66
Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding and bonding Webinars presented by NECA. This Webinar topic is grounding separately derived systems such as transformers and generators. Introduction of speaker and subject. 1

Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

  • Upload
    others

  • View
    14

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding and bonding Webinars presented by NECA. This Webinar topic is grounding separately derived systems such as transformers and generators. Introduction of speaker and subject.

1

Page 2: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Presenters should use this slide to provide and overview of what will be covered in the presentation. This program covers the general requirements for grounding separately derived systems on the load side of the service disconnecting means. A complete review of the requirements in Section 250.30 are included in this presentation. This program provides specific focus on transformer-type as well as generator-type separately derived systems.

22

Page 3: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Presenters should review the requirements in 250.30(A)(1) through (8). These will be covered in detail in this presentation.

3

Page 4: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

This slide provides the definition of the term separately derived system from article 100 of the NEC-2008.

4

Page 5: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

This slide shows two examples of systems that are not separately derived. In the transfer switch, there is no switching action in the neutral conductor, thus the generator is not to be grounded as a separately derived system because with the transfer equipment in the normal position or the standby position, the grounded conductor remains connected to ground (earth). The auto transformer is not separately derived because one conductor (the grounded conductor) is common to both primary and secondary. A luminaire (lightning fixture) ballast is a good example of an auto transformerof an auto transformer.

5

Page 6: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Photo shows a transformer separately derived system that is typical of many commercial and industrial facilities. Note the primary and secondary feeder entries on the lower right front of the enclosure. The grounding electrode conductor can be seen routed through the masonry wall to an electrode according to 250.30(A)(7).

6

Page 7: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Photo shows an electrician making connections in a dry-type transformer. Note the primary and secondary feeder conductors are connected and identified according 215.12(C). Equipment grounding conductors (with the primary) and equipment bonding jumpers (with the secondary) can be seen exiting the left side of the enclosure. The transformer is not energized and the worker is wearing suitable PPE (hard hat, safety glases, and vest).

7

Page 8: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Section 250.20(A) and (B) provides the requirements for whether a system must be grounded, or if grounding the system is optional.

If systems are required to be grounded based on the criteria in 250.20(A) or (B), then the system shall be grounded in accordance with 250.30(A).

Where a generator-type systems is provided with transfer equipment that includes a switching action in the grounded (neutral) conductor, the generator is required to be grounded in accordance with Section 250.30(A).

88

Page 9: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Presenters should emphasize how important the transfer switch is in determining the grounding requirements for generators. If there is a switching action in grounded conductor in the transfer equipment, The generator has to be grounded as a separately derived system according to 250.30(A).

9

Page 10: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

If there is a switching action in grounded conductor in the transfer equipment, The generator has to be grounded as a separately derived system according to 250.30(A). Graphic shows a switch in the grounded conductor. When the transfer switch is in the standby mode, the grounded conductor is not connected to the service grounding electrode.

10

Page 11: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

If there is no switching action in grounded conductor in the transfer equipment, the generator is not grounded as a separately derived system according to 250.30(A). Graphic shows solidly connected grounded conductor that remains whether the transfer switch is in the normal mode or the standby mode. When the transfer switch is in the standby mode, the grounded conductor remains connected to the service grounding electrode. Note the separation and isolation between the grounding conductor and the equipment bonding jumper/equipment grounding conductor at the generator This meets the requirements in 250 24(A)(5)conductor at the generator. This meets the requirements in 250.24(A)(5).

11

Page 12: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

This slide provides a review of the arrangement of Section 250.30. Presenters should review the required grounding components for grounded systems as compared to ungrounded systems. An ungrounded system includes only ungrounded conductors and as no grounded conductor (a conductor that is intentionally connected to ground).

1212

Page 13: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

This slide provides the arrangement of 250.30(B), for ungrounded systems. There is no grounded conductor in an ungrounded system. Presenters should make the point about requirements for ground detectors for ungrounded systems.

13

Page 14: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

This slide is a graphic representation of a transformer-type separately derived system showing all elements of 250.30(A). Instructors should use the Code book and review with the students each of the elements addressed in 250.30(A)(1) through (8). Make the point that the system bonding jumper connection can be made in the source enclosure or the first system overcurrent device enclosure.

14

Page 15: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Photo of a transformer separately derived system showing system bonding jumpers, grounding electrode conductor, grounded conductor, equipment grounding conductors, and equipment bonding jumpers. This installation uses parallel conductors according to 310.4.

15

Page 16: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

This slide reviews the general provisions in Section 250.30(A). It is important to review the restriction of grounding connections to the grounded conductor on the load side of the grounding point. The grounding point can be either at the source enclosure or at any point up to and including the first disconnecting means or overcurrent device enclosure.

1616

Page 17: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

The system bonding jumper shall connect the equipment grounding conductors of the derived system to the grounded conductor.

This connection shall be made at any single point on the derived system from the source to the first system overcurrent device or

disconnecting means enclosure.

1717

Page 18: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

System bonding jumpers are permitted in the source enclosure and the first system disconnecting means enclosure where doing so does not create a parallel path for the grounded conductor (neutral current). See Exception No. 2 to 250.30(A)(1).

18

Page 19: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

This graphic shows the system bonding jumper in the source enclosure and an equipment bonding jumper between enclosures that serves as an effective ground-fault current path to the source. Note that the grounding electrode conductor connection to the system is made in the same enclosure as the system bonding jumper.

19

Page 20: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

The photo shows the source enclosure and the first system overcurrent device enclosure. The transformer secondary connection have to meet the 10 or 25 foot rules in 240.21.

20

Page 21: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

The system bonding jumper is shown in the first system overcurrent device enclosure. Note the equipment bonding jumper between enclosures serving as an effective ground-fault current path. The grounding electrode conductor connection to the system is made in the same enclosure where the system bonding jumper is installed.

21

Page 22: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Review the definition of the term system bonding jumper in 250.2.

22

Page 23: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Size system bonding jumper according to 250.28(C). Use Table 250.66 or 12.5% rule as necessary. Note that the system bonding jumper could be any of the types provided in 250.28(A) where it is part of listed equipment. Where it is a wire-type conductor, use Table 250.66 or the 12.5% rule where the cm area of the largest derived phase conductor exceeds 1100 kcmil copper or 1750 kcmil aluminum.

23

Page 24: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

The equipment bonding jumper (wire-type) run between the source enclosure and the first system overcurrent device enclosure shall

be sized in accordance with 250.102(C). The equipment bonding jumper could be a raceway of any type provided in 250.118.

Use Table 250.66 or the 12.5% rule for larger derived phase conductors supplied by the derived systemthe derived system.

2424

Page 25: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Bonding between the source enclosure and the first system overcurrent device enclosure can be with any of the acceptable equipment grounding conductors (raceway-types) listed in 250.118. This serves as an effective ground-fault current path. Workmanship is important here. Fittings must be made up tight.

25

Page 26: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Equipment bonding jumpers of the wire-type must be sized according to 250.102(C). Note that from the secondary of a derived system to the first system overcurrent device enclosure, the conductors are supply-side. Size the EBJ according to Table 250.66 or use the 12.5% rule where the cm area of the largest derived phase conductor exceeds 1100 kcmil copper or 1750 kcmil aluminum. Note that flexible metal conduit and liquidtight flexible metal conduit have limitations as an effective ground-fault current path per 250.118(5) and (6). Equipment bonding jumpers of the wire type must be installedjumpers of the wire type must be installed.

26

Page 27: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Review the sizing requirements for the equipment grounding conductor (primary side) using 250.122 and the equipment bonding jumper (secondary side) using 250.66.

27

Page 28: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Grounding electrode conductor rules in 250.30(A) address single grounding electrode conductors and a common grounding electrode

conductor used with multiple separately derived systems.

Size the grounding electrode conductor using Table 250.66 based on the size of the cm area of the largest derived phase conductor

supplied by the systemsupplied by the system.

2828

Page 29: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Section 250.8 provides a complete list of methods for connecting grounding and bonding conductors.

The type of grounding conductor connection or bonding conductor connection must meet any specific requirements of either

250.30(A)(3) and (A)(4) and the general requirements in 250.8.

2929

Page 30: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Presenters should provide a review of using Table 250.66 for sizing the grounding electrode conductor for separately derived systems.

3030

Page 31: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Instructors should review the provisions of 250.66(A), (B), and (C). These sizing allowances only apply where the grounding electrode conductor is solely connected to the electrode and no other electrodes are connected to the same grounding electrode conductor. This slides reviews the provisions for rod, pipe, and plate electrodes in (A) and concrete-encased electrodes in (B).

3131

Page 32: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Section 250.66(C) indicates that a grounding electrode conductor connected to just a ring electrode does not have to be any larger than the ring. The minimum size required for a ground ring is 2 AWG in accordance with 250.52(A)(4).

32

Page 33: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

A grounding electrode conductor for a single separately derived system shall be sized in accordance with 250.66 based on the cm of

the largest derived phase conductor

Shall be used to connect the grounded conductor of the derived system to the grounding electrode as specified in 250.30(A)(7).

3333

Page 34: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

The graphic shows the grounding electrode conductor connected to the grounded conductor of the derived system. This connection is made in the source enclosure with the system bonding jumper. Size the GEC using Table 250.66. The GEC does not have to be larger than the maximum values provided in Table 250.66.

34

Page 35: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Where more than one separately derived system is installed, it shall be permissible to connect a tap from each separately derived

system to a common grounding electrode conductor.

Each tap conductor shall connect the grounded conductor of the separately derived system to the common grounding electrode

conductorconductor.

3535

Page 36: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

The grounding electrode conductors and taps shall comply with 250.30(A)(4)(a) th h (A)(4)( )through (A)(4)(c).

The common grounding electrode conductor tap concept is addressed in 250.30(A)(4).

The common grounding electrode conductor shall not be smaller than 3/0 AWG 2 0 k il l icopper or 250 kcmil aluminum.

Each tap conductor shall be sized in accordance with 250.66 based on the derived phase conductors of the separately derived system

it serves.

3636

Page 37: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Use this graphic to differentiate between the common grounding electrode conductor and the grounding electrode conductor tap. Remind the students that the common grounding electrode conductor shall be not smaller than the maximum values in Table 250.66.

37

Page 38: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

All tap connections to the common grounding electrode conductor shall be made at an accessible location by one of the following

methods:

(1) A listed connector(2) Listed connections to aluminum or copper busbars not less than 6 mm × 50

mm (1/4 in × 2 in )mm (1/4 in. × 2 in.)(3) The exothermic welding process.

3838

Page 39: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Grounding electrode conductor connections required to be listed. Note that for water pipe electrodes, the connection shall be made within 1.52 m (5 ft) of the point of entry to the building. The purpose is to reduce the length of water pipe that has to serve as a grounding electrode conductor.

39

Page 40: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

There are also bonding requirements for metal piping systems. Section 250.30(A)(6) refers to 250.104(D) for the bonding requirements.

Metal water piping systems and structural metal that is interconnected to form a building frame shall be bonded to separately derived

systems in accordance with (D)(1) through (D)(3).

The grounded conductor of the derived system shall be bonded to the nearest available point of the metal water piping system(s) in

the area served by each separately derived system.

4040

Page 41: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Where exposed structural metal that is interconnected to form the building frame exists in the area served by the separately derived system, it shall be bonded to the grounded conductor of each separately derived system.

4141

Page 42: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

The grounding electrode required for a separately derived system are required by 250.30(A)(7). The electrode has to be as near as practicable and preferably in the same areas as the grounding electrode conductor connection to the system.

4242

Page 43: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

The grounding electrode has to be the nearest of either a water pipe electrode or a building frame electrode. If neither is available for use, any of the other electrodes in 250.52(A) shall be used for grounding the separately derived system.

43

Page 44: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Article 100 of the NEC defines the term Grounding Electrode as a conducting object through which a direct connection tothrough which a direct connection to

earth is established.

The grounding electrode establishes and maintains a direct connection to earth.

A list of grounding electrodes is provided in Section 250.52(A).

4444

Page 45: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

A metal underground water pipe is required to be in direct contact with the earth for 3.0 m (10 ft) or more.

Interior metal water piping located more than 1.52 m (5 ft) from the point of entrance to the building shall not be used as a part of

the grounding electrode system or as a conductor to interconnect electrodes that are part of the grounding electrode systemare part of the grounding electrode system.

4545

Page 46: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Water pipe electrode connection made using a listed pipe clamp. Connection is made within 1.52 m (5 ft) of the water pipe point of entry to the building.

46

Page 47: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

The metal frame of the building or structure that is connected to the earth by any of the methods in 250.52(A)(2) items (1) through (3).

4747

Page 48: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Section 250.30(A)(8) provides sizing rules for the grounded conductor supplied by a separately derived system.

These sizing rules are similar to the sizing requirements for grounded conductors of services as provided in 250.24(C)(1).

4848

Page 49: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Grounded conductors have to be identified according to 200.6.

Overcurrent devices are generally prohibited in any grounded conductor in accordance with 240.22.

49

Page 50: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

All generators are electrical power sources or systems. How they are grounded depends on the transfer equipment employed.

5050

Page 51: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

The photo shows a utility transformer (normal power source for the building) and a generator (standby power system for the building). There should be some form of transfer equipment located on the premises for switching from normal to standby power when the utility source is interrupted.

51

Page 52: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Where the transfer switch for the generator system includes a switching action in the grounded (neutral) conductor, the generator (system) must be grounded as required in 250.30(A).

5252

Page 53: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

If there is a switching action in grounded conductor in the transfer equipment, The generator has to be grounded as a separately derived system according to 250.30(A). Graphic shows a switch in the grounded conductor. When the transfer switch is in the standby mode, the grounded conductor is not connected to the service grounding electrode.

53

Page 54: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Photo shows a transfer switch in an electric room of a building.

54

Page 55: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

This photo shows a transfer switch that includes a switching action in the grounded (neutral) conductor (far right side of switch). Note that the photo was taken with the equipment shut off. See NFPA 70 for requirements for safety-related work practices.

55

Page 56: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Where the transfer switch for the generator system does not include a switching ti i th d d ( t l) d t th t ( t ) i taction in the grounded (neutral) conductor, the generator (system) is not

grounded as specified in 250.30(A).

The grounded (neutral) conductor and the equipment grounding conductor/equipment bonding jumper must be isolated from each

other in accordance with 250.24(A)(5).

5656

Page 57: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Generators are equipment that requires grounding. The frame of a generator is usually connected to an equipment grounding conductor but can also be connected to an auxiliary electrode, especially of the generator is located outside. There is a terminal lug provided on most generators for this purpose.

57

Page 58: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

If there is no switching action in grounded conductor in the transfer equipment, the generator is not grounded as a separately derived system according to 250.30(A). Graphic shows solidly connected grounded conductor that remains whether the transfer switch is in the normal mode or the standby mode. When the transfer switch is in the standby mode, the grounded conductor remains connected to the service grounding electrode. Note the separation and isolation between the grounding conductor and the equipment bonding jumper/equipment grounding conductor at the generator This meets the requirements in 250 24(A)(5)conductor at the generator. This meets the requirements in 250.24(A)(5).

Note that the generator frame is connected to an auxiliary electrode in accordance with 250.54.

58

Page 59: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

This slide provides a high level review of the elements of the grounding and bonding scheme for an ungrounded separately derived system. Note that there is no grounded conductor.

5959

Page 60: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

This slide is a graphic illustration of the grounding scheme for an ungrounded separately derived system. Note that there is no grounded (neutral) conductor and system bonding jumper. All other grounding and bonding conductors are required and must be sized the same way as if it were a grounded system.

60

Page 61: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

For ungrounded systems, a grounding electrode conductor, sized in accordance with 250.66 for the derived phase conductors, shall

be used to connect the metal enclosures of the derived system to the grounding electrode.

The grounding electrode conductor connection shall be made at any point on the separately derived system from the source to theseparately derived system from the source to the

first system disconnecting means.

6161

Page 62: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

There is no grounded conductor in an ungrounded system. There is an equipment grounding conductor (primary side), equipment bonding jumper (secondary side), grounding electrode conductor, and a grounding electrode.

62

Page 63: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

The grounding electrode for ungrounded separately derived systems shall comply with 250.30(A)(7).

This requirement does not apply to portable and vehicle-mounted generators as indicated in 250.34.

6363

Page 64: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

This slide serves as the summary of the presentation and a review of the learning objectives. Separately derived systems are defined in Article 100 of the NEC. Section 250.20(D) provides key requirements that determine how and when separately derived system must comply with Section 250.30(A).

Section 250.20(D) outlines the general requirement for grounding a Section 250.20(D) outlines the general requirement for grounding a separately derived system and provides a reference to Section 250.30(A).

Rules for separately derived systems that are not grounded are provided in Section 250.30(B).

Transfer equipment used for generator systems determines how a generator-type separately derived system is to be grounded.

64

Page 65: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

Rules for separately derived systems that are not grounded are provided in Section 250.30(B).

Transfer equipment used for generator systems determines how a generator-type separately derived system is to be grounded.

65

Page 66: Welcome to a NECA Webinar based on the National ......Welcome to a NECA Webinar based on the National Electrical Code. This seminar is the fourth in a series of electrical grounding

This NECA Webinar is based on the National Electrical Code (NFPA 70-2008). This seminar is the fourth in a series of electrical grounding and bonding Webinars presented by NECA. This Webinar topic is grounding separately derived systems such as transformers and generators.

66