1
XMC0 Series Definite Purpose Contactors
Description HOMER XMC0 series high performance definite purpose contactors (1- pole, 1-pole+shunt, 2-pole, 3-pole(optional Auxiliary Contact Blocks or Microswitch Blocks available, from 25A to 90A ) are ideal for (HVAC) air conditioning, refrigeration, heating, data processing, welding, elevators, hoists & cranes, washing machine, lighting, pools & spas and food service equipments. XMC0 series definite purpose contactors meet IEC 60947-4- 1, GB 14048.4 and UL508 standard.
Features 1. Tools-free accessories make quick & easy snap on. 2. Various terminal optional for specific application. 3. Universal mounting plate allows an easy replacement other brands. 4. Heavy duty Silver Metal Oxide composition contacts with longer electrical endurance. 5. Coils are Class F (155 ) temperature insulated with wide range of voltage℃ s and 50/60Hz ratings. 6. Different with main competitors,our1&2P contactors have the options to add coil cover to effectively
protect the coil from being damaged by outer force. 7. UL and CCC approved, some models SEMKO, KETI or TÜV plus.
Type model nomenclature - Ordering Information
XM C 0 – 25 3 . E B B C 30 F Q □ □ □ 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Number digit 1: Manufacturer’s code XM – Xiamen Hongmei Electronic Co., Ltd.
Number digit 2: Product Type C – Contactor
Number digit 3: Design Sequence Number – 0
2
Number digit 4: Full Load Amperes (FLA) – 25, 32, 40, 50, 63, 75 or 90
25 – 25A 32 – 32A 40 – 40A 50 – 50A 63 – 63A 75 – 75A 90 – 90A
Number digit 5: Number of Poles – 1, 2, 3, 3A, 7
Number digit 5 1 2 3 3A 7
Number of poles 1-pole+shunt 2-pole 3-pole 2-pole (at 3p frame) 1-pole
Number digit 6: Coil Voltage – E, F, I, L, N
Number digit 6 E F I L N 50Hz 24VAC 110-120VAC 208-220VAC -- 380-415VACCoil voltage 60Hz 24VAC 110-120VAC 208-240VAC 277VAC 440-480VAC
Number digit 7: Mounting plate – A, B (B: Normal)
A – Plastic base(For 25-40FLA only, not recommend)
B – Metal plate
Number digit 8: Cover – A, B (B:Normal)
A – Long cover(For 25-40FLA only, not recommend)
B – Short cover Number digit 9: Terminal – A, B, C, D, E, F
A – Screw w/ quick connect (For 25-40FLA only)
B – Sems clamp w/ quick connect (For 25-40FLA only) C – Slotted & Hex head washer w/ quick connect
D – Box lug w/ quick connect E – Box lug w/ quick connect (Line side)
Slotted & Hex head washer w/ quick connect (Load side)
3
F – Slotted & Hex head washer w/ quick connect (Line side)
Box lug w/ quick connect (Load side)
Number digit 10: Auxiliary Contact Blocks or Microswitch Blocks (for 3-pole) (Left & Right) side
(SPDT is Microswitch) – 0, 1, 3, 4, 5, 6, 1P, 3P, 4P, 5P, 6P, L, L1, L2, R, R1, R2
Aux. contact Blocks or Microswitch Blocks on left side
Aux. contact Blocks or Microswitch Blocks on right side
0 None (Standard Type)
1 1NC+1NO, 0.250” quick connect terminal
3 1NC, 0.250” quick connect terminal
4 1NO, 0.250” quick connect terminal
5 2NC, 0.250” quick connect terminal
6 2NO, 0.250” quick connect terminal
1P 1NC+1NO, pressure plate screw
3P 1NC, pressure plate screw
4P 1NO, pressure plate screw
5P 2NC, pressure plate screw
6P 2NO, pressure plate screw
L 2 SPDT
L1 1 SPDT, left side(position 1) of microswitch block
L2 1 SPDT, right side(position 2) of microswitch block
0 None (Standard Type)
1 1NC+1NO, 0.250” quick connect terminal
3 1NC, 0.250” quick connect terminal
4 1NO, 0.250” quick connect terminal
5 2NC, 0.250” quick connect terminal
6 2NO, 0.250” quick connect terminal
1P 1NC+1NO, pressure plate screw
3P 1NC, pressure plate screw
4P 1NO, pressure plate screw
5P 2NC, pressure plate screw
6P 2NO, pressure plate screw
R 2 SPDT
R1 1 SPDT, left side(position 1) of microswitch block
R2 1 SPDT, right side(position 2) of microswitch block
For example: 34P – 1NC pressure plate screws w/ quick connect on left side, 1NO pressure plate screws on right side 56 – 2NC pressure plate screws w/ quick connect on left side, 2NO pressure plate screws w/ quick connect on right side LR1 – 2SPDT on left side, 1SPDT(position 1) on right side 3R2 – 1NC pressure plate screws w/ quick connect on left side, 1SPDT(position 2) on right side
Note: If “00” will be the final digit(s) in selection, omit from model nomenclature. Number digit 11: Coil terminals – Blank, F
Blank – Dual terminals without screws in 1- and 2- pole models and Single terminals with screws in 3-pole models F – Dual terminals with screws in 3- pole models
Number digit 12: Power quick terminals – Blank, G, Q Blank – Quad terminals in 1-and 2- pole models and Dual terminals in
3-pole models G – Without any terminals Q – Dual terminals at the side near coil terminal and Quad terminals at the other
side in 3-pole 25-40FLA models
4
Number digit 13: Nameplate – Blank, T
Blank – Nameplate shows actual product rating T – Nameplate shows derated product rating
Number digit 14: Contact construction style (for 50/63 FLA) – Blank, Z
Blank – Flat construction in shape Z – Bend construction in shape (new design)
Number digit 15: Option Customer assigned suffix “X” where “X” may be any alphanumeric character or any combined alphanumeric character. Characteristics
Conforming to standard IEC60947-4-1, GB14048.4, UL508
Approvals UL(USR/CNR) and CCC Some models SEMKO, KETI or TÜV plus
Protective treatment Total climate tropical use “TH”
Operating position Vertical or Horizental (Metal/Plastic base mounting)
operation ℃ -25℃~+70℃ Ambient temperature storage ℃ -40℃~+70℃ Relative humidity 90-95%RH at 40℃ Pollution degree 3
Performance
XMC0- Poles 1 2 3 3A 7 Rated insulation voltage V 690 Rated operating voltage V 240/277,480,600 (60Hz) or 230,400 (50Hz) Rate current(AC-8a) A 25 32 40 50 63 75 90 Conventional free air thermal current (Ith) A 32 40 50 63 80 94 120Full Load Ampere(FLA) A 25 32 40 50 63 75 90
Resistive Amps Rating(RES) A 35 40 50 63 75 94 120
Switching frequency op/h 360
Electrical endurance(ARI 780/790) cycle 200,000
Mechanical life (ARI 780/790) cycle 500,000
5
Pole Characteristics
Maximum Horsepower(HP) Full Load
Amps(FLA)/ Rated
operation Amps(AC-8a)
Poles VoltageLocked Rotor Amps (LRA)
Resistive Amps Rating (RES)
Conventional free air thermal
current(Ith) Voltage Single Phase
ThreePhase
Catalog Number
25 1 240/277
480 600
150 - -
35 32 240/277 2 - XMC0-257* XMC0-251*
32 1 240/277
480 600
180 150 120
40 40 240/277 2 - XMC0-327* XMC0-321*
40 1 240/277
480 600
240 - -
50 50 240/277 3 - XMC0-407* XMC0-401
40 1 240/277
480 600
240 200
- 50 50 240/277 3 - XMC0-407*H
XMC0-401*H
25 2 240/277
480 600
150 125 100
35 32 240/277 3 - XMC0-252*
32 2 240/277
480 600
180 150 120
40 40 240/277 3 - XMC0-322*
40 2 240/277
480 600
240 200 160
50 50 240/277 3 - XMC0-402*
25 2 3
240/277480 600
150 125 100
35 32 240/277
480 600
3 - -
5 7.5 10
XMC0-253A* XMC0-253*
32 2 3
240/277480 600
180 150 120
40 40 240/277
480 600
3 - -
7.5 10 15
XMC0-323A* XMC0-323*
40 2 3
240/277480 600
240 200 160
50 50 240/277
480 600
5 - -
10 15 20
XMC0-403A* XMC0-403*
50 2 3
240/277480 600
300 250 200
63 63 240/277
480 600
5 - -
15 20 25
XMC0-503A* XMC0-503*
63 2 3
240/277480 600
360 300 240
75 80 240/277
480 600
7.5 - -
20 25 30
XMC0-633A* XMC0-633*
75 2 3
240 480 600
450 375 300
94 94 240 480 600
15 - -
25 40 40
XMC0-753A* XMC0-753*
90 2 3
240 480 600
540 450 360
120 120 240 480 600
15 - -
30 50 50
XMC0-903A* XMC0-903*
Note: All the models also could be marked or used for the actual applications which have less contact ratings than the certificated ratings. The rating can be Voltage, FLA, LRA or RES.
6
Auxiliary contacts block characteristics
Conventional thermal current (A) 10
Rated insulation voltage (V) 690
A600(AC-15) 230/380V 3/1.9 Rated operational current (A)
N600(DC-13) 110/230V 2.2/1.1
Microswitch Blocks characteristics
Contact Rating(SPDT) 10A or 11A, 1/3 HP, 125 or 250 VAC
1/2A, 125 VDC; 1/4A, 250 VDC 4A 120 VAC on Lamp Load
Coil characteristics @ 25℃(Cold state)
Part number Inrushed VA Sealed VA Sealed Watts Voltage 60Hz 50Hz 60Hz 50Hz 60Hz Pick-up Drop-out
XMC0-□1/7 40 55 7.5 10 3 XMC0-□2 45 55 8 10.5 3.5 XMC0-□3/3A 80 90 12 16 5 XMC0-503/633 145 160 17.6 23 7 XMC0-753/903 300 325 35 46 12
≤0.8Us ≥0.2Us
Notes:Us=24VAC 50/60Hz(“E“coil) or 120VAC 50/60Hz(“F“coil) or 220VAC/50Hz, 240VAC/60Hz(“I“coil) or 277VAC/60Hz(“L“ coil) or 415VAC/50Hz, 480VAC/60Hz(“N“coil). Inrushed VA and Sealed VA test at Us.
Dimensions & Wiring diagram
7
8
9
10
11
12
13
14
15
Remarks
1) Torque for Screws 25 lb-in/Lugs 25 lb-in for 25-40FLA types;
Torque for Screws 45 lb-in /Lugs 50 lb-in for 50-63FLA types;
Torque for Screws 50 lb-in /Lugs 60 lb-in for 75-90FLA types;
Torque for Screws 8 lb-in for Auxiliary Contact Blocks;
Torque for Coil Screws 8 lb-in for 3-pole 25-40FLA types and 12 lb-in for 50-90FLA types;
2) For QC wiring, the female connector should meet IEC60760, necessary to ensure the
reliability of connection between female connectors and QC terminals.
3) If the actual condition differs from this specification, please contact us for further discussion.