply with minimum radio strength for fire department communications and twoway radio system enhancement communications as required by the Florida Fire Prevention Code until January 1, 2022. However, by December 31, 2019, an existing building that is not in compliance with the requirements for minimum radio strength for fire department communications must apply for an appropriate permit for the required installation with the local government agency having jurisdiction and must demonstrate that the building will become compliant by January 1, 2022. Existing apartment buildings are not required to comply until January 1, 2025. However, existing apartment buildings are required to apply for the appropriate permit for the required communications installation by December 31, 2022. City of Jacksonville

BDA Survey and Installation RequirementsNFPA 70, 2014 Edition, National Electrical Code Retrofit BDA systems will require a building permit through The City of Jacksonville’s Building

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: BDA Survey and Installation RequirementsNFPA 70, 2014 Edition, National Electrical Code Retrofit BDA systems will require a building permit through The City of Jacksonville’s Building

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | [email protected]  

TheCityofJacksonvilleinordertooptimizefireandrescueoperationcommunicationsonscenesoffireandotheremergenciesandtocomplywiththeFloridaFirePreventionCodeNFPA1Chapter11.10asmodifiedbyFloridaStatute633.202(18)willrequireminimumradiosignalstrengthlevelsforcommunicationsforallnewandexistingbuildings.(Seebelowforcode,statutorylanguage,andDeclaratoryStatement). NFPA1Chapter11.1011.10Two‐WayRadioCommunicationEnhancementSystems11.10.1Inallnewandexistingbuildings,minimumradiosignalstrengthforfiredepartmentcommunicationsshallbemaintainedataleveldeterminedbytheAHJ.TheleveldeterminedtobeacceptableintheCityofJacksonvillewillbeasstipulatedintheInternationalFireCodeSection510.4.1Thebuildingshallbeconsideredtohaveacceptableemergencyresponderradiocoveragewhensignalstrengthmeasurementsin95%ofallgeneralareasofthebuildingand99%incriticalareasincludingelevators(measuredattheprimaryrecallfloor),stairshaftsandFireCommandCenterswheretheminimumsignalstrengthof‐95dBmshallbereceivablewithinthebuilding.FS633.202 FloridaFirePreventionCode:(18)Theauthorityhavingjurisdictionshalldeterminetheminimumradiosignalstrengthforfiredepartmentcommunicationsinallnewhigh‐riseandexistinghigh‐risebuildings.Existingbuildingsarenotrequiredtocomplywithminimumradiostrengthforfiredepartmentcommunicationsandtwo‐wayradiosystemenhancementcommunicationsasrequiredbytheFloridaFirePreventionCodeuntilJanuary1,2022.However,byDecember31,2019,anexistingbuildingthatisnotincompliancewiththerequirementsforminimumradiostrengthforfiredepartmentcommunicationsmustapplyforanappropriatepermitfortherequiredinstallationwiththelocalgovernmentagencyhavingjurisdictionandmustdemonstratethatthebuildingwillbecomecompliantbyJanuary1,2022.ExistingapartmentbuildingsarenotrequiredtocomplyuntilJanuary1,2025.However,existingapartmentbuildingsarerequiredtoapplyfortheappropriatepermitfortherequiredcommunicationsinstallationbyDecember31,2022.

City of Jacksonville 

Page 2: BDA Survey and Installation RequirementsNFPA 70, 2014 Edition, National Electrical Code Retrofit BDA systems will require a building permit through The City of Jacksonville’s Building

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | [email protected]  

NoticeofDeclaratoryStatement

NOTICEISHEREBYGIVENthatDepartmentofFinancialServiceshasissuedanorder disposing of the petition for declaratory statement filed by Charles B.Parks, Chief Fire CodeOfficial ofBroward County on February 02, 2018.Thefollowingisasummaryoftheagency'sdispositionofthepetition:TheAmendedPetition requests a determination as towhether Section 633.202(18), FloridaStatutes,prohibitstheenforcementofNFPA1,section11.10,inbuildingsunder75 feet in height. The Department concludes section 633.202(18), FloridaStatutes,doesnotapplytotheenforcementofNFPA1,section11.10,inbuildingsunder75feetinheight.Sowhatdoesthatallmean?

Allnewandexistingbuildingsbelowrequiredthresholdmustcomply.Ifradiosignalstrengthaftersignalsurveyisfoundtobebelowacceptablethreshold,aBDAsystemwillberequired.

ExistingHigh‐risesmustcomplybyJan1,2022howeverapermitforsaidbuildingsmustbepulledbyDec.31,2019.

ExistingapartmentbuildingsarenotrequiredtocomplyuntilJanuary1,2025.However,existingapartmentbuildingsarerequiredtoapplyfortheappropriatepermitfortherequiredcommunicationsinstallationbyDecember31,2022.

Asperthe69ADec.statement(forclarification)allotherbuildingsnotmeetingminimumsignalstrengthsasdeterminedbyaradiosurveyperformedbyaFCClicensedentityaredeemednon‐compliantandwillberequiredtoinstallaBDA.TheCityofJacksonvillehasdeterminedthatthoseoccupancieswillbeallowedtoshowcompliancebyapplyingfortheappropriatepermitfortherequiredcommunicationsinstallationbyDecember31,2022withinstallationcompletednolaterthanJan1,2025.Allnewconstructionbuildingwillberequiredtocomplyaspartoftheirpermittingprocess.

Page 3: BDA Survey and Installation RequirementsNFPA 70, 2014 Edition, National Electrical Code Retrofit BDA systems will require a building permit through The City of Jacksonville’s Building

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | [email protected]  

BuildingSurveyRequirements:

ThecityofJacksonvilleutilizesa28channelMotorola800MhzLinearsimulcastP25radiosystem.Wehave4availablecontrolchannelstransmittingintherangeof855.2100Mhzand856.000Mhz.Oursystemfrequencyrangeis807.000Mhz.to816.00Mhz.forBaseRXand854.900Mhz.to861.000Mhz.forBaseTX.

Ourcontrolchannelsareasfollows:

Wearecurrentlyusechannel4asprimary.

Oncethebuildingissubstantiallycompleteoranexistingbuildingissuspectedofhavingcomplianceissues,aqualifiedFCCGrollicensedvendorwillperformthesignalsurveytocheckthecurrentradiosignallevelsinsidethebuilding.

VendorwillmeasuretheincomingsignallevelsbymonitoringtheAHJradiorepeatertalk‐outfrequency.VendorshallnotifyCityofJacksonvilleRadioShopandgetapprovalforthetesting.StevenHaynerRadioSystemsEngineer(904)904‐255‐7418/Email:[email protected]

Ifthemeasurementsshowthatthelevelsareabovetherequiredthreshold,thevendorwillthanprepareareportstatingbuildingisincompliancesignedbyFCCLicenseewithtestingdataattached.PassingsurveyresultswillbesubmittedtotheOfficeofFirePlansreviewforarchivalpurposes.Iflevelsarebelowtherequiredthreshold,aBDAwillberequired.

1 855.9875 810.9875

2 855.9625 810.9625

3 855.4875 810.4875

4 855.2125 810.2125

Page 4: BDA Survey and Installation RequirementsNFPA 70, 2014 Edition, National Electrical Code Retrofit BDA systems will require a building permit through The City of Jacksonville’s Building

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | [email protected]  

TechnicalInformationforBDAdesign:Systemshallcomplyandmeetthefollowingrequirements:

FloridaAdministrationCode:61G15‐33.005DesignofCommunicationSystemsFloridaStateStatues:TitleXXXVII,Insurance–Chapter633.202and633.551,FirePreventionandControlFloridaFirePreventionCode(FFPC)SixthEdition;69A‐60.005NFPA1.11.10Two–WayCommunicationNFPA1221,2016Edition,Standardfortheinstallation,Maintenance,andUseofEmergencyServicesCommunicationSystemsNFPA72,2013Edition,NationalFireAlarmCode;Chapt.10Section6;Chapt.24;Sections24.5.2.21through24.5.2.2.3FloridaBuildingCode(FBC)2017SixthEditionNFPA70,2014Edition,NationalElectricalCode

RetrofitBDAsystemswillrequireabuildingpermitthroughTheCityofJacksonville’sBuildingDepartmentduetotheratedenclosurerequirements.Newconstructionbuildingsthatareabletoshowenclosuresonnewconstructionbuildingplanswillbeabletopullanassociatedfirepermitinlieuofbuildingpermit.AdditionalassociatedelectricalandfirepermitsmayberequiredforelectricalandfirealarmworkrelatedtoBDA.

Licenserequirementforinstallation:ECCertifiedElectricalContractor,EFCertifiedAlarmSystemContractorI,EYRegisteredAlarmSystemContractor1,ESCertifiedTwo‐WayRadioCommunicationsEnhancementSystemSpecialtyalongwithFCCGrolLicense.

Page 5: BDA Survey and Installation RequirementsNFPA 70, 2014 Edition, National Electrical Code Retrofit BDA systems will require a building permit through The City of Jacksonville’s Building

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | [email protected]  

Frequenciesrequired:Systemfrequencyrangeis807.000Mhz.to816.00Mhz.forBaseRXand854.900Mhz.to861.000Mhz.forBaseTX

Locationofradiositesforpublicsafetyradioenhancementsystem:

1.) HoganRoad8675HoganRd.2.) YellowWater2015YellowWaterRd.3.) LloydRd.2630LloydRd.4.) Greenland14247OldSt.AugustineRd.5.) JaxBeach95010thStreetSouth6.) Firestone6878FirestoneRd.7.) SJRPP11201NewBerlinRd.8.) CenterPark2797KernanRd.S9.) JEAPlaza21W.ChurchSt.

Listofspecificallyapprovedsystemcomponents:Allsystemcomponentsshallbedesigned,installed,tested,inspected,andmaintainedinaccordancewiththemanufacturers’publishedinstructionsandtherequirementsofSection9.6.ofNFPA12212016.

Ratingrequirements:

Risercoaxialcables(AntennadonorCabletoBDAheadend)shallberatedasrisercablesandroutedthrougha2‐hour–ratedenclosure.

Thefeederandrisercoaxialcables(FromBDAHeadendtoantennasorremotes)shallberatedasplenumcablesthatmatchthebuilding’sfireratingandpathwaysurvivability.See12212016TIA16‐2

Theconnectionbetweentheriserandfeedercoaxialcablesshallbe

madewithinanenclosurematchingthebuilding’sfireratingandpathwaysurvivability,andpassageofthefeedercableinandoutoftheenclosureshallbefire‐stoppedtothebuilding’sfireratingandpathwaysurvivability.See12212016TIA16‐2

Page 6: BDA Survey and Installation RequirementsNFPA 70, 2014 Edition, National Electrical Code Retrofit BDA systems will require a building permit through The City of Jacksonville’s Building

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | [email protected]  

PathwaySurvivabilityRequirements:

PathwaysurvivabilityrequirementswillbebasedoffcurrentlyadoptededitionofNFPA72.

Forsystemsemployingrelocationorpartialevacuation,Level2orLevel3pathwaysurvivabilityshallberequired.Forsystemsthatdonotemployrelocationorpartialevacuation,aLevel1,Level2,orLevel3pathwaysurvivabilityshallberequired.

Page 7: BDA Survey and Installation RequirementsNFPA 70, 2014 Edition, National Electrical Code Retrofit BDA systems will require a building permit through The City of Jacksonville’s Building

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | [email protected]  

PathwaySurvivabilityLevelsDefined:

PathwaySurvivabilityLevel1:PathwaysurvivabilityLevel1shallconsistofpathwaysinbuildingsthatarefullyprotectedbyanautomaticsprinklersysteminaccordancewithNFPA13,StandardfortheInstallationofSprinklerSystems,withanyinterconnectingconductors,cables,orotherphysicalpathwaysinstalledinmetalraceways.

PathwaySurvivabilityLevel2:PathwaysurvivabilityLevel2shallconsistofoneormoreofthefollowing:(1)2‐hourfire‐ratedcircuitintegrity(CI)cable(2)2‐hourfire‐ratedcablesystem[electricalcircuitprotectivesystem(s)](3)2‐hourfire‐ratedenclosureorprotectedarea(4)2‐hourperformancealternativesapprovedbytheauthorityhavingjurisdiction.PathwaySurvivabilityLevel3PathwaysurvivabilityLevel3shallconsistofpathwaysinbuildingsthatarefullyprotectedbyanautomaticsprinklersysteminaccordancewithNFPA13,StandardfortheInstallationofSprinklerSystems,andoneormoreofthefollowing:(1)2‐hourfire‐ratedcircuitintegrity(CI)cable(2)2‐hourfire‐ratedcablesystem[electricalcircuitprotectivesystem(s)](3)2‐hourfire‐ratedenclosureorprotectedarea(4)2‐hourperformancealternativesapprovedbytheauthorityhavingjurisdictionisapathwayinbuildingsthatarefullyprotectedbyautomaticsprinklersystemandcablesareinstalledinmetalraceways.RadioCoverageRequirements: Criticalareastoincludefirecommandcenters,firepumprooms,exitstairs,

exitpassageways,elevatorlobbies,standpipecabinets,sprinklersectionalvalvelocations,andotherareasdeemedcriticalbytheauthorityhavingjurisdiction,shallbeprovidedwith99%floorarearadiocoverage.

Generalbuildingareasshallbeprovidedwith95%floorarearadio

coverage.

Page 8: BDA Survey and Installation RequirementsNFPA 70, 2014 Edition, National Electrical Code Retrofit BDA systems will require a building permit through The City of Jacksonville’s Building

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | [email protected]  

SignalStrengthRequirements:

Minimuminboundsignalstrengthof−95dBmshallbeprovidedthroughoutthecoverageareawithaninboundsignallevelofDAQ3.0

Minimumoutboundsignalstrengthof−95dBmatthedonorsiteshallbeprovided

fromthecoverageareawithanoutboundsignallevelofDAQ3.0

IsolationRequirements: Isolationshallbemaintainedbetweenthedonorantennaandallinside

antennastoaminimumof20dBunderalloperatingconditions.

MaximumacceptablepropagationDelay:

15Microseconds.

FrequencyChanges:

Systemsshallbeupgradeabletoallowforinstanceswherethejurisdictionchangesoraddssystemfrequenciestomaintainradiosystemcoverageasitwasoriginallydesigned.

ComponentEnclosureRequirements:

Allrepeater,transmitter,receiver,signalboostercomponents,externalfilters,andbatterysystemcomponentsshallbecontainedinaNEMA4‐orNEMA4X‐typeenclosure(s).

ComponentRequirements:

RFemittingdevicesandcablingusedintheinstallationofthepublicsafetytwo‐wayradiocommunicationsenhancementsystemsshallbeapprovedbytheAHJ,andallRFemittingdevicesshallhavethecertificationofthe

Page 9: BDA Survey and Installation RequirementsNFPA 70, 2014 Edition, National Electrical Code Retrofit BDA systems will require a building permit through The City of Jacksonville’s Building

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | [email protected]  

Radiolicensingauthorityandbesuitableforpublicsafetyusepriorto

installation.

RFemittingdevicesshallmeetthefollowingrequirementsinadditiontoanyotherrequirementsdeterminedbytheAHJ:

(1)RFemittingdevicesshallhavethecertificationoftheradiolicensingauthoritypriortoinstallation.(2)AllRFemittingdevicesshallbecompatiblewithbothanaloganddigitalcommunications,asrequiredtobeusedbytheradiolicensingauthorityandtheAHJ,simultaneouslyatthetimeofinstallation.

PowerSupplies:

AtleasttwoindependentandreliablepowersuppliesshallbeprovidedforallRFemittingdevicesandanyothercomponentsofthesystem:oneprimaryandonesecondary.

TheprimarypowersourceshallbesuppliedfromadedicatedbranchcircuitandcomplywithNFPA72.

Thesecondarypowersourceshallconsistofoneofthefollowing:Astoragebatterydedicatedtothesystemwith12hoursof100percentsystemoperationcapacity

Analternativepowersourceof12hoursat100percentsystemoperationcapacityasapprovedbytheAHJ

SystemMonitoringRequirements:

Thesystemshallincludeautomaticsupervisorysignalsformalfunctionsofthetwo‐wayradiocommunicationsenhancementsystemsthatareannunciatedbythefirealarmsysteminaccordancewithNFPA72,andshallcomplywiththefollowing:

Page 10: BDA Survey and Installation RequirementsNFPA 70, 2014 Edition, National Electrical Code Retrofit BDA systems will require a building permit through The City of Jacksonville’s Building

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | [email protected]  

MonitoringforintegrityofthesystemshallcomplywithNFPA72,Chapter10.

Systemsupervisorysignalsshallincludethefollowing:

(a)Donorantennamalfunction(b)ActiveRFemittingdevicefailure(c)Low‐batterycapacityindicationwhen70percentofthe12‐houroperatingcapacityhasbeendepleted(d)Systemcomponentfailure.PowersupplysupervisorysignalsshallincludethefollowingforeachRFemittingdeviceandsystemcomponent:(a)Lossofnormalacpower(b)Failureofbatterycharger

Thecommunicationslinkbetweenthefirealarmsystemandthetwo‐wayradiocommunicationsenhancementsystemmustbemonitoredforintegrity.

DedicatedPanelrequirements:

AdedicatedmonitoringpanelshallbeprovidedwithinthefirecommandcentertoannunciatethestatusofallRFemittingdevicesandsystemcomponentlocations.ThemonitoringpanelshallprovidevisualandlabeledindicationsofthefollowingforeachsystemcomponentandRFemittingdevice:(a)Normalacpower(b)Lossofnormalacpower(c)Batterychargerfailure(d)Lowbatterycapacity(to70percentdepletion)(e)Donorantennamalfunction(f)ActiveRFemittingdevicemalfunction(g)Systemcomponentmalfunction.Thecommunicationslinkbetweenthededicatedmonitoringpanelandthetwo‐wayradiocommunicationsenhancementsystemmustbemonitoredforintegrity.

Page 11: BDA Survey and Installation RequirementsNFPA 70, 2014 Edition, National Electrical Code Retrofit BDA systems will require a building permit through The City of Jacksonville’s Building

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | [email protected]  

ConvergedSystems:

RadioenhancementsystemsBDAandDAScanshareantennasandcablingaslongasbothcomplywithalltherequirementsintheaforementionedtechnicalinformationforBDAdesignaspreviouslylisted.

Planssubmittalminimumrequirements:

Buildingownerandaddress(FAC61G6) CopyofthecontractwiththeownerorGC(FBC118.1.4) SignatureandsealoftheEngineerofRecordwithexperienceandtraining

inelectricalengineering.Thename,PEnumber,businessname,CAnumber,address,andcontactinformationshallbeshownontheplans.(NFPA72‐10.5)(FAC118.1.4)(61G15‐30.003(2)

Applicablecodesandeditiondates(61g15‐30.003(1b) Buildingdescriptionshowingbuildingconstruction,buildingoccupancy,

totalsquarefootage,numberoffloors,totalheightofbuilding(FAC61G15) Floorplansshowingdevicelocations,fire‐ratedenclosures,conduitruns,

andpropagationmodeling,etc.Propagation(heat)mapdrawingsshallincludethefollowing(FBC118.2.1.4):☐IndoorPredictionLegend☐MaterialsLegend☐PictogramLegend☐CablesLegend☐CalculationsLegend☐NumberofChannels☐Frequencies☐Predictivepropagationonfloorplans☐Nameofcertifieddesignerandcompany

Riserplansforsystems(FAC61G15) Specificationswithmanufacturer’spartsnumbers(FAC61G15) Details,includingfirewallpenetration,etc.(FAC61G15) Manufacturer’sspecificationsforequipment(FAC61G15) Antennaandsurgeprotectordetail(FAC61G15) Notesonplansshallstate(FBC118.4.2.2):“Thesystemshallneverbe

energizedfortestingoroperationuntilwritten,oronsite,approvalisobtainedfromtheFCCLicenseHolder.”

Page 12: BDA Survey and Installation RequirementsNFPA 70, 2014 Edition, National Electrical Code Retrofit BDA systems will require a building permit through The City of Jacksonville’s Building

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | [email protected]  

TheBDAenclosureshallbepaintedredandasignshallshowpermit

number,vendornameandtelephonenumber.(FBC118.2.1.8) Pathwaysurvivabilitylevelshallbe1,2,or3.Level1:Allcoaxialcables

shallbeinmetalconduit.(NFPA72‐12.4) Radiocoverageshallbeaminimumof99%incriticalareasand95%in

generalbuildingareas.(NFPA72‐24.5.2.2)☐16. Signalstrengthinboundshallbeaminimumof‐95dBm.Signalstrength

outboundshallbeaminimumof‐95dBm.(NFPA72‐24.5.2.3)Note:asignalstrengthoflessthan‐90dBmasshownontheplanshasahighprobabilityoffailingthefinalinspectionofDAQ3.0minimum.SeeNFPA72‐14.4.10.3TestProcedures;Recommend‐90dBm.

Isolationshallbeaminimumof15dBmabovethesignalboostergainunderalloperatingconditions.(NFPA72‐24.5.2.3.3)Note:NFPA1221(2016)requiresaminimumof20dBm.Anylowervaluemayresultintheprobabilityoffailingthefinalinspection.☐

Systemradiofrequencies:systemshallbecapableoftransmittingallpublicsafetyradiofrequenciesusedbytheFCCAHJ.(NFPA72‐24.5.2.4)

Frequencychanges.Systemshallbecapableofupgrading.(NFPA72‐24.5.2.4.2)BCRCESGuidelinesPart2ADLRDraftEdition2019‐07‐202A.82A.1.4NFPA72(2013)PlanReview‐FCCLicenseHolder(cont.)

SystemComponents:ComponentsshallbeapprovedandcompatiblewiththePublicSafetyRadioSystem.(NFPA72‐24.5.2.5)Showthepropagationdelay.SignalBoostersshallhaveFCCCertification.Powersuppliesshallhaveatleasttwoindependentsupplies.Batteryshallprovidetwelve(12)hourminimumoperationalruntime.

SystemMonitoring:(NFPA72‐24.5.2.6.1)Thefirealarmsystemshallmonitorthefollowingitemsasaminimum:(1)Integrityofthecircuitmonitoringsignalbooster(s)andpowersupply(ies)shallcomplywithNFPA72‐24.10.6.9andNFPA72‐12.6.(2)Systemandsignalboostersupervisorysignalsshallincludethefollowing:(a)Antennamalfunction(b)Signalboosterfailure(c)Low‐batterycapacityindicationwhen70percentofthe12‐houroperatingcapacityhasbeendepleted.(3)Powersupplysignalsshallincludethefollowingforeachsignalbooster:(a)LossofnormalACpower(b)Failureofbatterycharger

Page 13: BDA Survey and Installation RequirementsNFPA 70, 2014 Edition, National Electrical Code Retrofit BDA systems will require a building permit through The City of Jacksonville’s Building

    BDA Survey and Installation Requirements

214 N. Hogan Street | Jacksonville, FL 32202-4128 | Phone: 904-255-8320 | Fax: 904-255-8320 | [email protected]  

DedicatedPanel(annunciatorpanel)(NFPA72‐24.5.2.6.2)(1)NormalACpower(2)Signalboostertrouble(3)LossofnormalACpower(4)Failureofbatterycharger(5)Lowbatterycapacity

TechnicalCriteria(NFPA72‐24.5.2.7)(1)Frequenciesrequired(2)Locationofeffectiveradiatedpower(ERP)oftheFCCAHJradiosite(3)Maximumpropagationdelay(30microseconds)(4)Listofspecificallyapprovedcomponents(5)Othersupporttechnicalinformationasneeded.

Note:Theelevatorcodedoesnotallowtheelevatorshafttobeusedforcoaxialcablerisers.(ASMEA17.1.2.)AvarianceshallbeobtainedfromtheStateElevatorInspectionServicesSectionatpermittingpriortoanyworkinsideanelevatorshaftorelevatormachineroom.Thevarianceshallbetoinstalloneormoreantenna(s)intheelevatorshaft(s).(ASMEA17.1)