13
BRISTOL BABCOCK APPLICATION NOTE TeleFlow/AATM Page 1 Wiring TeleFlow (3530-XXX) To Invensys Auto-Adjust Turbo-Meter Table of Contents Section 1 - FORWARD .............................................................................................................. 2 Section 2 - DEFINITIONS ........................................................................................................2 Section 3 - WIRING ................................................................................................................... 3 Section 4 - SOFTWARE CONFIGURATION.......................................................................... 13

Wiring TeleFlow (3530-xxx) to Invensys Auto-Adjust … Invensys Auto-Adjust Turbo-Meter ... Wiring diagrams are provided for the following 4 different ... Wiring TeleFlow (3530-XXX)

  • Upload
    trannhi

  • View
    228

  • Download
    1

Embed Size (px)

Citation preview

BRISTOL BABCOCK APPLICATION NOTE

TeleFlow/AATM Page 1

Wiring TeleFlow (3530-XXX)To

Invensys Auto-Adjust Turbo-Meter

Table of Contents

Section 1 - FORWARD ..............................................................................................................2

Section 2 - DEFINITIONS ........................................................................................................2

Section 3 - WIRING...................................................................................................................3

Section 4 - SOFTWARE CONFIGURATION..........................................................................13

BRISTOL BABCOCK APPLICATION NOTE

Page 2 TeleFlow/AATM

Section 1 - Forward

This document provides technical information on wiring the Bristol Babcock line ofTeleFlow series products to an Invensys Auto-Adjust Turbo-Meter.

TeleFlow series (3530) units listed in Table 1-1 can be interconnected to an Invensys Auto-Adjust Turbo-Meter. Interface requirements dictate the 3530 be equipped with at least twoPulse (Counter) Inputs. The TeleFlow Plus (Model 3530-20B) is equipped with a TeleFlowCPU Board and will require the use of a BBI Low Power I/O Expansion Board since theCPU Board has only one Pulse Input. Units equipped with the TeleRTU CPU Board don’trequire an additional Low Power I/O Expansion Board (unless an additional Pulse Input isdictated) since the TeleRTU CPU Board is equipped with two Pulse Inputs.

Table 1-1 – 3530-XXX Organizational Overview & I/O Requirements

Model NumberProduct Name

Expansion I/ORequired?

Notes

3530-15B - TeleRTU NO Expansion Bd. Not Accommodated3530-20B - TeleFlow Plus YES Expansion Bd. Accommodated3530-25B - TeleRTU Plus NO Expansion Bd. Accommodated3530-35B - TeleRTU Module NO Expansion Bd. Accommodated3539-45B - TeleRecorder NO Expansion Bd. Not Accommodated

This documents provides illustrations that show the recommended connections betweenBBI Series 3530s and the Invensys Auto-Adjust Tubo-Meter in a Class I, Division 2environment.

Section 2 - Definitions

The Auto-Adjust Turbo-Meter (AAT) meter referenced herein is manufactured by InvensysEnergy Metering, 805 Liberty Blvd. DuBois, PA 15801.

Control Amplifiers shown in the illustrations provided herein are manufactured byPepperl+Fuchs.

Abbreviations used within this document (text and illustrations) are provided below:

AAT Auto-Adjust Turbo-MeterBTS Blade Tip SensorCPU Central Processing UnitEXC Excitation (+12Vdc) from 3530-XXX CPU Bd.MR AAT Main RotorSR AAT Sensor RotorSS Slot Sensor

BRISTOL BABCOCK APPLICATION NOTE

TeleFlow/AATM Page 3

Section 3 - Wiring

Recommended wiring is shown for connection of a Bristol Babcock Series 3530-XXX unit toan AAT. Figures 2 through 5 are provided for 3530s equipped with a TeleFlow CPU Board,i.e., 3530-10B, -20B and –50B. These units require the use of a Low Power I/O ExpansionBoard. The Low Power I/O Expansion Board provides a second counter input for the SensorRotor. Figures 6 through 9 are provided for 3530s that utilize the TeleRTU CPU Board, i.e.,3530-15B, -25B, -35B and -45B. Figure 1 shows and edge view of the BBI 3530-XXX circuitboards utilized to interface to an AAT.

Figure 1 - BBI CPUs and Low Power I/O Expansion Boards

BRISTOL BABCOCK APPLICATION NOTE

Page 4 TeleFlow/AATM

A control amplifier/barrier is required between the AAT and the 3530-XXX; the amplifiermodel numbers shown (“K” numbers) in Figures 2 through 9 are for Pepprl+Fuchs devices.

Wiring diagrams are provided for the following 4 different types of amplifiers:

24 Vdc with Slot Sensor (SS)24 Vdc with Blade Tip Sensor (BTS)120 Vac with SS120 Vac with BTS

The Blade tip configuration requires +12 VDC to the AAT sensors through a MTL715+isolator made by MTL Instruments Inc.

The amplifier outputs are connected in “emitter-follower” mode i.e., the emitter of theoutput transistor connects to the 3530-XXX counter input which has a 1000 ohm “pulldown” resistor to circuit common.

+12 Vdc for the amplifier output stage is supplied from the 3530-XXX CPU Board via anExcitation (EXC) terminal. On the TeleRTU CPU Board, EXC is available from Pin #2 ofconnectors P10, P11, P12 or P13. On the TeleFlow CPU Board, EXC is available from Pin#7 of connector P14.

Table 3-1 – Wiring Diagrams

CONFIGURATION 3530-XXX CPU Bd. FIGURE PAGE #24 Vdc with Slot Sensor (SS) TeleFlow 2 5120 Vac with Slot Sensor (SS) TeleFlow 3 624 Vdc with Blade Tip Sensor (BTS) TeleFlow 4 7120 Vac with Blade Tip Sensor (BTS) TeleFlow 5 824 Vdc with Slot Sensor (SS TeleRTU 6 9120 Vac with Slot Sensor (SS) TeleRTU 7 1024 Vdc with Blade Tip Sensor (BTS) TeleRTU 8 11120 Vac with Blade Tip Sensor (BTS) TeleRTU 9 12

BRISTOL BABCOCK APPLICATION NOTE

TeleFlow/AATM Page 5

Figure 2 - Slot Sensor AAT Meter to BBI 3530-20B (via 24 Vdc Control Amplifier)

BRISTOL BABCOCK APPLICATION NOTE

Page 6 TeleFlow/AATM

Figure 3 - Slot Sensor AAT Meter to BBI 3530-20B (via 120 Vac Control Amplifier)

BRISTOL BABCOCK APPLICATION NOTE

TeleFlow/AATM Page 7

Figure 4 - Blade Tip Sensor AAT Meter to BBI 3530-20B(via 24 Vdc Control Amplifier)

BRISTOL BABCOCK APPLICATION NOTE

Page 8 TeleFlow/AATM

Figure 5 - Blade Tip Sensor AAT Meter to BBI 3530-20B(via 120 Vac Control Amplifier)

BRISTOL BABCOCK APPLICATION NOTE

TeleFlow/AATM Page 9

Figure 6 - Slot Sensor AAT Meter to BBI 3530-XXB (with TeleRTU CPU Bd.)(via 24 Vdc Control Amplifier)

BRISTOL BABCOCK APPLICATION NOTE

Page 10 TeleFlow/AATM

Figure 7 - Slot Sensor AAT Meter to BBI 3530-XXB (with TeleRTU CPU Bd.)(via 120 Vac Control Amplifier)

BRISTOL BABCOCK APPLICATION NOTE

TeleFlow/AATM Page 11

Figure 8 - Blade Tip Sensor AAT Meter to BBI 3530-XXB (with TeleRTU CPU Bd.)(via 24 Vdc Control Amplifier)

BRISTOL BABCOCK APPLICATION NOTE

Page 12 TeleFlow/AATM

Figure 9 - Blade Tip Sensor AAT Meter to BBI 3530-XXB (with TeleRTU CPU Bd.)(via 120 Vac Control Amplifier)

BRISTOL BABCOCK APPLICATION NOTE

TeleFlow/AATM Page 13

Section 4 - Software Configuration

In order to access data from the Invensys Auto-Adjust Turbo-Meter, you will need toconfigure the AAT Module in your ACCOL Load. Full details on configuring the AATModule are included in the ‘AAT’ section of the ACCOL II Reference Manual (documentD4044).