Number K86656/02
Issued July 9th, 2015
Valid July 10th, 2016
Declaration of Conformity, based on parts of UL subject 2775, regarding
DSPA
Non-Pressurized Condensed Aerosol Generators and
Components
Kiwa Nederland B.V.
Groningenweg 10
Postbus 256
2800 AG Gouda
Tel. +31-182-820460
Fax +31-182-820465
Internet www.kiwafss.nl
Company
DSPA B.V.
Hulzenseweg 10-20
6534 AN NIJMEGEN
P.O. Box 6572
6503 GB NIJMEGEN
The Netherlands
Tel. +31 24 352 25 73
Fax +31 24 37 87 583
www.dspa.nl
This declaration consists of 11 pages.
Publication of the declaration is allowed.
Note: Publication of only this front page or parts of the declaration is considered as “not valid”.
Underwriters Laboratories (or UL in short) was not involved with the performed tests as
mentioned in this product declaration.
STATEMENT BY KIWA
With this declaration, Kiwa declares that legitimate confidence exists that the
products supplied by
DSPA B.V.
complying with the technical specifications as laid down in this product
declaration and marked with the Kiwa®-mark in the manner as indicated in
this product declaration.
Bouke Meekma
Kiwa
Kiwa®
product declaration K86656/02 Page 2 of 11
DSPA Non-Pressurized Condensed Aerosol Generators and Components
Declaration
This product declaration by Kiwa is based on test protocol PRO10-001-AFG-nk rev 06 and parts of UL subject 2775. Please note that Underwriters Laboratories (or UL in short) was not involved with the performed tests as mentioned in this product
declaration.
Generator specifications
The products mentioned below belong to this product declaration.
DSPA 11-1, DSPA 11-2, DSPA 11-3, DSPA 11-4, DSPA 11-5, DSPA 11-6, DSPA 11-7 and DSPA 8-1.
Type Housing Red coated steel
Activation
DSPA 11-1 Disk, radial, double shaped plate Electrical
DSPA 11-2 Disk, radial, double shaped plate Electrical
DSPA 11-3 Disk, radial, double shaped plate Electrical
DSPA 11-4 Disk, radial, double shaped plate Electrical
DSPA 11-5 Disk, radial, double shaped plate Electrical
DSPA 11-6 Disk, radial, double shaped plate Electrical
DSPA 11-7 Disk, axial, double shaped plate Electrical
DSPA 8-1 Cylindrical, axial Electrical
Non-pressurized generator.
Application and use
This product declaration covers the construction and operation of condensed aerosol generators for total flooding applications when
installed, inspected, tested, and maintained in accordance with the Standard for Fixed Aerosol Fire Extinguishing Systems, NFPA 2010.
The fire extinguishing components shall be suitable for extinguishing fires of the following classes:
• Class A according NFPA 2010
• Class B according NFPA 2010
• Class C according NFPA 2010
Conditions for application
• The numbers and types of the extinguishing components have to be determined in conformity with the guidelines and calculation
methods of the supplier.
• Distribution is to be done by supplier or companies authorised by the supplier.
• Before usage an instruction is to be given by a trainer or instructor for this product authorized by the supplier.
• The installation and maintenance of the fire extinguishing components have to take place according to the specifications of the
supplier, NFPA 2010 or evaluation guideline BRL-K23003.
Point of interest during use or limitation of use
The condensed aerosol extinguishing components should not be used on fires involving the following unless relevant testing by accredited testing laboratories has been carried out to the satisfaction of the Authority:
• Deep seated fires in Class A materials
• Certain chemicals or mixtures of chemicals material, such as cellulose nitrate and gunpowder, that are capable of rapid oxidation in
the absence of air
• Reactive metals such as lithium, sodium, potassium, magnesium, titanium, zirconium, uranium and plutonium.
• Metal hydrides
• Chemicals capable of undergoing auto thermal decomposition, such as certain organic peroxides and hydrazine
• Condensed aerosol generators shall not be used to protect classified hazards or similar spaces containing flammable liquids or
dusts that can be present in explosive air–fuel mixtures unless the generators are specifically listed for use in those environments.
• Temperatures for use of aerosol extinguishing agents shall be within the supplier’s listed limits.
• Unless specifically approved as an agent blend or mixture, systems employing the simultaneous discharge of different agents to
protect the same enclosed space shall not be permitted.
• Where unrelated extinguishing or suppression systems, such as a sprinkler system or a gaseous fire-extinguishing system are
provided and can operate prior to or during the hold time of the aerosol system, the other agent shall not adversely affect the
aerosol.
The above list may not be exhaustive.
Kiwa®
product declaration K86656/02 Page 3 of 11
DSPA Non-Pressurized Condensed Aerosol Generators and Components
• The design, installation, service, and maintenance of aerosol systems shall be performed by persons skilled in aerosol fire-
extinguishing system technology.
• Local applications 1) of condensed aerosol extinguishing systems are not covered by this product declaration.
• Local applications require a pre-engineered and pre-designed system which has been tested and approved for a specific application
by a authority such as Kiwa or by an accredited testing laboratory.
1)
a local application is used for the extinguishment of surface fires in flammable liquids, gasses, and shallow solids, where the
enclosure does not conform to the requirements for total flooding.
Owner’s manual
At delivery the product should be accompanied by an operation manual in the English language, known and authorized by Kiwa.
Following minimum items shall be described according UL 2775:
• Clear indication that it is not a detailed design, installation, operation, and maintenance instruction manual.
• Clear reference to the availability of the design, installation, operation, and maintenance instruction manual by contacting the
supplier.
• A statement that periodic inspection is conducted by trained personnel.
• Information regarding the essentials required to maintain the extinguishing system unit in operation both before and after a fire.
• For extinguishing system units, a statement that no modifications are to be made to the extinguishing system unit without consulting
a qualified designer who is to refer to the detailed design, installation, operation, and maintenance instruction manual. The statement
shall include the following or equivalent wording: “This system is made up of units tested within limitations contained in the detailed
design, installation, operation, and maintenance instruction manual.
The designer must be consulted whenever changes are planned for the system or area of protection. An authorized installer or
designer must be consulted after discharge”.
Design, Installation, Operation, and Maintenance Instruction Manual
At delivery the product should be accompanied by an operation manual in the English language, known and authorized by Kiwa.
Following minimum items shall be described according UL 2775:
• Description of all variations of each unit, including the limitations for each variation;
• Operating temperature range limitations;
• Mass of aerosol-forming compound for each condensed aerosol generator size;
• Discharge time for each condensed aerosol generator size;
• Reference to the type of occupancy to be protected;
• Reference to NFPA 2010, “Standard for Fixed Aerosol Fire Extinguishing Systems” for installation, inspection, testing, and
maintenance requirements;
• Material Safety Data Sheet (MSDS) information and cautionary instructions;
• Description of the design procedure and typical layout with specific limitations and recommendations for correct installation and
effective protection;
• Specific information for condensed aerosol generator placement within the enclosure and orientation of discharge port(s);
• Minimum safe distance between condensed aerosol generator discharge ports and personnel;
• Minimum safe distance between condensed aerosol generator discharge ports and combustible materials;
• Minimum safe distance between condensed aerosol generator casing and personnel;
• Minimum safe distance between condensed aerosol generator casing and combustible materials;
• Information on inspection after installation;
• Description of requirements for maintenance of all equipment;
• A list of part numbers for all replacement parts;
• Useful life limitation for mandatory replacement of the condensed aerosol generators;
• The name of the supplier or private labeller, or equivalent designation; and
• Date and manual designation number on each page.
• Description and operating details of each unit, mounting brackets, and all accessory equipment (as applicable), including
identification by part or model number;
• Degree and type of protection with associated design application densities for surface-type Class A and Class B fires including
design application density limitations;
• Condensed aerosol generator discharge port limitations, including maximum dimensional and area coverage, minimum and
maximum height limitations, and location in the protected volume.
Kiwa®
product declaration K86656/02 Page 4 of 11
DSPA Non-Pressurized Condensed Aerosol Generators and Components
• For extinguishing system units, reference to the specific types of detection and control panels (when applicable) intended to be
connected to the extinguishing system unit;
• For extinguishing system units, specifications and instructions for interconnection of multiple extinguishing system units; or when a
means for interconnecting is unavailable, a caution statement to not use multiples of extinguishing system units;
• Details on installation of each unit, mounting brackets, and all accessory equipment (as applicable);
Marking
The products should be marked with the Kiwa®-mark.
Place of the mark Required specifications Method of marking
• On the generator
• Name of the product and supplier
• Supplier’s type designation
• Production date and serial number
• Mass of aerosol-forming compound
• Temperature range
• Storage humidity range
• Service life
• Distances as specified in table 5
• Reference to the application
instructions
• Certification mark
• Fire Class A according EN2
• Fire Class B according EN2
• Non-erasable and non-detachable;
• Non-flammable;
• Permanent an legible
Recommendations for Customers
Check at the time of delivery whether:
• The supplier has delivered in accordance with the agreement;
• The mark and the marking method are correct;
• The products show no visible defects as a result of transport etc.
If you should reject a product on the basis of the above, please contact:
• DSPA B.V.
and, if necessary,
• Kiwa Nederland B.V.
Consult the suppliers processing guidelines for the proper storage and transport methods.
Kiwa®
product declaration K86656/02 Page 5 of 11
DSPA Non-Pressurized Condensed Aerosol Generators and Components Cross reference UL subject 2775, outline of investigation for fixed condensed aerosol extinguishing system units, November 5, 2008
Chapter Description Demand 1) Result Remarks
Introduction
1. Scope Implemented
2. Components Implemented
3 Units of measurements Implemented
4 Undated references Implemented
5 Glossary Implemented
Construction
6 General Implemented
7 Electrically operating alarm N/A
8 Control and indicators N/A
9 Pneumatic control assembly pressure vessels N/A
10 Pressure relief devices for pneumatic control assemblies N/A
11 Gaskets and O-rings N/A
12 Pressure gauges for pneumatic control assemblies N/A
13 Puncturing mechanisms N/A
14 Electrically operating devices N/A
15 Condensed aerosol extinguishing agents A Pass See SNAP listing by US
Environmental Protection
Agency (EPA)
16 Pneumatic control gases N/A
17 Polymeric materials and nonmetallic parts N/A
18 Anti-recoil devices N/A
19 Pressure switches N/A
Performance
20 General Implemented
21 Discharge test A See table 4.
Discharge time of DSPA 8-1 is
over 60 sec.
Kiwa®
product declaration K86656/02 Page 6 of 11
DSPA Non-Pressurized Condensed Aerosol Generators and Components
Chapter Description Demand 1) Result Remarks
22 Temperature measurement test A Pass See table 5.
23 Mounting device test A Pass
24 Rough Usage test A Pass
25 Vibration test A Pass Implemented
DSPA 11-3, DSPA 11-6, DSPA
11-7 and DSPA 8-1 were tested.
DSPA 11-1, DSPA 11-2, DSPA
11-4 and DSPA 11-5 are
members of the same generator
family as DSPA 11-3 and DSPA
11-6.
DSPA 8-1 only at 0,5G
26 Pyrotechnic reaction containment test Not Tested
27 Fire exposure test Not Tested
28 High humidity test A Pass
29 Moist hydrogen sulfide air mixture corrosion test A Pass
30 Moist carbon dioxide sulfur dioxide air mixture corrosion
test
A Pass
31 Salt spray corrosion test A Pass
32 Thirty day elevated temperature test A Pass
33 Temperature cycling test A Pass
34 One-year time leakage test N/A
35 Hydrostatic pressure test N/A
36 Pressure relief tests N/A
37 Flexible hose assembly hose low temperature test N/A
38 Calibration test gauges N/A
39 Burst strength test gauges N/A
40 Overpressure test gauges N/A
41 Impulse test gauges N/A
42 Pressure relief test gauges N/A
43 Water resistance test gauges N/A
44 Pneumatic operation test N/A
Kiwa®
product declaration K86656/02 Page 7 of 11
DSPA Non-Pressurized Condensed Aerosol Generators and Components
Chapter Description Demand 1) Result Remarks
45 Pneumatic time delay verification test N/A
46 Pressure operated alarm test N/A
47 Operation test of manual activators and manual pull
stations
N/A
48 500 cycle operation test Implemented
48.1 Electrical initiators A Pass Aging test 116 days at 90 ºC =
15 years and Temperature range
-40°C and +75°C
48.2 Other devices N/A
49 Class A and B fire extinguishment tests Implemented
49.1 General Implemented
49.2 Class A fire extinguishment tests A Pass Not tested:
Wood cribs according 49.2.2
See table 1.
49.3 Class B fire extinguishment tests A Pass See table 1.
50 Distribution verification extinguishment tests with
extinguishing system units
Implemented
50.1 General Implemented
50.2 Test enclosure Implemented
50.3 Maximum area coverage and minimum height test
arrangement procedure
A Pass See table 3.
50.4 Maximum height test procedure A Pass See table 3.
51 Distribution verification extinguishment test with automatic
extinguisher unit
N/A
51.1 General N/A
51.2 Test enclosure N/A
51.3 Maximum area coverage, minimum height and maximum
volume test arrangement procedure
N/A
51.4 Maximum height and maximum volume test arrangement
procedure
N/A
52 Automatic extinguisher unit automatic operation
extinguishment unit
N/A
Kiwa®
product declaration K86656/02 Page 8 of 11
DSPA Non-Pressurized Condensed Aerosol Generators and Components
Chapter Description Demand 1) Result Remarks
52.1 General N/A
52.2 Test enclosures N/A
52.3 Test arrangement procedure N/A
53 Elastomeric parts test N/A
54 Stress corrosion cracking test for brass parts A Pass Materials used in the
construction are not susceptible
to ammonia stress corrosion.
55 Aging test condensed aerosol generator Pass 116 days at 90 ºC = 15 years
56 Aging test plastic materials N/A
56.1 Air-oven aging test N/A
56.2 Light and water test N/A
57 Nameplate exposure test N/A
58 Nameplate adhesion test N/A
59 Nameplate abrasion test N/A
60 Locking device and tamper indicator test N/A
Manufacturing and production tests
61 General Implemented
61.1 General Implemented
61.2 Aerosol-forming compound A Pass
61.3 Electrical initiators A Pass
61.4 Hydraustatic pressure test – shells for pneumatic control
assemblies
N/A
61.5 Gauge calibration test for pneumatic control assemblies N/A
61.6 Leakage test for pneumatic control assemblies N/A
Markings
62 General A Pass
Instructions
63 General Implemented
64 Owner’s manual A Pass See DSPA Manual V7.3 2015
65 Design, installation, operating and maintenance instruction A Pass See DSPA Manual V7.3 2015
Kiwa®
product declaration K86656/02 Page 9 of 11
DSPA Non-Pressurized Condensed Aerosol Generators and Components
Chapter Description Demand 1) Result Remarks
manual
1) A = Applicable N/A = Not Applicable Not tested
Tests not performed (with requirements):
• Aerosol generator explosive atmosphere test according to UL 2775 § 26
• Fire Exposure test according to UL 2775 § 27
• Wood cribs test according to UL 2775 § 49.2.2
Kiwa®
product declaration K86656/02 Page 10 of 11
DSPA Non-Pressurized Condensed Aerosol Generators and Components
Product specifications
Table 1
Fire
Class
Listing According
UL 2775
Pre burn
time
Soak period Test room Density
Material / fuel in seconds in seconds in m3 in grams per m3
A & C Polymethylmethacrylate 49.2.3 210 600 112.12 97
A & C Polypropylene 49.2.3 210 600 112.12 58
A & C ABS 49.2.3 210 600 112.12 87
B Heptane 49.3 30 30 112.12 34
Table 2
Type Efficiency in %
DSPA 11-1 100
DSPA 11-2 88 - 100
DSPA 11-3 90 - 100
DSPA 11-4 100
DSPA 11-5 94 - 100
DSPA 11-6 100
DSPA 11-7 100
DSPA 8-1 100
Table 3
Type Housing
Type and
Discharge
method
Agent distribution according UL2775
Minimum height /
Maximum area coverage (in m)
Maximum height /
Maximum area coverage (in m)
DSPA 11-1 Disk, radial 0.5 3.66 x 1.22 1.83 1.22 x 1.22
DSPA 11-2 Disk, radial 0.5 3.66 x 2.44 2.44 1.22 x 1.22
DSPA 11-3 Disk, radial 0.5 3.66 x 2.44 2.44 1.22 x 1.22
DSPA 11-4 Disk, radial 1.22 3.66 x 3.66 3.05 1.83 x 1.83
DSPA 11-5 Disk, radial 1.22 4.88 x 3.66 3.66 2.44 x 2.44
DSPA 11-6 Disk, radial 1.22 7.32 x 3.66 3.66 2.44 x 2.44
DSPA 11-7 Disk, axial 1.22 7.32 x 1.22 3.05 1.83 x 1.83
DSPA 8-1 Cylinder, axial 2.44 9.76 x 3.66 4.88 4.88 x 3.66
Table 4
Type Discharge time
In Sec
DSPA 11-1 6 - 10
DSPA 11-2 9 - 15
DSPA 11-3 14 - 26
DSPA 11-4 19 - 31
DSPA 11-5 40 - 60
DSPA 11-6 30 - 50
DSPA 11-7 30 - 50
DSPA 8-1 67 - 89
Kiwa®
product declaration K86656/02 Page 11 of 11
DSPA Non-Pressurized Condensed Aerosol Generators and Components
Table 5
Type Distance in m
75°C 200°C 400°C
DSPA 11-1 0.5 0.15 0.05
DSPA 11-2 0.5 0.15 0.05
DSPA 11-3 0.5 0.15 0.05
DSPA 11-4 1.0 0.25 0.15
DSPA 11-5 1.0 0.25 0.15
DSPA 11-6 1.5 0.35 0.15
DSPA 11-7 1.5 0.50 0.10
DSPA 8-1 1.5 0.75 0.15