Insync Services Pty Ltd Page 1 of 21 Revision A – Preliminary Issue
Water Management Report
Supermarket Development
Corner of Merimbola St & Bullara St,
Pambula, NSW
Insync Services Pty Ltd Page 2 of 21 Revision A – Preliminary Issue
Client: Great Southern Developments Pty Ltd
Hydraulic & Fire Consultant: Insync Services Pty Ltd Suite 6.02, Level 6, 89 York Street, Sydney NSW 2000 (T) 02 9262 3400 (F) 02 9262 3422 Date: 18 September 2015 File: 20130059 Water Management Report.docx
Review and Approval Record: Rev Date Description of Release Prepared By Reviewed By Approved By A Preliminary Issue MH BL BL This document is and shall remain the property of Insync Services Pty Ltd. The document may only be used for the purpose for which it was commissioned and in accordance with the Terms of Engagement for the commission. Unauthorised use of this document in any form whatsoever is prohibited.
Insync Services Pty Ltd Page 3 of 21 Revision A – Preliminary Issue
TABLE OF CONTENTS
1 EXECUTIVE SUMMARY ............................................................................................................................ 5 1.1 BACKGROUND ........................................................................................................................................................................ 5 1.2 WATER CONSUMPTION .............................................................................................................................................................. 5 1.3 DESCRIPTION ......................................................................................................................................................................... 6 2 INTRODUCTION ..................................................................................................................................... 7 2.1 BACKGROUND ........................................................................................................................................................................ 7 2.2 AIMS .................................................................................................................................................................................. 7 2.3 ESD TARGETS ....................................................................................................................................................................... 7 2.4 BRIEFING DOCUMENTS .............................................................................................................................................................. 7 3 BASE DESIGN DATA ............................................................................................................................... 8 3.1 LOCATION & DEVELOPMENT DESCRIPTION ........................................................................................................................................ 8 3.2 POPULATION DATA ................................................................................................................................................................... 9 3.3 FIXTURE USAGE DATA ............................................................................................................................................................... 9 3.4 FIXTURE WATER CONSUMPTION.................................................................................................................................................... 9 3.5 PROCESS WATER CONSUMPTION .................................................................................................................................................. 9 4 WATER SUPPLY OPTIONS ..................................................................................................................... 10 4.1 WATER QUALITY ................................................................................................................................................................... 10 4.2 POTABLE AUTHORITY MAINS WATER ............................................................................................................................................ 10 4.3 NON-POTABLE AUTHORITY MAINS WATER ...................................................................................................................................... 10 4.4 STORMWATER HARVESTING ...................................................................................................................................................... 11 4.4.1 RAINFALL DATA ................................................................................................................................................................. 12 4.4.2 CATCHMENT DATA .............................................................................................................................................................. 12 5 BASE CASE - WATER CONSUMPTION EVALUATION ................................................................................... 14 5.1 RETAIL AMENITY WATER REQUIREMENTS ....................................................................................................................................... 14 5.2 RETAIL TENANCY WATER REQUIREMENTS ...................................................................................................................................... 14 5.3 OUTDOOR WATER REQUIREMENTS .............................................................................................................................................. 15
Insync Services Pty Ltd Page 4 of 21 Revision A – Preliminary Issue
5.4 TOTAL BASE BUILDING RETAIL WATER CONSUMPTION ......................................................................................................................... 16 6 WATER EFFICIENCY - WATER CONSUMPTION EVALUATION ........................................................................ 17 6.1 RETAIL AMENITY WATER REQUIREMENTS ....................................................................................................................................... 17 6.2 RETAIL TENANCY WATER REQUIREMENTS ...................................................................................................................................... 18 6.3 OUTDOOR WATER REQUIREMENTS .............................................................................................................................................. 18 6.4 TOTAL WATER EFFICIENCY WATER CONSUMPTION............................................................................................................................. 19 7 APPENDIX .......................................................................................................................................... 21 7.1 RAINFALL DATA .................................................................................................................................................................... 21 7.2 RAINWATER TANK SIZING CALCULATIONS ....................................................................................................................................... 21 7.3 WATER CONSUMPTION CALCULATIONS .......................................................................................................................................... 21
Insync Services Pty Ltd Page 5 of 21 Revision A – Preliminary Issue
1 EXECUTIVE SUMMARY
1.1 Background The aim of this report is to provide an outline of the water management design initiatives that may be considered for this project with regard to hydraulic and wet fire services, and to identify the preferred option together with a recommendation for its inclusion in the project scope of works.
1.2 Water Consumption Potable water consumption has been estimated throughout the entire development for the base building case to be used as a benchmark against which to compare the efficiency of various potable water consumption reduction strategies that have been proposed. BASE BUILDING ASSESSMENT Water consumption estimates for the Base Building benchmark have been prepared with regard to the following base data;
• Water Closets – 3 Star WELS rated, having an average flush volume of 4 litres • Urinals – 3 Star WELS rated, having an average flush volume of 2 litres • Tapware – 3 Star WELS rated, having a flow rate of 9 litres/minute • Showers – 3 Star WELS rated, having a flow rate of 9 litres/minute
Category Water Consumption
(kL/week) Consumption Reduction
(kL/week) Alternative Water Supply
(kL/week) Total Water Saving
(%) Retail Amenities 2.272 0.000 0.000 0 Retail Tenancies 4.058 0.000 0.000 0 Irrigation 145.138 0.000 0.000 0 Totals 151.468 0.000 0.000 0
WATER EFFICIENCY ASSESSMENT Water consumption estimates for Water Efficiency Option have been prepared with regard to the following base data;
• Water Closets – 4 Star WELS rated, having an average flush volume of 3.5 litres • Urinals – 6 Star WELS rated, having an average flush volume of 1 litres • Tapware – 6 Star WELS rated, having a flow rate of 4.5 litres/minute
Insync Services Pty Ltd Page 6 of 21 Revision A – Preliminary Issue
• Showers – 3 Star WELS rated, having a flow rate of 9 litres/minute • Irrigation – non-potable water supplied for 45% of total consumption
Category Water Consumption
(kL/week) Consumption Reduction
(kL/week) Alternative Water Supply
(kL/week) Total Water Saving
(%) Retail Amenities 1.743 0.530 0.000 23% Retail Tenancies 4.058 0.000 0.000 0% Irrigation 79.826 65.312 65.312 45% Totals 85.627 65.842 58.643 43%
1.3 Description The Water Efficiency option achieves a potable cold water consumption reduction of 43% when compared to the base case benchmark. The improvement in water efficiency is achieved via the installation of more water efficient fixtures and tapware, as well as the substitution of a non-potable water supply for landscape irrigation purposes. The non-potable water supply will be provided as described below;
• a 8kL rainwater storage tank. • a non-potable cold water service booster pump and filtration system. • a non-potable cold water reticulation system throughout the landscape.
Insync Services Pty Ltd Page 7 of 21 Revision A – Preliminary Issue
2 INTRODUCTION 2.1 Background Great Southern Developments Pty Ltd (the Client), have commissioned Insync Services Pty Ltd (the Hydraulic & Wet Fire Consultant) to prepare a Water Management Report for the proposed supermarket development on the corner of Merimbola Street and Bullara, Pambula.
2.2 Aims The aim of this report is to provide an outline of the water management design initiatives that may be considered for this project with regard to hydraulic and wet fire services, and to identify the preferred option together with a recommendation for its inclusion in the project scope of works.
2.3 ESD Targets Environmentally Sustainable Development targets for this development have been adopted as detailed below; Development Minimum Code Requirement Project Target Retail Not Applicable Minimise potable cold water consumption in fixtures, fittings and landscape irrigation.
2.4 Briefing Documents The engineering elements considered in this report have based or taken into consideration the following documents:
• Architectural drawings prepared by Oztal Architects Pty Ltd.
Insync Services Pty Ltd Page 8 of 21 Revision A – Preliminary Issue
3 BASE DESIGN DATA
3.1 Location & Development Description The proposed retail development is located on the corner of Argyle St and Lackey Road, Moss Vale The retail development has a total net lettable floor area of 920m2, generally distributed in accordance with the following allocations;
Category Area Supermarket 920m2 Retail 0m2 Liquor 0m2 TOTALS 920m2
Supermarket 100%
Area Schedule
Supermarket
Insync Services Pty Ltd Page 9 of 21 Revision A – Preliminary Issue
3.2 Population Data Population data for the retail development has been calculated from the following assumptions; Population Retail Staff 1/50m2 Visitors 1/3m2
3.3 Fixture Usage Data Fixture usage data for the retail development has been calculated from the following assumptions; Population Water Closet Urinal Tapware
(20 seconds per use) Showers
(5 minutes per use) Male Staff 1 per day 2 per day 3 per day 0.2 per day Female Staff 3 per day 0 per day 3 per day 0.2 per day Male Visitors 0.2 per day 0.4 per day 0.6 per day 0 per day Female Visitors 0.6 per day 0 per day 0.6 per day 0 per day
3.4 Fixture Water Consumption Fixture water consumption for the retail development has been calculated from the following assumptions; Fixture 3 Star 4 Star 5 Star 6 Star Water Closet (L/flush) 4 3.5 3 2.5 Urinal (L/flush) 3 1.5 1 1 Tapware (L/min) 9 7.5 6 4.5 Showers (L/min) 9 7.5 6 6
3.5 Process Water Consumption Process water consumption for the retail development has been calculated from the following assumptions; Process Flow Rate Retail Tenancy 0.11L/m2/day Food Retail Tenancy 5.23L/m2/day Supermarket 0.23L/m2/day
Insync Services Pty Ltd Page 10 of 21 Revision A – Preliminary Issue
4 Water Supply Options 4.1 Water Quality For the Base Case model, all of the water consumed within the development is potable water drawn from the local Authority potable water supply infrastructure. However, not all of the processes generating water consumption throughout the development require a water supply of potable quality (suitable for drinking). A summary of the water quality requirements for the various building uses detailed within this report is provided below; Building Use Water Quality Toilet Flushing Non-Potable Urinal Flushing Non-Potable Tapware Potable Showers Potable Irrigation Non-Potable Fire Services Potable The range of potential water supply options considered within this report are listed below;
• Potable Authority Mains Water (potable) • Non-Potable Authority Mains Water (non-potable) • Stormwater Harvesting (non-potable)
4.2 Potable Authority Mains Water Potable mains water is traditionally used to supply all of the water requirements within a building. It is of a quality suitable for drinking, and therefore exceeds the quality requirements of many water consuming processes within a building. Regardless of various water saving initiatives that may be employed within a development, a potable mains water connection will always be required to supply the potable water requirements of the building and to provide a back-up water supply to any non-potable water supplies sources.
4.3 Non-Potable Authority Mains Water Non-potable mains water is available in some locations and can be used to supply all of the non-potable water requirements within a building. It is of a quality unsuitable for drinking, and therefore requires careful planning regarding its application and integration into developments in order to avoid cross connections and potential contamination of any potable water supplies. Non-potable mains water cannot be considered for the supermarket development, as no such Authority supply exists.
Insync Services Pty Ltd Page 11 of 21 Revision A – Preliminary Issue
4.4 Stormwater Harvesting Stormwater harvesting refers to the collection of stormwater from the developments internal stormwater drainage system. Stormwater from the stormwater drainage system can be classified as either rainwater, where the flow is from roof areas only or stormwater where the flow is from all areas of the development. For the purposes of this development we refer to a rainwater harvesting system, where the following benefits can be achieved over a stormwater harvesting system;
• Rainwater collected from roof areas is generally less polluted than general stormwater drainage. In general terms, the rainwater harvesting system will be an in-line tank for the collection and storage of rainwater. At times when the rainwater storage tank is full rainwater can pass through the tank and continue to be discharged via gravity into the stormwater drainage system. Rainwater from the storage tank will be pumped for distribution throughout the development in a dedicated non-potable water reticulation system. The collected rainwater is not classified in terms of water quality, but the use of rainwater for cooling tower make up water supply, toilet flushing and spray irrigation systems is recommended as safe practice by all Australian Health Departments. Rainwater falling on roofs is soft, clear and generally low in microbial and chemical contamination. The use of simple and cost effective rainwater collection and treatment systems ensures reliable operation and water quality for non-potable use. The objective of rainwater treatment is to maintain a high quality of water in the rainwater storage tank. A typical rainwater treatment process would include the following;
1. Primary treatment before water enters the storage tank via a first flush system. 2. Media filtration before to water enters the non-potable cold water reticulation system. 3. UV treatment before water enters the non-potable cold water reticulation system.
The use of rainwater harvesting reduces potable water demand within the development, and the amount of stormwater runoff generated by the development. By collecting the rainwater run-off from roof areas, rainwater tanks provide a valuable water source suitable for flushing toilets and landscape irrigation. Rainwater harvesting systems can be considered to have the following advantages;
• Collected rainwater is of high quality allowing for uses including toilet flushing, cooling tower make up and un-controlled irrigation. • Rainwater harvesting can provide a large reduction in potable water consumption. • Rainwater harvesting is well suited to buildings where the available roof footprint is large for collection of the rainwater. • Rainwater harvesting systems have a relatively low capital cost. • Rainwater harvesting systems do not require specialized maintenance.
Insync Services Pty Ltd Page 12 of 21 Revision A – Preliminary Issue
Rainwater harvesting systems can be considered to have the following dis-advantages;
• Rainwater harvesting systems rely upon favorable climatic conditions. • Rainwater harvesting systems are relatively inflexible as they rely on gravity discharge from the roof collection point to the storage
tank. • Rainwater harvesting systems are relatively inefficient in terms of their spatial requirements due to the need to store larger
volumes of rainwater allowing for periods of little or no rainfall. • Rainwater harvesting systems require a potable cold water supply make up facility for periods when the storage has been
exhausted.
4.4.1 Rainfall Data
Rainfall data for the retail development has been sourced from the Bureau of Meteorology, specifically from the Merimbula Airport weather station (069147). A summary of the rainfall data is as follows; January Mean Rainfall 54.4mm February Mean Rainfall 93mm March Mean Rainfall 72.1mm April Mean Rainfall 74mm May Mean Rainfall 49.1mm June Mean Rainfall 69.4mm July Mean Rainfall 50.6mm August Mean Rainfall 49mm September Mean Rainfall 47.2mm October Mean Rainfall 56.7mm November Mean Rainfall 79.8mm December Mean Rainfall 59.4mm Mean Annual Rainfall 756.5mm Mean Rain Days > 1mm 71.1
4.4.2 Catchment Data
Catchment data for the retail development has been sourced from the architectural drawings prepared by Oztal Architects Pty Ltd. A summary of the catchment data is as follows; Total Roof Area 970 m2 Harvested Catchment 450 m2 Harvesting Ratio 46%
Insync Services Pty Ltd Page 13 of 21 Revision A – Preliminary Issue
Run-off Coefficient 0.95 The total available rainfall harvesting supply with these parameters has been estimated at 6.2kL per week.
Insync Services Pty Ltd Page 14 of 21 Revision A – Preliminary Issue
5 Base Case - Water Consumption Evaluation 5.1 Retail Amenity Water Requirements Base case retail amenity water consumption for the Retail development, has been modelled based upon following information;
• 7 days of building operation per week. • 3 Star WELS rated water closets, having an average volume per flush of 4 litres. • 3 Star WELS rated urinals, having an average volume per flush of 2 litres. • 3 Star WELS rated tapware, having a flow rate of 9.0 litres per minute. • 3 Star WELS rated showers, having a flow rate of 9.0 litres per minute.
A summary of the estimated base case retail amenity water consumption for the parameters listed above is as follows; Base Building Assessment Water Closet Urinal Tapware Showers Totals Area 920 920 920 920 920 Male - Staff 6 6 6 6 6 Female - Staff 6 6 6 6 6 Male - Visitor 0 0 0 0 0 Female - Staff 0 0 0 0 0 Fixture Efficiency 3 Star 3 Star 3 Star 3 Star Consumption Per Use (L) 4 2 3 45 Male - Staff - Consumption (L) 23 23 52 52 150 Female - Staff - Consumption (L) 69 0 52 52 173 Male - Visitor - Consumption (L) 0 0 1 0 1 Female - Visitor - Consumption (L) 1 0 1 0 1 Total Consumption (L/day) 93 23 105 104 325 Efficiency (L/m2/day) 0.10 0.03 0.11 0.11 0.35 Days Of operation Per Week 7 7 7 7 7 Total Consumption (kL/week) 0.652 0.163 0.733 0.725 2.272 The total base case retail amenity water consumption with these parameters has been estimated at 2.272kL per week throughout the development.
5.2 Retail Tenancy Water Requirements Retail tenant water consumption for the retail development, has been modelled based upon actual metered consumption data from similar retail centres. Specifically the base model has been developed upon following information;
Insync Services Pty Ltd Page 15 of 21 Revision A – Preliminary Issue
• 7 days of building operation per week. • Non-food tenants having an average water consumption rate of 0.11kL/m2 per annum. • Food tenants having an average water consumption rate of 5.23kL/m2 per annum. • Supermarkets having an average water consumption rate of 0.23kL/m2 per annum. • Majors and Mini Majors having an average water consumption rate of 0.11kL/m2 per annum.
A summary of the estimated retail tenancy water consumption for the parameters listed above is as follows; Base Building Assessment Supermarket Food Specialty Specialty Totals Area 920 0 0 920 Consumption Rate 0.23 5.23 0.11 Total Consumption (L/day) 580 0 0 580 Efficiency (L/m2/day) 0.63 N/A N/A 0.63 Days Of operation Per Week 7 7 7 7 Total Consumption (kL/week) 4.058 0.000 0.000 4.058 The total retail tenant water consumption with these parameters has been estimated at 4.058kL per week throughout the development.
5.3 Outdoor Water Requirements Water consumption within each landscape irrigation system varies depending upon the nature of the irrigation system, species of planting, and the prevailing climate. For the Retail development, the base case outdoor water demand has been developed using following information;
• Irrigation area of approximately 780m2 • Irrigation rate 15mm/m2
A summary of the estimated irrigation water consumption for the parameters listed above is as follows; Base Building Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Totals Weeks 4.4 4.0 4.4 4.3 4.4 4.3 4.4 4.4 4.3 4.4 4.3 4.4 52.0 Applications 3 3 2 2 2 1 1 1 2 2 2 3 Area 780 780 780 780 780 780 780 780 780 780 780 780 Irrigation Rate 15 15 15 15 15 15 15 15 15 15 15 15 Requirement 198 180 132 129 132 65 66 66 129 132 129 198 Rainfall 54.4 93.0 72.1 74.0 49.1 69.4 50.6 49.0 47.2 56.7 79.8 59.4 754.7 Monthly 112.0 67.9 46.7 42.9 64.7 0.0 12.0 13.3 63.8 58.7 38.4 108.1 628.4 Weekly 25.5 17.0 10.6 10.0 14.7 0.0 2.7 3.0 14.8 13.3 8.9 24.6 145.1
Insync Services Pty Ltd Page 16 of 21 Revision A – Preliminary Issue
The average base case outdoor water demand with these parameters has been estimated at 11.125kL per week throughout the development.
5.4 Total Base Building Retail Water Consumption Based on the estimated retail amenity water requirements of 2.272kL per week, the estimated retail tenancy water requirements of 4.058kL per week, and the estimated outdoor water requirements of 145.138kL per week, the total retail water consumption for this development will be 151.468kL per week.
Retail Amenities 1% Retail Tenancies
3%
Outdoor 96%
Base Case - Weekly Water Consumption (kL)
Retail Amenities
Retail Tenancies
Outdoor
Insync Services Pty Ltd Page 17 of 21 Revision A – Preliminary Issue
6 Water Efficiency - Water Consumption Evaluation
6.1 Retail Amenity Water Requirements Water efficiency retail amenity water consumption for the retail development, has been modelled based upon following information;
• 7 days of building operation per week. • 4 Star WELS rated water closets, having an average volume per flush of 3.5 litres. • 6 Star WELS rated urinals, having an average volume per flush of 1 litre. • 6 Star WELS rated tapware, having a flow rate of 4.5 litres per minute. • 3 Star WELS rated showers, having a flow rate of 9.0 litres per minute.
A summary of the estimated water efficiency retail amenity water consumption for the parameters listed above is as follows; Efficiency Assessment Water Closet Urinal Tapware Showers Totals Area 920 920 920 920 0.8 Male - Staff 6 6 6 6 0 Female - Staff 6 6 6 6 0 Male - Visitor 0 0 0 0 0 Female - Staff 0 0 0 0 0 Fixture Efficiency 4 Star 6 Star 6 Star 3 Star Consumption Per Use (L) 3.5 1 1.5 45 Male - Staff - Consumption (L) 20 12 26 52 109 Female - Staff - Consumption (L) 60 0 26 52 138 Male - Visitor - Consumption (L) 0 0 0 0 1 Female - Visitor - Consumption (L) 1 0 0 0 1 Total Consumption (L/day) 81 12 52 104 249 Efficiency (L/m2/day) 0.09 0.01 0.06 0.11 311.22 Days Of operation Per Week 7 7 7 7 7 Weekly Consumption (kL/week) 0.570 0.081 0.367 0.725 1.743 Non-Potable Ratio 0% 0% 0% 0% Non-Potable Contribution (kL/week) 0.000 0.000 0.000 0.000 0.000 Total Consumption (kL/week) 0.570 0.081 0.367 0.725 1.743 The total water efficiency retail amenity water consumption with these parameters has been estimated at 1.743kL per week throughout the development.
Insync Services Pty Ltd Page 18 of 21 Revision A – Preliminary Issue
6.2 Retail Tenancy Water Requirements Water efficiency retail tenant water consumption for the retail development, has been modelled based upon actual metered consumption data from similar retail centres. Specifically the base model has been developed upon following information;
• 7 days of building operation per week. • Non-food tenants having an average water consumption rate of 0.11kL/m2 per annum. • Food tenants having an average water consumption rate of 5.23kL/m2 per annum. • Supermarkets having an average water consumption rate of 0.23kL/m2 per annum. • Majors and Mini Majors having an average water consumption rate of 0.11kL/m2 per annum.
A summary of the estimated retail tenancy water consumption for the parameters listed above is as follows; Efficiency Assessment Supermarket Food Specialty Specialty Totals Area 920 0 0 920 Consumption Rate 0.23 5.23 0.11 Total Consumption (L/day) 580 0 0 580 Efficiency (L/m2/day) 0.63 N/A N/A 0.63 Days Of Operation Per Week 7 7 7 7 Weekly Consumption (kL/week)
4.058 0.000 0.000 4.058
The total water efficiency retail tenant water consumption with these parameters has been estimated at 4.058kL per week throughout the development.
6.3 Outdoor Water Requirements Water consumption within each landscape irrigation system varies depending upon the nature of the irrigation system, species of planting, and the prevailing climate. For the retail development, the water efficiency outdoor water demand has been developed using following information;
• Irrigation area of approximately 780m2 • Irrigation rate 15mm/m2
A summary of the estimated water efficiency irrigation water consumption for the parameters listed above is as follows;
Insync Services Pty Ltd Page 19 of 21 Revision A – Preliminary Issue
Water Efficiency Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Totals Weeks 4.4 4.0 4.4 4.3 4.4 4.3 4.4 4.4 4.3 4.4 4.3 4.4 52.0 Applications 3 3 2 2 2 1 1 1 2 2 2 3 Area 780 780 780 780 780 780 780 780 780 780 780 780 Irrigation Rate 15 15 15 15 15 15 15 15 15 15 15 15 Requirement 198 180 132 129 132 65 66 66 129 132 129 198 Rainfall 54.4 93.0 72.1 74.0 49.1 69.4 50.6 49.0 47.2 56.7 79.8 59.4 754.7 Monthly 112.00
8 67.860 46.722 42.900 64.662 0.000 12.012 13.260 63.804 58.734 38.376 108.10
8 628.446
Weekly Consumption (kL/week)
25.456 16.965 10.619 9.977 14.696 0.000 2.730 3.014 14.838 13.349 8.925 24.570 145.138
Non-Potable Ratio 45% 45% 45% 45% 45% 45% 45% 45% 45% 45% 45% 45% Non-Potable Contribution (kL/week)
11.455 7.634 4.778 4.490 6.613 0.000 1.229 1.356 6.677 6.007 4.016 11.057 65.312
Total Consumption (kL/week)
14.001 9.331 5.840 5.487 8.083 0.000 1.502 1.658 8.161 7.342 4.909 13.514 79.826
The average water efficiency outdoor water demand with these parameters has been estimated at 79.826kL per week throughout the development.
6.4 Total Water Efficiency Water Consumption Based on the estimated retail amenity water requirements of 1.743kL per week, the estimated retail tenancy water requirements of 4.058kL per week, and the estimated outdoor water requirements of 79.862kL per week, the total retail water consumption for this development will be 85.627kL per week.
Insync Services Pty Ltd Page 20 of 21 Revision A – Preliminary Issue
Retail Amenities 2%
Retail Tenancies 4%
Outdoor 94%
Water Efficiency - Weekly Water Consumption (kL)
Retail Amenities
Retail Tenancies
Outdoor
Insync Services Pty Ltd Page 21 of 21 Revision A – Preliminary Issue
7 Appendix 7.1 Rainfall Data
7.2 Rainwater Tank Sizing Calculations 7.3 Water Consumption Calculations
View: Main statistics All available Period:
red = highest value blue = lowest value
Text size: Normal Large
Statistics Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Annual Years
Temperature
Mean maximum temperature (°C) 24.7 24.6 23.5 21.5 19.1 16.8 16.5 17.4 19.5 20.5 21.5 23.1 20.7 1819982015
Mean minimum temperature (°C) 15.1 15.2 13.3 10.9 7.6 5.6 4.1 4.8 6.8 8.8 11.8 13.5 9.8 1819982015
Rainfall
Mean rainfall (mm) 54.4 93.0 72.1 74.0 49.1 69.4 50.6 49.0 47.2 56.7 79.8 59.4 756.5 1719982015
Decile 5 (median) rainfall (mm) 44.6 73.9 44.9 64.4 29.8 46.5 41.0 33.6 26.0 62.8 74.4 43.5 749.3 1719982015
Mean number of days of rain ≥ 1 mm 6.5 6.1 5.5 6.2 3.9 5.9 4.2 5.1 6.2 7.2 7.8 6.5 71.1 1719982015
Other daily elements
Mean daily sunshine (hours)
Mean number of clear days
Mean number of cloudy days
9 am conditions
Mean 9am temperature (°C) 20.4 19.9 17.9 17.1 13.6 10.7 10.1 11.7 14.8 16.5 17.6 19.3 15.8 1319982010
Mean 9am relative humidity (%) 70 73 76 70 74 78 76 69 63 62 68 65 70 1319982010
Mean 9am wind speed (km/h) 10.0 8.1 6.7 7.8 7.6 7.8 7.8 8.6 9.7 11.2 11.1 11.6 9.0 1219982010
3 pm conditions
Mean 3pm temperature (°C) 22.8 22.9 22.0 19.9 17.4 15.4 14.9 15.7 17.2 17.9 19.4 21.2 18.9 1319982010
Mean 3pm relative humidity (%) 65 64 62 61 60 60 58 55 58 61 65 63 61 1319982010
Mean 3pm wind speed (km/h) 20.1 19.1 17.6 15.1 13.6 12.4 13.6 16.1 18.3 18.9 19.4 19.6 17.0 1219982010
Monthly statistics are only included if there are more than 10 years of data. The number of years (provided in the 2nd last column of the table) may differ between elements if the observing program at the site changed. More detailed data for individual sites can be obtained by contacting the Bureau.
Related Links
This page URL: http://www.bom.gov.au/climate/averages/tables/cw_069147.shtml
About climate averages: http://www.bom.gov.au/climate/cdo/about/about-stats.shtml
Bureau of Meteorology website: http://www.bom.gov.au
Page created: Thu 17 Sep 2015 00:52:06 AM EST
Climate statistics for Australian locations
Monthly climate statistics
All years of record
30 year period not available
Product IDCJCM0028 Prepared at Thu 17 Sep 2015 00:52:06 AM EST
© Copyright Commonwealth of Australia , Bureau of Meteorology (ABN 92 637 533 532) | Disclaimer | Privacy | Accessibility
This page was created at on
View larger map
Elevation - metres
Site information
Site name: MERIMBULA AIRPORT AWS Site number: 069147Latitude: 36.91 °S Longitude: 149.90 °EElevation: 2 mCommenced: 1998 Status: Open Latest available data: 16 Sep 2015
Additional information
Additional site information
Nearest alternative sites
1. 069093 MERIMBULA AIRPORT COMPARISON (0.4km)2. 069002 BEGA (NEWTOWN ROAD) (24.8km)3. 069139 BEGA AWS (27.0km)
Page 1 of 1Climate statistics for Australian locations
17/09/2015http://www.bom.gov.au/climate/averages/tables/cw_069147.shtml
20150018 Water Efficiency Assessment.xlsx DESIGN DATA 18/09/2015
INSYNC SERVICES PTY LTD PAGE 1 OF 5
Project: Retail DevelopmentAddress: Corner of Merimbola and Bullara RdClient: Great Southern Developments Pty LtdEngineer: Max HoughRevision: A
AREA SCHEDULE
Category AreaSupermarket 920Retail 0Mini-Major 0Liquor 0Total Area 920
POPULATION SCHEDULE (BUILDING AREA PER OCCUPANT)
Occupants Retail LiquorStaff 80 4Visitors 1333.3 66.6
FIXTURE USAGE SCHEDULE (NUMBER OF USES PER DAY PER OCCUPANT)
Occupants Water Closet Urinal Tapware ShowersMale Staff 1 2 3 0.2Female Staff 3 0 3 0.2Male Visitors 0.2 0.4 0.6 0Female Visitors 0.6 0 0.6 0
FIXTURE WATER CONSUMPTION (LITRES PER USE)
Occupants Water Closet Urinal Tapware (20 seconds) Showers (5 minutes)3 Star 4 2 3 454 Star 3.5 1.5 2.5 37.55 Star 3 1 2 306 Star 2.5 1 1.5 30
20150018 Water Efficiency Assessment.xlsx CONSUMPTION SUMMARY 18/09/2015
INSYNC SERVICES PTY LTD PAGE 2 OF 5
Project: Retail DevelopmentAddress: Corner of Merimbola and Bullara RdClient: Great Southern Developments Pty LtdEngineer: Max HoughRevision: A
WATER CONSUMPTION SUMMARY
Category Base Building (kL/week) Water Efficiency (kL/week) Consumption Saving (kL/week) Non-Potable Saving (kL/week) Reduction (%)Retail Amenities 2.272 1.743 0.530 0.000 23%Retail Tenancies 4.058 4.058 0.000 0.000 0%Irrigation 145.138 79.826 65.312 0.000 45%Totals 151.468 85.627 65.842 0.000 43%
20150018 Water Efficiency Assessment.xlsx RETAIL AMENITIES 18/09/2015
INSYNC SERVICES PTY LTD PAGE 3 OF 5
Project: Retail DevelopmentAddress: Corner of Merimbola and Bullara RdClient: Great Southern Developments Pty LtdEngineer: Max HoughRevision: A
Base Building Assessment Water Closet Urinal Tapware Showers TotalsArea 920 920 920 920 920Male - Staff 6 6 6 6 6Female - Staff 6 6 6 6 6Male - Visitor 0 0 0 0 0Female - Staff 0 0 0 0 0Fixture Efficiency 3 Star 3 Star 3 Star 3 StarConsumption Per Use (L) 4 2 3 45Male - Staff - Consumption (L) 23 23 52 52 150Female - Staff - Consumption (L) 69 0 52 52 173Male - Visitor - Consumption (L) 0 0 1 0 1Female - Visitor - Consumption (L) 1 0 1 0 1Total Consumption (L/day) 93 23 105 104 325Efficiency (L/m2/day) 0.10 0.03 0.11 0.11 0.35Days Of operation Per Week 7 7 7 7 7Total Consumption (kL/week) 0.652 0.163 0.733 0.725 2.272
Efficiency Assesssment Water Closet Urinal Tapware Showers TotalsArea 920 920 920 920 0.8Male - Staff 6 6 6 6 0Female - Staff 6 6 6 6 0Male - Visitor 0 0 0 0 0Female - Staff 0 0 0 0 0Fixture Efficiency 4 Star 6 Star 6 Star 3 StarConsumption Per Use (L) 3.5 1 1.5 45Male - Staff - Consumption (L) 20 12 26 52 109Female - Staff - Consumption (L) 60 0 26 52 138Male - Visitor - Consumption (L) 0 0 0 0 1Female - Visitor - Consumption (L) 1 0 0 0 1Total Consumption (L/day) 81 12 52 104 249Efficiency (L/m2/day) 0.09 0.01 0.06 0.11 311.22Days Of operation Per Week 7 7 7 7 7Weekly Consumption (kL/week) 0.570 0.081 0.367 0.725 1.743Non-Potable Ratio 0% 0% 0% 0%Non-Potable Contribution (kL/week) 0.000 0.000 0.000 0.000 0.000Total Consumption (kL/week) 0.570 0.081 0.367 0.725 1.743
20150018 Water Efficiency Assessment.xlsx RETAIL TENANCIES 18/09/2015
INSYNC SERVICES PTY LTD PAGE 4 OF 5
Project: Retail DevelopmentAddress: Corner of Merimbola and Bullara RdClient: Great Southern Developments Pty LtdEngineer: Max HoughRevision: A
Base Building Assessment Supermarket Food Specialty Specialty TotalsArea 920 0 0 920Consumption Rate 0.23 5.23 0.11Total Consumption (L/day) 580 0 0 580Efficiency (L/m2/day) 0.63 #DIV/0! #DIV/0! 0.63Days Of operation Per Week 7 7 7 7Total Consumption (kL/week) 4.058 0.000 0.000 4.058
Efficiency Assessment Supermarket Food Specialty Specialty TotalsArea 920 0 0 920Consumption Rate 0.23 5.23 0.11Total Consumption (L/day) 580 0 0 580Efficiency (L/m2/day) 0.63 #DIV/0! #DIV/0! 0.63Days Of Operation Per Week 7 7 7 7Weekly Consumption (kL/week) 4.058 0.000 0.000 4.058
20150018 Water Efficiency Assessment.xlsx IRRIGATION 18/09/2015
INSYNC SERVICES PTY LTD PAGE 5 OF 5
Project: Retail DevelopmentAddress: Corner of Merimbola and Bullara RdClient: Great Southern Developments Pty LtdEngineer: Max HoughRevision: A
Base Building January February Macrh April May June July August September October November December TotalsWeeks 4.4 4.0 4.4 4.3 4.4 4.3 4.4 4.4 4.3 4.4 4.3 4.4 52.0Applications 3 3 2 2 2 1 1 1 2 2 2 3Area 780 780 780 780 780 780 780 780 780 780 780 780Irrigation Rate 15 15 15 15 15 15 15 15 15 15 15 15Requirement 198 180 132 129 132 65 66 66 129 132 129 198Rainfall 54.4 93.0 72.1 74.0 49.1 69.4 50.6 49.0 47.2 56.7 79.8 59.4 754.7Monthly 112.0 67.9 46.7 42.9 64.7 0.0 12.0 13.3 63.8 58.7 38.4 108.1 628.4Weekly 25.5 17.0 10.6 10.0 14.7 0.0 2.7 3.0 14.8 13.3 8.9 24.6 145.1
Water Efficiency January February Macrh April May June July August September October November December TotalsWeeks 4.4 4.0 4.4 4.3 4.4 4.3 4.4 4.4 4.3 4.4 4.3 4.4 52.0Applications 3 3 2 2 2 1 1 1 2 2 2 3Area 780 780 780 780 780 780 780 780 780 780 780 780Irrigation Rate 15 15 15 15 15 15 15 15 15 15 15 15Requirement 198 180 132 129 132 65 66 66 129 132 129 198Rainfall 54.4 93.0 72.1 74.0 49.1 69.4 50.6 49.0 47.2 56.7 79.8 59.4 754.7Monthly 112.008 67.860 46.722 42.900 64.662 0.000 12.012 13.260 63.804 58.734 38.376 108.108 628.446Weekly Consumption (kL/week) 25.456 16.965 10.619 9.977 14.696 0.000 2.730 3.014 14.838 13.349 8.925 24.570 145.138Non-Potable Ratio 45% 45% 45% 45% 45% 45% 45% 45% 45% 45% 45% 45%Non-Potable Contribution (kL/week) 11.455 7.634 4.778 4.490 6.613 0.000 1.229 1.356 6.677 6.007 4.016 11.057 65.312Total Consumption (kL/week) 14.001 9.331 5.840 5.487 8.083 0.000 1.502 1.658 8.161 7.342 4.909 13.514 79.826
20150018 Rainwater Tank Sizing.xlsx Summary Data 18/09/2015
Insync Services Pty Ltd Page 1 Of 8
Project: Supermarket Development, PambulaProject Number: 20150018Date: 17/09/2015Engineer: Max Hough
Actual Water Consumption Indoor Water (kL) Outdoor Water (kL) Heat Rjection Water (kL) Total Water (kL)January 0.000 112.008 0.000 112.008February 0.000 67.860 0.000 67.860March 0.000 46.722 0.000 46.722April 0.000 42.900 0.000 42.900May 0.000 64.662 0.000 64.662June 0.000 0.000 0.000 0.000July 0.000 12.012 0.000 12.012August 0.000 13.260 0.000 13.260September 0.000 63.804 0.000 63.804October 0.000 58.734 0.000 58.734November 0.000 38.376 0.000 38.376December 0.000 108.108 0.000 108.108Total Water Consumption 0.000 628.446 0.000 628.446
Rainfall Data Average Rainfall (mm) Rain Days>1mm Average Storm (mm) WeeksJanuary 54.4 6.5 8.4 4.4February 93.0 6.1 15.2 4March 72.1 5.5 13.1 4.4April 74.0 6.2 11.9 4.3May 49.1 3.9 12.6 4.4June 69.8 5.9 11.8 4.3July 50.6 4.2 12.0 4.4August 49.0 5.1 9.6 4.4September 47.2 6.2 7.6 4.3October 56.7 7.2 7.9 4.4November 79.8 7.8 10.2 4.3December 59.4 6.5 9.1 4.4Annual 756.5 70.0 15.2 52
Building DataTotal Site Area (m2) 2555Total Roof Area (m2) 970Harvestable Catchment (%) 46%Harvestable Catchment (m2) 450Run-Off Coefficient 0.95
Tank Sizes Minimum Option 1 Option 2 MaximumTank Size (L) 6.518 16.457 26.396 39.758Weekly Collection (kL) 6.208 6.208 6.208 6.208Weekly Contribution (kL) 5.426 5.618 5.809 6.066Weekly Overflow (kL) 0.781 0.590 0.399 0.142Annual Potable Cold Water Top Up (kL) 346.270 336.330 326.391 313.030Annual Rainwater Contirbution 44.9% 46.5% 48.1% 50.2%Rainwater Available Per Day (kL) 0.104 0.108 0.112 0.117
Project: Supermarket Development, PambulaProject Number: 20150018Date: 17/09/2015Engineer: Max Hough
Location Weekly Potable Consumption (kL) Weekly Non-Potable Consumption (kL)Retail Amenities 1.743 0.000Retail Tenancies 4.058 0.000Totals 5.801 0.000
Month Weeks Per Month Monthly Potable Consumption (kL) Monthly Non-Potable Consumption (kL) Monthly Totals (kL)January 4.4 25.524 0.000 25.524February 4 23.203 0.000 23.203March 4.4 25.524 0.000 25.524April 4.3 24.944 0.000 24.944May 4.4 25.524 0.000 25.524June 4.3 24.944 0.000 24.944July 4.4 25.524 0.000 25.524August 4.4 25.524 0.000 25.524September 4.3 24.944 0.000 24.944October 4.4 25.524 0.000 25.524November 4.3 24.944 0.000 24.944December 4.4 25.524 0.000 25.524Totals 52 301.6 0.0 301.643
0.000
5.000
10.000
15.000
20.000
25.000
30.000
January February March April May June July August September October November December
Indoor Water Consumption Analysis
Monthly Potable Consumption (kL)
Monthly Non-Potable Consumption (kL)
Project: Supermarket Development, PambulaProject Number: 20150018Date: 17/09/2015Engineer: Max Hough
Month Weeks Per Month Applications Per Week Irrigation Rate Requirement Rainfall Irrigation Area Monthly Consumption (kL) Weekly Consumption (kL)January 4.4 3.0 15 198 54.4 780 112.008 25.456February 4 3.0 15 180 93.0 780 67.860 16.965March 4.4 2.0 15 132 72.1 780 46.722 10.619April 4.3 2.0 15 129 74.0 780 42.900 9.977May 4.4 2.0 15 132 49.1 780 64.662 14.696June 4.3 1.0 15 65 69.8 780 0.000 0.000July 4.4 1.0 15 66 50.6 780 12.012 2.730August 4.4 1.0 15 66 49.0 780 13.260 3.014September 4.3 2.0 15 129 47.2 780 63.804 14.838October 4.4 2.0 15 132 56.7 780 58.734 13.349November 4.3 2.0 15 129 79.8 780 38.376 8.925December 4.4 3.0 15 198 59.4 780 108.108 24.570Totals 52 628.446 145.138
0.000
20.000
40.000
60.000
80.000
100.000
120.000
January February March April May June July August September October November December
Outdoor Water Consumption Analysis
Monthly Consumption (kL)
Project: Supermarket Development, PambulaProject Number: 20150018Date: 17/09/2015Engineer: Max Hough
Monthly Water Balance Rainfall Collection (kL) Indoor Consumption (kL) Outdoor Consumption (kL) Heat Rejection Consumption (kL) Total Consumption (kL)January 23.256 0.0 112.0 0.000 112.008February 39.7575 0.0 67.9 0.000 67.860March 30.82275 0.0 46.7 0.000 46.722April 31.635 0.0 42.9 0.000 42.900May 20.99025 0.0 64.7 0.000 64.662June 29.8395 0.0 0.0 0.000 0.000July 21.6315 0.0 12.0 0.000 12.012August 20.9475 0.0 13.3 0.000 13.260September 20.178 0.0 63.8 0.000 63.804October 24.23925 0.0 58.7 0.000 58.734November 34.1145 0.0 38.4 0.000 38.376December 25.3935 0.0 108.1 0.000 108.108Totals 322.80525 0 628 0.000 628.446
0.0
20.0
40.0
60.0
80.0
100.0
120.0
January February March April May June July August September October November December
Non-Potable Water Consumption Analysis
Heat Rejection Consumption (kL)
Outdoor Consumption (kL)
Indoor Consumption (kL)
Project: Supermarket Development, PambulaProject Number: 20150018Date: 17/09/2015Engineer: Max Hough
Minimum Tank Size (m3) 6.518
Month Monthly Collection (kL) Monthly Consumption (kL) Monthly Balance (kL) Tank Storage Level (kL) Tank Overflow (kL) Potable Top Up (kL)January 23.256 112.0 -88.8 0.000 0.000 88.752February 39.7575 67.9 -28.1 0.000 0.000 28.1025March 30.82275 46.7 -15.9 0.000 0.000 15.89925April 31.635 42.9 -11.3 0.000 0.000 11.265May 20.99025 64.7 -43.7 0.000 0.000 43.67175June 29.8395 0.0 29.8 6.518 23.322 0July 21.6315 12.0 9.6 6.518 9.620 0August 20.9475 13.3 7.7 6.518 7.688 0September 20.178 63.8 -43.6 0.000 0.000 37.10837705October 24.23925 58.7 -34.5 0.000 0.000 34.49475November 34.1145 38.4 -4.3 0.000 0.000 4.2615December 25.3935 108.1 -82.7 0.000 0.000 82.7145Totals 322.80525 628.446 40.629 346.269627
Rainwater Contribution 44.9%
0%10%20%30%40%50%60%70%80%90%
100%
January February March April May June July August September October November December
Non-Potable Water Supply Analysis
Potable Top Up (kL)
Tank Storage Level (kL)
Monthly Collection (kL)
Project: Supermarket Development, PambulaProject Number: 20150018Date: 17/09/2015Engineer: Max Hough
Option 1 Tank Size (m3) 16.457
Month Monthly Collection (kL) Monthly Consumption (kL) Monthly Balance (kL) Tank Storage Level (kL) Tank Overflow (kL) Potable Top Up (kL)January 23.256 112.0 -88.8 0.000 0.000 88.752February 39.7575 67.9 -28.1 0.000 0.000 28.1025March 30.82275 46.7 -15.9 0.000 0.000 15.89925April 31.635 42.9 -11.3 0.000 0.000 11.265May 20.99025 64.7 -43.7 0.000 0.000 43.67175June 29.8395 0.0 29.8 16.457 13.383 0July 21.6315 12.0 9.6 16.457 9.620 0August 20.9475 13.3 7.7 16.457 7.688 0September 20.178 63.8 -43.6 0.000 0.000 27.16900205October 24.23925 58.7 -34.5 0.000 0.000 34.49475November 34.1145 38.4 -4.3 0.000 0.000 4.2615December 25.3935 108.1 -82.7 0.000 0.000 82.7145Totals 322.80525 628.446 30.690 336.330252
Rainwater Contribution 46.5%
0%10%20%30%40%50%60%70%80%90%
100%
January February March April May June July August September October November December
Non-Potable Water Supply Analysis
Potable Top Up (kL)
Tank Storage Level (kL)
Monthly Collection (kL)
Project: Supermarket Development, PambulaProject Number: 20150018Date: 17/09/2015Engineer: Max Hough
Option 2 Tank Size (m3) 26.396
Month Monthly Collection (kL) Monthly Consumption (kL) Monthly Balance (kL) Tank Storage Level (kL) Tank Overflow (kL) Potable Top Up (kL)January 23.256 112.0 -88.8 0.000 0.000 88.752February 39.7575 67.9 -28.1 0.000 0.000 28.1025March 30.82275 46.7 -15.9 0.000 0.000 15.89925April 31.635 42.9 -11.3 0.000 0.000 11.265May 20.99025 64.7 -43.7 0.000 0.000 43.67175June 29.8395 0.0 29.8 26.396 3.443 0July 21.6315 12.0 9.6 26.396 9.620 0August 20.9475 13.3 7.7 26.396 7.688 0September 20.178 63.8 -43.6 0.000 0.000 17.22962705October 24.23925 58.7 -34.5 0.000 0.000 34.49475November 34.1145 38.4 -4.3 0.000 0.000 4.2615December 25.3935 108.1 -82.7 0.000 0.000 82.7145Totals 322.80525 628.446 20.750 326.390877
Rainwater Contribution 48.1%
0%10%20%30%40%50%60%70%80%90%
100%
January February March April May June July August September October November December
Non-Potable Water Supply Analysis
Potable Top Up (kL)
Tank Storage Level (kL)
Monthly Collection (kL)
Project: Supermarket Development, PambulaProject Number: 20150018Date: 17/09/2015Engineer: Max Hough
Maximum Tank Size (m3) 39.758
Month Monthly Collection (kL) Monthly Consumption (kL) Monthly Balance (kL) Tank Storage Level (kL) Tank Overflow (kL) Potable Top Up (kL)January 23.256 112.0 -88.8 0.000 0.000 88.752February 39.7575 67.9 -28.1 0.000 0.000 28.1025March 30.82275 46.7 -15.9 0.000 0.000 15.89925April 31.635 42.9 -11.3 0.000 0.000 11.265May 20.99025 64.7 -43.7 0.000 0.000 43.67175June 29.8395 0.0 29.8 29.840 0.000 0July 21.6315 12.0 9.6 39.459 0.000 0August 20.9475 13.3 7.7 39.758 7.389 0September 20.178 63.8 -43.6 0.000 0.000 3.8685October 24.23925 58.7 -34.5 0.000 0.000 34.49475November 34.1145 38.4 -4.3 0.000 0.000 4.2615December 25.3935 108.1 -82.7 0.000 0.000 82.7145Totals 322.80525 628.446 7.389 313.02975
Rainwater Contribution 50.2%
0%10%20%30%40%50%60%70%80%90%
100%
January February March April May June July August September October November December
Non-Potable Water Supply Analysis
Potable Top Up (kL)
Tank Storage Level (kL)
Monthly Collection (kL)
FIRST FLOOR DICKSON SQUARE DICKSON PH: (02) 6257 3488GPO BOX 2170 CANBERRA CITY ACT 2601 FAX: (02) 6257 3385
LEVEL 2 621 PACIFIC HIGHWAY PH: (02) 9906 1922St LEONARDS NSW 2065 FAX: (02) 9439 0255A R C H I T E C T S
O Z T A L
DRAWING INDEX:DWG No: DESCRIPTION: SCALE:
DWG NO:DATE:PROJECT NO:ISSUED FOR:
AC AIR-CONDITIONING UNITAD/H ADAPTABLE HOUSINGBED BEDROOMbrm BROOM CUPBOARDCSD CAVITY SLIDING DOORCL CENTRE LINECTS CENTRESCL CEILING LEVELcupb CUPBOARDD DOORdp DOWN PIPEMB ELECTRICAL METRE BOXENS ENSUITEeql EQUALFFL FINISHED FLOOR LEVELFHR FIRE HOSE REALFH FIRE HYDRANTFL FLOOR LEVELF FRIDGEGFA GROSS FLOOR AREAGL GROUND LINEht HOT PLATELDRY LAUNDRY
lin LINEN CUPBOARDNGL NATURAL GROUND LINEP PANRTYPWR POWDER ROOMPOS PRIVATE OPEN SPACERWT RAIN WATER TANKRFL REDUCED FLOOR LEVELSD SLIDING DOORS STOREst STOVES.U. SURVEILLANCE UNITV VISITOR CARPARKWIR WALK IN ROBEWMO WALL MOUNTED OVENrobe WARDROBEWM WASHING MACHINEWC WATER CLOSETW WINDOWFHSD FULL HIEGHT SLIDING DOORSH SHEVLES
KEY:
Great Southern Developments
Proposed Supermarket Lot 11 DP 835239 Pambula NSW
03.09.15A000
Development Application15868
A000 Cover SheetA001 Site AnalysisA002 Sub-Division Design ConceptA003 Site PlanA100 Floor PlanA101 Roof PlanA200 ElevationsA201 Colour / Material SelectionsA202 StreetscapeA300 SectionsA400 Fire Hydrant Pump Room
2
D P 8 3 5 2 3 9
D P 5 6 8 2 01
D P
5
7
3
0
2
7
11
M E
R I M
B O
L A
S T
R E
E T
4
1.51.5
2
2.5
3
3.5
4
EDGE
BIT U
MEN
SEWER
SEWER
SEWER SEWER
SEWER
SEWER
MANHOLE
MANHOLE
MANHOLE
MANHOLE
MANHOLE
MANHOLE
SEWERMANHOLE
800∅
R.C.
P IPE
S
EDGE BITUMEN
SEWERPUMPINGSTATION
APPROXIMATE BOUNDARY
BOUN
DARY
A PP R
O XI MA T
E
8 00∅
R.C.
P IPE
SEWERMANHOLE
B U L L A R A S T R E E T
2.49
2.43
2.20
2.56 2.2
4
1.962.16
2.52
1.91
1.74
1.40
1.771.58
1.32
1.32
2.64
2.52
2.53
1.97
2.67
2.93
2.49
3.07
3.37
4.11
3.55
3.02
2.34
2.96
2.73
2.74
3.35
3.42
3.20
3.37
1.89
0 5 10 20
Bar Scale (Metres)
50
Overall Site
LEGEND
CLIENT:DRAWING TITLE:
DESIGNED /DRAWN:
DATE:
SCALE:
JOB No:
DRAWING STATUS:
REV:
FIRST FLOOR DICKSONDICKSON SQUAREGPO BOX 2170 CANBERRACITY ACT 2601PH: (02) 6257 3488FAX: (02) 6257 3385LEVEL 2 621 PACIFICHIGHWAYSt LEONARDS NSW2065PH: (02) 9906 1922FAX: (02) 9439 0255
REPRODUCTION OF THIS WHOLE OR PART OF THE DOCUMENT CONSTITUTES AN INFRINGEMENT OFCOPYRIGHT THE INFORMATION, IDEAS AND CONCEPT CONTAINED IN THIS DOCUMENT ARE CONFIDENTIALTHE RECIPIENT(s) OF THIS DOCUMENT IS/ARE PROHIBITED FROM DISCLOSING SUCH INFORMATION, IDEASAND CONCEPTS TO ANY PERSON WITHOUT THE PRIOR WRITTEN CONCENT OF THE COPYRIGHT HOLDER
C COPYRIGHT
Rev DATE:DESCRIPTION: BY:
DWG No:
PROJECT NAME:PROJECT ADDRESS:
NOMINATED ARCHITECT:NICK PELLENSW REGISTRATION NO:5628
A R C H I T E C T S
O Z T A L 1 : 500
G:\15868 Great Southern Devl Pambula Supermarket, Cnr Merimbula nad Bullara St Pambula\D1.1 Development Application\15868_DA.rvt
Great SouthernDevelopments
Site Analysis
NP,DK/DK03.09.15
A001DevelopmentApplication
15868
Proposed Supermarket Lot 11 DP 835239 PambulaNSW
NORTH
Location PlanNTS
- Proposed Site
PRECINCT 2 - MIXED RESIDENTIAL / COMMERCIALZONE: B2 LOCAL CENTRE
AREA ANALYSISEXISTING SITE AREA: 10013.78m²PROPOSED LOT A AREA: 7019.24m²PROPOSED LOT B - SUPERMARKET AREA: 2994.54m²SUPERMARKET GFA: 919.97m²
CARPARKING ANALYSIS
REQUIRED1 PARKING SPACE PER 25M2 GROSS FLOOR AREA GROUNDFLOOR FOR COMMERCIAL PREMISES - INCLUDING BUSINESS,OFFICE AND RETAIL PREMISES.REQUIRED - 37 CAR SPACES
OF THE CAR PARKING SPACES PROVIDED 1 DISABLED PERSONSSPACE IS TO BE PROVIDED PER DEVELOPMENT, PLUS 1 PER 25SPACES DESIGNED IN ACCORDANCE WITH THEAUSTRALIAN STANDARD 2890.6
PROVIDED37 CAR SPACES INCLUDING 3 DISABLED CAR SPACES.BICYCLE PARKING - N/A
LANDSCAPE AREAPROPOSED LANDSCAPE: 116.43m²
Proposed Supermarket
New Lot created forsupermarket
New lot boundary line
New lot boundary line
@A1
Proposed Lot A
Vacant Land
Proposed Lot B
Vacant Land
Pambula Wetlands
Commercial
2
D P 8 3 5 2 3 9
D P 5 6 8 2 01
D P
5
7
3
0
2
7
11
M E
R I M
B O
L A
S T
R E
E T
1.51.5
2
2.5
3
3.5
4
EDGE
BIT U
MEN
SEWER
SEWER
SEWER SEWER
SEWER
SEWER
MANHOLE
MANHOLE
MANHOLE
MANHOLE
MANHOLE
MANHOLE
SEWERMANHOLE
800∅
R.C.
P IPE
S
EDGE BITUMEN
SEWERPUMPINGSTATION
APPROXIMATE BOUNDARY
BOUN
DARY
A PP R
O XI MA T
E
8 00∅
R.C.
P IPE
SEWERMANHOLE
B U L L A R A S T R E E T
2.49
2.43
2.20
2.56 2.2
4
1.962.16
2.52
1.91
1.74
1.40
1.771.58
1.32
1.32
2.64
2.52
2.53
1.97
2.67
2.93
2.49
3.07
3.37
4.11
3.55
3.02
2.34
2.96
2.73
2.74
3.35
3.42
3.20
3.37
1.89
2
D P 8 3 5 2 3 9
D P 5 6 8 2 01
D P
5
7
3
0
2
7
11
M E
R I M
B O
L A
S T
R E
E T
1.51.5
2
2.5
3
3.5
4
EDGE
BIT U
MEN
SEWER
SEWER
SEWER SEWER
SEWER
SEWER
MANHOLE
MANHOLE
MANHOLE
MANHOLE
MANHOLE
MANHOLE
SEWERMANHOLE
800∅
R.C.
P IPE
S
EDGE BITUMEN
SEWERPUMPINGSTATION
APPROXIMATE BOUNDARY
BOUN
DARY
A PP R
O XI MA T
E
8 00∅
R.C.
P IPE
SEWERMANHOLE
B U L L A R A S T R E E T
2.49
2.43
2.20
2.56 2.2
4
1.962.16
2.52
1.91
1.74
1.40
1.771.58
1.32
1.32
2.64
2.52
2.53
1.97
2.67
2.93
2.49
3.07
3.37
4.11
3.55
3.02
2.34
2.96
2.73
2.74
3.35
3.423.2
0
3.37
1.89
0 5 10 20
Bar Scale (Metres)
50 0 5 10 20
Bar Scale (Metres)
50
Potential Built Form
Potential Parking
LEGEND
CLIENT:DRAWING TITLE:
DESIGNED /DRAWN:
DATE:
SCALE:
JOB No:
DRAWING STATUS:
REV:
FIRST FLOOR DICKSONDICKSON SQUAREGPO BOX 2170 CANBERRACITY ACT 2601PH: (02) 6257 3488FAX: (02) 6257 3385LEVEL 2 621 PACIFICHIGHWAYSt LEONARDS NSW2065PH: (02) 9906 1922FAX: (02) 9439 0255
REPRODUCTION OF THIS WHOLE OR PART OF THE DOCUMENT CONSTITUTES AN INFRINGEMENT OFCOPYRIGHT THE INFORMATION, IDEAS AND CONCEPT CONTAINED IN THIS DOCUMENT ARE CONFIDENTIALTHE RECIPIENT(s) OF THIS DOCUMENT IS/ARE PROHIBITED FROM DISCLOSING SUCH INFORMATION, IDEASAND CONCEPTS TO ANY PERSON WITHOUT THE PRIOR WRITTEN CONCENT OF THE COPYRIGHT HOLDER
C COPYRIGHT
Rev DATE:DESCRIPTION: BY:
DWG No:
PROJECT NAME:PROJECT ADDRESS:
NOMINATED ARCHITECT:NICK PELLENSW REGISTRATION NO:5628
A R C H I T E C T S
O Z T A LAs indicated
G:\15868 Great Southern Devl Pambula Supermarket, Cnr Merimbula nad Bullara St Pambula\D1.1 Development Application\15868_DA.rvt
Great SouthernDevelopments
Sub-Division DesignConcept
NP,DK/DK03.09.15
A002DevelopmentApplication
15868
Proposed Supermarket Lot 11 DP 835239 PambulaNSW
NORTH
SCALE1:500@A1
Sub-Division Design Concept
ProposedSupermarket
SITE AREA: 4636.06m²
SITE AREA:2383.18m²
SITE AREA:2994.54m²
Sub-Division Design Concept 2
SITE AREA: 2487.82m²
SITE AREA:4531.41m²
ProposedSupermarketSITE AREA:
2994.54m²
SCALE1:500@A1
D P 8 3 5 2 3 9
D P
5
7
3
0
7
11
CNR MERIMLOT 11 DP
M E
R I M
B O
L A
S T
R E
E T
CADDEY SEARL ANDJARMAN PROJECT:
CONTOUR AOFCONSULTING SURVEYORS AND
VALUERS
4
1.5
1.5
2
2.5
DRAWN:DESIGN:
EGAALLEYAMBULA
MBSHEETDESCRIPTION:
EDGE
SEWER
SEWER
SEWER SEWER
SEWER
SEWER
MANHOLE
MANHOLE
MANHOLE
MANHOLE
MANHOLE
MANHOLE
SEWERMANHOLE
800 ∅
R .C.
PIPE
S
EDGE BITUMEN
SEWERPUMPINGSTATION
APPR
OXIMAT
E
800 ∅
R .C.
PIPEB U L L A R A S T R E E T
2.49
2.43
2.20
2.56 2.2
4
1.962.16
2.52
1.91
1.74
1.40
1.771.58
1.32
1.32
2.64
2.52
2.53
1.97
2.192.67
2.96
1.89
1000
37 ParkingSpaces
Trol
ley
Bay
RL. 3840
ProposedSupermarket
Area: 919.97m²
22810
2500
998
8998
1705
5
1.
2.
3.
1:20
SharedSpace
4.
5.
6.
7.
8.
9.
10. 11. 12. 13. 14. 15. 17.16. 18. 19. 20. 21. 22. 23. 24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
waste zone
Service &BOH
0 5 10 20
Bar Scale (Metres)
retaining wall as percivil documentation
Bicycle Parking -min. 5 spaces
Delivery truck sweep path &ramp as per Traffic and CivilConsultants documentation.
grat
ed su
mp
RL. 3
.550
sump to hydraulicengineers detail
Oxide coloured concretewith a broomed finish
Refer to Civil Engineersdocumentation for carparkand road RL's & surfacetreatment
54.8
91
RL. 3
.800
retaining wall as percivil documentation
retaining wall as percivil documentation
retaining wall as percivil documentation
55.0
00
54.500
54.500
2.0m
2.0m
2.5m
3.0m
Proposed Boundary
Prop
osed
Bou
ndar
y
SharedSpace
proposedlandscape designas per LandscapeConsultantsdocumentation.
Underground OSD - referto engineers detail
Sumps and the like tocivil engineers
documentation
RL3.55(BK)
*
RL3.55(BK)*
RL3.50*
*
*
RL3.55(BK)RL3.70(TK)
RL3.55(BK)RL3.70(TK) RL3.625(TK)
RL3.475(BK)
*
Refer to Civil Engineersdocumentation for drivewaycrossover and RL's
Refer to Civil Engineersdocumentation for drivewaycrossover and RL's
RL3.70
RL3.70
Fire Hydrant PumpRoom as perHydraulic Consultantsdocumentation.
200
1243
8
Path with 1:20max gradient
Steps in landscapeas per Landscape
Consultantsdocumentation.
LEGEND
CLIENT:DRAWING TITLE:
DESIGNED /DRAWN:
DATE:
SCALE:
JOB No:
DRAWING STATUS:
REV:
FIRST FLOOR DICKSONDICKSON SQUAREGPO BOX 2170 CANBERRACITY ACT 2601PH: (02) 6257 3488FAX: (02) 6257 3385LEVEL 2 621 PACIFICHIGHWAYSt LEONARDS NSW2065PH: (02) 9906 1922FAX: (02) 9439 0255
REPRODUCTION OF THIS WHOLE OR PART OF THE DOCUMENT CONSTITUTES AN INFRINGEMENT OFCOPYRIGHT THE INFORMATION, IDEAS AND CONCEPT CONTAINED IN THIS DOCUMENT ARE CONFIDENTIALTHE RECIPIENT(s) OF THIS DOCUMENT IS/ARE PROHIBITED FROM DISCLOSING SUCH INFORMATION, IDEASAND CONCEPTS TO ANY PERSON WITHOUT THE PRIOR WRITTEN CONCENT OF THE COPYRIGHT HOLDER
C COPYRIGHT
Rev DATE:DESCRIPTION: BY:
DWG No:
PROJECT NAME:PROJECT ADDRESS:
NOMINATED ARCHITECT:NICK PELLENSW REGISTRATION NO:5628
A R C H I T E C T S
O Z T A L 1 : 200
G:\15868 Great Southern Devl Pambula Supermarket, Cnr Merimbula nad Bullara St Pambula\D1.1 Development Application\15868_DA.rvt
Great SouthernDevelopments
Site Plan
NP,DK/DK03.09.15
A003DevelopmentApplication
15868
Proposed Supermarket Lot 11 DP 835239 PambulaNSW
Site Plan.
NORTH
PRECINCT 2 - MIXED RESIDENTIAL / COMMERCIALZONE: B2 LOCAL CENTRE
AREA ANALYSISEXISTING SITE AREA: 10013.78m²PROPOSED LOT A AREA: 7019.24m²PROPOSED LOT B - SUPERMARKET AREA: 2994.54m²SUPERMARKET GFA: 919.97m²
CARPARKING ANALYSIS
REQUIRED1 PARKING SPACE PER 25M2 GROSS FLOOR AREA GROUNDFLOOR FOR COMMERCIAL PREMISES - INCLUDING BUSINESS,OFFICE AND RETAIL PREMISES.REQUIRED - 37 CAR SPACES
OF THE CAR PARKING SPACES PROVIDED 1 DISABLED PERSONSSPACE IS TO BE PROVIDED PER DEVELOPMENT, PLUS 1 PER 25SPACES DESIGNED IN ACCORDANCE WITH THEAUSTRALIAN STANDARD 2890.6
PROVIDED37 CAR SPACES INCLUDING 3 DISABLED CAR SPACES.BICYCLE PARKING - N/A
LANDSCAPE AREAPROPOSED LANDSCAPE: 116.43m²
THIS DRAWING SHALL BE READ IN CONJUNCTION WITH CONSULTANTS DOCUMENTATION.
ALL MATERIALS AND FINISHES SHALL BE APPROVED BY THE OWNERS.VARIATIONS TO PLAN AND SPECIFICATION SHALL NOT BE MADE WITHOUT THE CONSENT OF THEOWNERS.ALL DIMENSIONS SHALL BE VERIFIED ON SITE.ALL WORK SHALL BE CARRIED OUT IN ACCORDANCE WITH THE BCA.DO NOT SCALE OFF DRAWINGS.FIRE PRECAUTIONS DURING CONSTRUCTION SHALL BE IN ACCORDANCE WITH SECTION ECLAUSEE1.6 OF THE BCA.PROVIDE PORTABLE FIRE EXTINGUISHES IN ACCORDANCE WITH SECTION E CLAUSE E1.6 OF THEBCA.FIRE EXTINGUISHERS SHALL COMPLY WITH AS 2444.ALL MATERIALS AND ASSEMBLIES SHALL COMPLY WITH C1.10 OF THE BCA.ALL WET AREA FLOORS SHALL BE GRADED AND DRAINED TO FLOOR WASTES TO PLUMBINGCODES AND THE BCA.PROVIDE IMPERVIOUS WALL TO FLOOR JOINT TO THE PERIMETER OF ALL WET AREASWATERPROOFING SHALL COMPLY WITH C1. F1.7 OF THE BCA.CONFIRM LOCATION OF ALL SERVICES PRIOR TO CONSTRUCTION
EGRESS.REQUIRED PATHS OF EXIT BE IN ACCORDANCE WITH PART D1.6 OF THE BCA THEUN-OBSTURCTED HEIGHT MUST BE NO LESS THEN 2.0M EXCEPT AT DOORWAYS WHERE THEHEIGHT MAY BE REDUCED TO 1.98M. THE UNOBSTRUCTED WIDTH OF EACH EXIT OR PATH OFTRAVEL TO AN EXIT, EXCEPT AT DOORWAYS MUST BE 1.0M MINIMUM.
REQUIRED EXIT SIGNS SHALL BE IN ACCORDANCE WITH PART E4 OF THE BCAPROVIDE EMERGENCY ILLUMINATED EXIT SIGNS TO REQUIRED EXITS TO AS 2293.1
EXITS MUST NOT BE BLOCKED AT THE POINT OF DISCHARGE, AND WHERE NECESSARY SUITABLEBARRIERS MUST BE PROVIDED TO PREVENT VEHICLES FROM BLOCKING EXITS
OPERATION OF LATCHES MUST BE IN ACCORDANCE WITH PART D2.1 OF THE BCAA REQUIRED EXIT DOOR MUST BE READILY OPENABLE WITHOUT A KEY FROM THE SIDE THATFACES THE PERSON SEEKING EGRESS BY A SINGLE HAND DOWNWARD ACTION OR PUSHINGACTION ON A SINGLE DEVICE WHICH IS LOCATED BETWEEN 900MM AND 1200MM FROM THEFLOOR
LIGHTINGINSTALL EMERGENCY LIGHTING IN ACCORDANCE WITH AS 2293.1 AND PART E4.2 OF THE BCAINCLUDING DIRECTIONAL SIGNAGE (NOT SHOWN ON PLANS) TO BCA REQUIREMENTS
PROVIDE ARTIFICIAL LIGHTING TO AS 1680
ACESSIBILITY
ACCESS FOR PEOPLE WITH DISABILITIES SHALL COMPLY WITH PART D3 OF THE BCA AND AS1428.1DISABLED PERSON TOILETS SHALL COMPLY WITH AS 1428.1DISABLED PERSON WC SHALL HAVE ADEQUATE FACILITIES FOR THE DISPOSAL OF SANITARYTOWELS AND A SHELF MUST ALSO BE PROVIDED.DISABLED PERSON CAR PARKING SHALL BE IN ACCORDANCE WITH D3.5
TACTILE INDICATORS.
PROVIDE TACTILE INDICATORS IN ACCORDANCE WITH D3.8 OF THE BCA AND AS 1428.1 AT THEENTRANCE TO THE CARPARK AREA AND AT THE APPROACH TO THE STAIRWAY
THE BUILDING ACCESS SHALL HAVE A SLIP RESISTANT SURFACEPROVIDE BRAILLE AND TACTILE SIGNS TO IDENTIFY SANITARY FACILITIES
SARKING
INSTALL ROOF SARKING TO AS/NZ 4200 PARTS 1 AND 2.
IMPORTANT NOTE
THIS PLAN IS PREPARED FOR THE CLIENT FROM A COMBINATION OF FIELD SURVEYS ANDEXISTING RECORDS PROVIDED BY THE CLIENTSERVICES AND INFORMATION SHOWN HEREON HAVE BEEN LOCATED WHERE POSSIBLE BYFIELDIF NOT ABLE TO BE LOCATED, SERVICES HAVE BEEN PLOTTED FROM RECORDS OFRELEVANT AUTHORITIES WHERE AVAILABLE AND HAVE BEEN NOTED ACCORDINGLY ON THISPLAN
PRIOR TO ANY DEMOLITION, EXCAVATION OR CONSTRUCTION ON THE SITE, RELEVANTAUTHORITY SHOULD BE CONTACTED FOR THE POSSIBLE LOCATION OF FURTHERUNDERGROUNDSERVICES AND DETAILED LOCATION OF ALL SERVICES.
@A1
Northern Elevation.
A200
2
Eas
ther
n E
leva
tion.
A20
0
1
Wes
tern
Ele
vatio
n.
A20
0
4
Southern Elevation.
A200
3
SupermarketArea: 919.97m²
Back of House &Storage Areas
Entry
Entry
8000
2830
059
0
3689
0
690 18200 2800 7500 1500 300
30690 300
300
200
7500
1231
029
8047
1088
90
3689
0
8890 5070 3340 8730 4160 800
30990
Staff
DisabledWC
Lockers
RL. 3840
Load
ing
Doc
k
Aut
omat
ic D
oors
Automatic Doors
rolle
r doo
r
920920
920
920
920
roller door
1
A300
2
A300
3
A300
4
A300
Awning over
Awning over
Awningover
dp
dp
dp
dp
dpdp
dp
dp
dp
Pull down ladderaccess to plant room to
comply to AS 1657
W3032W3032W3032
W3010W3010W3010W3010
W30
10W
3010
W30
10W
3010
W30
28W
3028
W30
28W
3028
Ambulantwc
Plant Room
Lower levelawning
Pull down ladder
200 7100 200
200
7910
90
Step ladder accessto the roof
box gutter
Potential location forroof top plant
Plant room accesscladding of door to match
wall cladding
Ground Floor
LEGEND
CLIENT:DRAWING TITLE:
DESIGNED /DRAWN:
DATE:
SCALE:
JOB No:
DRAWING STATUS:
REV:
FIRST FLOOR DICKSONDICKSON SQUAREGPO BOX 2170 CANBERRACITY ACT 2601PH: (02) 6257 3488FAX: (02) 6257 3385LEVEL 2 621 PACIFICHIGHWAYSt LEONARDS NSW2065PH: (02) 9906 1922FAX: (02) 9439 0255
REPRODUCTION OF THIS WHOLE OR PART OF THE DOCUMENT CONSTITUTES AN INFRINGEMENT OFCOPYRIGHT THE INFORMATION, IDEAS AND CONCEPT CONTAINED IN THIS DOCUMENT ARE CONFIDENTIALTHE RECIPIENT(s) OF THIS DOCUMENT IS/ARE PROHIBITED FROM DISCLOSING SUCH INFORMATION, IDEASAND CONCEPTS TO ANY PERSON WITHOUT THE PRIOR WRITTEN CONCENT OF THE COPYRIGHT HOLDER
C COPYRIGHT
Rev DATE:DESCRIPTION: BY:
DWG No:
PROJECT NAME:PROJECT ADDRESS:
NOMINATED ARCHITECT:NICK PELLENSW REGISTRATION NO:5628
A R C H I T E C T S
O Z T A L 1 : 100
G:\15868 Great Southern Devl Pambula Supermarket, Cnr Merimbula nad Bullara St Pambula\D1.1 Development Application\15868_DA.rvt
Great SouthernDevelopments
Floor Plan
NP,DK/DK03.09.15
A100DevelopmentApplication
15868
Proposed Supermarket Lot 11 DP 835239 PambulaNSW
NORTH
PRECINCT 2 - MIXED RESIDENTIAL / COMMERCIALZONE: B2 LOCAL CENTRE
AREA ANALYSISEXISTING SITE AREA: 10013.78m²PROPOSED LOT A AREA: 7019.24m²PROPOSED LOT B - SUPERMARKET AREA: 2994.54m²SUPERMARKET GFA: 919.97m²
CARPARKING ANALYSIS
REQUIRED1 PARKING SPACE PER 25M2 GROSS FLOOR AREA GROUNDFLOOR FOR COMMERCIAL PREMISES - INCLUDING BUSINESS,OFFICE AND RETAIL PREMISES.REQUIRED - 37 CAR SPACES
OF THE CAR PARKING SPACES PROVIDED 1 DISABLED PERSONSSPACE IS TO BE PROVIDED PER DEVELOPMENT, PLUS 1 PER 25SPACES DESIGNED IN ACCORDANCE WITH THEAUSTRALIAN STANDARD 2890.6
PROVIDED37 CAR SPACES INCLUDING 3 DISABLED CAR SPACES.BICYCLE PARKING - N/A
LANDSCAPE AREAPROPOSED LANDSCAPE: 116.43m²
@A1
Plant Room
Northern Elevation.
A200
2
Eas
ther
n E
leva
tion.
A20
0
1
Wes
tern
Ele
vatio
n.
A20
0
4
Southern Elevation.
A200
3
dp withspreader
dp withspreader
dp
dp
dp
dpdp withspreader
dp withspreader
dp withspreader
dp withspreader
Box
Gut
ter
Box Gutter under
2° Fall 2° Fall10
° Fal
l
10° Fall
10° F
all
1° F
all
1° FallBox Gutter
Box Gutter
Lower levelsteel pergola
Half Round Gutter
rain waterhead
rain waterhead
rain waterhead
Half Round Gutter
Parapet
Para
pet
Para
pet
dp
Parapet
Parapet
Para
pet
Lower levelawning
Lower levelawning
dp
1
A300
2
A300
3
A300
4
A300
Step ladder accessto the roof
Box Gutter to lowerlevel awning
Box Gutter to lowerlevel awning
Potential location forroof top plant
LEGEND
CLIENT:DRAWING TITLE:
DESIGNED /DRAWN:
DATE:
SCALE:
JOB No:
DRAWING STATUS:
REV:
FIRST FLOOR DICKSONDICKSON SQUAREGPO BOX 2170 CANBERRACITY ACT 2601PH: (02) 6257 3488FAX: (02) 6257 3385LEVEL 2 621 PACIFICHIGHWAYSt LEONARDS NSW2065PH: (02) 9906 1922FAX: (02) 9439 0255
REPRODUCTION OF THIS WHOLE OR PART OF THE DOCUMENT CONSTITUTES AN INFRINGEMENT OFCOPYRIGHT THE INFORMATION, IDEAS AND CONCEPT CONTAINED IN THIS DOCUMENT ARE CONFIDENTIALTHE RECIPIENT(s) OF THIS DOCUMENT IS/ARE PROHIBITED FROM DISCLOSING SUCH INFORMATION, IDEASAND CONCEPTS TO ANY PERSON WITHOUT THE PRIOR WRITTEN CONCENT OF THE COPYRIGHT HOLDER
C COPYRIGHT
Rev DATE:DESCRIPTION: BY:
DWG No:
PROJECT NAME:PROJECT ADDRESS:
NOMINATED ARCHITECT:NICK PELLENSW REGISTRATION NO:5628
A R C H I T E C T S
O Z T A L 1 : 100
G:\15868 Great Southern Devl Pambula Supermarket, Cnr Merimbula nad Bullara St Pambula\D1.1 Development Application\15868_DA.rvt
Great SouthernDevelopments
Roof Plan
NP,DK/DK03.09.15
A101DevelopmentApplication
15868
Proposed Supermarket Lot 11 DP 835239 PambulaNSW
Roof Plan
@A1
NGL
Boun
dar
y Lin
e
4000
FCL
RL 003.840FFL
6300
7691
Precast Panels corrugatedprofile with an applied finish
as selected
metal awning roof asselected.
metal deck roof as selected.roof pitch 2deg
powdercoated steelas selected
metal deck roof asselected. roof pitch 10deg
3000
7320
10°
10°
1783
retaining wall toengineers spec. at
boundary
build up natural groundto suit flood level
requirements as per civilconsultants requirements
Precast Panels with anapplied finish as
selected
909
Boun
dar
y Lin
e
NGL
FCL
4000
1350
7691
7320
RL 003.840FFL
Precast Panels corrugated profilewith an applied finish as selected
Applied finish asselected
metal awning roof asselected.
metal deck roof asselected. roof pitch 10deg
powdercoated steelas selected
3000 40
00
Precast Panels with anapplied finish as selected
10°
plant room ventilation
854
lightweight metalcladding or similar as
selected
metal roller door asselected
metal awning roof asselected.
signage wall fixed individuallettering "Pambula Supermarket"
NGL
Boun
dar
y Lin
e
4000
FCL
RL 003.840FFL
5350
2300
3691
7320
4200
commercial glazing systemas selected
metal deck roof asselected. roof pitch 10deg
400
6111
1783
300040
00
powdercoated steelas selected
10°
Applied finish asselected 16
40
NGL
Boun
dar
y Lin
e
FCL
RL 003.840FFL
7691
7320
5800
4000
4000
2300
400
6111
4000
3000
Precast Panels corrugatedprofile with an applied
finish as selected
metal roller door asselected
metal awning roof asselected.
signage wall fixed individuallettering "Pambula Supermarket"
commercial glazing systemas selected
powdercoated steelas selected
520010°
10°
plant room accesscladding of door to
match wall cladding
lightweight metalcladding or similar as
selected
Applied finish as selected
1243 commercial
glazing - clearProprietarysunshading system
LEGEND
CLIENT:DRAWING TITLE:
DESIGNED /DRAWN:
DATE:
SCALE:
JOB No:
DRAWING STATUS:
REV:
FIRST FLOOR DICKSONDICKSON SQUAREGPO BOX 2170 CANBERRACITY ACT 2601PH: (02) 6257 3488FAX: (02) 6257 3385LEVEL 2 621 PACIFICHIGHWAYSt LEONARDS NSW2065PH: (02) 9906 1922FAX: (02) 9439 0255
REPRODUCTION OF THIS WHOLE OR PART OF THE DOCUMENT CONSTITUTES AN INFRINGEMENT OFCOPYRIGHT THE INFORMATION, IDEAS AND CONCEPT CONTAINED IN THIS DOCUMENT ARE CONFIDENTIALTHE RECIPIENT(s) OF THIS DOCUMENT IS/ARE PROHIBITED FROM DISCLOSING SUCH INFORMATION, IDEASAND CONCEPTS TO ANY PERSON WITHOUT THE PRIOR WRITTEN CONCENT OF THE COPYRIGHT HOLDER
C COPYRIGHT
Rev DATE:DESCRIPTION: BY:
DWG No:
PROJECT NAME:PROJECT ADDRESS:
NOMINATED ARCHITECT:NICK PELLENSW REGISTRATION NO:5628
A R C H I T E C T S
O Z T A L 1 : 100
G:\15868 Great Southern Devl Pambula Supermarket, Cnr Merimbula nad Bullara St Pambula\D1.1 Development Application\15868_DA.rvt
Great SouthernDevelopments
Elevations
NP,DK/DK03.09.15
A200DevelopmentApplication
15868
Proposed Supermarket Lot 11 DP 835239 PambulaNSW
Eastern Elevation.
Northern Elevation.
Southern Elevation.
Western Elevation.
@A1
LEGEND
CLIENT:DRAWING TITLE:
DESIGNED /DRAWN:
DATE:
SCALE:
JOB No:
DRAWING STATUS:
REV:
FIRST FLOOR DICKSONDICKSON SQUAREGPO BOX 2170 CANBERRACITY ACT 2601PH: (02) 6257 3488FAX: (02) 6257 3385LEVEL 2 621 PACIFICHIGHWAYSt LEONARDS NSW2065PH: (02) 9906 1922FAX: (02) 9439 0255
REPRODUCTION OF THIS WHOLE OR PART OF THE DOCUMENT CONSTITUTES AN INFRINGEMENT OFCOPYRIGHT THE INFORMATION, IDEAS AND CONCEPT CONTAINED IN THIS DOCUMENT ARE CONFIDENTIALTHE RECIPIENT(s) OF THIS DOCUMENT IS/ARE PROHIBITED FROM DISCLOSING SUCH INFORMATION, IDEASAND CONCEPTS TO ANY PERSON WITHOUT THE PRIOR WRITTEN CONCENT OF THE COPYRIGHT HOLDER
C COPYRIGHT
Rev DATE:DESCRIPTION: BY:
DWG No:
PROJECT NAME:PROJECT ADDRESS:
NOMINATED ARCHITECT:NICK PELLENSW REGISTRATION NO:5628
A R C H I T E C T S
O Z T A L
G:\15868 Great Southern Devl Pambula Supermarket, Cnr Merimbula nad Bullara St Pambula\D1.1 Development Application\15868_DA.rvt
Great SouthernDevelopments
Colour / MaterialSelections
NP,DK/DK03.09.15
A201DevelopmentApplication
15868
Proposed Supermarket Lot 11 DP 835239 PambulaNSW
Colour / Material Selections
5. Awnings / Pergola to be Galvanised Steel 6. Roof - Similar to ColorbondShale Grey
7. Commercial Galzing System -Anodized Aluminium
1.6.7.
1. Wall Type 1 - Corrugated ProfileMetal Wall Cladding - Colour Similarto Colorbond "Wallaby"
2. Wall Type 2 - Applied Finish - Similarto Dulux "Grand Piano"
3. Wall Type 3 - Applied Finish -Similar to Colorbond "Wallaby"
4. Wall Type 4 - Precast Panel:with an applied finish similar toDulux - "Paving Stone"
2.2. 3. 3.4. 5. 5.5.4.
LEGEND
CLIENT:DRAWING TITLE:
DESIGNED /DRAWN:
DATE:
SCALE:
JOB No:
DRAWING STATUS:
REV:
FIRST FLOOR DICKSONDICKSON SQUAREGPO BOX 2170 CANBERRACITY ACT 2601PH: (02) 6257 3488FAX: (02) 6257 3385LEVEL 2 621 PACIFICHIGHWAYSt LEONARDS NSW2065PH: (02) 9906 1922FAX: (02) 9439 0255
REPRODUCTION OF THIS WHOLE OR PART OF THE DOCUMENT CONSTITUTES AN INFRINGEMENT OFCOPYRIGHT THE INFORMATION, IDEAS AND CONCEPT CONTAINED IN THIS DOCUMENT ARE CONFIDENTIALTHE RECIPIENT(s) OF THIS DOCUMENT IS/ARE PROHIBITED FROM DISCLOSING SUCH INFORMATION, IDEASAND CONCEPTS TO ANY PERSON WITHOUT THE PRIOR WRITTEN CONCENT OF THE COPYRIGHT HOLDER
C COPYRIGHT
Rev DATE:DESCRIPTION: BY:
DWG No:
PROJECT NAME:PROJECT ADDRESS:
NOMINATED ARCHITECT:NICK PELLENSW REGISTRATION NO:5628
A R C H I T E C T S
O Z T A L
G:\15868 Great Southern Devl Pambula Supermarket, Cnr Merimbula nad Bullara St Pambula\D1.1 Development Application\15868_DA.rvt
Great SouthernDevelopments
Streetscape
NP,DK/DK03.09.15
A202DevelopmentApplication
15868
Proposed Supermarket Lot 11 DP 835239 PambulaNSW
Bullara Streetscape - Artists Impression
metal deck roof as selected.roof pitch 2 deg
Supermarket
Roof trusses tomanufacturers spec
Concrete footings & slabto engineers details andAS. 2870.1
commercial glazingsystem as selected
NGL
Boun
dar
y Lin
e
FCL
RL 003.840FFL
4000
Box gutter toengineers detail
10°2°
metal deck roof asselected. roof pitch10 deg
5310
metal deck roof as selected.roof pitch 2 deg
Supermarket
Roof trusses tomanufacturers spec
Concrete footings & slabto engineers details andAS. 2870.1
commercial glazing systemas selected
NGL
Boun
dar
y Lin
e
FCL
RL 003.840FFL
Box gutter toengineers detail
4000
3000
2°
metal deck roof asselected. roof pitch 10 deg
Supermarket
Roof trusses tomanufacturers spec
Concrete footings & slabto engineers details andAS. 2870.1
commercial glazing systemas selected
NGL
Boun
dar
y Lin
e
FCL
RL 003.840FFL
4000
10°
7691
5350
metal deck roof asselected. roof pitch 2 deg
Plant
Build up ground level to suit flood levelrequirements as per civil consultants specs
metal deck roof as selected.roof pitch 2 deg
Supermarket
Roof trusses tomanufacturers spec
Concrete footings & slabto engineers details andAS. 2870.1
NGL
Boun
dar
y Lin
e
FCL
RL 003.840FFL
4000
5350
4000
10°
metal deck roof as selected.roof pitch 10 deg
LEGEND
CLIENT:DRAWING TITLE:
DESIGNED /DRAWN:
DATE:
SCALE:
JOB No:
DRAWING STATUS:
REV:
FIRST FLOOR DICKSONDICKSON SQUAREGPO BOX 2170 CANBERRACITY ACT 2601PH: (02) 6257 3488FAX: (02) 6257 3385LEVEL 2 621 PACIFICHIGHWAYSt LEONARDS NSW2065PH: (02) 9906 1922FAX: (02) 9439 0255
REPRODUCTION OF THIS WHOLE OR PART OF THE DOCUMENT CONSTITUTES AN INFRINGEMENT OFCOPYRIGHT THE INFORMATION, IDEAS AND CONCEPT CONTAINED IN THIS DOCUMENT ARE CONFIDENTIALTHE RECIPIENT(s) OF THIS DOCUMENT IS/ARE PROHIBITED FROM DISCLOSING SUCH INFORMATION, IDEASAND CONCEPTS TO ANY PERSON WITHOUT THE PRIOR WRITTEN CONCENT OF THE COPYRIGHT HOLDER
C COPYRIGHT
Rev DATE:DESCRIPTION: BY:
DWG No:
PROJECT NAME:PROJECT ADDRESS:
NOMINATED ARCHITECT:NICK PELLENSW REGISTRATION NO:5628
A R C H I T E C T S
O Z T A L 1 : 100
G:\15868 Great Southern Devl Pambula Supermarket, Cnr Merimbula nad Bullara St Pambula\D1.1 Development Application\15868_DA.rvt
Great SouthernDevelopments
Sections
NP,DK/DK03.09.15
A300DevelopmentApplication
15868
Proposed Supermarket Lot 11 DP 835239 PambulaNSW
Section 1
Section 2
Section 3
Section 4
@A1
2100
4257
300
lightweight metalcladding or similar as
selected
signage wall fixed individuallettering "Pambula Supermarket"
RL 003.140FFL
metal deck roofas selected.roof pitch 2 deg
Applied finish asselected
2100
lightweight metalcladding or similar as
selected
RL 003.140FFL
metal deck roofas selected.roof pitch 2 deg
2100
lightweight metalcladding or similar as
selected
RL 003.140
metal deck roofas selected.roof pitch 2 deg
FFL
Applied finish asselected
2100
lightweight metalcladding or similar
as selected
RL 003.140FFL
metal deck roofas selected.roof pitch 2 deg
Ele
vatio
n 1
- a
A40
0
1
Elevation 2 - a
A400
2
Ele
vatio
n 3
- a
A40
0
3
Elevation 4 - a
A400
4
Fire Hydrant PumpRoom as perHydraulic Consultantsdocumentation.
200
8200
2620
5820
2620
LEGEND
CLIENT:DRAWING TITLE:
DESIGNED /DRAWN:
DATE:
SCALE:
JOB No:
DRAWING STATUS:
REV:
FIRST FLOOR DICKSONDICKSON SQUAREGPO BOX 2170 CANBERRACITY ACT 2601PH: (02) 6257 3488FAX: (02) 6257 3385LEVEL 2 621 PACIFICHIGHWAYSt LEONARDS NSW2065PH: (02) 9906 1922FAX: (02) 9439 0255
REPRODUCTION OF THIS WHOLE OR PART OF THE DOCUMENT CONSTITUTES AN INFRINGEMENT OFCOPYRIGHT THE INFORMATION, IDEAS AND CONCEPT CONTAINED IN THIS DOCUMENT ARE CONFIDENTIALTHE RECIPIENT(s) OF THIS DOCUMENT IS/ARE PROHIBITED FROM DISCLOSING SUCH INFORMATION, IDEASAND CONCEPTS TO ANY PERSON WITHOUT THE PRIOR WRITTEN CONCENT OF THE COPYRIGHT HOLDER
C COPYRIGHT
Rev DATE:DESCRIPTION: BY:
DWG No:
PROJECT NAME:PROJECT ADDRESS:
NOMINATED ARCHITECT:NICK PELLENSW REGISTRATION NO:5628
A R C H I T E C T S
O Z T A L 1 : 50
G:\15868 Great Southern Devl Pambula Supermarket, Cnr Merimbula nad Bullara St Pambula\D1.1 Development Application\15868_DA.rvt
Great SouthernDevelopments
Fire Hydrant Pump Room
NP,DK/DK03.09.15
A400DevelopmentApplication
15868
Proposed Supermarket Lot 11 DP 835239 PambulaNSW
Elevation 1 - a
Elevation 2 - a
Elevation 3 - a
Elevation 4 - a
Fire Hydrant Pump Room
@A1
SURVEY
INFORMATIONSURVEYED BY
CADDEY SEARL AND JARMANDATUM: A.H.D
ORIGIN OF LEVELS: SSM54794 RL4.396 (A.H.D)01 ISSUED FOR DA JL IA 23/07/2015
Date
Scale
Title
Project
Drawing number
Drawn
Checked
Revision
Designed
Approved
This drawing and design remains the property of Henry & Hymas and may not becopied in whole or in part without the prior written approval of Henry & Hymas.
Architect
Client
REVISION AMENDMENT DATEREVISION AMENDMENT DATE
Surveyor
DESIGNEDDRAWNDESIGNEDDRAWN
Level 5,
79 Victoria Avenue
Chatswood NSW 2067
+61 2 9417 8400
+61 2 9417 8337
www.henryandhymas.com.auGlobal-Mark.com.au® 0115114_DA_C000
PROPOSED SUPERMARKET
LOT 11 DP835239 PAMBULA NSW
COVER SHEET, DRAWING SCHEDULE,
NOTES AND LOCALITY SKETCH
A. ALKATEB I. AHMED
I. AHMED A. FRANCIS
JULY 2015
N.T.S
GREAT SOUTHERN DEVELOPMENTS
OZTAL ARCHITECTS
PROPOSED SUPERMARKET
CNR MERIMBOLA & BULLARA ST. PAMBULA NSW
CIVIL ENGINEERING WORKS
DRAWING SCHEDULE15114_DA_C000 COVER SHEET, DRAWING SCHEDULE & LOCALITY SKETCH
15114_DA_C100 GENERAL ARRANGEMENT PLAN
15114_DA_C200 STORMWATER MISCELLANEOUS DETAILS AND PIT LID SCHEDULE
15114_DA_C201 OSD DETAILS
15114_DA_C500 PAVEMENT PLAN & KERB DETAILS
15114_DA_SE01 SEDIMENT & EROSION CONTROL PLAN
15114_DA_SE02 SEDIMENT & EROSION CONTROL TYPICAL DETAILS
GENERAL NOTES:
1. ALL WORK TO BE CARRIED OUT IN ACCORDANCE WITH BEGA VALLEY SHIRE
COUNCIL SPECIFICATION. CONTRACTOR TO OBTAIN AND RETAIN A COPY
ON SITE DURING THE COURSE OF THE WORKS.
2. ALL NEW WORKS ARE TO MAKE A SMOOTH JUNCTION WITH EXISTING
CONDITIONS, AND MARRY IN A 'WORKMANLIKE' MANNER.
3. THE CONTRACTOR IS TO VERIFY THE LOCATION OF ALL SERVICES WITH
EACH RELEVANT AUTHORITY. ANY DAMAGE TO SERVICES SHALL BE
RECTIFIED BY THE CONTRACTOR OR THE RELEVANT AUTHORITY AT THE
CONTRACTOR'S EXPENSE. SERVICES SHOWN ON THESE PLANS ARE ONLY
THOSE EVIDENT AT THE TIME OF SURVEY OR AS DETERMINED FROM
SERVICE DIAGRAMS. HENRY AND HYMAS CONSULTING PTY. LTD. CANNOT
GUARANTEE THE INFORMATION SHOWN NOR ACCEPT ANY RESPONSIBILITY
FOR INACCURACIES OR INCOMPLETE DATA.
4. SERVICES & ACCESSES TO THE EXISTING PROPERTIES ARE TO BE
MAINTAINED IN WORKING ORDER AT ALL TIMES DURING CONSTRUCTION.
5. ADJUST EXISTING SERVICE COVERS TO SUIT NEW FINISHED LEVELS TO
RELEVANT AUTHORITY REQUIREMENTS WHERE NECESSARY.
6. REINSTATE AND STABILISE ALL DISTURBED LANDSCAPED AREAS.
7. MINIMUM GRADE OF SUBSOIL SHALL BE 0.5% (1:200) FALL TO OUTLETS.
8. ALL TEMPORARY SEDIMENT AND EROSION CONTROL DEVICES ARE TO BE
CONSTRUCTED, PLACED AND MAINTAINED IN ACCORDANCE WITH THE
TECHNICAL SPECIFICATIONS, EROSION AND SEDIMENTATION CONTROL
PLAN AND BEGA VALLEY SHIRE COUNCIL REQUIR EMENTS WHERE
APPLICABLE.
9. CONTRACTOR TO CHECK AND CONFIRM SITE DRAINAGE CONNECTIONS
ACROSS THE VERGE PRIOR TO COMMENCEMENT OF SITE DRAINAGE
WORKS.
10. PROPERTIES AFFECTED BY THE WORKS ARE TO BE NOTIFIED IN ADVANCE
WHERE DISRUPTION TO EXISTING ACCESS IS LIKELY.
LOCALITY SKETCHN.T.S.
SITE
SITEWORKS NOTES
• DATUM : A.H.D.
• ORIGIN OF LEVELS : REFER TO BENCH OR STATE SURVEY MARKS WHERE
SHOWN ON PLAN.
• CONTRACTOR MUST VERIFY ALL DIMENSIONS AND EXISTING LEVELS ON SITE
PRIOR TO THE COMMENCEMENT OF WORK.
• ALL WORKS TO BE UNDERTAKEN IN ACCORDANCE WITH THE DETAILS SHOWN
ON THE DRAWINGS & THE DIRECTIONS OF THE SUPERINTENDENT.
• EXISTING SERVICES UNLESS SHOWN ON THE SURVEY PLAN HAVE BEEN
PLOTTED FROM SERVICES SEARCH PLANS AND AS SUCH THEIR ACCURACY
CANNOT BE GUARANTEED. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO
ESTABLISH THE LOCATION AND LEVEL OF ALL EXISTING SERVICES PRIOR TO
THE COMMENCEMENT OF ANY WORK. ANY DISCREPANCIES SHALL BE
REPORTED TO THE SUPERINTENDENT. CLEARANCES SHALL BE OBTAINED
FROM THE RELEVANT SERVICE AUTHORITY.
• WHERE NEW WORKS ABUT EXISTING THE CONTRACTOR SHALL ENSURE THAT A
SMOOTH EVEN PROFILE, FREE FROM ABRUPT CHANGES IS ACHIEVED.
• THE CONTRACTOR SHALL ARRANGE ALL SURVEY SETOUT TO BE CARRIED OUT
BY A REGISTERED SURVEYOR.
• CARE IS TO BE TAKEN WHEN EXCAVATING NEAR EXISTING SERVICES. NO
MECHANICAL EXCAVATION IS TO BE UNDERTAKEN OVER TELSTRA OR
ELECTRICAL SERVICES. HAND EXCAVATE IN THESE AREAS.
• CONTRACTOR TO OBTAIN AUTHORITY APPROVALS WHERE APPLICABLE.
• MAKE SMOOTH TRANSITION TO EXISTING SURFACES AND MAKE GOOD.
• THESE PLANS SHALL BE READ IN CONJUNCTION WITH APPROVED LANDSCAPE,
ARCHITECTURAL, STRUCTURAL, HYDRAULIC AND MECHANICAL DRAWINGS AND
SPECIFICATIONS
OR WRITTEN INSTRUCTIONS THAT MAY BE ISSUED RELATING
TO DEVELOPMENT AT THE SITE.
• TRENCHES THROUGH EXISTING ROAD AND CONCRETE PAVEMENTS SHALL BE
SAWCUT TO FULL DEPTH OF CONCRETE AND A MINIMUM OF 50mm IN
BITUMINOUS PAVING.
• ALL BRANCH GAS AND WATER SERVICES UNDER DRIVEWAYS AND BRICK
PAVING SHALL BE LOCATED IN Ø80 uPVC SEWER GRADE CONDUITS EXTENDING
A MINIMUM OF 500mm BEYOND EDGE OF PAVING.
• GRADES TO PAVEMENTS TO BE AS IMPLIED BY RL'S ON PLAN . GRADE EVENLY
BETWEEN NOMINATED RL'S. AREAS EXHIBITING PONDING GREATER THAN 5mm
DEPTH WILL NOT BE ACCEPTED UNLESS IN A DESIGNATED SAG POINT.
• ALL COVERS AND GRATES ETC TO EXISTING SERVICE UTILITIES ARE TO BE
ADJUSTED TO SUIT NEW FINISHED SURFACE LEVELS WHERE APPLICABLE.
jliu, AutoPDF
RL. 3840
1:20
1.5
1.5
2
2.5
///////////////
//
//
//
//
//
//
/
1.89
1.74
1.40
2.49
2.43
2.56
1.96
2.16
1.771.58
1.32
1.32
2.64
2.52
2.53
1.97
2.19
2.67
2.96
2.73
3.10
3.15
3.20
3.25
3.30
3.35
3.40
3.45
3.50
3.55
3.60
3.65
3.70
3.75
3.80
3.50
3 .50
3 .50
3.503.50
3.45
3.40
3.35
3.40
3.35
3.30 3.25
3.20
3.15
3.10
3.15
3.45
RAMP
RW
3.00
ME
RIM
BO
LA S
TR
EE
T
11
DP 835239
BULLARA STREET
RL3.55
TK3.55
RL3.70
TK3.55
TK3.55
RL3.475
TK3.55
RL3.84
RL3.625
RL3.73
TK3.65
TK3.70
TK3.70
RL3.55
RL3.55
TK3.625
RW
RW
RW
RL 3.050
PROPOSED
SUPERMARKET
FFL. RL3.84
LOADING DOCK
IKIK
IK
KO
CONSTRUCT NEW DRIVEWAY
IN ACCORDANCE WITH BEGA
VALLEY SHIRE COUNCIL
REQUIREMENTS.
CONSTRUCT NEW DRIVEWAY
IN ACCORDANCE WITH BEGA
VALLEY SHIRE COUNCIL
REQUIREMENTS.
RL2.95
RL2.65
RL2.50
PROVIDE 31m³
UNDERGROUND OSD
7m x 5m x 0.88m
REFER C201 FOR DETAILS
-A 1-A 2
-A 3
-A 4
-A 5
-A 6
-A 7
-B 1
OUTLET PIPE TO CONNECT
TO EXISTING HEADWALL
OUTLET PIPE CONNECTION
TO FUTURE DETAILS
Ø22
5
Ø22
5Ø
300
Ø300
Ø300
Ø225
ACCESS RAMP TO
SUPERMARKET TO
HAVE LOCALISED
GRADE
RL3.45
RL3.44
RL3.43
ACCESS RAMP TO
SUPERMARKET TO HAVE
LOCALISED GRADE
LAY
BA
CK
LAYBACK
PROVIDE BOLLARDS
ADJUST SEWER
MANHOLE TO SUIT
NEW LEVELS
K&G
KO KO
KO
KO
-G 2
-G 1
RL3.74
RL3.74
RL3.72
RL3.72
RL3.74
RL3.74
RL3.70RL3.70
RL3.74
TW4.0
0
TW3.2
0
TW4.
00
TW4.
00
TW3.
70
TW3.
30
TW3.30
TW3.75
TW3.
75
TW3.60
TW3.35
FALL
FALL
FALL
FALL
FALL
RL3.74
KO
KO
RW
2.5% 1.3%
1.3%
4%
Ø375
5%
2.5%
RL3.55
RL3.575
DP
DP
DP
DP
DP
DP
DPDPDP
DP
DP
DP
DP
DP DP DP
Ø150
Ø150
Ø150
Ø15
0
Ø150
Ø150
Ø15
0
RWRW
RW
RW
RW
Ø150 DOWNPIPES TO RUN
BESIDE WALL AND CONNECT
TO IN-GROUND DRAINAGE
Ø150 DOWNPIPES TO RUN
BESIDE WALL AND CONNECT
TO IN-GROUND DRAINAGE
Ø150 DOWNPIPES TO RUN
BESIDE WALL AND CONNECT
TO IN-GROUND DRAINAGE
IN-GROUND PIPE TO BE
CONNECTED TO
STORMWATER PIT
IN-GROUND PIPE TO BE
CONNECTED TO
STORMWATER PIT
Ø150 DOWNPIPES TO RUN
BESIDE WALL AND CONNECT
TO IN-GROUND DRAINAGE
Ø15
0
Ø15
0Ø
150
SURVEY
INFORMATIONSURVEYED BY
CADDEY SEARL AND JARMANDATUM: A.H.D
ORIGIN OF LEVELS: SSM54794 RL4.396 (A.H.D)01 ISSUED FOR DA ONLY AA IA 23/07/2015
Date
Scale
Title
Project
Drawing number
Drawn
Checked
Revision
Designed
Approved
This drawing and design remains the property of Henry & Hymas and may not becopied in whole or in part without the prior written approval of Henry & Hymas.
Architect
Client
REVISION AMENDMENT DATEREVISION AMENDMENT DATE
Surveyor
DESIGNEDDRAWNDESIGNEDDRAWN
Level 5,
79 Victoria Avenue
Chatswood NSW 2067
+61 2 9417 8400
+61 2 9417 8337
www.henryandhymas.com.auGlobal-Mark.com.au ® 0215114_DA_C100
PROPOSED SUPERMARKET
LOT 11 DP835239 PAMBULA NSW
GENERAL ARRANGEMENT PLAN
A. ALKATEB I. AHMED
I. AHMED A. FRANCIS
JULY 2015
1:200 @ A1
GREAT SOUTHERN DEVELOPMENTS
OZTAL ARCHITECTS
GENERAL ARRANGEMENT PLANSCALE 1:20020m1684
SCALE 1:200
120
1234
LEGEND
EXISTING BOUNDARY
PROPOSED RIDGE LINE
PROPOSED VALLEY LINE
PROPOSED JUNCTION PITS
PROPOSED SURFACE INLET PITS
PROPOSED PIT TAG-A 1LINE LETTER
PIT NUMBER
PROPOSED GRATED DRAIN
PROPOSED STORMWATER PIPE
PROPOSED KERB & GUTTERK&G
PROPOSED KERB ONLYKO
PROPOSED INTEGRAL KERBIK
PROPOSED RETAINING WALLRW
EXISTING CONTOURS4.60
PROPOSED CONTOURS4.60
PROPOSED SPOT LEVELRL4.52
PROPOSED LINTEL ONGRADE & SAG PITS
TOP OF RETAINING WALL LEVELTW4.52
DP DOWNPIPE TO HYDRAULIC DETAILS
TOP OF KERBTK4.52
02 ISSUED FOR DA ONLY AA IA 21/08/2015
CL
(H1 & H2 SUPPORT)SCALE 1:20
O.D.
TRENCH WIDTH = O.D.+600
300
100
DESIGN PAVEMENT
SUBGRADE LEVEL
COMPACTED TO 98% SMDD
IN 150mm (MAX.) LAYERS
HAUNCH ZONE
BED ZONE
COMPACTED NON
COHESIVE BACKFILL =1/3 O.D.
COMPACTED TO 100% SMDD
IN 2x150mm(MAX.) LAYERS
COMPACTED TO 95% SMDD
IN 250mm (MAX.) LAYERS
ORDINARY FILL FREE FROM
CLAY LUMPS EXCEEDING 75mm,
STONES EXCEEDING 25mm AND
CONTAMINATE MATERIALS
CL
O.D.
TRENCH WIDTH = O.D.+600
300
100
100mm MIN. THICK TOP SOIL
COMPACTED TO 98% SMDD
IN 150mm(MAX.) LAYERS
HAUNCH ZONE
BED ZONE
COMPACTED NON
COHESIVE BACKFILL =1/3 O.D.
COMPACTED TO 100% SMDD
IN 2x150mm(MAX.) LAYERS
COMPACTED TO 95% SMDD
IN 250mm(MAX.) LAYERS
ORDINARY FILL FREE FROM
CLAY LUMPS EXCEEDING 75mm,
STONES EXCEEDING 25mm AND
CONTAMINATE MATERIALS
(H1 & H2 SUPPORT)SCALE 1:20
PIPE TRENCH INSTALLATION
IN LANDSCAPE AREAS
PIPE TRENCH INSTALLATION
BENEATH PAVEMENT
100Ø A.G. PIPE 3m IN LENGTH
DRAINING IN DIRECTION OF FALL
OF PIPE TO DOWNSTREAM PIT.
PIPE TO BE WRAPPED IN GEOFABRIC
300
MIN
.
TO
P L
AY
ER
700
IF A
PP
LIC
AB
LE
700
IF A
PP
LIC
AB
LE
300
MIN
.
TO
P L
AY
ER
TYPICAL STEP IRON DETAILSCALE 1:10
ELEVATION
300
350
100
220 45
R20 GALV. STEEL M.S.
@ 300 CTRS
PLAN SECTIONELEVATION
300 300
NOTE: SLOTTED RIGID PVC PIPE AND
FITTINGS MAY BE USED
600
MIN
. UN
O
LIGHT DUTY IN LANDSCAPED AND PEDESTRIAN
AREAS HEAVY DUTY IN VEHICULAR PAVEMENTS.
AIR TIGHT CAST IRON OR BRASS SCREW OR BOLT
DOWN CAP.
300x300x150
CONCRETE SURROUND
HEAVY DUTY uPVC TO BE CONNECTED
TO THE SUB SOIL DRAINAGE LINE
100 DIA RIGID PVC
45° BEND
FLUSHING POINT (FP)SCALE 1:10
600
MIN
UN
O
NOTE: SLOTTED RIGID PVC PIPE AND
FITTINGS MAY BE USED
LIGHT DUTY IN LANDSCAPED AND PEDESTRIAN AREAS
HEAVY DUTY IN VEHICULAR PAVEMENTS. AIR TIGHT CAST
IRON OR BRASS SCREW OR BOLT DOWN CAP
300 x 300 x 150 CONCRETE
SURROUND
45°BEND
45°BEND Y PIECE
FLOW 1% MIN
300 x 300 x 150
CONCRETE SURROUND
100Ø RIGID PVC
HEAVY DUTY uPVC
TO BE CONNECTED
TO THE SUB SOIL
DRAINAGE LINE
100 SUBSOIL DRAINAGE LINE
REFER SUBSOIL BEDDING DETAILS
INTERMEDIATE RISER (IR)SCALE 1:10
200
2-N16
N16@ 200 CENTRES
'T'
500
max
.
'T'
600
lap
450 lap
1000 max.
N16 @ 200 CENTRES
EACH WAY EACH FACE
PIT REINFORCEMENT
SHOWN DASHED
HAUNCH DETAIL -TYPICALSCALE 1:10
SURVEY
INFORMATIONSURVEYED BY
CADDEY SEARL AND JARMANDATUM: A.H.D
ORIGIN OF LEVELS: SSM54794 RL4.396 (A.H.D)
Date
Scale
Title
Project
Drawing number
Drawn
Checked
Revision
Designed
Approved
This drawing and design remains the property of Henry & Hymas and may not becopied in whole or in part without the prior written approval of Henry & Hymas.
Architect
Client
REVISION AMENDMENT DATEREVISION AMENDMENT DATE
Surveyor
DESIGNEDDRAWNDESIGNEDDRAWN
Level 5,
79 Victoria Avenue
Chatswood NSW 2067
+61 2 9417 8400
+61 2 9417 8337
www.henryandhymas.com.auGlobal-Mark.com.au® 0115114_DA_C200
PROPOSED SUPERMARKET
LOT 11 DP835239 PAMBULA NSW
STORMWATER MISCELLANEOUS DETAILS
& PIT LID SCHEDULE
J.Liu I. AHMED
I. AHMED A. FRANCIS
JULY 2015
SHOWN @ A1
GREAT SOUTHERN DEVELOPMENTS
OZTAL ARCHITECTS
20m1684
SCALE 1:200
120
1234
2000mm1200 16004000
200400
800
SCALE 1:20
A = 900
H
A
H
A
B
PIPE DIA. + 150
A = 600 FOR PIPES UP TO 375 DIA.
PIT CHAMBER DIMENSIONS
FOR PIPES UP TO 600 DIA.
PIT CHAMBER FOR PIPES
GREATER THAN 600 DIA.
H = 0-900mm - AxB = 600x600mm
H = 900-1200mm - AxB = 900x600mm
H = >1200mm - AxB = 900x900mm
FOR B = 600mm - MAX. SIDE ENTRY PIPE AT 45° SKEW = 225mm
FOR B = 900mm - MAX. SIDE ENTRY PIPE AT 45° SKEW = 375mm
FOR B = 1200mm - MAX. SIDE ENTRY PIPE AT 45° SKEW = 600mm
FOR B = 1500mm - MAX. SIDE ENTRY PIPE AT 45° SKEW = 825mm
FOR B = 1900mm - MAX. SIDE ENTRY PIPE AT 45° SKEW = 1050mm
FLOW FLOW
FLOW
PIT CHAMBER FOR
SIDE ENTRY ON SKEW
TYPICAL PIT CHAMBER SIZESIT IS THE CONTRACTORS RESPONSIBILITY TO SELECT PIT CHAMBER SIZE WITH REGARDS TO PIPE SIZE, DEPTH TO
INVERT AND SKEW ANGLE. REFER SKETCHES BELOW.SELECT PIT CHAMBER USING THE STEPS BELOW:
SELECT PIT CHAMBER SIZE DEPENDING ON THE PIPE DIAMETERS.
CHECK PIT CHAMBER SIZE TO SATISFY DEPTH TO INVERT REQUIREMENTS.
CHECK PIT CHAMBER DIMENSIONS TO SATISFY THE SKEW ANGLE IN THE TABLE.
SECTIONSECTION
PLAN
PIT SIZE & DEPTH
REQUIREMENTS
1
2
3
1 1
2
3
FOR REINFORCEMENT TO WALLS
AND FLOOR OF PITS (WHERE
REQUIRED) REFER TO NOTES 10
AND 21.
FOR REINFORCEMENT TO HAUNCH SEE BELOW
NTSNTS
NTS
1000mm800600400
SCALE 1:10
0
200 100
200
DRAINAGE NOTES:
1. ALL STORMWATER WORK TO COMPLY WITH AS 3500 PART 3.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE MINIMUM COVER OF
600mm ON ALL PIPES
3. PROTECTION OF PIPES DUE TO LOADS EXCEEDING W7 WHEEL LOAD SHALL BE THE
CONTRACTOR'S RESPONSIBILITY
4. BEDDING TYPE SHALL BE TYPE H2 FOR RCP. WHERE NECESSARY THE OVERLAY ZONE
SHALL BE REDUCED TO ACCOMMODATE PAVEMENT REQUIREMENTS. REFER TO THIS
DRAWING FOR DETAILS.
5. NO CONSTRUCTION LOADS SHALL BE APPLIED TO PLASTIC PIPES.
6. FINISHED SURFACE LEVELS SHOWN ON LAYOUT PLAN DRGS TAKE PRECEDENCE OVER
DESIGN DRAINAGE SURFACE LEVELS.
7. ALL PIPES UP TO AND INCLUDING 300 DIA. SHALL BE SOLVENT OR RUBBER RING JOINTED
PVC CLASS SH PIPE TO AS1260. ALL OTHER PIPES TO BE RCP USING CLASS 2 RUBBER
RING JOINTED PIPE. HARDIES FRC PIPE MAY BE USED IN LIEU OF RCP IF DESIRED IN
GROUND.
8. ALL PITS IN NON TRAFFICABLE AREAS TO BE PREFABRICATED POLYESTER CONCRETE
"POLYCRETE" WITH "LIGHT DUTY" CLASS B GALV. MILD STEEL GRATING AND FRAME.
ALL PITS IN TRAFFICABLE AREAS (CLASS "D" LOADING MAX) TO HAVE 150mm THICK
CONCRETE WALLS AND BASE CAST IN-SITU f'c=32 MPa, REINFORCED WITH N12-200 BOTH
LOADING WAYS CENTRALLY PLACE .U.N.O. ON SEPARATE DESIGN DRAWINGS IN THIS SET.
GALV.MILD STEEL GRATING AND FRAME TO SUIT DESIGN LOADING. PRECAST PITS,
RECTANGULAR OR CIRCULAR IN SHAPE, MAY BE USED IN LIEU AND SHALL COMPLY WITH
RELEVANT AUSTRALIAN STANDARDS.
PITS IN EXCESS OF 1.5 M DEEP TO HAVE WALL AND FLOOR THICKNESS INCREASED TO
200MM. REINFORCED WITH N12@200 CTS CENTRALLY PLACED BOTH WAYS THROUGHOUT
U.N.O.ON SEPARATE DESIGN DRAWINGS IN THIS SET. IF DEPTH EXCEEDS 5M CONTACT
ENGINEER.
9. ALL PITS, GRATINGS AND FRAMES SHALL BE INSTALLED IN ACCORDANCE WITH THE
MANUFACTURERS SPECIFICATION AND TO BE IN ACCORDANCE WITH AS3500.3 AND
AS3996.
10. PIT CHAMBER DIMENSIONS ARE TO BE SELECTED TO SATISFY THE FOLLOWING:
- PIPE SIZE
- DEPTH TO INVERT
- SKEW ANGLE
REFER TYPICAL PIT CHAMBER DETAILS BELOW
IF PIT LID SIZE IS SMALLER THAN THE PIT CHAMBER SIZE THEN THE PIT LID IS TO BE
CONSTRUCTED ON THE CORNER OF THE PIT CHAMBER WITH THE STEP IRONS DIRECTLY
BELOW. ALTERNATIVELY THE PIT LID TO BE USED, IS TO BE THE SAME SIZE AS THE PIT
CHAMBER.
11. FOR PIPE SIZES GREATER THAN Ø300MM, PIT FLOOR IS TO BE BENCHED TO FACILITATE
FLOW.
12. GALVANISED STEP IRONS SHALL BE PROVIDED AT 300 CTS FOR PITS HAVING A DEPTH
EXCEEDING 1200MM. SUBSOIL DRAINAGE PIPE (Ø100 SLOTTED PVC IN A FILTER SOCK)
SHALL BE PROVIDED IN PIPE TRENCHES ADJACENT TO INLET PIPES. MINIMUM LENGTH 3M
UPSTREAM OF ALL PITS.
13. ALL ROOF DRAINAGE TO BE INSTALLED IN ACCORDANCE WITH AS3500, PART 3. TESTING
TO BE UNDERTAKEN AND REPORTS PROVIDED TO THE SUPERINTENDENT.
14. LOCATION OF THE DIRECT DOWN PIPE CONNECTIONS MAY VARY ON SITE TO SUIT SITE
CONDITIONS.
15. SUBSOIL DRAINAGE LINES FOR LANDSCAPE AREA NOT SHOWN ON THESE DRAWINGS.
REFER TO LANDSCAPING PLANS FOR DETAILS.
PIT LID SCHEDULE
PIT/STRUCTURE NUMBER DESCRIPTION
-A 1 -B 1
-A 2 -A 7
-A 3
-A 4 -A 5 -A 6
-G 1 -G 2 225mm WIDE HEAVY DUTY GRATED DRAIN AND HEAVY
DUTY FRAME CLASS "D"
OSD TANK ACCESS OPENING WITH 900x900 HINGED
HEAVY DUTY GRATED LID CLASS "D" WITH LOCK-DOWN
SYSTEM
SAG KERB INLET PIT WITH 1.8m LINTEL AND HEAVY
DUTY GRATED LID CLASS "D" IN ACCORDANCE WITH
LOCAL COUNCIL REQUIREMENT
INLET PIT WITH 600x600 HINGED HEAVY DUTY GRATED
LID CLASS "C" IN ACCORDANCE WITH LOCAL COUNCIL
REQUIREMENT.
ON GRADE KERB INLET PIT WITH 1.8m LINTEL AND
HEAVY DUTY GRATED LID CLASS "D" IN ACCORDANCE
WITH LOCAL COUNCIL REQUIREMENT
01 ISSUED FOR DA ONLY JL IA 23/07/2015
jliu, AutoPDF
5000
900
RL2.96
RL1.76RL1.71
225
120
TRASH SCREEN
REFER DETAIL
ORIFICE PLATE
REFER DETAIL
Ø225 OUTLET
STEP IRONS
REFER DETAIL
RL3.25
1% FALL
PROPOSED OSD7x5x0.88=31m³
SECTION 1-SCALE: 1:20
RL2.58 2yr ARI TWL
ORIFICE PLATE DETAILSCALE 1:10
50 TYP.
400
400
5mm STAINLESS STEEL PLATE
Ø225 OUTLET PIPE BEHIND
FIX TO TANK WALL USING
4M10 MASONARY ANCHORS
NON REMOVABLE.
Ø120
TRASH SCREEN DETAILN.T.S
LIFTING HANDLE
'LYSAGHT'MAXIMESH RH3030
(HOT DIPPED GALVANISED)
OR EQUIVALENT FRONT AND
SIDE PANELS
MAX.600
MA
X.6
00
MAX.600
TRASH SREEN NOTES
1. MAXIMESH SCREENS MUST BE PLACED SUCH THAT THE LONG
AXIS OF THE OVAL SHAPED HOLES ARE ORIENTATED
HORIZONTALLY WITH THE PORTRUDING LIP ANGLED UPWARDS
AND FACING TOWRADS THE OUTLET.
2. THE SCREEN IS TO BE FORMED BY WELDING TWO TRIANGULAR
MAXIMESH (OR EQUIVALENT) PANELS TO A RECTANGULAR
FRONT MAXIMESH PANEL(OR EQUIVALENT)
7000
5000
900
900
1-
OSD PLANSCALE 1:50
OSD VOLUME7x5x0.88=31m³
SURVEY
INFORMATIONSURVEYED BY
CADDEY SEARL AND JARMANDATUM: A.H.D
ORIGIN OF LEVELS: SSM54794 RL4.396 (A.H.D)
Date
Scale
Title
Project
Drawing number
Drawn
Checked
Revision
Designed
Approved
This drawing and design remains the property of Henry & Hymas and may not becopied in whole or in part without the prior written approval of Henry & Hymas.
Architect
Client
REVISION AMENDMENT DATEREVISION AMENDMENT DATE
Surveyor
DESIGNEDDRAWNDESIGNEDDRAWN
Level 5,
79 Victoria Avenue
Chatswood NSW 2067
+61 2 9417 8400
+61 2 9417 8337
www.henryandhymas.com.auGlobal-Mark.com.au® 0115114_DA_C201
PROPOSED SUPERMARKET
LOT 11 DP835239 PAMBULA NSW
OSD DETAILS
J.Liu I. AHMED
I. AHMED A. FRANCIS
JULY 2015
SHOWN @ A1
GREAT SOUTHERN DEVELOPMENTS
OZTAL ARCHITECTS
5000mm3000 400010000
2006001000
2000
SCALE 1:50
2000mm1200 16004000
200400
800
SCALE 1:20
1000mm800600400
SCALE 1:10
0
200 100
200
1:1 YEAR 1 IN 2 YEAR
PRE-DEVELOPD (L/S) 38 64
POST DEVELOPED (L/S) 37 44
OSD TOTAL VOLUME: 31m³DISCHARGE FROM THE SITE CONTROLLED BY
ORIFICE TO LIMIT TO PRE DEVELOPED FLOW FOR
ALL EVENTS FROM 1:1 YEAR ARI TO 1:2 YEAR ARI.
01 ISSUED FOR DA ONLY JL IA 23/07/2015
jliu, AutoPDF
1.5
2
2.5
///////////
//
//
//
//
//
/
1.89
2.56
1.771.58
1.32
1.32
2.64
2.52
2.53
1.97
2.19
2.67
2.73
PO
ST
ED
GE
SEWER
MANHOLE
800Ø
R.C
. PIP
ES
EDGE BITUMEN
POST AND WIRE FENCE
BOUNDAAPPROXIMATE
AP
PR
OX
IMA
TE
ME
RIM
BO
LA S
TR
EE
T
BULLARA STREET
RW
RW
PROPOSED
SUPERMARKET
FFL. RL3.84
LOADING DOCK
IK
IK
GD
-1
LAY
BA
CK
LAYBACK
PROVIDE BOLLARDS
K&G
KO
KO
KO
RW
150
INTEGRAL KERB (IK)
125 25 NOMINAL KERB LINE
R6-600 COG 150
2N12
SCALE 1:10
100
R20
PAVEMENT AS SPECIFIED
R5
CUT BARS AT 50 EITHER
SIDE OF SAWN JOINT LOCATION
100
CJ OPTIONAL
600100 100
130
UN
O15
0 U
NO
100
125 450
25 NOMINAL KERB LINE
40
KERB & GUTTER (K&G)SCALE 1:10
R20R5
R5
NOTE:
CONFIRM DIMENSIONS AND DETAILS WITH
BEGA VALLEY SHIRE COUNCIL
100
MIN
100
MIN
200
MIN
150
UN
O10
0
125 25 NOMINAL KERB LINE
R20R5
KERB ONLY (KO)SCALE 1:10
SURVEY
INFORMATIONSURVEYED BY
CADDEY SEARL AND JARMANDATUM: A.H.D
ORIGIN OF LEVELS: SSM54794 RL4.396 (A.H.D)
Date
Scale
Title
Project
Drawing number
Drawn
Checked
Revision
Designed
Approved
This drawing and design remains the property of Henry & Hymas and may not becopied in whole or in part without the prior written approval of Henry & Hymas.
Architect
Client
REVISION AMENDMENT DATEREVISION AMENDMENT DATE
Surveyor
DESIGNEDDRAWNDESIGNEDDRAWN
Level 5,
79 Victoria Avenue
Chatswood NSW 2067
+61 2 9417 8400
+61 2 9417 8337
www.henryandhymas.com.auGlobal-Mark.com.au® 0115114_DA_C500
PROPOSED SUPERMARKET
LOT 11 DP835239 PAMBULA NSW
PAVEMENT PLAN & KERB DETAILS
J.LIU I. AHMED
I. AHMED A. FRANCIS
JULY 2015
1:200 @ A1
GREAT SOUTHERN DEVELOPMENTS
OZTAL ARCHITECTS
PAVEMENT PLANSCALE 1:200
20m1684
SCALE 1:200
120
1234
PAVEMENT TYPE 1HEAVY DUTY CONCRETE PAVEMENT
100mm THICK 25MPa CONCRETE WITH SL72 MESH CENTRAL
PAVEMENT TYPE 3PEDESTRIAN FOOTPATH PAVEMENT
SURFACING TO ARCHITECT'S DETAILS
50mm THICK SAND LAYER
PAVEMENT LEGEND
PAVEMENT TYPE 4OSD CONCRETE SLAB
FUTURE DETAILS BY STRUCTURAL ENGINEER
150 DGB20 OR APPROVAL EQUIVALENT
PAVEMENT TYPE 2LIGHT DUTY ASPHALT PAVEMENT
50mm ASPHALT CONCRETE AC10
COMPACTED SUBGRADE (ASSUMED CBR 3.0% MIN.)
160mm THICK 32MPa CONCRETE
WITH SL92 TOP 50mm COVER
COMPACTED SUBGRADE (ASSUMED CBR 3.0% MIN.)
125mm DGB40 COMPACTED TO 98% MODIFIED DENSITY
COMPACTED SUBGRADE (ASSUMED CBR 3.0% MIN.)
150 DGB40 OR APPROVAL EQUIVALENT
PAVEMENT TYPE 5HEAVY DUTY CONCRETE VEHICULAR CROSSING,
REFER BEGA VALLY SHIRE COUNCIL DRAWING
FOR DETAILS
1000mm800600400
SCALE 1:10
0
200 100
200
01 ISSUED FOR DA ONLY JL IA 23/07/2015
jliu, AutoPDF
mstimova, AutoPDF
1.5
2
2.5
/////////////
//
//
//
//
//
//
/
1.89
2.56
1.771.58
1.32
1.32
2.64
2.52
2.53
1.97
2.19
2.67
2.96
2.73
ME
RIM
BO
LA S
TR
EE
T
11
DP 835239
BULLARA STREET
PROPOSED
SUPERMARKET
FFL. RL3.84
LOADING DOCK
37 ParkingSpaces
Tro
lley B
ay
RL. 3840
ProposedSupermarket
Area: 919.97m²
1.
2.
3.
1:20
SharedSpace
4.
5.
6.
7.
8.
9.
10. 11. 12. 13. 14. 15. 17.16. 18. 19. 20. 21. 22. 23. 24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
waste zone
Service &BOH
retaining wall as percivil documentation
Bicycle Parking -min. 5 spaces
Delivery truck sweep path &ramp as per Traffic and CivilConsultants documentation.
gra
ted
su
mp
RL.
3.5
50
sump to hydraulicengineers detail
Oxide coloured concretewith a broomed finish
Refer to Civil Engineersdocumentation for carparkand road RL's & surfacetreatment
54.8
91
RL.
3.8
00
retaining wall as percivil documentation
retaining wall as percivil documentation
retaining wall as percivil documentation
55.0
00
54.500
54.500
Proposed Boundary
Pro
po
sed
Bo
un
da
ry
SharedSpace
proposedlandscape designas per LandscapeConsultantsdocumentation.
Underground OSD - referto engineers detail
Sumps and the like tocivil engineers
documentation
PROPOSED
STOCKPILE
LOCATION
PROPOSED GEOTEXTILE INLET
FILTER AROUND THE PROPOSED
PIT. TYPICAL
PROPOSED MESH & GRAVEL
INLET FILTER AROUND THE
GRATED DRAIN. TYPICAL
SEDIMENTATION FENCE
PROPOSED VEHICLE
SHAKER GRID AND
STABILISED SITE ACCESS
PROPOSED MESH & GRAVEL
INLET FILTER AROUND THE
KERB INLET PIT. TYPICAL
RW
SURVEY
INFORMATIONSURVEYED BY
CADDEY SEARL AND JARMANDATUM: A.H.D
ORIGIN OF LEVELS: SSM54794 RL4.396 (A.H.D)
Date
Scale
Title
Project
Drawing number
Drawn
Checked
Revision
Designed
Approved
This drawing and design remains the property of Henry & Hymas and may not becopied in whole or in part without the prior written approval of Henry & Hymas.
Architect
Client
REVISION AMENDMENT DATEREVISION AMENDMENT DATE
Surveyor
DESIGNEDDRAWNDESIGNEDDRAWN
Level 5,
79 Victoria Avenue
Chatswood NSW 2067
+61 2 9417 8400
+61 2 9417 8337
www.henryandhymas.com.auGlobal-Mark.com.au® 0115114_DA_SE01
PROPOSED SUPERMARKET
LOT 11 DP835239 PAMBULA NSW
SEDIMENT & EROSION CONTROL PLAN
J.LIU I. AHMED
I. AHMED A. FRANCIS
JULY 2015
1:200 @ A1
GREAT SOUTHERN DEVELOPMENTS
OZTAL ARCHITECTS
SEDIMENT & EROSION CONTROL PLANSCALE 1:200
20m1684
SCALE 1:200
120
1234
LEGEND
TRAFFIC MANOEUVRING
PROPOSED SEDIMENTATION FENCE
PROPOSED VEHICLE SHAKER GRID
PROPOSED STABILISED SITE ACCESS
PROPOSED STOCKPILE LOCATION
GEOTEXTILE INLET FILTER
PROPOSED MESH & GRAVEL INLET FILTER
SEDIMENT & EROSION CONTROL NOTES
• ALL SEDIMENT CONTROL DEVICES ARE TO BE CONSTRUCTED, PLACED AND
MAINTAINED IN ACCORDANCE WITH BEGA VALLEY SHIRE COUNCIL SPECIFICATIONS
AND LANDCOM'S "SOIL AND CONSTRUCTION" MANUAL.
• ALL PERIMETER & SILTATION CONTROL MEASURES ARE TO BE PLACED PRIOR TO,
OR AS THE FIRST STEP IN EARTH WORKS AND/OR CLEARING.
• THE SEDIMENT & EROSION CONTROL PLAN MAY REQUIRE FUTURE ADJUSTMENT TO
REFLECT CONSTRUCTION STAGING. IT IS ALSO THE CONTRACTORS
RESPONSIBILTY TO PREPARE THEIR OWN SEDIMENT AND EROSION CONTROL PLAN
WHICH SUITS THE DESIGNED CONSTRUCTION STAGING.
• FILTRATION BUFFER ZONES ARE TO BE FENCED OFF AND ACCESS PROHIBITED TO
ALL PLANT AND MACHINERY.
• ALL TEMPORARY EARTH BERMS, DIVERSIONS & SILT DAM EMBANKMENTS ARE TO
BE MACHINE COMPACTED, SEEDED & MULCHED FOR TEMPORARY VEGETATION
COVER AS SOON AS THEY HAVE BEEN FORMED.
• ALL SEDIMENT TRAPPING STRUCTURES AND DEVICES ARE TO BE INSPECTED
AFTER STORMS FOR STRUCTURAL DAMAGE OR CLOGGING. TRAPPED MATERIAL IS
TO BE REMOVED TO A SAFE LOCATION.
• ALL TOPSOIL IS TO BE STOCKPILED ON SITE FOR REUSE (AWAY FROM TREES AND
DRAINAGE LINES). MEASURES SHALL BE APPLIED TO PREVENT EROSION OF THE
STOCKPILES.
• ALL EARTHWORK AREAS SHALL BE ROLLED EACH EVENING TO SEAL THE
EARTHWORKS.
• ALL FILLS ARE TO BE LEFT WITH A LIP AT THE TOP OF THE SLOPE AT THE END. ALL
CUT AND FILL SLOPES ARE TO BE SEEDED AND STRAW MULCHED WITHIN
14 DAYS OF COMPLETION OF FORMATION U.N.O. BY LANDSCAPE ARCHITECTS.
• UPON COMPLETION OF ALL EARTHWORKS OR AS DIRECTED BY COUNCIL SOIL
CONSERVATION TREATMENTS SHALL BE APPLIED SO AS TO RENDER AREAS THAT
HAVE BEEN DISTURBED, EROSION PROOF WITHIN 14 DAYS.
• EROSION AND SILT PROTECTION MEASURES ARE TO BE MAINTAINED AT ALL TIMES.
01 ISSUED FOR DA ONLY JL IA 23/07/2015
Date
Scale
Title
Project
Drawing number
Drawn
Checked
Revision
Designed
Approved
This drawing and design remains the property of Henry & Hymas and may not becopied in whole or in part without the prior written approval of Henry & Hymas.
Architect
Client
REVISION AMENDMENT DATEREVISION AMENDMENT DATE
Surveyor
DESIGNEDDRAWNDESIGNEDDRAWN
Level 5,
79 Victoria Avenue
Chatswood NSW 2067
+61 2 9417 8400
+61 2 9417 8337
www.henryandhymas.com.auGlobal-Mark.com.au® 0115114_DA_SE02
PROPOSED SUPERMARKET
LOT 11 DP835239 PAMBULA NSW
SEDIMENT & EROSION CONTROL
TYPICAL DETAILS
J.LIU I. AHMED
I. AHMED A. FRANCIS
JULY 2015
1:200 @ A1
GREAT SOUTHERN DEVELOPMENTS
OZTAL ARCHITECTS
SECTION DETAIL
1.5m STAR PICKETS@ MAX. 2.5m CENTRES
SELF-SUPPORTINGGEOTEXTILE
DIRECTION OF FLOW
ON SOIL, 150mm x 100mmTRENCH WITH COMPACTEDBACKFILL AND ON ROCK, SETINTO SURFACE CONCRETE
DISTURBED AREA DIRECTION OFFLOW
1.5m STAR PICKETS@ MAX. 2.5m CENTRES
UNDISTURBED AREAS
PLAN
FLOWSTAR PICKETS @ MAX.2.5m SPACINGS TYPICAL
SEDIMENT FENCESCALE N.T.S.
MIN
. 1.5
m
20m MAX.
600m
m M
IN.
500
- 60
0mm
SEDIMENT FENCE CONSTRUCTION NOTES:1. CONSTRUCT SEDIMENT FENCES AS CLOSE AS POSSIBLE TO BEING PARALLEL TO THE CONTOURS OF THE
SITE, BUT WITH SMALL RETURNS AS SHOWN IN THE DRAWING TO LIMIT THE CATCHMENT AREA OF ANY ONE
SECTION. THE CATCHMENT AREA SHOULD BE SMALL ENOUGH TO LIMIT WATER FLOW IF CONCENTRATED
AT ONE POINT TO 50 LITRES PER SECOND IN THE DESIGN STORM EVENT, USUALLY THE 10-YEAR EVENT.
2. CUT A 150mm DEEP TRENCH ALONG THE UPSLOPE LINE OF THE FENCE FOR THE BOTTOM OF THE FABRIC
TO BE ENTRENCHED.
3. DRIVE 1.5m LONG STAR PICKETS INTO GROUND @ 2.5m INTERVALS (MAX.) AT THE DOWNSLOPE EDGE OF
THE TRENCH. ENSURE ANY STAR PICKETS ARE FITTED WITH SAFETY CAPS.
4. FIX SELF-SUPPORTING GEOTEXTILE TO THE UPSLOPE SIDE OF THE POSTS ENSURING IT GOES TO THE
BASE OF THE TRENCH. FIX THE GEOTEXTILE WITH WIRE TIES OR AS RECOMMENDED BY THE
MANUFACTURER. ONLY USE GEOTEXTILE SPECIFICALLY PRODUCED FOR SEDIMENT FENCING. THE USE OF
SHADE CLOTH FOR THIS PURPOSE IS NOT SATISFACTORY.
5. JOIN SECTIONS OF FABRIC AT A SUPPORT POST WITH A 150mm OVERLAP.
6. BACKFILL THE TRENCH OVER THE BASE OF THE FABRIC AND COMPACT IT THOROUGHLY OVER THE
GEOTEXTILE.
RUNOFF DIRECTED TO
SEDIMENT TRAP/ FENCE
GEOTEXTILE FABRIC DESIGNED TO PREVENT
INTERMIXING OF SUB GRADE AND BASE
MATERIALS AND TO MAINTAIN GOOD
PROPERTIES OF THE SUB-BASE LAYERS. GEOTEXTILE MAY BE A WOVEN OR NEEDLE
PUNCHED PRODUCT WITH A MINIMUM CBR
BURST STRENGTH (AS3706.4-90) OF 2500 N
DGB 20 ROAD BASE OR
30mm AGGREGATE. 150mm
THICK MIN TO BE PLACED
OVER GEOTEXTILE FABRIC
N.T.S.
MIN LENGTH 15 METERS
PROPERTY BOUNDARY
EXISTING ROADWAY
300mm MIN
MIN WIDTH 3 METERS
STABILISED SITE ACCESS WITH SHAKER RAMP
NOTES:1. THIS DEVICE IS TO BE LOCATED AT ALL EXITS FROM CONSTRUCTION SITE.
2. THIS DEVICE IS TO BE REGULARLY CLEANED OF DEPOSITED MATERIAL SO AS TO
MAINTAIN A 50mm DEEP SPACE BETWEEN PLANKS.
3. ANY UNSEALED ROAD BETWEEN THIS DEVICE AND NEAREST ROADWAY IS TO BE
TOPPED WITH 100mm THICK 40-70mm SIZE AGGREGATE.
4. ALTERNATIVELY, THREE(3) PRECAST CONCRETE CATTLE GRIDS (AS
MANUFACTURED BY "HUMES CONCRETE MAY BE USED. 1, 2 & 3 ABOVE ALSO
APPLY.
PLAN
STABILISED SITE ACCESS WITH SHAKER RAMPN.T.S.
PR
OP
ER
TY
BO
UN
DA
RY
EX
IST
ING
RO
AD
WA
Y
min 15 m
150mm THICK 40-70mm
AGGREGATE
SHAKER RAMP
OF TIMBER OR
STEEL SLATS
200m
m M
IN
CONSTRUCTION SEQUENCE
WORKS SHALL BE UNDERTAKEN IN THE FOLLOWING SEQUENCE:
1. INSTALL SEDIMENT FENCING AND CUT DRAINS TO MEET THE
REQUIREMENTS OF THE SEDIMENT AND EROSION CONTROL
PLAN. WASTE COLLECTION BINS SHALL BE INSTALLED
ADJACENT TO SITE OFFICE.
2. CONSTRUCT STABILISED SITE ACCESS IN ACCORDANCE WITH
WOLLONGONG CITY COUNCIL'S REQUIREMENTS.
3. REDIRECT CLEAN WATER AROUND THE CONSTRUCTION SITE.
4. INSTALL SEDIMENT CONTROL PROTECTION MEASURES AT ALL
NATURAL AND MAN-MADE DRAINAGE STRUCTURES. MAINTAIN
UNTIL ALL THE DISTURBED AREAS ARE STABILISED.
5. CLEAR AND STRIP THE WORK AREAS. MINIMISE THE DAMAGE TO
THE GRASS AND LOW GROUND COVER OF NON-DISTURBED
AREAS.
6. ANY DISTURBED AREAS, OTHER THAN BUILDING PAD AREAS,
SHALL IMMEDIATELY BE COVERED WITH SITE TOPSOIL WITHIN 7
DAYS OF CLEARING. BUILDING PAD AREAS SHALL BE COVERED
WITH BITUMEN EMULSION AS SPECIFIED.
7. APPLY PERMANENT STABILISATION TO SITE (LANDSCAPING).
SILT FENCE
TIE TO FENCE AT 1m INTERVAL
N.T.S.
PERIMETER SECURITY FENCE WITH WIND BARRIER
PERIMETER SECURITY FENCE WITH
WIND BARRIER & SILT FENCE
TIMBER SPACERTO SUIT
KERB-SIDE INLET
OVERFLOW
GRAVEL-FILLED WIRE MESHOR GEOTEXTILE "SAUSAGE"
RUNOFF WATERWITH SEDIMENT
FILTERED WATER
SEDIMENT
GRAVEL-FILLED WIRE MESHOR GEOTEXTILE "SAUSAGE"
1. FABRICATE A SLEEVE MADE FROM GEOTEXTILE OR WIRE MESH LONGER THAN THE LENGTH OF THE INLET PIT AND FILL IT WITH 25mm TO 50mm GRAVEL.2. FORM AN ELLIPTICAL CROSS-SECTION ABOUT 150mm HIGH x 400mm WIDE.3. PLACE THE FILTER AT THE OPENING LEAVING AT LEAST A 100mm SPACE BETWEEN IT AND THE KERB INLET. MAINTAIN THE OPENING WITH SPACER BLOCKS.4. FORM A SEAL WITH THE KERB TO PREVENT SEDIMENT BYPASSING THE FILTER.5. SANDBAGS FILLED WITH GRAVEL CAN SUBSTITUTE FOR THE MESH OR GEOTEXTILE PROVIDING THEY ARE PLACED SO THAT THEY CAN FIRMLY ABUT EACH OTHER AND SEDIMENT / LADEN WATERS CANNOT PASS
TIMBER SPACERTO SUIT
MESH & GRAVEL INLET FILTERSCALE N.T.S.
BETWEEN.
MESH & GRAVEL INLET FILTER CONSTRUCTION NOTES:
EARTH BANK
FLOW
STABILISE STOCKPILE SURFACE
2:1 SLOPE (MAX.) 2:1 SLOPE (MAX.)
SEDIMENT FENCE
STOCKPILE CONSTRUCTION NOTES:PLACE STOCKPILES MORE THAN 2 (PREFERABLY 5) METRES FROM EXISTING VEGETATION,CONCENTRATED WATER FLOW, ROADS AND HAZARD AREAS.CONSTRUCT ON THE CONTOUR AS LOW, FLAT, ELONGATED MOUNDS.WHERE THERE IS SUFFICIENT AREA, TOPSOIL STOCKPILES SHALL BE LESS THAN 2 METRES IN HEIGHT.WHERE THEY ARE TO BE PLACED FOR MORE THAN 10 DAYS, STABILISE FOLLOWING THE APPROVEDE.S.C.P. OR S.W.M.P. TO REDUCE THE C-FACTOR TO LESS THAN 0.10.CONSTRUCT EARTH BANKS ON THE UPSLOPE SIDE TO DIVERT WATER AROUND STOCKPILES ANDSEDIMENT FENCES 1 TO 2 METRES DOWNSLOPE.
1.
2.3.4.
5.
STOCKPILESSCALE N.T.S.
DROP INLET WITH GRATE
WIRE OR STEEL MESH(14 GAUGE x 150mmOPENINGS) WHERE GEOTEXTILEIS NOT SELF-SUPPORTING
WOVEN GEOTEXTILE
STAR PICKET FITTEDWITH SAFETY CAP
RUNOFF WATERWITH SEDIMENT
GEOTEXTILE EMBEDDED150mm INTO GROUND
SANDBAGS
WATERWAY
EXCAVATION
EARTH BANK
FILTEREDWATER
WOVEN GEOTEXTILE
FOR DROP INLETS @ NON-SAG POINTS,SANDBAGS, EARTH BANK OR EXCAVATIONUSED TO CREATE ARTIFICIAL SAG POINT
FLO
W
1 METER MAX.
1. FABRICATE A SEDIMENT BARRIER MADE FROM GEOTEXTILE.2. PICKET SPACING TO BE MAXIMUM 1.0m.3. IN WATERWAYS, ARTIFICIAL SAG POINTS CAN BE CREATED WITH SANDBAGS OR EARTH BANKS AS SHOWN IN THE DRAWING.4. DO NOT COVER THE INLET WITH GEOTEXTILES UNLESS THE DESIGN IS ADEQUATE TO ALLOW FOR ALL WATERS TO BYPASS IT.
GEOTEXTILE INLET FILTERSCALE N.T.S.
STAR PICKETS
GEOTEXTILE INLET FILTER CONSTRUCTION NOTES:
01 ISSUED FOR DA ONLY JL IA 23/07/2015
jliu, AutoPDF
PIPEWORK SYMBOLOGY & ABBREVIATIONS
NOTE: THIS IS A STANDARD LEGEND. ALL SYMBOLS MAY NOT NECESSARILY BE USED IN THESE DRAWINGS.
SYMBOLSRISER
DROPPERTEE DROPPERPIPEWORK CAPPIPEWORK CONTINUATION
PIPEWORK SECTIONDIRECTION ARROWNEW CONNECTION
NEXT DRAWING
STOP VALVECHECK VALVEBALANCING VALVE3 - WAY VALVEBALL VALVEREDUCED PRESSURE ZONE DEVICEPRESSURE RELIEF VALVEPRESSURE LIMITING VALVESOLENOID VALVEDOUBLE CHECK VALVEINFRA RED SENSOR
THERMOSTATIC MIXING VALVE
WATER FILTERREFLUX VALVE
REFLUX VALVE IN PIT
PATHBOXWATER METERGAS METER
STRAINERPRESSURE GAUGEFLOW SWITCHPRESSURE SWITCHWATER POINTTAP SETHOSE TAPBAYONET POINTREGULATORPUMPCONTROL PANEL
FIRE HOSE REEL
HOT WATER UNIT
FIRE HYDRANT
STREET HYDRANT
DUAL SUCTION POINT
QUAD SUCTION POINT
DUAL BOOSTER POINT
QUAD BOOSTER POINT
FLOORWASTETUNDISHBUCKET TRAP FLOORWASTECLEAROUT TO SURFACE
SEWER MANHOLE
BOUNDARY TRAPSURCHARGE GULLYINSPECTION SHAFTINDUCT PIPE MICA FLAPKAMLOCK CONNECTIONAIR ADMITTANCE VALVESYPHONIC OUTLETRAINWATER OUTLETSPREADER
OVERLAND FLOW ARROW
GREASE ARRESTOR
STORMWATER GRATE
STORMWATER COVER
REVISION
EXPANTION JOINT
PENETRATION / CORE HOLE IN SLAB
REDUCER
MONITORED VALVE
TRENCH GRATE
UNDOCUMENTED CONTINUED LINE
TEMPERING VALVE
ABBREVIATIONS ABBREVIATIONS cont. ABBREVIATIONS cont.
HYDRAULIC SERVICES LEGEND
STORMWATER FLOW ARROW
KERB ENTRY PIT
X-XXX
M
TT
PFSPS
H
--
BEAM PENETRATION
SYMBOLSDRAINAGE PIPING SYSTEMSAAV Air Admittance ValveBO Balcony OutletBT Boundary trapBTFW Bucket Trap FloorwasteCO Clear OutCST Condensate StackDG Disconnector GullyDP DownpipeDR Drainage RiserDTU Drainage Turn UpFU Fixture UnitsFW Floor WasteGA Grease ArrestorGD Grated DrainGO Gutter OutletGST Grease StackGTU Grease Turn UpGWST Grease Waste StackIO Inspection OpeningIPMF Induct Pipe Mica FlapIS Inspection ShaftKIP Kerb Inlet PitO/F OverflowORG Overflow Relief GullyPAPA Positive Air Pressure AttenuatorPO Planter OutletPFW Plantroom Floor WasteRVP Relief Vent PipeRWH Rain Water HeadRO Rainwater OutletS/TR Safe TraySDO Spoon Drain OutletSFW Sealed FloorwasteSMH Sewer ManholeSO Syphonic OutletSOF Syphonic OverflowSST Soil StackST StackSWP Stormwater PitSYP SyphonicTG Trench GrateTWMH Trade Waste ManholeTWST Trade waste StackTWTU Tradewaste Turn UpWST Waste Stack
VALVESBV Balancing ValveCV Check ValveDCV Double Check ValveECV Expansion Control valveFV Flush ValvePG Pressure GaugePLV Pressure Limiting ValvePRV Pressure Reduction ValveRPZD Reduced Pressure Zone DeviceRV Reflux ValveSV Stop ValveTMV Thermostatic Mixing ValveTPRV Temperature & Pressure Relief ValveTV Tempering ValveVB Vacuum Breaker
WATER PIPING SYSTEMSHWM Hot Water MeterHWU Hot Water UnitWM Water Meter
FLUID FLOWkPa KilopascalL LitresL/s Litres Per SecondLU Loading Unitsm.HEAD Metres Headm/s Metres per Secondm³/hr Cubic Metres per Hour
FIXTURESB BasinBBQ BarbequeBM Bain MarieBP Bayonet PointBSK Bar SinkBTH BathBWU Boiling Water UnitCWM Clothes Washing MachineCHWU Chilled Water UnitCS Cleaners SinkCT Cook TopDF Drinking FountainDU Dental UnitDWC Disabled Water ClosetDWM Dish Washing MachineEW Eye WashFC Fume CupboardFR FridgeFRS Flushing Rim SinkGWM Glass Washing MachineHT Hose TapIM Ice MachineLSK Laboratory SinkLT Laundry TubPS Pan SanitiserPSK Pot SinkSB Surgeons BasinSH Slop HopperSHR ShowerSK SinkSSHR Safety ShowerSTER SteriliserTD TundishTTD Trapped TundishUR UrinalUW Utensil WasherWC Water ClosetWT Wash Trough
MATERIALSBR BrassCI Cast IronCP Chrome PlatedCICL Cast Iron Cement LinedCu CopperDICL Ductile Iron Cement LinedFRC Fibre Reinforced ConcreteGAL GalvanisedGMS Galvanised Mild SteelHDPE High Density PolyethyleneMDPE Medium Density PolyethyleneMS Mild SteelNY NylonPEX Cross Linked PolyethylenePVC Polyvinyl ChlorideRCP Reinforced Concrete PipeS/S Stainless SteelUPVC Unplasticised Polyvinal ChlorideVCP Vitrified Clay Pipe
GAS PIPING SYSTEMSGFP Gas Fire PlaceGM Gas MeterGR Gas RegulatorkW KilowattLPG Liquified Petroleum GasMJ Megajoules
FIRE PROTECTION PIPING SYSTEMEXT ExtinguisherFH Fire HydrantFHBV Fire Hydrant Booster ValveFHR Fire Hose ReelFIP Fire Indicator PanelFSBV Fire Sprinkler Booster ValveSPR SprinklerSTD Sprinkler Test Drain
LEVELSAHD Australian Height DatumBWL Bottom Water LevelCL Ceiling LevelFFL Finished Floor LevelFSL Finished Surface LevelGL Ground LevelH/L High LevelHP High PointIL Invert LevelL/L Low Levelm Metremm MillimetresRL Reduced LevelSL Surface LevelSOB Soffit of BeamSOS Soffit of SlabSSL Structural Slab LevelTWL Top Water LevelU/S UndersideWL Water Level
MISCELLANEOUSA/C Air ConditioningAP Access PanelAS Australian StandardsBCA Building Code Of AustraliaCIC Cast In ColumnCIS Cast In SlabD DisabledDIA DiameterDWG DrawingEJ Expansion JointELEC Electrical ServiceHD Heavy DutyHV High VoltageID Inside DiameterLD Light DutyLV Low VoltageMIN MinimumMJD Movement Joint DrainNTS Not To ScaleOD Outside DiameterRHS Rectangular Hollow SectionSQ SquareTB Thrust BlockTEL Telecommunication ServiceTYP TypicalUNO Unless Noted OtherwiseUV Ultra Violet
THRUST BLOCK
P.A.P.A VALVERAINWATER HEAD
PROPOSED SUPERMARKETLOT 11 DP 835239 PAMBULA NSW
DA ISSUE
LOCALITY PLAN
AMENDMENT
CHAMBER VENT PIPE
CONDENSATE DRAIN
COLD WATER
DIESEL EXHAUSTDISCONNECTED SERVICEELECTRICAL SERVICE
FIRE HYDRANT
FIRE HOSE REEL
GAS SERVICE
GREASE WASTE
GREASE WASTE VENT PIPE
HOT WATER
IRRIGATION LINE
NON-POTABLE COLD WATER
NON-POTABLE HOT WATER
ULTRA PURE WATER
SANITARY PLUMBING
SUBSOIL
SANITARY RISING MAIN
STORMWATER DRAINAGE
STORMWATER RISING MAIN
SYPHONIC OVERFLOW
SYPHONIC STORMWATER
TRADE WASTE
TRADE WASTE VENT PIPE
VENT PIPE
WARM WATER
CASTIN
FIRE SERVICE
FIRE SPRINKLER MAIN
FIRE SPRINKLER RANGE PIPE
GAS FLUE
RAINWATER RE-USE
STORMWATER CATCHMENT
TRADE WASTE RISING MAIN
COLD WATER - EXISTING
CONDENSATE DRAIN - EXISTING
FIRE HOSE REEL - EXISTING
FIRE HYDRANT - EXISTING
FIRE SERVICE - EXISTING
FIRE SPRINKLER MAIN - EXISTING
FIRE SPRINKLER RANGE PIPE - EXISTING
GAS SERVICE - EXISTING
GREASE WASTE - EXISTING
GREASE WASTE VENT PIPE - EXISTING
HOT WATER - EXISTINGHOT WATER - HEAT TRACED
INSET BORDER
IRRIGATION LINE - EXISTING
NON-POTABLE COLD WATER - EXISTING
NON-POTABLE HOT WATER - EXISTING
RAINWATER RE-USE - EXISTING
ULTRA PURE WATER - EXISTINGSANITARY DRAINAGESANITARY DRAINAGE - EXISTING
SANITARY PLUMBING - EXISTING
SANITARY RISING MAIN - EXISTING
STORMWATER DRAINAGE - EXISTING
STORMWATER RISING MAIN - EXISTING
SUBSOIL - EXISTING
SYPHONIC OVERFLOW - EXISTING
SYPHONIC STORMWATER - EXISTING
TRADE WASTE - EXISTING
TRADE WASTE VENT PIPE - EXISTING
VENT PIPE - EXISTING
WARM WATER - EXISTING
CHVP CHVP
CW CW CWeCW eCW
CD CD CDeCD eCD
DE DE DEX X X X X X X X X X X
ELEC ELECFHR FHR
eFHR eFHRFH FH FH
eFH eFHFS FS FS
eFS eFSFSM FSM
eFSM eFSM
GF GF GFGAS GAS
eGAS eGAS
HW HW HWeHW eHW
IR IR IReIR eIR eIR
NPCW NPCWeNPCW eNPCWNPHW NPHW
eNPHW eNPHW
RR RR RReRR eRR
UPW UPWeUPW eUPW
SD SD SDeSD eSD
SP SP SPeSP eSP
SRM SRMeSRM eSRM
STW STWeSTW eSTW
SWRM SWRMeSWRM eSWRM
SS SS SSeSS eSSSOF SOF
eSOF eSOFSSW SSW
eSSW eSSWTW TW TW
eTW eTWTWRM TWRM
TWVP TWVPeTWVP eTWVP
VP VP VPeVP eVPWW WW
eWW eWW
GW GW GWeGW eGW
GWVP GWVPeGWVP eGWVP
CHAMBER VENT PIPE - EXISTINGeCHVP eCHVP
TRADE WASTE RISING MAIN - EXISTINGeTWRM eTWRM
PLANT LINE
STD STD SPRINKLER TEST DRAIN
CONDUIT
GAS SUPPRESSION PIPEGS GS GS
PD PD PD PD POOL DRAINPHW PHW PHW PHW POOL HEATING WATER
PW PW PW PW POOL WATER
eHWR eHWR
eWWR eWWR
HWR HWR
NHW-R NHW-R
WWR WWR
HOT WATER RETURNHOT WATER RETURN - EXISTING
NON-POTABLE HOT WATER RETURN
WARM WATER RETURNWARM WATER RETURN - EXISTING
DIRECTION OF FLOW
DIRECTION OF FLOW
--
--RISER --
SERVICE DESCRIPTION
SERVICE SIZERISER NUMBER / FLOW RATE
ADAPTABLE FIXTURE POINT(CAPPED FLUSH WITH SLAB)
OVERFLOWO/F
SITE
DRAWING SCHEDULEDRAWINGNUMBER
DRAWINGSCALE DRAWING TITLE
SW-00 N.T.S STORMWATER SERVICES COVER SHEET & LEGEND
SW-01 1:200 INGROUND GROUND LEVEL SERVICES AND SITE PLAN
SW-02 1:100 GROUND LEVEL STORMWATER SERVICES PLAN
SW-03 1:100 ROOF LEVEL STORMWATER SERVICES PLAN
N.T.S
SW-00 03
DA ISSUE
STORMWATER SERVICESCOVER SHEET & LEGEND
01 18/08/15 PRELIMINARY ISSUE BM BL
02 21/08/15 DA ISSUE BM BL
03 25/08/15 REVISED DA ISSUE BM BL
North Point:
Job No:
Dwg No:
Scale:
Issue:20150018 (A1)
Drawing Title:Architect: Project:
Lot 11 DP 835239PAMBULA NSW
PROPOSED SUPERMARKETServices Consultant:
NOTE: SYMBOLS ARE DRAWN IN THE CORRECT POSITION BUT ARE NOTSHOWN TO SCALE.
Int. App.AmendmentDateIssue
DRAWING NUMBER
COORDINATED REFERENCE DRAWINGS
MECH
STRUCT
ELEC
CIVIL
SERVICE
ARCH
ISSUE DATE
Client:
GOULBURN NSW 2580
Unit 122 Elizabeth Street
GREAT SOUTHERN
THIS DRAWING IS CONFIDENTIAL AND IS NOT TO BE REPRODUCED IN ANY FORM AS AWHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN AUTHORITY OF INSYNC SERVICESPTY. LTD. THIS DRAWING IS NOT TO BE USED PREJUDICIAL TO THE INTEREST OF INSYNCSERVICES PTY. LTD.THIS DRAWING CONTAINS PATENTS PENDING AND INTELLECTUAL PROPERTY OWNED BYINSYNC SERVICES PTY. LTD.© COPYRIGHT. ALL RIGHTS RESERVED
TM
Quality ISO 9001
Certified System
FS 581006
Suite 6.02, Level 689 York StreetSYDNEY NSW 2000Ph (02) 9262 3400Fax (02) 9262 3422A.C.N.: 150 234 870A.B.N.: 24 917 388 129
O Z T A LA R C H I T E C T S
DEVELOPMENTS Pty Ltd
DP
1007.29L/s
DP
1000.57L/s
DP
1004.29L/s
DP
1004.29L/s
DP
1004.29L/s
DP
1004.29L/s
DP
1004.27L/s
DP
1002.44L/s
DP
1004.82L/s
DP
1004.68L/s
DP
1005.25L/s
DP
1005.25L/s
DP
1005.25L/s
DP
1005.25L/s
CWCWCWCWCW
eCW
eCWeCW
eCWeCW
eCWeCW
eCWeCW
eCW
H
FHFH
FHFH
FHFH
FH
FH FH FH FH FH FH FH
CW CW CW CW CW CW CW
CW
100
100
100
100 100FH
FH
FH
FH
LOCATE AND CONNECT NEW COMBINED FIREHYDRANT AND POTABLE WATER SERVICE TOEXISTING AUTHORITY WATER MAIN LOCATED INMERIMBOLA STREET.
SUPPLY AND INSTALL FIRE HYDRANTBOOSTER ASSEMBLY WITH DOUBLECHECK DETECTOR BACKFLOWDEVICE. SUPPLY AND INSTALL COLD WATER
METER AND SITE CONTAINMENTREDUCED PRESSURE ZONE DEVICE.
GWSDSD
SDSD
SDSD
SDSD
VP VP CW
40--
VP
100--
40 40
100
100
100
100
100
2000L SUPERMARKETGREASE ARRESTOR.
eSD eSD eSD eSD eSD eSDSD
100
eSD
eSD
eSD
eSD
eSD
eSD
eSD
eSD
eSD
eSD
eSD eSD
eSMH
eSMHAUTHORITY SEWER MAIN.
DP
1006.02L/s
DP
1001.00L/s
DP
1501.63L/s
LOCATE AND CONNECT TOEXISTING SEWER MANHOLE.
SUPERMARKET
EXIS
TING
AUT
HORI
TY W
ATER
MAI
N
FIRE HYDRANT PUMP HOUSE LOCATED MINIMUM10M FROM BUILDING. PUMP HOUSE TO HAVEROOF INSTALLED TO PROTECT EQUIPMENT.DIESEL EXHAUST TO DISCHARGE AT HIGH LEVELOUT OF STREET SIDE WALL.INTERNAL DIMENSIONS:2300mm (WIDTH) x 5600mm (LENGTH) x 2100mm(HEIGHT)
NOTE:CIVIL CONTRACTOR TO CONNECTDOWNPIPES TO IN GROUND STORMWATERSYSTEM.
North Point:
Job No:
Dwg No:
Scale:
Issue:20150018 (A1)
Drawing Title:Architect: Project:
Lot 11 DP 835239PAMBULA NSW
PROPOSED SUPERMARKETServices Consultant:
NOTE: SYMBOLS ARE DRAWN IN THE CORRECT POSITION BUT ARE NOTSHOWN TO SCALE.
Int. App.AmendmentDateIssue
DRAWING NUMBER
COORDINATED REFERENCE DRAWINGS
MECH
STRUCT
ELEC
CIVIL
SERVICE
ARCH
ISSUE DATE
Client:
GOULBURN NSW 2580
Unit 122 Elizabeth Street
GREAT SOUTHERN
THIS DRAWING IS CONFIDENTIAL AND IS NOT TO BE REPRODUCED IN ANY FORM AS AWHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN AUTHORITY OF INSYNC SERVICESPTY. LTD. THIS DRAWING IS NOT TO BE USED PREJUDICIAL TO THE INTEREST OF INSYNCSERVICES PTY. LTD.THIS DRAWING CONTAINS PATENTS PENDING AND INTELLECTUAL PROPERTY OWNED BYINSYNC SERVICES PTY. LTD.© COPYRIGHT. ALL RIGHTS RESERVED
TM
Quality ISO 9001
Certified System
FS 581006
Suite 6.02, Level 689 York StreetSYDNEY NSW 2000Ph (02) 9262 3400Fax (02) 9262 3422A.C.N.: 150 234 870A.B.N.: 24 917 388 129
O Z T A LA R C H I T E C T S
DEVELOPMENTS Pty Ltd01 18/08/15 PRELIMINARY ISSUE BM BL
02 21/08/15 DA ISSUE BM BL
03 25/08/15 REVISED DA ISSUE BM BL
1:200
SW-01 03
DA ISSUE
INGROUND GROUND LEVELSERVICES AND SITEPLAN
N
SERVICES TO BE INSTALLED BELOW SLAB
Line of Vision
DP
1007.29L/s
DP
1000.57L/s
GO ABOVEGO ABOVE
DP
1004.29L/s
DP
1004.29L/s
DP
1004.29L/s
DP
1004.29L/s
DP
1004.27L/s
DP
1002.44L/s
DP
1006.02L/s
GO ABOVE
GO ABOVE
DP
1004.68L/s
GO ABOVE
DP
1005.25L/s
GO ABOVE
GO ABOVE
DP
1005.25L/s
GO ABOVE
DP
1005.25L/s
GO ABOVE
DP
1005.25L/s
GO ABOVE
GO ABOVE
GO ABOVE
GO ABOVE
GO ABOVE
GO ABOVE
GO ABOVE
DP
1001.63L/s
DP
1001.00L/s
North Point:
Job No:
Dwg No:
Scale:
Issue:20150018 (A1)
Drawing Title:Architect: Project:
Lot 11 DP 835239PAMBULA NSW
PROPOSED SUPERMARKETServices Consultant:
NOTE: SYMBOLS ARE DRAWN IN THE CORRECT POSITION BUT ARE NOTSHOWN TO SCALE.
Int. App.AmendmentDateIssue
DRAWING NUMBER
COORDINATED REFERENCE DRAWINGS
MECH
STRUCT
ELEC
CIVIL
SERVICE
ARCH
ISSUE DATE
Client:
GOULBURN NSW 2580
Unit 122 Elizabeth Street
GREAT SOUTHERN
THIS DRAWING IS CONFIDENTIAL AND IS NOT TO BE REPRODUCED IN ANY FORM AS AWHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN AUTHORITY OF INSYNC SERVICESPTY. LTD. THIS DRAWING IS NOT TO BE USED PREJUDICIAL TO THE INTEREST OF INSYNCSERVICES PTY. LTD.THIS DRAWING CONTAINS PATENTS PENDING AND INTELLECTUAL PROPERTY OWNED BYINSYNC SERVICES PTY. LTD.© COPYRIGHT. ALL RIGHTS RESERVED
TM
Quality ISO 9001
Certified System
FS 581006
Suite 6.02, Level 689 York StreetSYDNEY NSW 2000Ph (02) 9262 3400Fax (02) 9262 3422A.C.N.: 150 234 870A.B.N.: 24 917 388 129
O Z T A LA R C H I T E C T S
DEVELOPMENTS Pty Ltd01 18/08/15 PRELIMINARY ISSUE BM BL
02 21/08/15 DA ISSUE BM BL
03 25/08/15 REVISED DA ISSUE BM BL
1:100
SW-02 03
DA ISSUE
GROUND LEVELSTORMWATER SERVICESPLAN
N
SERVICES TO BE INSTALLED BELOW SLAB
Line of Vision
A= 70.0m²Q100= 5.25L/s
A= 70.0m²Q100= 5.25L/s
A= 70.0m²Q100= 5.25L/s
A= 70.0m²Q100= 5.25L/s
A= 62.3m²Q100= 4.68L/s
A= 97.2m²Q100= 7.29L/s
A= 21.7m²Q100= 1.63L/s
A= 7.6m²Q100= 0.57L/s
A= 6.8m²Q100= 0.51L/s
GO
GOGO
GO
GO
GO
GO
GO
GO
GO
GO
O/F
O/F
O/F
O/F
O/F
O/F
O/F
O/F
O/F
O/F
O/F
200mm HALF ROUND MAINROOF EAVES GUTTER.
600mm WIDE x 150mm DEEPMAIN ROOF BOX GUTTER.150mm DEEP SUMPREQUIRED.
450mm WIDE x 150mm DEEPSMALLER CATCHMENT BOXGUTTER. 150mm DEEP SUMPREQUIRED.
600mm WIDE x 150mm DEEPMAIN ROOF BOX GUTTER.150mm DEEP SUMPREQUIRED.
450mm WIDE x 150mm DEEPSMALLER CATCHMENT BOXGUTTER. 150mm DEEP SUMPREQUIRED.
600mm WIDE x 150mm DEEPMAIN ROOF BOX GUTTER.150mm DEEP SUMPREQUIRED.
GO
GO
GO
GO
GO
GO200mm HALF ROUND MAINROOF EAVES GUTTER.
A= 99.3m²Q20= 6.07L/s
A= 39.9m²Q20= 2.44L/s
A= 69.9m²Q20= 4.27L/s
A= 70.1m²Q20= 4.29L/s
A= 70.1m²Q20= 4.29L/s
A= 70.1m²Q20= 4.29L/s
A= 70.2m²Q20= 4.29L/s
200mm HALF ROUND MAINROOF EAVES GUTTER.
GOO/F O/F GO
O/F
GO
600mm WIDE x 200mm LONGx 400mm DEEP RAIN HEADWITH 100mm DOWNPIPE.
SPREADER FROM HALFROUNDGUTTER TO LOWER ROOF.
SPREADER FROM HALF ROUNDGUTTER TO LOWER ROOF.
200mm HALF ROUND MAINROOF EAVES GUTTER.
200mm HALF ROUND MAINROOF EAVES GUTTER.
North Point:
Job No:
Dwg No:
Scale:
Issue:20150018 (A1)
Drawing Title:Architect: Project:
Lot 11 DP 835239PAMBULA NSW
PROPOSED SUPERMARKETServices Consultant:
NOTE: SYMBOLS ARE DRAWN IN THE CORRECT POSITION BUT ARE NOTSHOWN TO SCALE.
Int. App.AmendmentDateIssue
DRAWING NUMBER
COORDINATED REFERENCE DRAWINGS
MECH
STRUCT
ELEC
CIVIL
SERVICE
ARCH
ISSUE DATE
Client:
GOULBURN NSW 2580
Unit 122 Elizabeth Street
GREAT SOUTHERN
THIS DRAWING IS CONFIDENTIAL AND IS NOT TO BE REPRODUCED IN ANY FORM AS AWHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN AUTHORITY OF INSYNC SERVICESPTY. LTD. THIS DRAWING IS NOT TO BE USED PREJUDICIAL TO THE INTEREST OF INSYNCSERVICES PTY. LTD.THIS DRAWING CONTAINS PATENTS PENDING AND INTELLECTUAL PROPERTY OWNED BYINSYNC SERVICES PTY. LTD.© COPYRIGHT. ALL RIGHTS RESERVED
TM
Quality ISO 9001
Certified System
FS 581006
Suite 6.02, Level 689 York StreetSYDNEY NSW 2000Ph (02) 9262 3400Fax (02) 9262 3422A.C.N.: 150 234 870A.B.N.: 24 917 388 129
O Z T A LA R C H I T E C T S
DEVELOPMENTS Pty Ltd01 18/08/15 PRELIMINARY ISSUE BM BL
02 21/08/15 DA ISSUE BM BL
03 25/08/15 REVISED DA ISSUE BM BL
1:100
SW-03 03
DA ISSUE
ROOF LEVELSTORMWATER SERVICESPLAN
N
SERVICES TO BE INSTALLED BELOW SLAB
Line of Vision