Emerson Climate Technologies January 01, 2013 Compressor Information Inputs Results Compressor Model: Refrigerant: Condensing Temperature (°F): Evaporator Temperature (°F): Phase: Frequency (Hz): Volts: Compressor Superheat (°F): Evaporator Superheat (°F): Total Subcooling (F): Return Gas Temperature (°F): Power (W): Net Refrigeration Effect (Btu/hr): Isentropic Efficiency (%): Current (Amps): Evaporator EER (Btu/Wh): Compressor Capacity (Btu/hr): Compressor EER (Btu/Wh): Refrigerant Flow Rate (lb/hr): Liquid Temp. (°F): ZR72KCE-TFD 380-420 50 3 R-407C , Dew Pt. 130.0 45.0 65.0 20.0 20.0 15.0 56,500 56,500 10.97 10.97 825.0 69.1 107.0 5,150 9.1 Discharge Temp. (°F): Application: Air Conditioning Note: Net Refrigeration Capacity is the amount of useful cooling delivered to refrigerated space. Rating Conditions 20 °F Superheat 15 F Subcooling 95 °F Ambient Air Over 189.0 Discharge Temperature Estimation Accuracy ± 10 °F. Condenser Heat Rejection (Btu/hr): 74,077 RLA (MCC/1.4) (Amps): MCC (Amps): 10.0 14.0 74.0 9.0 LRA: RLA (MCC/1.56) (Amps): 6.0 HP: 2013 Emerson Climate Technologies, Inc.

ZR72KCE-TFD

Embed Size (px)

DESCRIPTION

Copeland

Citation preview

  • Emerson Climate Technologies January 01, 2013

    Compressor Information

    Inputs

    Results

    Compressor Model:

    Refrigerant:

    Condensing Temperature (F):

    Evaporator Temperature (F):

    Phase:

    Frequency (Hz):

    Volts:

    Compressor Superheat (F):

    Evaporator Superheat (F):

    Total Subcooling (F):Return Gas Temperature (F):

    Power (W):

    Net Refrigeration Effect (Btu/hr):

    Isentropic Efficiency (%):

    Current (Amps):

    Evaporator EER (Btu/Wh):

    Compressor Capacity (Btu/hr):

    Compressor EER (Btu/Wh):

    Refrigerant Flow Rate (lb/hr):

    Liquid Temp. (F):

    ZR72KCE-TFD

    380-420

    50

    3

    R-407C , Dew Pt.

    130.0

    45.0

    65.0

    20.0

    20.0

    15.0

    56,500

    56,500

    10.97

    10.97

    825.0

    69.1

    107.0

    5,150

    9.1

    Discharge Temp. (F):

    Application: Air Conditioning

    Note: Net Refrigeration Capacity is the amount of useful cooling delivered to refrigerated space.

    Rating Conditions20 F Superheat15 F Subcooling95 F Ambient Air Over

    189.0

    Discharge Temperature Estimation Accuracy 10 F.

    Condenser Heat Rejection (Btu/hr): 74,077

    RLA (MCC/1.4) (Amps):

    MCC (Amps):

    10.0

    14.0 74.0

    9.0

    LRA:

    RLA (MCC/1.56) (Amps):

    6.0HP: