Agency Listings
5600 Series Mechanical Heat Detectors
System Sensor’s 5600 series mechanical heat detectors
offer a low-cost means for property protection against fire,
and for non-life-safety installations where smoke detectors
are inappropriate.
Features
• Multipleconfigurationsforinstallations: –Single-anddual-circuitmodels –Fixedtempandcombinationfixed-temp/rate-of-rise
135°For194°Fratings.
• Plainhousingforresidentialinstallations(Model5601P)
• Easy-to-useterminalscrews
• Abroadrangeofbackboxmountingoptions: –Singlegang –3.5˝and4˝Octagonal –4˝squarewithsquaretoroundplasterring
• Reversiblemountingbracket
Multiple configurations.The5600seriesoffersafull-lineofconfigurationstoaccommodateabroadrangeofapplications.Bothsingle-anddual-circuitmodelsareavailableforlow-andhigh-temperatureratingswitheitherfixedtemperatureorcombinationfixedtemperature/rate-of-rise(ROR)activation.TheRORelementofthefixed/RORmodelsisrestorabletoaccommodatefield-testing.
Installation flexibility.Tosatisfyavarietyofinstallationneeds,the5600serieseasilymountstosingle-gangandoctagonalbackboxes.Andthesemodelsaccommodatefour-squarebackboxes,whenusedwithasquaretoroundplasterring.Thereversiblemountingbracketpermitsbothflush-andsurface-mountbackboxinstallations.
Visual identification.The5600seriesprovidesclearmarkingsontheexterioroftheunittoensurethattheproperdetectorisbeingused.Alphanumericcharactersidentifytheactivationmethod,aswellasthetemperaturerating,inFahrenheitandCelsiusdegrees.FixedtemperaturemodelsareidentifiedFX,whilecombinationfixed/rate-of-riseunitsaremarkedFX/ROR.The5600seriesalsoprovidesapost-activationindicatorintheformofacollector.Whenthedetectorisactivated,thecollectordropsfromtheunit,makingiteasytoidentifytheunitinalarm.
S2101 3016008 CS630 7270-1653:0167
5601P
5621
3825OhioAvenue•St.Charles,IL60174Phone:800-SENSOR2•Fax:630-377-6495
www.systemsensor.com
©2013SystemSensor.Productspecificationssubjecttochangewithoutnotice.Visitsystemsensor.comforcurrentproductinformation,includingthelatestversionofthisdatasheet.
SPDS30001•7/13
SpecificationsArchitectural/Engineering Specifications
MechanicalheatdetectorshallbeaSystemSensor5600seriesmodelnumber_________,listedtoUnderwritersLaboratoriesUL521forHeatDetectorsforFireProtectiveSignalingSystems.Thedetectorshallbeeitherasingle-circuitoradual-circuittype,normallyopen.Thedetectorshallberatedforactivationateither135°F(57°C)or194°F(90°C),andshallactivatebymeansofafixedtemperaturethermalsensor,oracombinationfixedtemperature/rate-of-risethermalsensor.Therate-of-riseelementshallbeactivatedbyarapidriseintemperature,approximately15°F(8.3°C)perminute.Thedetectorshallincludeareversiblemountingbracketformountingto3½-inchand4-inchoctagonal,singlegang,and4-inchsquarebackboxeswithasquaretoroundplasterring.WiringconnectionsshallbemadebymeansofSEMSscrewsthatshallaccommodate14–22AWGwire.Thedetectorshallcontainalphanumericmarkingsontheexteriorofthehousingtoidentifyitstemperatureratingandactivationmethod.Therate-of-riseelementofcombinationfixedtemperature/rate-of-risemodelsshallberestorable,toallowforfield-testing.Thedetectorsshallincludeanexternalcollectorthatshalldropuponactivationtoidentifytheunitinalarm.Physical/Operating Specifications
Maximum Installation Temperature 5601P,5603,5621,and5623:100°F(38°C)5602,5604,5622,and5624:150°F(65.6°C)
Operating Humidity Range 5to95%RHnon-condensingDimensions with mounting bracket Diameter:4.57inches(11.6cm)
Height:1.69inches(4.3cm)Alarm Temperature 5601P,5603,5621,and5623:135°F(57°C)
5602,5604,5622,and5624:194°F(90°C)Weight 6oz.(170grams)Rate-of-Rise Threshold 15°F(8.3°C)riseperminute(models5601P,5602,5621,and5622only)Mounting 3½-inchoctagonalbackbox
4-inchoctagonalbackboxSinglegangbackbox4-inchsquarebackboxwithasquaretoroundplasterring
Electrical Specifications
Operating Voltage / Contact Ratings
6–125VAC/3A6–28VDC/1A125VDC/0.3A250VDC/0.1A
Input Terminals 14–22AWG
Ordering Information
Model Circuit
Identification Methodon Exterior
TemperatureRating Activation
UL Protected Spacing – 10 Foot Ceiling*
5601P Single None 135°F(57°C) FixedTemperature/Rate-of-Rise 50feet×50feet(15.24m×15.2m)
5602 Single Lettering 194°F(90°C) FixedTemperature/Rate-of-Rise 50feet×50feet(15.24m×15.2m)
5603 Single Lettering 135°F(57°C) FixedTemperature 25feet×25feet(7.62m×7.62m)
5604 Single Lettering 194°F(90°C) FixedTemperature 25feet×25feet(7.62m×7.62m)
5621 Dual Lettering 135°F(57°C) FixedTemperature/Rate-of-Rise 50feet×50feet(15.24m×15.2m)
5622 Dual Lettering 194°F(90°C) FixedTemperature/Rate-of-Rise 50feet×50feet(15.24m×15.2m)
5623 Dual Lettering 135°F(57°C) FixedTemperature 25feet×25feet(7.62m×7.62m)
5624 Dual Lettering 194°F(90°C) FixedTemperature 25feet×25feet(7.62m×7.62m)
*NOTE:RefertoNFPA72guidelinesforspacingreductionswhenceilingheightsexceed10feet.
5601P
FX/ROR
1 9 4 ° F / 9 0 ° C5602, 5622
FX
1 3 5 ° F / 5 7 ° C5603, 5623
FX
1 9 4 ° F / 9 0 ° C5604, 5624
FX/ROR
1 3 5 ° F / 5 7 ° C5621