29
TELEHOUSE NORTH TWO A WORLD FIRST IN DATA CENTRE COOLING

Telehouse north 2 presentation for dcw 2015 final

Embed Size (px)

Citation preview

Page 1: Telehouse north 2 presentation for dcw 2015 final

TELEHOUSE NORTH TWOA WORLD FIRST IN DATA CENTRE COOLING

Page 2: Telehouse north 2 presentation for dcw 2015 final

Smallest footprint and weight per kW.

Speakers

Newly developed emergency water save mode reduces stored water requirement by a further 30%

Mark Collins Director

Andrew DewingTechnical Services Director

Malcolm HowePartner Critical Systems

Page 3: Telehouse north 2 presentation for dcw 2015 final

Smallest footprint and weight per kW.

Independently verified efficient water and energy consumption.

Contents

Highly developed , tested and independently verified control strategies.

INDIRECT COOLING – Technology Overview

TELEHOUSE NORTH 2 – The Design Challenge

TELEHOUSE NORTH 2 – The Design Solution

Page 4: Telehouse north 2 presentation for dcw 2015 final

Smallest footprint and weight per kW.

Contents

Highly developed , tested and independently verified control strategies.

Newly developed emergency water save mode reduces stored water requirement by a further 30%

INDIRECT COOLING – Technology Overview

Page 5: Telehouse north 2 presentation for dcw 2015 final

INDIRECTLeverage natural cooling properties of outdoor air but keep contamination out. Outdoor air cools indoor air without direct contact.

ADIABTIC & EVAPORATIVEDecrease temperature of summer outdoor air by increasing moisture content.

INDIRECT adiabatic & evaporative

Page 6: Telehouse north 2 presentation for dcw 2015 final

What's in the box?

H X

Room air

Outdoor air

ECDC Plug Fans

DX cooling coil

DX condenser coil

Adiabatic misting system

Page 7: Telehouse north 2 presentation for dcw 2015 final

UK design ambient condition

Heat exchanger entering condition

35°C

25% RH

21°C

SECONDARY air at summer peak

Page 8: Telehouse north 2 presentation for dcw 2015 final

0.0

5.0

10.0

15.0

20.0

25.0

30.0

35.0

Jan Feb Mar Apr May June Jul Aug Sep Oct Nov Dec

Dry Bulb

Wet Bulb

Free cooling threshold to maintain 27°C supply Temp

OPERATIONAL thresholds

ASHRAE WDView50 London Heathrow Temperature Data

Page 9: Telehouse north 2 presentation for dcw 2015 final

The largest energy consuming element apart from the IT load is the Compressor!!

SOLUTION – reduce or completely remove dependency on mechanical cooling

Where does the power go?

Traditional Systems

Excool

100%

50%

25%

75%

IT Load Cooling Electrical Losses

DATACENTRE asset efficiency

Page 10: Telehouse north 2 presentation for dcw 2015 final

City % Free Cooling Mech Cooling Hours pPUE

Recommended Allowable Recommended Allowable

London 100 100 0 0 1.030

Paris 99.95 100 4 0 1.031

Amsterdam 99.99 100 1 0 1.030

Madrid 99.95 100 4 0 1.032

Moscow 100 100 0 0 1.027

New York 97.91 100 183 0 1.039

Riyadh 99.95 100 4 0 1.071

• ‘Recommended’ and ‘Allowable’ refer to the environmental control envelopes recommended by ASHRAE TC 2011 Thermal Guidelines for Data Processing Environments • Based upon 1MW IT load running at an annualised average of 75%• Data Source ASHRAE weather data viewer 4.0• Supply temp 24°C, return 36°C. Supply temp allowed to rise to 27°C (recommended) and 32°C (allowable).• Aisle containment in place maintaining a 12K ΔT between supply and return.• Resilience based on N+1 and pPUE calculated with all units running.• pPUE = (Cooling input power + IT power ) ÷ IT power

Key observation – PUE of ≤ 1.15 achievable in many locations

EXCOOL global efficiency

Page 11: Telehouse north 2 presentation for dcw 2015 final

Compact design

Highly efficient

Controls

Water storage

Smallest footprint and weight per kW.

Independently verified efficient water and energy consumption.

SIX years of R&D

Highly developed , tested and independently verified control strategies.

Newly developed emergency water save mode reduces stored water requirement by a further 30%

Page 12: Telehouse north 2 presentation for dcw 2015 final

Smallest footprint and weight per kW.

Independently verified efficient water and energy consumption.

Contents

Newly developed emergency water save mode reduces stored water requirement by a further 30%

TELEHOUSE NORTH 2 – The Design Challenge

Page 13: Telehouse north 2 presentation for dcw 2015 final

Smallest footprint and weight per kW.

Independently verified efficient water and energy consumption.

Introduction to the Telehouse Campus

Highly developed , tested and independently verified control strategies.

Newly developed emergency water save mode reduces stored water requirement by a further 30%

Site Context

• Telehouse has operated at East India Dock since 1990, close to Canary Wharf and the City of London.

• Major connectivity hub for the UK

• Significant power available via our own 132kV substation and the 11kV local utility.

• Adjacent vacant site offers opportunity for further development of the Telehouse campus

Opportunity for Expansion was too Good to Miss!

Page 14: Telehouse north 2 presentation for dcw 2015 final

Smallest footprint and weight per kW.

Independently verified efficient water and energy consumption.

Introduction to Telehouse North 2 Project

Highly developed , tested and independently verified control strategies.

Newly developed emergency water save mode reduces stored water requirement by a further 30%

How Best to Exploit this Opportunity?

DC Design has moved on since our last project - Telehouse West. Customer demands now along the lines of:

• High efficiency/low PUE

• Flexible and scalable power requirements based on base design power density of 2kW/m2 up to bespoke High Density requirements.

• Flexible and scalable connectivity

Requirement for high resilience, high availability.

Page 15: Telehouse north 2 presentation for dcw 2015 final

Smallest footprint and weight per kW.

Independently verified efficient water and energy consumption.

TN2 - High Level Requirements

Highly developed , tested and independently verified control strategies.

Newly developed emergency water save mode reduces stored water requirement by a further 30%

Telehouse Requirements

• High rise solution required – because of plot size.

• Best in Class PUE < 1.2 (better than any CW solution and making best use of available power on site)

• Ability to serve HD requirements on all floors

• BREEAM Excellent rating

• Redundancy in components and systems

• No single points of failure

• Concurrently maintainable

Page 16: Telehouse north 2 presentation for dcw 2015 final

Smallest footprint and weight per kW.

Independently verified efficient water and energy consumption.

TN2 – Cooling Solution

Highly developed , tested and independently verified control strategies.

Newly developed emergency water save mode reduces stored water requirement by a further 30%

Considerations:

PUE Target necessitates Outside Air based cooling solution. Direct or Indirect?

• Urban location, with lots of traffic pollution -Extent of filtration needed with Direct Air

• Need for full cooling back-up with Direct Air

• Roof allocated to ancillary plant for plant room cooling and specific High Density Cooling

Indirect does not have outside air issues and no need for back-up cooling system

Telehouse Preference for Indirect Air Cooling Solution!

Page 17: Telehouse north 2 presentation for dcw 2015 final

Smallest footprint and weight per kW.

TN2 – Project Brief

Highly developed , tested and independently verified control strategies.

Newly developed emergency water save mode reduces stored water requirement by a further 30%

The Challenge:

To develop a multi-storey, indirect air cooled data centre, providing sufficient capacity to deliver 2kW/m2 average load

To provide ancillary cooling system to deliver maximum possible High Density capacity

Best in Class PUE < 1.2

BREEAM Excellent Rating

Concurrently maintainable - Redundancy in components and systems, with no single points of failure.

Challenge to the Cundall Team was to provide the Solution!

Page 18: Telehouse north 2 presentation for dcw 2015 final

Smallest footprint and weight per kW.

Independently verified efficient water and energy consumption.

Contents

Highly developed , tested and independently verified control strategies.

Newly developed emergency water save mode reduces stored water requirement by a further 30%

TELEHOUSE NORTH 2 – The Design Solution

Page 19: Telehouse north 2 presentation for dcw 2015 final

Smallest footprint and weight per kW.

Independently verified efficient water and energy consumption.

TN2 – Project Overview

Highly developed , tested and independently verified control strategies.

Newly developed emergency water save mode reduces stored water requirement by a further 30%

Design Overview:

• 6no IAC-Cooled Technical Halls of 1,200m2 per floor, providing total IT Load of 13.68MW

• 528 Racks per floor @ 4.32kW per Rack, providing 2.281MW of IT Load per Floor

• Indirect air cooling system (IAC) to Technical floors. Units located on external gantry

• Annualised PUE <= 1.16

• Space provision to add cooling plant to support additional 2.4MW of High Density IT Cooling

• Chilled water / Free Cooling to plant areas

• Development designed to meet BREEAM Excellent

Page 20: Telehouse north 2 presentation for dcw 2015 final

Smallest footprint and weight per kW.

Independently verified efficient water and energy consumption.

TN2 – Drivers and Challenges

Highly developed , tested and independently verified control strategies.

Newly developed emergency water save mode reduces stored water requirement by a further 30%

Design Drivers and Challenges:

• Deliver sufficient Technical Space on a confined site:

• Multi-Storey Data Centre

• Limited Roof Plant Area, relative to Technical Area

• Provide Next Generation Data Centre:

• Low Energy Operation / Low PUE

• Flexibility to suit Tenant Fit-out Requirements

• ASHRAE TC 9.9 Class A1 Environment

• Obtain LPA & GLA Planning Approval:

• Gateway Building to Tower Hamlets

• Meet Energy Targets of BREEAM Excellent

Indirect Air Cooling (IAC) solution in Multi-Storey setting. IAC Units stacked on external plant gantry.

Page 21: Telehouse north 2 presentation for dcw 2015 final

Independently verified efficient water and energy consumption.

TN2 – Building Form

Highly developed , tested and independently verified control strategies.

Newly developed emergency water save mode reduces stored water requirement by a further 30%

Ground Floor

Typical TechnicalFloor

Building Form follows function – Driven by IAC Cooling Solution

• Data Halls are 57m wide by 19.5m deep, to suit single-sided supply of cooling air.

• Technical Halls occupy floors 2 to 7

• IAC units mounted on gantry on Western face of building from floors 2 to 7

• Chillers and air handling plant on raised gantry above roof level

• Generator rooms and Meet-me rooms provided at Ground Floor level

• East façade looks out over arterial route –Signature Circuit Board Motif

Page 22: Telehouse north 2 presentation for dcw 2015 final

Smallest footprint and weight per kW.

Independently verified efficient water and energy consumption.

TN2 – CFD Study of Plant Gantry

Highly developed , tested and independently verified control strategies.

Key Challenge – Operation of Evaporative cooling system:

• Localised increase in wet bulb temperature caused by rising plume of moist air.

• Risk of De-Rating IAC units serving Upper Floors.

• CFD analysis to study air movement patterns under ‘still air’ conditions.

• Optimal solution to completely segregate intake and discharge airstreams.

Page 23: Telehouse north 2 presentation for dcw 2015 final

TN2 – Building Form

Key Challenge – Retro-Fitting of IAC Units onto External Gantry:

• At Day 1, IAC Units will only be Installed on Floors 6 and 7.

• Robust strategy needed for installation of future IAC units, as progressive floors are fitted-out.

• Optimal Solution to hoist IAC Units up inside Gantry from temporary platforms constructed at each end of the building

Page 24: Telehouse north 2 presentation for dcw 2015 final

Smallest footprint and weight per kW.

Independently verified efficient water and energy consumption.

TN2 – ‘Flooded Room’ Cooling Arrangement

Highly developed , tested and independently verified control strategies.

Newly developed emergency water save mode reduces stored water requirement by a further 30%

Page 25: Telehouse north 2 presentation for dcw 2015 final

Smallest footprint and weight per kW.

Independently verified efficient water and energy consumption.

TN2 – Overview of ‘Flooded Room’ Cooling Arrangement

Highly developed , tested and independently verified control strategies.

Key Challenge - Proving adequate distribution of Cooling Air within Data Halls:

• Single-sided supply of cooling air dictated by Building Form.

• Risk of ‘Hot Spots’ caused by Server Cages

• CFD analysis to study air movement patterns within Data Halls, under ‘Normal’ and ‘Failure’ conditions.

• Optimal solution developed for layout of tenant racks and return air path through ceiling.

Page 26: Telehouse north 2 presentation for dcw 2015 final

Smallest footprint and weight per kW.

Independently verified efficient water and energy consumption.

TN2 – Typical Floor Layouts

Highly developed , tested and independently verified control strategies.

Newly developed emergency water save mode reduces stored water requirement by a further 30%

Wholesale Floor

Shared Floor

Page 27: Telehouse north 2 presentation for dcw 2015 final

Smallest footprint and weight per kW.

Independently verified efficient water and energy consumption.

TN2 – ‘Flooded Room’ Cooling Arrangement

Highly developed , tested and independently verified control strategies.

Newly developed emergency water save mode reduces stored water requirement by a further 30%

FM Cages

Hot aisle

containment

Wholesale

Hall

Shared Hall

Page 28: Telehouse north 2 presentation for dcw 2015 final

Smallest footprint and weight per kW.

TN2 – Process Water System

Highly developed , tested and independently verified control strategies.

Newly developed emergency water save mode reduces stored water requirement by a further 30%

Connections to IAC Units

Level 07: 10 No. IAC 300 kW

Level 06: 8 No. IAC 300 kW

Future StagesLevel 02-05Process Water Plant Room A

• Pumps (N+1)• Multistage filtration + UV

Disinfection• Break tank• Water meters

Process Water Plant Room B• Pumps (N+1)• Multistage filtration + UV

Disinfection• Break tank• Water meters

Mains water supply to plant room A

Mains water supply to the plant room B

Mains water supply to the buried tanks

Water Tank

160m3

Water Tank

160m3

Connections to IAC Units

Page 29: Telehouse north 2 presentation for dcw 2015 final

Thank You for Your Attention.

Questions