44
VAV700 Multi-functional air volume ow controller with integrated web server 1 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com Product description High-speed adaptive control system for variable control of room supply air and room exhaust air volume ows, particularly suitable for clean rooms and laboratories. The integrated dual port switch allows a simple and effective Ethernet-networking of volume ow controllers (supply air/ exhaust air) and fume hood controllers FC700 within the laboratory and the complete building. The parameterisation and the data access occur with a standard web browser. Native BACnet ® /IP with trendlog and intrinsic reporting are optional implemented. Modbus ® is supported as further eld bus systems. Extended requirements afford a radiator respectively a coo- ler as well as pressure maintenance of the room. Besides these performance features the multi-functional volume ow controller VAV700 balances all network-connected consu- mer loads and calculates the necessary room supply air re- spectively room exhaust air needed for the maintenance of the parameterised room air exchange (e. g. eightfold). A high-speed control algorithm compares the setpoint with the actual value measured by a differential pressure trans- mitter and controls the air volume quickly, precisely and steadily, independent of pressure uctuations in the duct system. The system data and setpoint values (volume ow, temperature, pressure, humidity, etc.) are freely program- mable and will be saved voltage fail-safe in the FLASH. Up to three freely congurable static differential pressure sensors allow the detection and regulation of the room pres- sure of two independent rooms besides the volume ow re- gulation. Up to four free slots allow a exible and cost-effective adjustment of the controlling respectively measuring task to the customer specic requirements. Operation and activation mode (setpoint setting) analogue, digital, BACnet ® , Modbus ® The multi-functional volume ow controller VAV700 is available in seven activation versions with the setpoint setting as the main distinctive feature. The following operation and activation modes are supported (depending on the version): Type Operation mode Activation mode VAV700 variable (VAV) constant (CAV) TCP/IP, Ethernet -IP Yes Yes Analogue 0(2) - 10 V Digital (1-3-level) -AD -AD Yes No No Yes BACnet, TCP/IP, Ethernet -BIP Yes Yes BACnet, MS/TP, RS485 -BM Yes Yes Modbus ® IP -MIP Yes Yes Modbus ® , RS485 -M Yes Yes Performance features Modular variable volume ow control system System data stored voltage fail-safe Integrated web server Simple Ethernet-networking with dual port switch Modular expandable by pluggable boards Parameterisation and fetch of all system values via standard web browser Up to three position independent static differential pressure sensors -100 to 300 Pa, freely congurable for exhaust air, supply air, room pressure Volume ow range 1:15 Patented maintenance-free measuring device with two ring chambers and self-cleaning effect Fast, predictive and adaptive control algorithm Fast, stable and precise control via direct activation of hysteresis-free actuator Suitable for supply air and exhaust air volume ow control in laboratories and clean rooms (consider a sufciently large room leakage) Adjustment of the volume ow 2 sec Closed loop control Analogue setpoint input 0(2) - 10 V DC/1 mA Analogue actual value outpur 0(2) - 10 V DC/10 mA Two freely programmable relays with potential free reverse contact Two (expandable) digital inputs for forced control V MIN , V MED , V MAX and damper = SHUT (CAV-mode). Additional temperature loop control for heating and/or cooling Integrated room balancing in network operation Internal plausibility monitoring of the sensor system Various extension moduls for digital in/out, analogue in/ out and eld bus Control mode after power failure is freely program- mable Integrated native BACnet ® (IP or MS/TP) with trendlog and intrinsinic reporting Supply voltage 24 V AC provided by customer or 230 V AC optional via internal transformer Round and rectangular version made of steel and PPs Product description Performance features

VAV700 Multi-functional air volume fl ow controller with ... *new... · Order code: volume fl ow controller with integrated web server [a] Type VAV700 Variable Air Volume Controller

Embed Size (px)

Citation preview

VAV700Multi-functional air volume fl ow controller with integrated web server

1 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

Product descriptionHigh-speed adaptive control system for variable control of room supply air and room exhaust air volume fl ows, particularly suitable for clean rooms and laboratories.

The integrated dual port switch allows a simple and effective Ethernet-networking of volume fl ow controllers (supply air/exhaust air) and fume hood controllers FC700 within the laboratory and the complete building. The parameterisation and the data access occur with a standard web browser. Native BACnet®/IP with trendlog and intrinsic reporting are optional implemented. Modbus® is supported as further fi eld bus systems.

Extended requirements afford a radiator respectively a coo-ler as well as pressure maintenance of the room. Besides these performance features the multi-functional volume fl ow controller VAV700 balances all network-connected consu-mer loads and calculates the necessary room supply air re-spectively room exhaust air needed for the maintenance of the parameterised room air exchange (e. g. eightfold).

A high-speed control algorithm compares the setpoint with the actual value measured by a differential pressure trans-mitter and controls the air volume quickly, precisely and steadily, independent of pressure fl uctuations in the duct system. The system data and setpoint values (volume fl ow, temperature, pressure, humidity, etc.) are freely program-mable and will be saved voltage fail-safe in the FLASH.

Up to three freely confi gurable static differential pressure sensors allow the detection and regulation of the room pres-sure of two independent rooms besides the volume fl ow re-gulation.

Up to four free slots allow a fl exible and cost-effective adjustment of the controlling respectively measuring task to the customer specifi c requirements.

Operation and activation mode (setpoint setting) analogue, digital, BACnet®, Modbus®

The multi-functional volume fl ow controller VAV700 is available in seven activation versions with the setpoint setting as the main distinctive feature. The following operation and activation modes are supported (depending on the version):

Type Operation modeActivation mode

VAV700variable

(VAV)constant

(CAV)TCP/IP, Ethernet -IP Yes Yes

Analogue 0(2) - 10 VDigital (1-3-level)

-AD-AD

YesNo

NoYes

BACnet, TCP/IP, Ethernet -BIP Yes Yes

BACnet, MS/TP, RS485 -BM Yes Yes

Modbus® IP -MIP Yes Yes

Modbus®, RS485 -M Yes Yes

Performance features

Modular variable volume fl ow control system System data stored voltage fail-safe Integrated web server Simple Ethernet-networking with dual port switch Modular expandable by pluggable boards Parameterisation and fetch of all system values via

standard web browser Up to three position independent static differential

pressure sensors -100 to 300 Pa, freely confi gurable for exhaust air, supply air, room pressure Volume fl ow range 1:15 Patented maintenance-free measuring device with two

ring chambers and self-cleaning effect Fast, predictive and adaptive control algorithm Fast, stable and precise control via direct activation of

hysteresis-free actuator Suitable for supply air and exhaust air volume fl ow

control in laboratories and clean rooms (consider a suffi ciently large room leakage) Adjustment of the volume fl ow ≤ 2 sec Closed loop control Analogue setpoint input 0(2) - 10 V DC/1 mA Analogue actual value outpur 0(2) - 10 V DC/10 mA Two freely programmable relays with potential free

reverse contact Two (expandable) digital inputs for forced control VMIN,

VMED, VMAX and damper = SHUT (CAV-mode). Additional temperature loop control for heating and/or

cooling Integrated room balancing in network operation Internal plausibility monitoring of the sensor system Various extension moduls for digital in/out, analogue in/

out and fi eld bus Control mode after power failure is freely program-

mable Integrated native BACnet® (IP or MS/TP) with trendlog

and intrinsinic reporting Supply voltage 24 V AC provided by customer or 230 V

AC optional via internal transformer Round and rectangular version made of steel and PPs

Product description ● Performance features

2 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

VAV700Multi-functional air volume fl ow controller with integrated web server

Order code: volume fl ow controller with integrated web server

[a] TypeVAV700 Variable Air Volume Controller

[b] Connection to BMS/fi eld bus module

IP Internal networking TCP/IP, Ethernet

AD Analogue/digital (expandable module EM10)

BIP Native BACnet®

BM Native BACnet®, MS/TP, RS485

MIP Modbus®, IP

M Modbus®, RTU, RS485

[c] Supply voltage0 24 V AC/30 VA externT Internes Netzteil 230 VAC/24 VAC/30 VA

[d] Sensor equipment with static differential pressure sensorsAll sensors are freely confi gurable as exhaust air, supply air, room pressure, duct pressure

1 1. Sensor -100...+300 Pa

2 1. Sensor -100...+300 Pa2. Sensor -100...+300 Pa

5 1. Sensor -100...+300 Pa3. Sensor -50...+50 Pa

5

VAV700 - BIP - T - 2

a b c d

Important:Specify air volume VMIN, VMAX respectively VCONST and mode of analogue activation 0 - 10 V DC or 2 - 10 V DC.Order additionally measuring device with damper and actuator (page 4). Order additionally optional expandable modules (page 3).

Ordering example: volume fl ow controller VAV700High-speed multi-functional variable balancing volume fl ow controller via BACnet® IP, 2 relays, with internal power supply 230 V AC, with 2 static differential pressure sensors (-100 - 300 Pa).

Make: SCHNEIDER Type: VAV700-BIP-T-2

VAV700Multi-functional air volume fl ow controller with integrated web server

3 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

Extension modules Remarks/Scope of delivery

EM102 analogue inputs, 2 analogue outputs, 2 digital inputs, 2 relay outputs

Suitable for conventional connection to the building management system (BMS)

EM20 4 analogue inputs, 4 analogue outputs General applications, actuator and valve activation (in preparation)

EM30 6 relay outputs General applications, actuator and valve activation (in preparation)

EM40 4 Triac outputs For valve activation, heating/cooling

EM50 12 digital inputs, opto coupler General applications, e.g. switchable air (2-step CAV)

EMNA Charging circuit with discharge circuit for battery backup 12 V DC

With battery backup 12 V DC/1,2 Ah in its own housing (in preparation)

EM10

Order code: Extension modules

Important:Maximal 4 extension modules are pluggable (4 free slots in the FC700). Please order separately according to the desired functionality.

Ordering example: Extension module1 x EM10 for conventional connection to the building management system with 2 analogue inputs, 2 analogue outputs, 2 digital inputs, 2 relay outputs.

Make: SCHNEIDER Type: EM10

--

--

--

--

--

4 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

VAV700Multi-functional air volume fl ow controller with integrated web server

Ordering example: damper with measuring device and actuator, round version, galvanised steelMeasuring nozzle with damper, DN 250, galvanised steel with damper blade seal, with rubber lip seal, without clad-ding, pipe/pipe, fast running actuator 3 s for 90 ° (fast direct drive SCHNEIDER).

Make: SCHNEIDER Type: DD-250-S-K-G-0-RR-1

Material Versionsmeasuring device

Available nominal diameter

Polypropylene (PPs) P MD, VD 110, 160, 200, 225, 250, 280 315, 355, 400PPs-el (electrically conductive) Pel MD, VD 110, 160, 200, 225, 250, 280 315, 355, 400Polyvinyl chloride (PVC) PV MD, VD 110, 160, 200, 225, 250, 280 315, 355, 400Galvanised steel S DD, KD, SD 100, 125, 160, 200, 225, 250, 280 315, 355, 400Stainless steel 1.4301 (V2A) V2 DD, KD, SD 100, 125, 160, 200, 225, 250, 280 315, 355, 400Stainless steel 1.4571 (V4A) V4 DD, KD, SD 100, 125, 160, 200, 225, 250, 280 315, 355, 400

DD-250-S-K-G-0-RR-1

VAV700-BIP-T-2

Order code: measuring device with damper and actuator, round version

Important:Volume fl ows and dimensions see page 28 to 31. Order Volume fl ow controller VAV700 and measuring device (MD, VD, DD, KD or SD) with damper always separately.Depending on the selected measuring device pay attention on suffi cient infl ow and outfl ow (> 2 x D).

[a] Measuring device MD Maintenance-free measuring device

VD Venturi nozzle

DD Measuring nozzle

KD Measuring cross with orifi ce ring

SD Measuring cross without orifi ce ring

[b] Nominal diameter DN [mm]

100bis400

100, 110, 160,

200, 225, 250, 280

315, 355, 400

[c] MaterialP Polypropylene (PPs), fi re retardent

Pel PPs-el (electrically conductive)

PVC Polyvinyl chloride (PVC)

S Galvanised steel

V2 Stainless steel 1.4301 (V2A)

V4 Stainless steel 1.4571 (V4A)

[d] Damper blade seal (0 = without)K with (stainless steel = standard), see [c]

[e] Rubber lip seal (0 = without)G with (only steel and stainless steel), see [c]

[f] Cladding (0 = without)D with cladding

[g] Pipe connectionsInfl ow Outfl ow Remarks

MM socket socket only PPs(el), PVC

FF fl ange fl ange PPs(el), PVC, steel, stainless steel

MF socket fl ange only PPs(el), PVC

FM fl ange socket only PPs(el), PVC

RR pipe pipe PPs(el), PVC, steel, stainless steel

[h] Fast running actuator

1 Fast Direct Drive SCHNEIDER 12 V, 3 Nm, 3 sec for 90°

8 Analogue actuator 24 V, 8 Nm, 4 sec for 90°

DD - 250 - S -K -G -0 - RR -1

a b c d e f g h

Order preferred Fast running actuator type 1 for VAV700 controller (better positioning).Order Fast running actuator type 8 (8 Nm) for nominal pipe diameter ≥ 280 mm.

VAV700Multi-functional air volume fl ow controller with integrated web server

5 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

Order code: measuring device with damper and actuator, rectangular version

DD-600-400-S-0-0-1

VAV700-BIP-T-2

[a] Measuring device MD Maintenance-free measuring device

DD Measuring nozzle

KD Measuring cross with orifi ce ring

SD Measuring cross without orifi ce ring

[b] Nominal width B [mm]

200bis

1000

200, 300, 400

500, 600, 700

800, 900, 1000

[c] Nominal height H [mm]

100bis400

100, 160, 200, 250, 300, 400

Designs: PPs, airtight shutting consider special nominal height (195, 360, 525, 690)

[d] MaterialP Polypropylene (PPs), fi re retardent

Pel PPs-el (electrically conductive)

PVC Polyvinyl chloride (PVC)

S Galvanised steel

V2 Stainless steel 1.4301 (V2A)

V4 Stainless steel 1.4571 (V4A)

[e] Damper blade seal (0 = without)K with (steel, stainless steel = standard), see [c]

[f] Cladding (0 = without)D with cladding

[g] Fast running actuator

1 Fast Direct Drive SCHNEIDER 12 V, 3 Nm, 3 sec for 90°

8 Analogue actuator 24 V, 8 Nm, 4 sec for 90°Stetiger Antrieb 24 V, 8 Nm, 3-5sec für 90°Use always with airtight design (with damper blade seal)

DD - 600 -400 -S -0 -0 -1

a b c d e f g

Order preferred Fast running actuator type 1 for VAV700 controller (better positioning).Order Fast running actuator type 8 (8 Nm) for nominal width ≥ 250 mm and nominal height ≥ 250 mm.

Important:Volume fl ows and dimensions see page 32 to 34. Order Volume fl ow controller VAV700 and measuring device (MD, VD, DD, KD or SD) with damper always separately.Depending on the selected measuring device pay attention on suffi cient infl ow and outfl ow (> 2 x D).

Material Versionsmeasuring device

Nominal widthsB [mm]

Nominal heightsH [mm]

Airtight versionspecial nominal heights

H [mm]Polypropylene (PPs) P MD 200 - 1000 100...400 195, 360, 525, 690PPs-el (electrically conductive) Pel MD 200 - 1000 100...400 195, 360, 525, 690Polyvinyl chloride (PVC) PV MD 200 - 1000 100...400 195, 360, 525, 690Galvanised steel S DD, KD, SD 200 - 1000 100...400 100...400Stainless steel 1.4301 (V2A) V DD, KD, SD 200 - 1000 100...400 100...400Stainless steel 1.4571 (V4A) V DD, KD, SD 200 - 1000 100...400 100...400

Ordering example: damper with measuring device and actuator, rectangular version, galvanised steelMeasuring nozzle with damper, width = 600 mm, height = 400 mm, galvanised steel, without damper blade seal, without rubber lip seal, without cladding, fl ange/fl ange, fast running actuator 3 s for 90 ° (fast direct drive SCHNEIDER).

Make: SCHNEIDER Type: DD-600-400-S-0-0-1

6 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

VAV700Multi-functional air volume fl ow controller with integrated web server

Block diagramPicture 1 shows the block diagram and the piping of the static differential pressure sensor with a maintenance-free measuring system.

All plugs of the sensors and actuators are pre-assembled and directly pluggable on the outside of the FC700-housing. That means an immense reduction of the assembly time and a simplifi cation of the commissioning. The high speed hysteresis-free actuator is operated in the proven direct drive mode and guarantees high control accuracy, highest durability and lifetime.

The pre-assembled CAT6/CAT7-cable for the Ethernet-networking will be plugged in the dual port switch and the system is ready for commissioning.

.

NetworkingThe networking offers maximum fl exibility and safety. The connection to the building management system offers the complete ventilation control and monitoring of all laborato-ries.A fl exible network-adjustment is simply realised by modu-lar extension cards. Besides the already integrated native BACnet® (IP or MS/TP) and Modbus® (IP or MS/TP) LON® is also available. The fi eld bus boards can be retrofi tted simply and at any time for all SCHNEIDER LabSystem products.

Internet technology with integrated web serverThe FC700 possesses an integrated web server for a simple data exchange and to improve the system security and it communicates via the Internet protocol TCP/IP. The operation and parameterisation is carried out by a laptop with a standard web browser. For this reason a simple circuit-entering into multivendor capable building management systems is guaranteed and the system is therefore prepared for all future applications.

Web browser operationThe internal web sites of the integrated web server can be visualised via a standard web browser. Adjustments and parameter can be simply changed. By using a standard web browser project-dependent fi les are no longer necessary to access the central building control system worldwide and at any time. The internal visualisation software VIS7000 reduces signifi cantly the system costs (data points) on the building management system level and can assume the building management functions if necessary.

Native BACnet®-IPThe building management system is provided with a multitude of data and therefore allows an optimsed requirement planning and process control. Native BACnet® (IP or MS/TP) guarantees a fast, simple and direct connection to the building management system without additional gateways. Our own BACnet® stack developed by SCHNEIDER guarantees maximum fl exibility. We support the read-out and storage of trendlog data as well as intrinsic reporting.

Simple wiring and fast commissioning

A simple and fast wiring and commissioning are the main parameters to reduce signifi cantly the installation and assembly costs. The dual port switch integrated on the CPU-board allows an easy daisy chain wiring with pre-assembled cables.

Picture 2: Daisy chain wiring

The wiring can be executed radially as well.Therefore the connection of the bus cable is omitted. All standard cables, e. g. sensor cable, actuator cable, etc. are pre-assembled and externally pluggable.

The commissioning, confi guration, diagnosis and visualisation of all system data (e. g. control time, damper position and setpoint settings) occur centrally through the network by a control unit via PC with standard web browser or decentrally via infrared interface of the graphic indication and operation panel.

VAV-controller

VAV700

Backupaccumulator

230 VAC Power lineDay/Night operationDigital In-/Outputs

Analogue In-/Output 0...10 VDC

Laptop

BACnet / LON-Network

Actuator

Measuring system

Feedback Potentiometer

Ethernet/IP

M

+ -

Picture 1: block diagram volume fl ow controller VAV700

General functional description

VAV700

Roomsupply air

Roomexhaust air

FC700

Controller

FC700

Controller

FC700

Controller

FC700

Controller

VAV700

VAV700Multi-functional air volume fl ow controller with integrated web server

7 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

Extension modules

Up to four free extension slots are available on the motherboard of the VAV700-controller. The controller can be easily and cost-effectively extended to further functions.

Customer specifi cally developed extension modules for special measuring, control and regulation functions on demand.

The following extension modules are available:

Extension module

Function

EM10 2 analogue inputs, 2 analogue outputs, 2 digital inputs, 2 relay outputs

EM20 4 analogue inputs, 4 analogue outputs (in preparation)

EM30 6 relay outputs (in preparation)EM40 4 Triac outputs for fan regulation,

heating/coolingEM50 12 digital inputs, opto couplerEMNA Charging circuit with discharge circuit

for battery backup 12 V DC (in prepa-ration)

EMSC Automatic sash closing module

Picture 4: Four free slots

Slot 6 (right) is always equipped with the sensor board and slot 5 with the CPU board. The slots 1 to 4 (left to right) can be freely equipped with the above listed extension modules.

General functional description

Building management system

The building management system (BMS) balances the air requirement of the complete building and can additionally run a plausibility check on all room controllers. Day/night-switch, visualisation of status and fault detections as well as actual values can be simply integrated. Remote main-tenance and fault remote diagnosis as well as an air con-sumption recording relating to the laboratory respectively to the fume hood with an individual accounting can be realised as well.

Up to three position independent sensors

For VAV700 up to three position independent static sensors (-100-300 Pa) are available and can be freely confi gured. Because of the high sensibility and resolution a volume fl ow range of 1:15 can be adjusted smoothly.

The function classifi cations exhaust air, supply air and room pressure to the static differential pressure sensors are freely confi gurable. Therefore the controller can be simply and fl exibly adjusted to all kind of applications. All data and measuring values are available at any time by the connected network.

Picture 3: Sensor board with three static differential pressure sensors

8 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

VAV700Multi-functional air volume fl ow controller with integrated web server

Heating and cooling of the laboratory

The heating and cooling of laboratories via appropriate heating and cooling registers can also be executed by FC700. The appropriate analogue and Triac outputs to regulate the heating and cooling valves will be made availabe by the extension modules EM10 to EM40. The power supply of the valves is provided by FC700 and the independent closed loop which is already implemented by default.

All measured room values e. g. temperatures, humidity, pressure are available as actual value via network.

Picture 5: Valve activation

Project planning

The project planning and parameterisation software PRO7000 is compatible to Windows and is used for a simple and fast commissioning. Parameterisation of devices can be executed from a central point for the entire room respectively the entire building. All data of the connected devices with integrated web server by SCHNEIDER can be indicated via standard web browser and entries can be done password protected.

Visualisation

All relevant data is available for the building management system (BMD) via the network and can be used for facility management functions. A better planning and utilisation of the ressources as well as a reduction of energy and operational costs are the significant characteristics.

Laboratory occupation plans, night setback and individual accounting of the air consumption data, energy-efficient operation as well as the safety improvement via remote maintenance and remote diagnosis of the fume hood controller and the volume flow controller for room supply air and room exhaust air are the outstanding advantages of the network technology with an integrated building management system (BMS).

The visualisation software module VIS7000 is the reasonable extension of PRO7000 and allows the simple creation of room graphics and a free alignment of single devices (e. g. fume hood, volume flow controller, etc.) in the room. This is a cost-efficient integral system solution with functions of the building management system.

The touchscreen controller PAD7000 developed by SCHNEIDER is especially adjusted to the requirements of the laboratory ventilation system and adopts the functionalities of the building management system. Special templates are freely disposable. Trendlog and intrinsic reporting are implemented as well. Networking via BACnet®

(IP or MS/TP) and LON® is supported.

Picture 6: Touchscreen Controller PAD7000

General functional description

VAV controller

VAV700

Backupaccumulator

230 VAC Power lineDay/Night operationDigital In-/Outputs

Analogue In/Output 0...10 VDC

Laptop

BACnet / LON-Netzwork

Actuator

Measuring system

Feedback Potentiometer

Ethernet/IP

M

+ -

EM204 Analogue inputs4 Analogue outputs

HeatingM

CoolingM

HumidifyM

DehumidifyM

-

+

VAV700Multi-functional air volume fl ow controller with integrated web server

9 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

Functional descriptionVolume fl ow measurement with a position inde-pendent static differential pressure transmitter

Using a suitable measuring device (maintenance-free measuring system (MD), Venturi measuring tube (VD), measuring tube (DD) or measuring cross (KD) the diffe-rential pressure is determined by a position independent differential pressure transmitter. The measurement is very accurate and stable over the entire measuring range of -100 - 300 pa , making it possible to regulate a volume fl ow range of upt to 1:15.

Unlike the thermo-anemometric measuring principle (dyna-mic sensor), air does not fl ow through the static differen-tial pressure transmitter, making it particularly suitable for measuring in dusty and contaminated (corrosive) media (its suitability should be checked in individual cases). The sui-tability of the thermo-anemometric measuring principle for such media is very limited, as the sensor becomes dirty or is affected by corrosive air and thus measurement may be very imprecise or inaccurate.

Volume fl ow setting VMIN, VMAX

The volume fl ow adjustment and parameterisation is done via laptop (with software PC2500) or via the web browser in the network. The demanded volume fl ow is entered as a numeric value. Thereby means:

Function Volume fl ow Reference signal w VMIN minimum 0(2) < w ≤ 10 V DCVMAX maximum w = 10 V DC

The allocation of the analogue demand signal w to the volu-me fl ow Vmin and Vmax illustrates the VAV-curve (variable operation mode).

Demand signal w (setpoint setting via analogue input A-In)

With the demand signal w (setpoint selection), the volume fl ow can be constantly switched between VMIN and VMAX, at which the following is always true: 0 m3/h = 0(2) V DC, VMAX = 10 V DC

The regulated volume fl ow actual value (A-Out) is availa-ble as 0(2) - 10 V DC output voltage (with extension board EM10) or via network. Various master/slave operating modes can be implemented with this signal.

Shield factor (C-value)

The shield factor is the design and geometry dependent constant of the used measuring device. The volume fl ow is calculated according to the following formula:

Parameterisation of the volume fl ow controller

The volume fl ow controller can be parameterised via laptop (with software PC2500) or web browser in the network as follows:

Function Signifi cance RemarksVMIN minimum

volume fl ow≥ shield factor B * 1,5 (rule of thumb)

VMAX maximumvolume fl ow

≤ shield factor B * 16 (ule of thumb)

Shield factor

measuring device constant

10 - 2000

Type default

controller confi gu-ration

analogue (VAV)digital (CAV)

Offset steady +/- value for constant load

+9990 m3/h to- 9990 m3/h

Typ default (setpoint value = analogue or digital)

The controller confi guration specifi es the operating mode (analogue or digital).

In network operation mode (variable volume fl ow control-ler = VAV) the volume fl ow is regulated linearly via network depending on the setpoint setting.

In analogue operating mode (variable volume fl ow con-troller = VAV) the volume fl ow is regulated linearly based on the analogue demand signal w (setpoint value via analogue input A-In).

In digital operating mode (constant volume fl ow controller = CAV) the volume fl ow is regulated in stages based on the digital inputs In1 and In2. Up to four different volume fl ows (VMIN, VMED and VMAX and VEMERGENCY) can be regulated. An analogue demand signal is not required.

In both operating modes (VAV and CAV) pressure fl ucta-tions in the duct system are recognised and automatically regulated.

Offset for integrating of constant loads

With the offset value a fi xed value is programmed (+9990 to - 9990 m3/h) that is added to the volume fl ow setpoint (+ offset = increases the volume fl ow setpoint, - offset decre-ases the volume fl ow setpoint). This makes it possible to integrate constant loads.

A constant difference between supply and exhaust air is therefore possible in master/slave mode. This function is particularly important in airtight rooms (e.g. clean rooms).

V = c . p.p

.V = air volumec = geometrical constant (shield factor)

= differential pressure

= air density

10 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

VAV700Multi-functional air volume fl ow controller with integrated web server

Function description ● Analogue operational modeNotes on controller dimensioning (dimensions and volume fl ow)

Due to measurement accuracy it must be ensured that at the minimum volume fl ow VMIN the fl ow velocity in the volu-me fl ow controller does not fall below 2 m/s.

Due to noise development, in laboratory applications it must be ensured that at the maximum volume fl ow VMAX the fl ow velocity in the volume fl ow controller does not exceed 7,5 m/s.

The volume fl ows VMIN, VMED, VMAX are freely programma-ble within the range 50 - 25.000 m3/h, but care must be taken to ensure suitable volume fl ow controller dimensions with regard to the volume fl ow range while at the same time taking the fl ow velocity into account.

Analogue operation mode Variable volume fl ow controller (VAV)

In variable volume fl ow operating mode the desired volume fl ow is predefi ned by a demand signal w (setpoint setting). The value range of the demand signal is 0(2)...10V DC.

The volume fl ow can be constantly controlled between VMIN und VMAX with the demand signal w, at which the following is always true:

0m3/h = 0(2) V DC 0(2) < VMIN ≤ 10 V DC VMAX = 10 V DCAlways note:1. Minimum control value VMIN = shield factor B * 1.52. Values < VMIN are not regulated3. With reference signal w < 0.3 V, the damper will be SHUT

In the example diagram 1 the volume fl ows VMIN = 300 m3/h and VMAX = 750 m3/h are programmed. The volume fl ow actual value signal (A-Out2) correlates with the regulated volume fl ow.The advanced setpoint at analogue output A1-Out is available and the value to be achieved by the actual value. An advanced setpoint is very effective for intercon-necting modules with their own operating time requiring a stable signal (e.g. control of frequency inverters, etc.).

The volume fl ow does not fall below VMIN, even when the demand signal w lies below the corresponding VMAX signal (in the example diagram 1: w = 4V).

Forced control via digital inputsThrough appropriate wiring of the digital inputs In2, In3 and In4 the functions described in table 1 can be executed di-rectly.

The wiring of the digital inputs is as follows: 0 = contact open (no current) 1 = contact closed (under current)

Digital inputsFunction In1 In2Analogue setpoint setting via A-In 0 0VMAX 0 0VMIN 1 0VEMERGENCY, damper SHUT/OPENON/OFF

0 1

VEMERGENCY, damper SHUT/OPENON/OFF

1 1

Contact open = 0, contact closed = 1.

The variable operation mode (analogue setpoint setting via A-in) is only possible, if the digital inputs are In1 = 0 and In2 = 0, which means that they are not under current (contact open). All functions are freely confi gurable under considera-tion of the digital inputs.

Table 1: Forced control during digital operational mode (CAV-mode)

VMAXVMIN

0 [m3/h]1000200 400 600 800

[V]

10

8

6

4

2

0

9

7

5

3

1

Lead

ing

sign

al w

(A-In

1)

[V]

10

8

6

4

2

0

9

7

5

3

1

Air

flow

vol

ume

actu

al v

alue

(A-O

ut1)

Variable operation Air flow volume

VMIN

VMAX

Diagram 1: Variable volume fl ow regulation (VAV)

Determination of the volume fl ow for laboratory ap-plications under consideration of the fl ow velocity v

Volume fl ow Flow velocity vVMIN v ≥ 1,5 m/sVMAX v ≤ 7,0 m/s

The fl ow velocity of the volume fl ow VMin has to be 1,5 m/s at least (lower control range) and must not exceed 7,0 m/s (Vmax) due to noise protection reasons.

VAV700Multi-functional air volume fl ow controller with integrated web server

11 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

Digital operating mode (CAV) ● Master-slave-sequence control

VAV700-ADMaster

Supply air VAV

Exhaust air VAV

Mdp

VAV700-ADSlave

Mdp

Leading signal w

Net

wor

k

Building Management System

T

Air flow volume actual value

DDC

Substation

Air volumeactual value

Picture 7: Block diagram: Master-slave-sequence control in VAV-mode

Digital inputsFunction In1 In2Analogue setpoint setting via A-In 0 0VMAX 0 0VMIN 1 0VEMERGENCY, damper SHUT/OPENON/OFF

0 1

VEMERGENCY, damper SHUT/OPENON/OFF

1 1

Contact open = 0, contact closed = 1.

Table 2: Forced control during digital operational mode (CAV-mode)

Diagram 2: Constant volume fl ow control (CAV)Digital operating modeConstant volume fl ow controller (CAV)

In constant volume fl ow operating mode (digital operating mode) the desired volume fl ow is controlled based on the digital inputs.

The available operating stages are shown in diagram 2 and table 2. 1 level, 2 level, 3 level or 4 level operation can be easily implemented by direct control of the digital inputs.

The volume fl ows are programmed to the values VMIN = 875 m3/h, VMED = 1750 m3/h and VMAX = 2150 m3/h. VMED must always lie between VMIN and VMAX. The volume fl ow actual value signal (A2-Out) correlates with the regulated volume fl ow.

The following is valid for the volume fl ow actual value:

SHUT = 0m3/h = 0(2) V DC 0(2) < VMIN ≤ 10 V DC VMAX = 10 V DC

Master-slave-sequence control with equal per-centage ratio in VAV operation

This master-slave sequence control is always used if the room pressure must be maintained at an equal percentage ratio of supply and exhaust air. Suffi cient replacement fl ow of the difference between the supply and exhaust air must be ensured in this operating mode.

The master controller is programmed with the volume fl ow values VMIN and VMAX and the demand signal w is added on directly. The volume fl ow actual value of the master con-troller provides the demand signal for the slave controller, which can be programmed with other VMIN and VMAX volu-me fl ow values depending on the application.

If the master controller is mounted in the supply air and the slave controller in the exhaust air and positive (+) room pressure is required, the slave controller must be program-med with the lower percentage volume fl ow values VMIN and VMAX in relation to the master controller.

If negative (-) room pressure is required, the slave control-ler must be programmed with the lower percentage volume fl ow values VMIN and VMAX in relation to the master con-troller. Sample settings for master-slave controllers:

Slave (+) Master Slave(-)VMIN 240 300 360VMAX 600 750 900

The master slave sequence control applies for both equal percentage ratio and constant difference between supply and exhaust air. The demand signal w (A-In) is added on to the master controller and the volume fl ow actual value A1-Out (with extension module EM10) provides the demand signal for the slave controller.

This ensures that the slave controller always follows the master controller. For safety reasons, master/slave se-quence control must always be given preference over par-allel control.

VMAXVMIN

0 [m3/h]2500500 1000 1500 2000

Function In1 In2 [V]

10

8

6

4

2

0

9

7

5

3

1

Air

flow

vol

ume

actu

al v

alue

(A-O

ut)

Air flow volume

VMAX

VMAX 0 0

VMIN

VMIN 1 0

SHUTSHUT 0 1VEMERGENCY 1 1

DamperSHUT

12 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

VAV700Multi-functional air volume fl ow controller with integrated web server

VMAXVMIN

0 [m3/h]1000200 400 600 800

[V]

10

8

6

4

2

0

9

7

5

3

1

Lead

ing

sign

al w

(A-In

)

[V]

10

8

6

4

2

0

9

7

5

3

1

Air

flow

vol

ume

actu

al v

alue

(A-O

ut)

Air flow volume Master

VMIN

VMAX

VMAXVMIN Air flow volume Slave(-)

VMAXVMIN Air flow volume Slave(+)

Diagram 3: Sequence control (master-slave) in equal percentage ratio

Master-Slave sequence control

VMAXVMIN

0 [m3/h]1000200 400 600 800

[V]

10

8

6

4

2

0

9

7

5

3

1

Lead

ing

sign

al w

(A-In

)

[V]

10

8

6

4

2

0

9

7

5

3

1A

ir flo

w v

olum

e ac

tual

val

ue (A

-Out

)

Air flow volume Master

VMIN

VMAX

VMAXVMIN Air flow volume Slave(-)

VMAXVMIN Air flow volume Slave(+)

constant difference

Supply-/Exhaust

Diagram 4: Sequence control (master-slave) with con-stant difference

In the sample settings, the volume fl ow values VMIN und VMAX of the slave (+) controller were programmed to -20% (negative room pressure) in relation to the volume fl ow va-lues of the master controller. For negative room pressure the volume fl ow values VMIN and VMAX of the slave (-) con-troller must be programmed to +20 % in relation to the volu-me fl ow values of the master controller.

The equal percentage ratio between supply and exhaust air is maintained throughout the entire volume fl ow range of VMIN to VMAX.

Master-slave sequence control with constant difference in VAV operating mode (analogue ope-rating mode)

This form of master/slave sequence control is used when room pressure with a constant difference between supply and exhaust air is required. This operating mode is selected for airtight rooms (e.g. clean rooms).

The master controller is programmed with the volume fl ow values VMIN and VMAX and the demand signal w (A8-in) is added on directly. The volume fl ow actual value (A2-out) of the master controller provides the demand signal for the sla-ve controller, which is programmed with the same volume fl ow values VMIN and VMAX, depending on the application.

In addition, the offset is also programmed in the slave con-troller. If the master controller is mounted in the supply air and the slave controller in the exhaust air and positive (+) room pressure is required, the slave controller must be pro-grammed with a negative offset.

If negative (-) room pressure is required, the slave controller must be programmed with a positive offset. Sample settings for master-slave controllers:

Slave (+) Master Slave(-)VMIN 300 300 300VMAX 750 750 750Offset -150 0 +150

In this example, the volume fl ow values VMIN and VMAX of the slave (+) controller and the slave (-) controller were pro-grammed with the volume fl ow values of the master con-troller. For negative room pressure the offset of the slave (-) controller must be programmed with +150 m3/h.

The constant difference between supply and exhaust air is maintained over the entire volume fl ow range of VMIN to VMAX.

Master-slave sequence control in CAV operating mode (digital mode)

In CAV operating mode the digital inputs of the master con-troller are wired to control the different operating stages (see table 3). The volume fl ow actual value A1-Out (with ex-tension board EM10) of the master controller provides the demand signal for the slave controller.

DDC/BMS control

If the master controller is controlled via a DDC/BMS (de-mand signal w or digital control) the volume fl ow actual va-lue of the slave controller can be added on as feedback and therefore used to monitor the functioning of both volume fl ow controllers (master and slave).

VAV700Multi-functional air volume fl ow controller with integrated web server

13 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

Multi functional applications in analogue or network operating mode • Heating and/or cooling

Volume fl ow controller network operating modes

The variable volume fl ow controller VAV700 is especial-ly developed for the networked operation and possesses different operating modes which can be confi gured via the network. The following controller types are implemented :

Variable volume fl ow controller 2-level constant volume fl ow controller Balancing volume fl ow controller Room volume fl ow differential controller

Multi-functional applications in the network operating mode (BACnet, Modbus®)

Besides the on the previous pages described classical vo-lume fl ow controller operating modes e. g. variable volume fl ow controller, 3-level constant volume fl ow controller, ba-lancing volume fl ow controller and room volume fl ow dif-ferential controller the following additional multi-functional applications are implemented on the VAV700:

Actual value collection of room pressures Own temperature control loop for heating and/or

cooling Own pressure cascade control loop

Via the available extension modules any customer specifi c applications can be cost-effectively implemented.

Actual value collection of room pressures

The volume fl ow controller VAV700 has up to two free static differential pressure transmitter -100 - 300 Pa which can be freely confi gured e. g. for a pressure cascade control loop or for measuring of room pressures.

Additionally, any analog values 0 (2) ... 10 VDC can be con-nected to the analog inputs of the expansion modules (eg EM10) and are available as BACnet objects on the network.

The PICS-list (Protocol Inplementation Conformance State-ments) for BACnet® applications can be requested or down-loaded from our web sitewww.schneider-elektronik.com

14 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

VAV700Multi-functional air volume fl ow controller with integrated web server

Extension modules

The motherboard of the FC700 controller possesses up to four free extension slots for special functions. The controller can be arbitrarily extended to further functions besides the sash closing function (extension module EMSC).

Custom made extension modules for special measuring,

Extension modules

Functionality Description

EM10 In- and outputs Suitable for general applications:2 analogue inputs Measuring of temperature, humidity, pressure2 analogue outputs Building management system connection, volume fl ow

controller regulation, valve regulation2 digital inputs Building management system connection, regulation2 relay outputs Building management system connection, valve

regulation (2-point), status report

EM20 In- and outputs Suitable for general applications:(in preparation) 4 analogue inputs Measuring of temperature, humidity, pressure

Analogue room balancing4 analogue outputs Building management system connection, volume fl ow

controller regulation, valve regulation

EM30 Outputs Suitable for general applications:(in preparation) 6 relay outputs Building management system connection, valve

regulation (2-point), status report

EM40 Outputs Suitable for valve regulation:4 Triac outputs Direct regulation of heating and cooling valves (2-point)

EM50 Inputs Suitable for switchable extraction and alarm:12 digital inputs, opto coupler 2 steps constant air volume, alarm, status report

EMNA Special module Suitable for external battery backup:(in preparation) Charging circuit with discharge circuit for

battery backup 12 V DCThis module is required for an optional external battery backup 12 V DC.

controlling and regulation functions can be easily and cost-effectively developed.

The following extension modules are available:

VAV700Multi-functional air volume fl ow controller with integrated web server

15 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

Room plan 1 (standard) ● fume hood controller FC700 with TCP/IP-networking via Ethernet

To more Laboratories

FC

FUME HOOD #1

VAV700-IP

Room supply airflow control Room exhaust

airflow control

FC

FUME HOOD #2

Mdp

FC

FUME HOOD #3

VAV700-IP

Mdp

Cable type: CAT 6Building Management System

Cab

le ty

pe:

IY(S

t)Y 1

x2x0

,8

Notes:

FC700-IP = Fume hood controller, fully variable, with Internet Protokoll TCP/IP

RMC700 = Room management controllerDay/Night operation (optional), Status display

VAV700-IP = High speed variable airflow controller VAV, with Internet Protokoll TCP/IP

24 VAC = 24 VAC external voltage for VAV700-IPand RMC700

Attention! Ethernet-Network cable must be wired with CAT6 cable.Do not exceed the maximum cable length.

ETHERNET TCP/IP

24 VAC

24 VAC

ETHERNET TCP/IP

Optional:Room management controller RMC700

24 VDC

Modbus RS485

Tagbetrieb

RMC700

Tag Nacht

Notfall I/O

Ein/Aus

Isttemperatur: 21 °C 75 % rF

ETHERNET TCP/IP

The room plan 1 shows the networking by default with the Internet protocol TCP/IP via Ethernet. Due to the high data transfer rate it is possible to network any number of sub-scribers. The response time of the linked subscribers (e. g. room supply volume fl ow controller) is suffi ciently secured even during heavy data traffi c.

WiringThe integrated dual port switches of VAV700 and FC700 al-low a simple and fast daisy chain wiring with pre-assembled CAT6/CAT7 patch cables and therefore reduce the assem-bly and installation costs signifi cantly. Therefore the con-necting of the bus cable is omitted and all standard cables like sensor cable, actuator cable, etc. are pre-assembled and pluggable on the outside.

Balancing

The volume fl ow controller VAV700-IP balances the re-quired room supply air and room exhaust air independent-ly according to the laboratory exhaust air and controls the calculated value self-suffi ciently. If the added exhaust air of the fume hoods is not suffi cient for the maintenance of a defi ned room air exchange rate (e. g. room air exchange rate = quadruple or octuple) the room exhaust air volume fl ow controller raises the volume fl ow as long as the reque-sted room air exchange rate is reached.

The room supply air volume fl ow controller follows the total room exhaust air, reduced by a fi xed value or a percentaged reduction. Therefore the required low pressure in the labo-ratory according to DIN 1946, part 7 is guaranteed for all operating conditions. The supply of the volume fl ow control-ler with 24 V AC has to be provided by the customer.

The optional room management controller RMC700 can be connected directly to the network via LON® or Modbus® and regulates e. g. day/night operation per room. Status and operation information (temperature, humidity, pressure) can be indicated additionally on the graphic display.

Commissioning via Internet protocol TCP/IP

For a simple data transfer and to improve the system se-curity VAV700-IP has an integrated web server and com-municates via the Internet protocol TCP/IP by default. The operation, parameterisation and commissioning occur via laptop with standard web browser.

The commissioning can occur decentrally for all linked sub-scribers via a standard web browser or directly via infrared interface at the fume hood with a laptop and the installed software PC2500.

The internal websites of the integrated web server can be visualised worldwide with a standard web browser. Therefore a simple remote maintenance can be realised. The internal visualisation software VIS7000 reduces signifi cantly the system costs (data points) on the building management system level and can assume the building management functions if necessary. Extension modules

Any function extensions can be simply and modulary realised by the subsequently pluggable extension modules. Besides the sash closing function (extension module EMSC) miscellaneous input and output modules (analogue and digital) for measuring value collection (temperature, humidity) respectively for controlling heating and cooling valves as well as fi eld bus modules (LON®) are available. The controller can be arbitrarily extended to further functions besides the sash closing function (extension module EMSC).

All extension modules are embedded in the networking and provide the data and measuring values via the Internet protocol TCP/IP.

16 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

VAV700Multi-functional air volume fl ow controller with integrated web server

Room scheme 2 ● Volume fl ow controller VAV700/FC700 with BACnet-IP networking and room visualisation

The room plan 2 shows a networking with native BACnet®-IP protocol. The BACnet®-IP protocol is increasingly esta-blished as de facto standard for the building automation. Due to the high data transfer rate it is possible to network any number of subscribers. The response time of the linked subscribers (e. g. room supply volume fl ow controller) is suffi ciently secured even during heavy data traffi c.

Wiring

Refer to description of room plan 1.

Balancing

Refer to description of room plan 1.

Native BACnet®-IP

A BACnet® stack implemented in the 700 product series allows the direct communication with the business management system RMS700 by SCHNEIDER. Gateways are not required anymore and due to the direct implementation of the BACnet® stack to the CPU board the term „native BACnet®“ has been created.

BACnet® is a multivendor capable interface for management systems and allows the simple implementation and visualisation of functions.

Extension modules

Refer to description of room plan 1.

List of objects and object typesThe PICS list (Protocol Implementation Conformance Statements) for BACnet® applications can be required or downloaded from our website: www.schneider-elektronik.com.

Room visualisation

The project planning and parameterisation software PRO7000 is compatible to Windows® and is used for a simple and fast commissioning. Parameterisation of devices can be executed from a central point for the entire room respectively the entire building. All data of the connected devices with integrated web server by SCHNEIDER can be indicated via standard web browser and entries can be done password protected.

The visualisation software module VIS7000 is the reasonable extension of PRO7000 and allows the simple creation of room graphics and a free alignment of single devices (e. g. fume hood, volume flow controller, etc.) in the room. This is a cost-efficient integral system solution with functions of the building management system.

The touchscreen controller PAD7000 developed by SCHNEIDER is especially adjusted to the requirements of the laboratory ventilation system and adopts the functionalities of the building management system. Special templates are freely available. Trendlog and intrinsic reporting are implemented as well.

Bild 8: Touchscreen Controller PAD7000

To more Laboratories

FC

FUME HOOD #1

VAV700-BIP

Room supply airflow control

Room exhaust airflow control

FC

FUME HOOD #2

Mdp

FC

FUME HOOD #3

VAV700-BIP

Mdp

Cable type: CAT 6Building Management System

Notes:

FC700-BIP = Fume hood controller, fully variable, with BACnet-IP protocol

RMS700-BIP = Room Management and Information system,Touchscreen graphik display with BACnet-IP protocol

VAV700-BIP = High speed variable airflow controller VAV, with BACnet-IP protocol

24 VAC = 24 VAC external power supply for VAV700-BIP

Attention! Ethernet-Network cable must be wired with CAT6 cable.Do not exceed the maximum cable length.

BACnet-IP

24 VAC

24 VAC

BACnet-IP

BACnet-IP

24 VDC

OptionalRoom Management and Information System RMS700-BIP

VAV700Multi-functional air volume fl ow controller with integrated web server

17 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

Extended applications

To more labrooms

FC

Fume hood #1

VAV700-IP

Supply VAV Exhaust VAV

FC

Fume hood #2

Mdp

FC

Fume hood #n

VAV700-IP

Mdp

Cable type: CAT 6

Building Management System

ETHERNET TCP/IP

24 VAC

24 VAC

ETHERNET TCP/IP

ETHERNET TCP/IP

EM204 Analog inputs4 Analog outputs

Act.Set

Roomtemperature

Set% rH

Roomhumidity

Act.

HeatingM

CoolingM

HumidifyM

DehumidifyM

-

+

+-

p

EM306 Relay outputs

Louver

M

Room light

Lab alarm(e.g. gas)

Lab alarm(e.g. water)

Room controller functionsEach fume hood controller FC700 can be upgraded with 4 boards at most with the universal extension modules EM, so that complete room controller functions can be re-alised. A permanently enhanced variety of modular boards is available for the individual process application. With the extension modules EM10 to EM50 the following functions can be realised:

Room temperature controlling with setpoint setting

Room humidity controlling with setpoint setting

Activation of heating and cooling valves for static radiators respectively cooling ceiling or fan coils (with EM30, 6 relay outputs for fan activation, step 1 to 3).

Activation of the demand-based room illumination

Activation of the curtains (automatic shading)

Alarm detection (e. g. gas alarm, water alarm)

Extinguish functions

With this technology sustainable and energy-effi cient offi ce and functional buildings can be realised which can be certifi ed according to LEED or DGNB.

All relevant data are available via TCP/IP, BACnet®/IP over Internet or for a central building management system. Decentral closed loops adopt the independent room controlling functions without intervention of the building management system which mainly dynamically visualises the processes and rooms.

The room pressure maintenance of laboratory and clean rooms as well as the energetic capacity accounting is easily realised.

The visualisation software module VIS7000 allows the simple creation of dynamic room graphics and a clear exposition on the PC. This is a cost-efficient integral system solution with functions of the building management system.

PAD7000 adopts the functionalities of a building management system.

18 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

VAV700Multi-functional air volume fl ow controller with integrated web server

Room scheme 3 ● Volume fl ow controller VAV700 with analogue input and laboratory controller LCO500

NETWORK (LON, BACnet or Modbus)

FC

FUME HOOD #1

VAV700-AD

Room supply airVAV

Room exhaust airVAV

FC

FUME HOOD #2

Mdp

FC

FUME HOOD #9

VAV700-AD

Mdp

Cable type: IY(St)Y 4x2x0,8

Laboratory ControllerLCO500

Ain1Din1T/N

Ain2Din2T/N

Ain3Din3T/N

Aout124 VDC

Aout224 VDC

Optional Fieldbus module:LON, BACnet or

Modbus

Building Management System

Ain9Din9T/N

……...

Option:Power supply24V DC/75 W

Power line230 VAC +-10%

Notes:

FC = Fume hood controller, fully variable, analogueoutput 0(2)...10 VDC

LCO500 = Laboratory controller, 10 analogue inputsRMC700 = Room management controller (option)

Day-/Night operation, status displayVAV700-AD = Fast variable multi-functional air volume flow

controller, with analogue input 0...10 VDCAin1 … Ain10 = 10 analogue inputs 0...10 VDCDin1 … Din10 = 10 digital inputs T/N = Day/Night operation fume hoods (room control)

wired as parallel day/night control via aditional connector board

Aout1 … Aout8 = 8 analogue outputs 0...10 VDC24 VDC = 24 VDC supply voltage for air volume

controller VAV700-AD

Attention! Observe cable specifications of the connected network. Don´t exceed max. cable lenght.

FUME HOOD #3 bis #8

Ain10

Option:Room Management Controller RMC700

24 VDC

Tagbetrieb

RMC700

Tag Nacht

Notfall I/O

Ein/Aus

Isttemperatur: 21 °C 75 % rF

NET

WO

RK

(LO

N o

r Mod

bus)

Cable type: IY(St)Y 4x2x0,8 Cable type: IY(St)Y 4x2x0,8

The room plan 2 shows the connection of the volume fl ow controller VAV700-AD (analogue input) with up to 9 fume hoods (Ain 1 to Ain 9) with the laboratory controller LCO500. The laboratory controller regulates up to eight freely con-fi gurable volume fl ow controllers for room supply air/room exhaust air (Aout1 to Aout8). The internal switching power supply (optional) provides a maximum of 8 volume fl ow con-trollers with supply voltage 24 V DC which simplifi es the planning and the implementation is more cost-effective.

The analogue inputs Ain1 to Ain10 will be summed-up and can be combined to miscellaneous groups on the analo-gue outputs Aout1 to Aout8. Thereby any confi gurations are possible. Therefore it is possible to regulate independently e. g. several laboratories (max. 8) with one room supply air volume fl ow controller each and 10 fume hoods at most. Like it is shown in room plan 2 an additionally room exhaust air can be confi gured besides the room supply air. Each room exhaust air volume fl ow controller requires an analo-gue input (recirculation actual value room exhaust air).

Networking with building management system

A cost-effective and simple connection to the multivendor capable building management system (BMS) can be reali-sed via the network by an optional fi eld bus module (LON®, BACnet® or Modbus®).

Via the BACnet® bus board a native BACnet® can be re-alised which means that no gateways are necessary to possibly implement protocols and data. Therefore a full compatibility as well as a simple and fast commissioning is guaranteed.

With the extension of the digital fault warning inputs (optio-nal) all fault warnings of the connected fume hoods will be gathered and sent via network to the building management

system (BMS).

The laboratory controller LCO500 fulfi lls the functionality of a DDC-substation respectively a router.

The following data are available as network variables in the business management system:

readout of the exhaust air actual values of the fume hoods Ain1 to Ain10 readout of the summed-up room balances

(room supply air/room exhaust air) setpoints for 8 analogue outputs readout of the 8 digital outputs setting of the 8 relay outputs

Therefore special functions like day/night switchover of the fume hood controller, regulation and monitoring of the room control unit, temperature regulation as well as controlling of the heating and cooling valves are simply realisable.

Extended functions like remote maintenance are realisable as well. By day/night switchover, retrieval and comparison of the individual exhaust air actual values each fume hood can be checked regarding this function.

The optional room management controller RMC700 can be connected directly via LON® or Modbus® to the network and regulates e. g. day/night operation per room. Status and operation information (temperature, humidity, pressure) can be additionally indicated on the graphic display.

The laboratory controller LCO500 combines the analogue technology with the advantages of the bus technology and offers a cost-effective, fl exible and secure regulation and vi-sualisation per room via the building management system.

For detailed description please refer to data sheet LCO500.

VAV700Multi-functional air volume fl ow controller with integrated web server

19 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

Connection via safety transformer

Master VAV700-AD

Leading signal w0(2)...10V DC

GND

24V AC Supply

N L

Slave

N LAir flow volume actual value

0(2)

...10

V D

C

GN

D

Air flow volume actual value

0(2)...10V DC

GND

from Laboratory controller LCO500, DDC/GLT

toLCO500,

DDC/GLT

10...

20 V

Am

ax. 1

0 V

A

VAV700-AD

VAV operation (analogue)

VAV operation (analogue)

Connection diagram VAV operating mode

Connection diagram VAV operating mode

The analogue lead signal is connected by the transmitter (e.g. temperature sensor, setpoint device) respectively by the laboratory controller LCO500, the DDC or BMS. The vo-lume fl ow actual value signal of the master-VAV generates the lead signal of the slave-VAV.

The volume fl ow actual value signal of the slave-VAV can be connected as a feedback signal to the laboratory controller LCO500, the DDC or BMS, whereby the functionality of the complete master-slave-sequence control can be checked. A forced control is possible as well (please refer to table 1 on page 9). The allocation digital input/function is freely programmable.

Connection diagram CAV operating mode

The different CAV operating steps are apparent in table 2 on page 10. The volume fl ow Vmax is adjusted if both digital inputs (In1 and In2) are not under current, which means that the contacts are open. The current feed of In1 adjusts Vmin and of In2 adjusts VEmergency. The allocation digital input /function is freely programmable.

The master is adjusted during CAV operating mode and the slave during VAV operating mode. The slave follows the ac-tual value of the master. The feedback of the volume fl ow actual value signal to the laboratory controller LCO500 or DDC/BMS is possible as well.

Connection diagram network operating mode

The volume fl ow controller VAV700 is designed as a net-work controller by default. The system is completely inde-pendent by direct connection with the fume hood controller FC700. The internal communication runs via Modbus® IP or via BACnet®-IP respectively LON® on demand. All relevant data and parameters are exchanged on a suffi cient rate and the balancing of room supply air respectively the required room exhaust air to maintain the necessary room air ex-change rate is automatically calculated and adjusted via the connected volume fl ow controllers VAV700.

The integrated Ethernet-dual port switch allows a fast and cost-effective daisy-chain-wiring with pre-assembled ca-bles. The commissioning and parameterisation of all con-nected devices (FC700, VAV700, etc) are carried out from an arbitrary central point.

All relevant data like actual values and parameterised set-points are available for the BMS connected to the network.

Connection via safety transformer

Master

24V AC supply

N L

Slave

N LAir flow volume actual value

0(2)

...10

V D

C

GN

D

Air flow volume actual value

0(2)...10V DC

GND toLCO500,DDC/GLT

10...

20 V

Am

ax. 1

0 V

A

VAV700-AD CAV operation (digital)

VAV operation (analogue)

In1

In2

Operating modes CAV

VAV700-AD

Connection diagram CAV operating mode

Connection diagrams

Connection via safety transformer

Master

24V AC Suppply

N L

Slave

N L

toLCO500,DDC/GLT

10...

20 V

Am

ax. 1

0 V

A

VAV700-IP VAV operation (Network)

VAV700-IP

from Laboratory controller LCO500, DDC/GLT

VAV operation (Network)

TCP/

IP-E

ther

net

TCP/

IP-E

ther

net

TCP/IP-Ethernet

Dua

l-Por

t-Sw

itch

Dua

l-Por

t-Sw

itch

Connection diagram network operating mode

20 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

VAV700Multi-functional air volume fl ow controller with integrated web server

BACnet®-cable specifi cations (MS/TP, RS485)

In a BACnet®-network (MS/TP, RS485) is only daisy-chain-wiring allowed (no free topology, like LON®)

MS/TP (master slave/token-passing)

The master slave/token passing-protocol has been develo-ped by ASHRAE and is only available for BACnet®.

The connection to the fi eld bus occurs via the cost-effective interface EIA RS 485. MS/TP can be operated in a pure ma-ster slave-mode, with token delivery between equal nodes (peer to peer token passing methods) or in a combination of both methods.

EIA RS 485 standard

The EIA RS 485 standard defi nes a bidirectional bus sys-tem with up to 32 participants. Given that several transmit-ters work on a common wire, it has to be guaranteed by a protocol that maximum one data transmitter is active at any time (e. g. MS/TP). All other transmitters have to be in a high-resistance condition during this time.

The ISO-standard 8482 standardises the cable topology with a maximum length of 500 m. The participants have to be connected to this daisy-chained bus cable ( line topolo-gy) via a branch line with a maximum length of 5 m. A cable termination with termination resistors (2 x 120 Ohm) on both ends is basically necessary, to avoid refl ections.

If no data transfer takes place (data transmitter inactive) a defi ned resting level should be adjusted on the bus system. This can be achieved by connecting wire B over 1 k Ohm to ground (pull down) and wire A over 1 k Ohm to + 5 V DC.

During installation each wire of the twisted pair (A and B) has to be necessarily applied alone. The correct polarity of the twisted pair has to be necessarily regarded because a false polarity causes the inversion of the data signals. Espe-cially in case of diffi culties in connection with the installation of new end devices each failure detection should begin with checking the bus polarity.

Generally recommended is the laying of daisy-chained shielded wires and to ground the shielding one-sided (GND).

Network cable specifi cations ● BACnet® ● Modbus®

VAV700Multi-functional air volume fl ow controller with integrated web server

21 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

Network extension in bus and daisy chain-struc-ture

The bus cable is laid in one string. The nodes are connected via short branch line (maximum 5 m).

For a safe transmission in networks with bus/daisy chain topology the following issues have to be regarded:

The bus wire has to be connected to bus terminator at both ends (R1 = R2 = 120 Ω)

The second terminator is necessary in either case

The maximum cable length of the branch lines must not exceed 5 m

The maximum cable length is 500 m

Maximum 32 participants can be connected to a bus /daisy chain- structure

Picture 10 shows the bus/daisy chain topology of EIA RS 485 standards with the maximum cable length.

Table 3 specifi es different cables suitable for EIA RS 485 standard.

Table 3: Specifi cations of different cable types

All cables have to be shielded and the shield has to be grounded (GND).

Picture 10: EIA RS 485 in bus/daisy chain to-pology

EIA RS 485 in bus/daisy chain topologyCable types Manufac-

turerConductor diameter

[mm]

AWG Conductor cross section

[mm²]

Rloop Ω/km

max. conductor length of bus cable [m]

Li2YCYPiMF Lapp 0,80 20,4 0,503 78,4 500JY(St)Y 2 x 2 x 0,8shielded

miscella-neous

0,80 20,4 0,503 73 300

9843 paired Belden 24 78,7 500FPLTC222-005 Northwire 22 52,8 400EIB-YSTY Diverse 1,0 0,80 31,2 500

Network cable specifi cations ● BACnet® ● Modbus®

max. 500 m

EIA RS 485 in Bus- / Line topology(daisy chain)

Maximum distance between busterminator: 500 m Maximum length of stub line: 5 m Use always drilled shielded cable. Only bus-/ line topology allowed.

max. 5 m

120

120

1 k

1 k

+5V

GND

Wires drilled.Cable shielded.

A

B

A B

Fieldmodule

A B

Fieldmodule

A B

Fieldmodule

A B

Fieldmodule

max. 5 m

1 2 3

max. 32Field modules

22 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

VAV700Multi-functional air volume fl ow controller with integrated web serverNetwork cable specifi cations ● BACnet® ● Modbus®

Ethernet-cable specifi cation

Ethernet-cable Cat-6A is suitable for structured wiring of all connected devices in the fi eld bus technology for an increased bandwidth requirement of 10 Gigabit-Ethernet (10GBASE-T).

Cat-6A is suitable for transmission frequencies up to 500 MHz and distances up to 100 m as well as downward com-patible to existing network protocols.

Cat-6A is defi ned by the international standards committee ISO/IEC (International Organization for Standardization/In-ternational Electrotechnical Commission).

Modbus®-cable specifi cation (RS485)

Modbus® is an application log for the information exchange between fi eld modules with integrated Modbus® controllers.

The Modbus® protocol is settled on the application layer of the OSI reference model and supports the master slave mode between intelligent devices. .

The Modbus® protocol defi nes the information type on which the Modbus® controllers communicate. It describes how a Modbus® controller approaches another controller via request, how this controller answers and how failures are detected and documented.

The Modbus® protocol functions on request answer-base and offers different services which are specifi ed by func-tion codes. The Modbus® protocol determines during the communication how each controller gets to know the device address and recognises the information which belong to it. Besides it defi nes the releasing actions and which informa-tion the Modbus® controller can gather from the information fl ow. If an answer is requested then it will be confi gured in the controller and is sent by the Modbus® protocol to the appropriate station.

The Modbus® can be cost-effi ciently realised via EIA RS 485 and is therefore excellently suitable for the laborato-ry internal networking. The wiring described for the EIA RS 485 standard (please refer to BACnet®) has to be absolutely complied with.

SCHNEIDER products in networked systems

Due to the retrofi t fi eld bus modules for LON®, BACnet® and Modbus® by SCHNEIDER the complete system is very fl exible, individual and cost-effi ciently adaptable to different networks.

We offer the complete system from one source without compatibility problems.

For detailed cable specifi cations please refer to SCHNEI-DER LabSystem handbook, chapter 10.0.

VAV700Multi-functional air volume fl ow controller with integrated web server

23 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

Mounting instructions

min. 1xD

Mounting instructionsVolume fl ow controller, round version

Mounting instructionsVolume fl ow controller, rectangular version

Distance after bend molded part

min. 1xDiag.

Distance after bend molded part

min. 2xD

Distance after miscellaneous molded parts(e. g. T-piece, swivel fi tting, reducer, etc.)

Distance after miscellaneous molded parts(e. g. T-piece, swivel fi tting, reducer, etc.)

min. 2xDiag.

min. 2xD

Distance after fi re damper Distance after fi re damper

min. 2xDiag.

Distance after silencer

min. 2xD

Distance after silencer

min. 2xDiag.

D = diameter W x H = width x heightS = slant

24 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

VAV700Multi-functional air volume fl ow controller with integrated web server

Nominal size

Volume fl ow VMIN, VMAX, VNENN

at a fl ow velocity vmeasuring nozzle DD (standard)

Installation length

NS[mm]

v ≈ 1 m/sVMIN

[m3/h]

v = 6 m/sVMAX

[m3/h]

v ≈ 10m/sVNOM

[m3/h]W

[mm]L1

[mm]L

[mm]100 28 160 277 378 40 298125 45 253 450 378 40 298160 76 418 762 388 40 308200 123 658 1230 408 40 328225 156 836 1559 433 40 353250 208 1035 2078 443 60 363280 236 1302 2356 513 60 393315 294 1651 2944 543 60 423355 381 2102 3811 613 60 493400 469 2674 4694 673 60 553

100

NW

Damper

250

Actuator NMQ-12

Cont

rolle

r VA

V500

100

100

Overall length = B

Pressure nibbles

L1

7Damper

300

Actuator NMQ-12

Controller VAV500

Measuring nozzle

-+

L1

Built-in length = L

Air direction

Dimensions ● Volume fl ow ranges, round version ● galvanised steel, stainless steel 1.4301

Volume fl ow controller with damper and inte-grated measuring nozzle, round version

Material: galvanised steel, stainless steel 1.4301 (V2A)Meas.system:

DD (measuring nozzle), standard galvanised steel

high controller precision and response sensitivity static differential pressure transmitter -100 - 300 Pa insensitive even under inappropriate infl ow measuring nozzle with integrated ring meas. chamber fast and stable volume fl ow control (< 2 s) damper with rubber lip seal

For the laboratory supply air (volume fl ow controller made of steel) the measuring nozzle DD (standard version) or optional the measuring cross with additional shield KD is delivered.

Given that the volume fl ow control range VMin, VMax and VNom is different for each measuring system the volume fl ow va-lues for each nominal size of the specifi c measuring device is listed below.

VAV700-X-X-X

DD-250-S-0-0-0-MM-1

Planning instruction for volume fl ow determination:Consider volume fl ow in relation to fl ow velocity v VMIN = volume fl ow at a fl ow velocity v = 1 bis 2 m/s VMAX = volume fl ow at a fl ow velocity v = 6 m/s (recommended) VNOM = volume fl ow at a fl ow velocity v = 10 bis 12 m/s

Due to the fl ow noise of the volume fl ow VMAX the fl ow velocity v should not overrun 6 m/s during the labora-tory operation (exhaust and supply air). In case of exceeding this value the required noise level of < 52 dB(A) according to DIN1946, part 7 can only be reached with complex sound absorption. The maximal adjustable volume fl ow VMAX should always be about 40 % below VNOM.

VAV700Multi-functional air volume fl ow controller with integrated web server

25 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

Nominal size

Volume fl ow control range VMIN, VMAX, VNOM of the measuring devices KD, MD at a fl ow velocity v

Installation length

Measuring cross with additional shield

KD (standard)

Measuring cross without additional shield

SD

Maintenance-free measuring device MD(only in stainl. steel

1.4301)

NS[mm]

v ≈ 1 m/s

VMIN

[m3/h]

v =6 m/sVMAX

[m3/h]

v ≈ 10 m/s

VNOM

[m3/h]

v ≈ 1 m/s

VMIN

[m3/h]

v =6 m/sVMAX

[m3/h]

v ≈ 10 m/s

VNOM

[m3/h]

v ≈ 1 m/sVMIN

[m3/h]

v =6 m/sVMAX

[m3/h]

v ≈ 10 m/sVNENN

[m3/h]

W[mm]

L1

[mm]L

[mm]

100 19 160 191 36 160 364 28 205 277 340 28 284

125 33 253 329 68 253 675 36 265 364 360 28 304

160 54 418 537 123 418 1230 59 434 589 410 28 354

200 95 658 953 189 658 1888 100 679 1005 450 28 394

225 128 836 1282 250 836 2500 130 850 1300 475 28 419

250 161 1035 1611 308 1035 3083 163 1060 1628 500 28 444

280 229 1302 2286 393 1302 3932 208 1330 2078 550 28 494

315 296 1651 2962 485 1651 4850 267 1683 2667 600 28 544

355 390 2102 3897 675 2102 6755 345 2138 3447 650 28 594

400 553 2674 5525 824 2674 8141 435 2714 4347 700 28 644

Recommended volume fl ow VMAX at a fl ow velocity v = 6m/s.Consider planning instruction for volume fl ow control range VMIN, VMAX und VNOM on page 28.

Dimensions ● Volume fl ow ranges, round version ● galvanised steel, stainless steel 1.4301

Volume fl ow controller with damper and inte-grated measuring cross respectively mainte-nance-free measuring device (only available in stainless steel), round version

Material: galvanised steel, stainless steel 1.4301 (V2A)Meas.system:

KD (measuring cross with additional shield)SD (measuring cross without additional shield)MD (maintenance-free measuring system), only available in stainless steel

high controller precision and response sensitivity static differential pressure transmitter -100 - 300 Pa consider suffi cient infl ow distance (≥ 2*D) measuring nozzle with shield fast and stable volume fl ow control (< 2 s) damper with rubber lip seal

For the laboratory supply air (volume fl ow controller in steel design) the measuring cross with additional shield KD or optional the measuring nozzle DD (standard version) is de-livered. The measuring device MD (patented by SCHNEI-DER) is only available in plastic or steel.

Given that the volume fl ow control range VMin, VMax and VNom is different for each measuring system the volume fl ow va-lues for each nominal size of the specifi c measuring device is listed below.

VAV700-X-X-X

KD-250-S-0-0-0-MM-1

100

NW

Damper

250

Actuator NMQ-12

Cont

rolle

r VA

V500

100

100

Overall length = B

Pressure nibbles

L1

12Damper

300

Actuator NMQ-12

Controller VAV500

Measuring cross

-+

L1

Built-in length = L

Air direction

26 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

VAV700Multi-functional air volume fl ow controller with integrated web serverDimensions ● Volume fl ow ranges, round version ● PPs, PPs-el, PVC

Volume fl ow controller with damper and inte-grated maintenance-free measuring system, round design

Material: PPs, PPs-el, PVCMeas.system:

MD (maintenance-free measuring device), standard in PPs, PPs-el, PVC

high controller precision and response sensitivity measuring device with integrated ring meas. chamber insensitive even under inappropriate infl ow maintenance-free and self cleaning static differential pressure transmitter -100 - 300 Pa option: tight closing damper according to DIN

The measuring device MD (patented by SCHNEIDER) of-fers the best quality/price ratio for the laboratory exhaust air (volume fl ow controller in PPs design) and is delivered by default.

Given that the volume fl ow control range VMin, VMax and VNom is different for each measuring system the volume fl ow va-lues for each nominal size of the specifi c measuring device is listed below.

Recommended volume fl ow VMAX at a fl ow velocity v = 6m/s.Consider planning instruction for volume fl ow control range VMIN, VMAX und VNOM on page 28.

Nominal size

Inner-Ø

Volume fl ow VMIN, VMAX, VNOM

at a fl ow velocity vMeasuring device MD (standard)

Installation length Flange dimensions

NS[mm]

D[mm]

v ≈ 1 m/sVMIN

[m3/h]

v = 6 m/sVMAX

[m3/h]

v ≈ 10m/sVNOM

[m3/h]W

[mm]L1

[mm]L

[mm]

Ext.Ø

D1[mm]K

[mm]d

[mm]No.

110 111 28 205 277 300 40 220 170 150 7 4

125 126 36 265 364 300 40 220 185 165 7 8

160 161 59 434 589 340 40 260 230 200 7 8

200 201 100 679 1005 350 50 250 270 240 7 8

250 251 163 1060 1628 400 50 300 320 290 7 12

315 316 267 1683 2667 490 50 390 395 350 9 12

400 401 435 2714 4347 580 50 480 480 445 9 16

Air direction

Ring chamber 1 withmeasuring drills d=3,0mm

Overall length = B

Ring chamber 2 both sides withmeasuring drills d=3,0mm

Damper 90° shifted arrangedto the measuring tube

Built-in length = LL1 L1

Air direction

Ring chamber 1 withmeasuring drills d=3,0mm

Overall length = built in length = B

Ring chamber 2 both sides withmeasuring drills d=3,0mm

Damper 90° shifted arrangedto the measuring tube

Make: MD-XXX-P-MM-1 (socket/socket) Make: MD-XXX-P-FF-1 (fl ange/fl ange)

VAV700-X-X-X

MD-250-P-0-0-0-MM-1

VAV700Multi-functional air volume fl ow controller with integrated web server

27 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

Volume fl ow controller with damper and inte-grated maintenance-free Venturi measuring nozzle, round version

Material: PPs, PPs-el, PVCMeas.system:

VD (Venturi meas. nozzle), against extra charge

high controller precision and response sensitivity Venturi nozzle with integrated ring meas. chamber

insensitive even under inappropriate infl ow maintenance-free and self cleaning

static differential pressure transmitter -100 - 300 Pa option: tight closing damper according to DIN

SCHNEIDER offers besides the patented measuring-de-vice MD the Venturi measuring nozzle VD (against extra charge) for the laboratory exhaust air (volume fl ow control-ler in PPs design).

Given that the volume fl ow control range VMin, VMax and VNom is different for each measuring system the volume fl ow va-lues for each nominal size of the specifi c measuring device is listed below.

Recommended volume fl ow VMAX at a fl ow velocity v = 6m/s.Consider planning instruction for volume fl ow control range VMIN, VMAX und VNOM on page 28.

Nominal size

Inner-Ø

Volume fl ow VMIN, VMAX, VNOM

at a fl ow velocity vMeasuring device VD

Installation length Flange dimensions

NS[mm]

D[mm]

v ≈ 1 m/sVMIN

[m3/h]

v = 6 m/sVMAX

[m3/h]

v ≈ 10m/sVNENN

[m3/h]W

[mm]L1

[mm]L

[mm]

Ext.-Ø

D1[mm]K

[mm]d

[mm]No.

110 111 33 205 329 300 40 220 170 150 7 4

125 126 45 265 450 300 40 220 185 165 7 8

160 161 69 434 693 340 40 260 230 200 7 8

200 201 106 679 1057 350 50 250 270 240 7 8

250 251 159 1060 1593 400 50 300 320 290 7 12

315 316 279 1683 2789 490 50 390 395 350 9 12

400 401 449 2714 4486 580 50 480 480 445 9 16

Overall length = B

D

Built-in length = L L1 L1

Ring chamber 1 with measuring drills d = 3,0mm

Ring chamber 2 with measuring drills d = 3,0mm

Air direction

Overall length = built in length = B

D1

d

K

D

Ring chamber 1 with measuring drills d = 3,0mm

Ring chamber 2 with measuring drills d = 3,0mm

Air direction

Make: VD-XXX-P-MM-1 (socket/socket) Make: VD-XXX-P-FF-1 (fl ange/fl ange)

VAV700-X-X-X

VD-250-P-0-0-0-MM-1

Dimensions ● Volume fl ow ranges, round version ● PPs, PPs-el, PVC

28 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

VAV700Multi-functional air volume fl ow controller with integrated web serverDimensions ● Volume fl ow ranges, rectangular design ● PPs, PPs-el, PVC ● not airteight closing

B

Damper

Act

uato

r

H

35

35

ca. 100

ca. 60

Con

trol

ler

400

Damper

Actuator

Pressure nibble

Measuring device

+ -

Controller

+-

Air direction

Volume fl ow controller with damper and inte-grated measuring device, rectangular version, not airteight closing

Material: PPs, PPs-el, PVCMeas.system:

MD (maintenance-free measuring device), standard in PPs, PPs-el, PVC

high controller precision and response sensitivity static differential pressure transmitter -100 - 300 Pa consider suffi cient infl ow distance (≥ 2*D) measuring nozzle with integrated ring meas. chamber fast and stable volume fl ow control (< 2 s) maintenance-free and self cleaning

The measuring device MD (patented by SCHNEIDER) of-fers the best quality/price ratio for the laboratory exhaust air (volume fl ow controller in PPs, PPs-el and PVC design) and is delivered by default.

Width Volume fl ow controller VMIN (at v = 2 m/sec), VMAX (at v = 6 m/s), VNOM (at v = 12 m/sec)

Range

W [mm]

Height H [mm]

[m3/h]150 200 250 300 350 400

216 288 360 432 504 576 VMIN200 648 864 1080 1296 1512 1728 VMAX

1296 1728 2160 2592 3024 3456 VNOM324 432 540 648 756 864 VMIN

300 972 1296 1620 1944 2268 2592 VMAX1944 2592 3240 3888 4536 5184 VNOM432 576 720 864 1008 1152 VMIN

400 1296 1728 2160 2592 3024 3456 VMAX2592 3456 4320 5184 6048 6912 VNOM540 720 900 1080 1260 1440 VMIN

500 1620 2160 2700 3240 3780 4320 VMAX3240 4320 5400 6480 7560 8640 VNOM648 864 1080 1296 1512 1728 VMIN

600 1944 2592 3240 3888 4536 5184 VMAX3888 5184 6480 7776 9072 10368 VNOM756 1008 1260 1512 1764 2016 VMIN

700 2268 3024 3780 4536 5292 6048 VMAX4536 6048 7560 9072 10584 12096 VNOM

- 1152 1440 1728 2016 2304 VMIN800 - 3456 4320 5184 6048 6912 VMAX

- 6912 8640 10368 12096 13824 VNOM- - 1620 1944 2268 2592 VMIN

900 - - 4860 5832 6804 7776 VMAX- - 9720 11664 13608 15552 VNOM- - 1800 2160 2520 2880 VMIN

1000 - - 5400 6480 7560 8640 VMAX- - 10800 12960 15120 17280 VNOM

VAV700-X-X-X

DD-400-300-P-0-0-1

Intermediate sizes on demand.Recommended volume fl ow VMAX at a fl ow velocity v = 6m/s.Consider planning instruction for volume fl ow control range VMIN, VMAX und VNOM on page 28.

VAV700Multi-functional air volume fl ow controller with integrated web server

29 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

Dimensions ● Volume fl ow ranges, rectangular version ● PPs, PPs-el, PVC ● airteight closing

Volume fl ow controller with damper and inte-grated measuring device, rectangular version, airteight closing according to DIN 1946, part 4

Material: PPs, PPs-el, PVCMeas.system:

MD (maintenance-free measuring device), standard in PPs, PPs-el, PVC

high controller precision and response sensitivity static differential pressure transmitter -100 - 300 Pa consider suffi cient infl ow distance (≥ 2*D) measuring nozzle with integrated ring meas. chamber fast and stable volume fl ow control (< 2 s) maintenance-free and self cleaning

The measuring device MD (patented by SCHNEIDER) of-fers the best quality/price ratio for the laboratory exhaust air (volume fl ow controller in PPs, PPs-el and PVC design) and is delivered by default. The airteight closing model is only available in the following special dimensions.

Width Volume fl ow controller VMIN (at v = 2 m/sec), VMAX (at v = 6 m/s), VNOM (at v = 12

m/sec)

Range

W [mm]

Height H [mm]

[m3/h]195 360 525 690 855

253 479 705 - - VMIN

200 759 1436 2114 - - VMAX1518 2873 4227 - - VNOM386 731 1075 1420 1764 VMIN

300 1159 2192 3226 4260 5293 VMAX2318 4385 6452 8519 10586 VNOM519 983 1446 1909 2373 VMIN

400 1558 2948 4338 5728 7118 VMAX3117 5897 8677 11457 14237 VNOM653 1235 1817 2399 2981 VMIN

500 1958 3704 5451 7197 8943 VMAX3916 7409 10902 14394 17887 VNOM786 1487 2188 2889 3590 VMIN

600 2358 4460 6563 8666 10796 VMAX4715 8921 13126 17332 21537 VNOM

- 1739 2559 3378 4198 VMIN700 - 5216 7676 10135 12594 VMAX

- 10433 15351 20269 25188 VNOM- 1991 2929 3868 4806 VMIN

800 - 5972 8788 11604 14419 VMAX- 11945 17576 23207 28838 VNOM- - 3300 4357 5415 VMIN

900 - - 9900 13072 16244 VMAX- - 19801 26145 32489 VNOM- - 3671 4847 6023 VMIN

1000 - - 11013 14541 18069 VMAX- - 22026 29082 36139 VNOM

VAV700-X-X-X

DD-400-360-P-K-0-1

Intermediate sizes on demand.Recommended volume fl ow VMAX at a fl ow velocity v = 6m/s.Consider planning instruction for volume fl ow control range VMIN, VMAX und VNOM on page 28.

B

Damper

Act

uato

r

H

35

35

ca. 100

ca. 60

Con

trol

ler

400

Damper

Actuator

Pressure nibble

Measuring device

+ -

Controller

+-

Air direction

30 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

VAV700Multi-functional air volume fl ow controller with integrated web serverDimensions ● Volume fl ow ranges, rectangular version ● galvanised steel, stainless steel 1.4301

B

Damper

Con

trol

ler

VAV5

00

Act

uato

rN

MQ

-12

H

35

35

105

400

Damper

Controller

Actuator

Pressure nibble

Measuring cross

+-

Air direction

Volume fl ow controller with damper and inte-grated measuring device, rectangular version

Material: galvanised steel, stainless steel 1.4301 (V2A)Meas.system:

MD (maintenance-free measuring device), standard, stainless steelDD (measuring nozzle), standard, galvanised steelKD (measuring cross with additional shield)SD (measuring cross without additional shield)

high controller precision and response sensitivity static differential pressure transmitter -100 - 300 Pa consider suffi cient infl ow distance (≥ 2*D) maintenance-free measuring device MD, stainless

steel 1.4301 fast and stable volume fl ow control (< 2 s) measuring nozzle DD, galvanised steel and stainless

steel 1.4301

For the laboratory supply air (volume fl ow controller in steel design) the measuring nozzle DD (standard version) or op-tional the measuring cross with additional shield KD is de-livered.

The measuring device MD (patented by SCHNEIDER) of-fers the best quality/price ratio for the laboratory exhaust air (volume fl ow controller in PPs, PPs-el and PVC design) and is delivered by default.

Width Volume fl ow controller VMIN (at v = 2 m/sec), VMAX (at v = 6 m/s), VNOM (at v = 12 m/sec

Range

B [mm]

Höhe H [mm]

[m3/h]100 150 200 250 300 350 400

144 216 288 360 432 504 576 VMIN200 432 648 864 1080 1296 1512 1728 VMAX

864 1296 1728 2160 2592 3024 3456 VNOM216 324 432 540 648 756 864 VMIN

300 648 972 1296 1620 1944 2268 2592 VMAX1296 1944 2592 3240 3888 4536 5184 VNOM288 432 576 720 864 1008 1152 VMIN

400 864 1296 1728 2160 2592 3024 3456 VMAX1728 2592 3456 4320 5184 6048 6912 VNOM360 540 720 900 1080 1260 1440 VMIN

500 1080 1620 2160 2700 3240 3780 4320 VMAX2160 3240 4320 5400 6480 7560 8640 VNOM432 648 864 1080 1296 1512 1728 VMIN

600 1296 1944 2592 3240 3888 4536 5184 VMAX2592 3888 5184 6480 7776 9072 10368 VNOM504 756 1008 1260 1512 1764 2016 VMIN

700 1512 2268 3024 3780 4536 5292 6048 VMAX3024 4536 6048 7560 9072 10584 12096 VNOM

- - 1152 1440 1728 2016 2304 VMIN800 - - 3456 4320 5184 6048 6912 VMAX

- - 6912 8640 10368 12096 13824 VNOM- - - 1620 1944 2268 2592 VMIN

900 - - - 4860 5832 6804 7776 VMAX- - - 9720 11664 13608 15552 VNOM- - - 1800 2160 2520 2880 VMIN

1000 - - - 5400 6480 7560 8640 VMAX- - - 10800 12960 15120 17280 VNOM

VAV700-X-X-X

DD-600-400-S-0-0-1

Intermediate sizes on demand.Recommended volume fl ow VMAX at a fl ow velocity v = 6m/s.Consider planning instruction for volume fl ow control range VMIN, VMAX und VNOM on page 28.

VAV700Multi-functional air volume fl ow controller with integrated web server

31 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

Nom

. siz

e in

mm

v in

m/s

V in

m3 /h

∆pg = 100 Pa ∆pg = 250 Pa ∆pg = 500 PaLW in dB/octave

L WA in

dB

(A)

L in

dB

(A)

LW in dB/octave

L WA in

dB

(A)

L in

dB

(A)

LW in dB/octave

L WA in

dB

(A)

L in

dB

(A)

fm in Hz fm in Hz fm in Hz

63 H

Z

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

8000

Hz

63 H

Z

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

8000

Hz

63 H

Z

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

8000

Hz

160

2 148 50 47 44 46 45 46 33 22 50 42 53 54 53 53 51 50 56 42 60 52 56 58 55 60 59 57 58 54 65 574 290 55 51 48 51 47 42 35 27 52 44 64 61 58 57 55 53 49 43 60 52 67 67 64 63 60 58 60 58 67 596 434 62 58 53 56 50 46 41 35 56 48 67 65 61 61 58 54 50 45 63 55 72 72 69 67 63 60 59 57 69 618 579 62 60 57 59 55 51 49 45 61 53 71 67 64 64 60 56 53 48 66 58 75 73 71 69 65 62 59 56 71 63

10 724 67 66 62 58 59 55 54 51 64 56 73 70 66 68 62 59 55 51 69 61 76 76 72 72 67 64 61 58 73 65

200

2 226 47 50 47 47 47 46 49 39 54 46 50 53 52 56 57 58 57 59 65 57 55 57 54 59 63 67 67 66 73 654 452 56 57 53 51 53 60 56 42 63 55 59 62 60 60 59 59 60 62 67 59 61 64 64 66 66 67 66 66 73 656 679 59 61 56 55 58 58 52 45 63 55 65 66 64 63 63 63 63 64 70 62 68 70 70 70 69 69 67 70 76 688 905 61 64 60 57 59 58 52 46 64 56 69 72 67 66 67 68 66 61 73 65 70 74 72 73 72 71 69 69 78 70

10 1131 63 65 62 59 62 60 55 50 66 58 74 72 70 68 69 69 65 61 75 67 75 77 74 74 74 73 71 70 80 72

250

2 353 50 47 44 46 45 46 33 22 50 42 53 54 53 53 51 50 56 42 60 52 56 58 55 60 59 57 58 54 65 574 707 55 51 48 51 47 42 35 27 52 44 64 61 58 57 55 53 49 43 60 52 67 67 64 63 60 58 60 58 67 596 1060 62 58 53 56 50 46 41 35 56 48 67 65 61 61 58 54 50 45 63 55 72 72 69 67 63 60 59 57 69 618 1414 62 60 57 59 55 51 49 45 61 53 71 67 64 64 60 56 53 48 66 58 75 73 71 69 65 62 59 56 71 63

10 1767 67 66 62 58 59 55 54 51 64 56 73 70 66 68 62 59 55 51 69 61 76 76 72 72 67 64 61 58 73 65

315

2 561 42 47 45 43 38 35 33 32 45 37 47 47 49 51 54 52 50 50 57 49 52 52 54 56 59 57 55 55 62 544 1122 52 55 50 49 43 38 31 29 50 42 60 61 57 55 55 51 47 48 59 51 65 66 62 60 60 56 52 53 64 566 1683 54 57 52 51 45 40 33 31 52 44 62 63 59 57 57 53 49 50 61 53 67 68 64 62 62 58 54 55 66 588 2244 59 57 56 55 47 43 38 33 55 47 67 68 64 61 58 55 51 50 64 58 72 73 69 66 63 60 56 55 69 61

10 2806 61 59 58 57 49 45 40 35 57 49 69 70 66 63 60 57 53 52 66 58 74 75 71 68 65 62 58 57 71 63

400

2 905 41 48 47 44 38 36 34 32 46 38 48 49 49 50 53 50 48 48 57 49 53 54 54 55 58 55 53 53 62 544 1810 53 54 53 52 46 40 34 30 52 44 62 62 59 57 54 52 48 47 60 52 67 67 64 62 59 57 53 52 65 576 2714 55 56 55 54 48 42 36 32 54 46 64 64 61 59 56 54 50 49 62 54 69 69 66 64 61 59 55 54 67 598 3619 60 58 61 62 53 46 42 35 61 53 66 68 67 64 59 56 51 50 66 58 73 73 72 69 64 61 56 55 71 63

10 4524 62 60 63 64 55 48 44 37 63 55 70 70 69 66 61 58 53 52 68 60 75 75 74 71 66 63 58 57 73 65

Sound values ● PPs-volume fl ow controller with maintenance-free measuring device, round design

Table 4: fl ow noise

Defi nitions:fm in Hz: mid-band frequency of the octave bandLW in dB/octave: sound power level determined in the echo chamberLWA in dB(A): overall noise level, A-ratedL in dB(A): noise level, A-rated, room attenuation of 8 dB/octave considered∆pg in Pa: total pressure difference (measured in front of and behind the volume fl ow controller)V in m3/h: volume fl owv in m/s: fl ow velocity

32 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

VAV700Multi-functional air volume fl ow controller with integrated web server

Nom

. siz

e in

mm

v in

m/s

V in

m3 /h

∆pg = 100 Pa ∆pg = 250 Pa ∆pg = 500 PaLW in dB/octave

L WA in

dB

(A)

L in

dB

(A)

LW in dB/octave

L WA in

dB

(A)

L in

dB

(A)

LW in dB/octave

L WA in

dB

(A)

L in

dB

(A)

fm in Hz fm in Hz fm in Hz63

HZ

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

8000

Hz

63 H

Z

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

8000

Hz

63 H

Z

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

8000

Hz

160

2 148 30 28 21 20 26 28 15 9 31 23 33 26 24 25 36 38 31 20 42 34 33 25 26 31 42 47 41 33 50 424 290 38 32 27 23 27 27 20 7 32 24 43 36 32 29 36 38 30 22 41 33 42 37 36 34 42 45 39 32 49 416 434 41 34 32 29 30 29 22 9 35 27 47 41 38 33 37 38 33 23 43 35 48 44 42 38 44 46 40 33 49 418 579 46 41 40 39 35 31 22 10 41 33 49 43 42 38 40 40 35 26 45 37 54 48 47 41 46 47 41 34 51 43

10 724 51 45 46 46 41 37 28 18 47 39 52 46 45 42 43 42 36 26 48 40 54 50 49 44 47 48 43 35 53 45

200

2 226 24 22 20 19 20 20 20 6 26 18 28 30 27 27 26 28 27 22 34 26 37 31 28 32 34 37 32 33 41 334 452 31 33 27 23 23 27 20 6 31 23 38 37 33 30 30 30 29 29 37 29 53 39 37 42 39 38 34 34 45 376 679 38 37 32 28 28 28 20 12 33 25 44 43 38 34 33 35 31 29 40 32 47 46 42 44 41 40 35 34 47 398 905 39 39 35 33 33 30 22 14 37 29 45 44 41 39 38 38 32 26 43 35 47 47 46 45 44 43 41 37 50 42

10 1131 43 43 39 37 38 33 26 19 41 33 52 49 45 41 40 40 34 30 46 38 54 52 49 47 44 44 41 38 51 43

250

2 353 30 28 21 20 26 28 15 9 31 23 33 26 24 25 36 38 31 20 42 34 33 25 26 31 42 47 41 33 50 424 707 38 32 27 23 27 27 20 7 32 24 43 36 32 29 36 38 30 22 41 33 42 37 36 34 42 45 39 32 49 416 1060 41 34 32 29 30 29 22 9 35 27 47 41 38 33 37 38 33 23 43 35 48 44 42 38 44 46 40 33 49 418 1414 46 41 40 39 35 31 22 10 41 33 49 43 42 38 40 40 35 26 45 37 54 48 47 41 46 47 41 34 51 43

10 1767 51 45 46 46 41 37 28 18 47 39 52 46 45 42 43 42 36 26 48 40 54 50 49 44 47 48 43 35 53 45

315

2 561 34 34 31 29 25 24 24 24 33 25 39 34 35 37 41 41 41 42 45 37 44 39 40 42 46 46 46 47 50 424 1122 44 42 36 35 30 27 22 21 38 30 52 48 43 41 42 40 38 40 47 39 57 53 48 46 47 45 43 45 52 446 1683 46 44 38 37 32 29 24 23 40 32 54 50 45 43 44 42 40 42 49 41 59 55 50 48 49 47 45 47 54 468 2244 51 44 42 41 34 32 29 25 43 35 59 55 50 47 45 44 42 42 52 44 64 60 55 52 50 49 47 47 57 49

10 2806 53 46 44 43 36 34 31 27 45 37 61 57 52 49 47 46 44 44 54 46 66 62 57 54 52 51 49 49 59 51

400

2 905 33 36 33 33 25 26 26 24 34 26 40 37 35 35 40 40 40 40 45 37 45 42 40 40 45 45 45 45 50 424 1810 45 42 39 39 33 30 26 22 40 32 54 50 45 45 41 42 40 39 48 40 59 55 50 50 46 47 45 44 53 456 2714 47 44 41 41 35 32 28 24 42 34 56 52 47 47 43 44 42 41 50 42 61 57 52 52 48 49 47 46 55 478 3619 52 46 47 47 40 36 34 27 49 41 60 56 53 53 46 46 43 42 54 46 65 61 58 58 51 51 48 47 59 51

10 4524 54 48 49 49 42 38 36 29 51 43 62 58 55 55 48 48 45 44 56 48 67 63 60 60 53 53 50 49 61 53

Table 5: Case-radiated noise

Sound values ● PPs-volume fl ow controller with maintenance-free measuring device, round design

Defi nitions:fm in Hz: mid-band frequency of the octave bandLW in dB/octave: sound power level determined in the echo chamberLWA in dB(A): overall noise level, A-ratedL in dB(A): noise level, A-rated, room attenuation of 8 dB/octave considered∆pg in Pa: total pressure difference (measured in front of and behind the volume fl ow controller)V in m3/h: volume fl owv in m/s: fl ow velocity

VAV700Multi-functional air volume fl ow controller with integrated web server

33 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

Sound values ● Steel volume fl ow controller with measuring nozzle, round designN

om. s

ize

in m

m

v in

m/s

V in

m3 /h

∆pg = 125 Pa ∆pg = 250 Pa ∆pg = 500 PaLW in dB/ocave

L WA in

dB

(A)

L in

dB

(A)

LW in dB/ocave

L WA in

dB

(A)

L in

dB

(A)

LW in dB/octave

L WA in

dB

(A)

L in

dB

(A)

fm in Hz fm in Hz fm in Hz

63 H

Z

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

8000

Hz

63 H

Z

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

8000

Hz

63 H

Z

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

8000

Hz

100

3 85 33 40 37 35 34 33 32 33 39 31 37 43 43 41 39 38 37 31 46 38 41 48 47 46 45 44 41 41 52 446 170 41 54 49 45 40 36 35 34 45 37 43 57 54 50 46 44 43 36 53 45 45 61 58 56 53 52 47 46 58 509 257 45 55 51 45 40 37 25 35 49 41 48 63 59 57 51 48 46 39 56 48 53 69 66 61 57 54 51 50 62 54

12 344 51 56 55 51 45 40 37 35 52 44 58 67 63 58 53 49 47 42 59 51 56 71 67 63 59 56 54 52 65 57

125

3 130 40 42 39 37 36 35 34 36 41 33 45 45 45 43 41 40 39 39 48 40 49 50 49 48 47 46 43 42 54 466 263 48 56 51 47 42 38 37 37 47 39 51 59 56 52 48 46 45 44 55 47 53 63 60 58 55 54 49 47 60 529 396 52 57 53 47 42 39 37 38 51 43 56 65 61 59 53 50 48 47 58 50 61 71 68 63 59 56 53 51 64 56

12 530 58 58 57 53 47 42 39 38 54 46 66 69 65 60 5 51 49 46 61 53 64 73 69 65 61 58 56 53 67 59

160

3 216 43 44 43 39 38 37 36 37 43 35 48 47 47 45 43 42 41 37 50 42 55 52 51 50 49 48 45 46 56 486 434 51 58 53 49 44 40 39 38 49 41 54 61 58 54 50 48 47 42 57 49 59 65 62 60 57 56 51 51 62 549 652 55 59 55 49 44 41 39 39 53 45 59 67 63 61 55 52 50 45 60 52 67 73 70 65 61 58 55 55 66 58

12 871 61 60 59 55 49 44 41 39 56 48 69 71 67 62 57 53 51 48 63 55 70 75 71 67 63 60 58 57 69 61

200

3 337 49 46 43 41 40 39 38 38 45 37 54 49 49 47 45 44 43 44 52 44 60 54 53 52 51 50 47 47 58 506 680 57 60 55 51 46 42 41 39 51 43 60 63 60 56 52 50 49 49 59 51 64 67 64 62 59 58 53 52 64 569 1024 61 61 57 51 46 43 41 40 55 47 65 69 65 63 57 54 52 52 62 54 72 75 72 67 63 60 57 56 68 60

12 1370 67 62 61 57 51 46 43 40 58 50 75 73 69 64 59 55 53 55 65 57 75 77 73 69 65 62 60 59 71 63

225

3 422 51 47 44 42 41 40 39 38 46 38 55 50 50 48 46 45 44 44 53 45 61 55 54 53 52 51 48 48 59 516 850 59 61 56 52 47 43 42 38 52 44 61 64 61 57 53 51 50 49 60 52 65 68 65 63 60 59 54 53 65 579 1279 63 62 58 52 47 44 42 39 56 48 66 70 66 64 58 55 53 52 63 55 73 76 73 68 64 61 58 57 69 61

12 1709 69 63 62 58 52 47 44 40 59 51 76 74 70 65 60 56 54 55 66 58 76 78 74 70 66 63 61 59 72 64

250

3 529 53 48 45 43 42 41 40 39 47 39 57 51 51 49 47 46 45 45 54 46 63 56 55 54 53 52 49 49 60 526 1065 61 62 57 53 48 44 43 40 53 45 63 65 62 58 54 52 51 50 61 53 67 69 66 64 61 60 55 54 66 589 1604 65 63 59 53 48 45 43 41 57 49 68 71 67 65 59 56 54 53 64 56 75 77 74 69 65 62 59 58 70 62

12 2144 71 64 63 59 53 48 45 41 60 52 78 75 71 66 61 57 55 56 67 59 78 79 75 71 67 64 62 60 73 65

280

3 666 54 49 46 44 43 42 41 38 48 40 58 52 52 50 48 47 46 46 55 47 64 57 56 55 54 53 50 50 61 536 1339 62 63 58 54 49 45 44 41 54 46 64 66 63 59 55 53 52 51 62 54 68 70 67 65 62 61 56 55 67 599 2014 66 64 60 54 49 46 44 41 58 50 69 72 68 66 60 57 55 54 65 57 76 78 75 70 66 63 60 59 71 63

12 2690 72 65 64 60 54 49 46 42 61 53 79 76 72 67 62 58 56 57 68 60 79 80 76 72 68 65 63 61 74 66

315

3 843 55 50 47 45 44 43 42 39 49 41 57 47 42 44 45 47 40 45 56 48 66 58 57 56 55 54 51 51 62 546 1692 63 64 59 55 50 46 45 41 55 47 63 61 53 53 52 53 46 50 63 55 70 71 68 66 63 62 57 56 68 609 2543 67 65 61 55 50 47 45 42 59 51 68 67 64 61 58 56 54 53 66 58 78 79 76 71 67 64 61 60 72 64

12 3394 73 66 65 61 55 50 47 42 62 54 78 71 62 60 58 57 56 56 69 61 81 81 77 73 69 66 64 62 75 67

355

3 1073 56 51 48 46 45 44 43 41 50 42 61 54 54 52 50 49 48 48 57 49 67 59 58 57 56 55 52 52 63 556 2160 64 65 60 56 51 47 46 41 56 48 67 68 65 61 57 55 54 53 64 56 71 72 69 67 64 63 58 57 69 619 3252 68 66 62 56 51 48 46 42 60 52 72 74 70 68 62 59 57 56 67 59 79 80 77 72 68 65 62 61 73 65

12 4347 74 67 66 62 56 51 48 43 63 55 82 78 74 69 64 60 58 59 70 62 82 82 78 74 70 67 65 63 76 68

400

3 1364 57 52 49 47 46 45 44 42 51 43 64 55 55 53 51 50 49 49 58 50 59 60 59 58 57 56 53 53 64 566 2736 65 66 61 57 52 48 47 43 57 49 70 69 66 62 58 56 55 54 65 57 73 73 70 68 65 64 59 58 70 629 4111 69 67 63 57 52 49 47 44 61 53 75 75 71 69 63 60 58 57 68 60 81 81 78 73 69 66 63 62 74 66

12 5488 75 68 67 63 57 52 49 44 64 56 85 79 75 70 65 61 59 60 71 63 84 83 79 75 71 68 66 64 77 69

Tabelle 6: Flow noise

Defi nitions:fm in Hz: mid-band frequency of the octave bandLW in dB/octave: sound power level determined in the echo chamberLWA in dB(A): overall noise level, A-ratedL in dB(A): noise level, A-rated, room attenuation of 8 dB/octave considered∆pg in Pa: total pressure difference (measured in front of and behind the volume fl ow controller)V in m3/h: volume fl owv in m/s: fl ow velocity

34 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

VAV700Multi-functional air volume fl ow controller with integrated web serverSound values ● Steel volume fl ow controller with measuring nozzle, round version

Nom

. siz

e in

mm

v in

m/s

V in

m3 /h

∆pg = 125 Pa ∆pg = 250 Pa ∆pg = 500 PaLW in dB/octave

L WA in

dB

(A)

L in

dB

(A)

LW in dB/octave

L WA in

dB

(A)

L in

dB

(A)

LW in dB/octave

L WA in

dB

(A)

L in

dB

(A)

fm in Hz fm in Hz fm in Hz63

HZ

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

8000

Hz

63 H

Z

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

8000

Hz

63 H

Z

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

8000

Hz

100

3 85 15 22 21 22 18 20 21 22 24 16 19 25 27 28 23 25 26 20 31 23 23 30 31 33 29 31 30 30 37 296 170 23 36 33 32 24 23 24 23 31 23 25 39 38 37 30 31 32 25 38 30 27 43 42 43 37 39 36 35 43 359 257 27 37 35 32 24 24 24 23 34 26 30 45 43 44 35 35 35 28 42 34 35 51 50 48 41 41 40 39 47 39

12 344 33 38 39 38 29 27 26 24 37 29 40 49 47 45 37 36 36 31 44 36 38 53 51 50 43 43 43 41 50 42

125

3 130 22 24 23 20 20 22 25 27 26 18 27 27 29 26 25 27 30 30 33 25 31 32 33 31 31 33 34 33 39 316 263 30 38 35 30 26 25 28 28 33 25 33 41 40 35 32 33 36 35 40 32 35 45 44 41 39 41 40 38 45 379 396 34 39 37 30 26 26 28 29 36 28 37 47 45 42 37 37 39 38 44 36 43 53 52 46 43 43 44 42 49 41

12 530 40 40 41 36 31 29 30 29 39 31 48 51 49 43 39 38 40 38 46 38 46 55 53 48 45 45 47 44 52 44

160

3 216 25 26 27 21 23 24 27 28 28 20 30 29 33 27 28 29 32 30 35 27 37 34 37 32 34 35 36 37 41 336 434 33 40 39 31 29 27 30 29 35 27 36 43 44 36 35 35 38 33 42 34 41 47 48 42 42 43 42 42 47 399 652 37 41 41 31 29 28 30 30 38 30 41 49 49 43 40 39 41 36 46 38 49 55 56 47 46 45 46 46 51 43

12 871 43 42 45 37 34 31 32 32 41 33 51 53 53 44 42 40 42 39 48 40 52 57 57 49 48 47 49 48 54 46

200

3 337 36 33 30 24 25 28 30 30 32 24 41 36 36 30 30 33 35 36 39 31 47 41 40 35 36 39 39 39 45 376 680 45 47 42 34 31 31 33 31 38 30 47 50 47 39 37 39 41 41 46 38 51 54 51 45 44 47 45 44 51 439 1024 48 48 44 34 31 32 33 32 42 34 52 56 52 46 42 43 44 44 49 41 59 62 59 50 48 49 49 48 55 47

12 1370 54 49 48 40 36 35 35 32 45 37 62 60 56 47 44 44 45 47 52 44 62 64 60 52 50 51 52 51 58 50

225

3 422 41 37 31 27 30 30 31 30 35 27 45 40 37 33 35 35 36 36 42 34 51 45 41 38 41 41 40 40 48 406 850 50 51 43 37 36 33 34 30 41 33 51 54 48 42 42 41 42 41 49 41 55 58 52 48 49 49 46 45 54 469 1279 53 52 45 37 36 34 34 31 45 37 56 60 53 49 47 45 45 44 52 44 65 66 60 53 53 51 50 49 58 50

12 1709 60 53 49 43 41 37 36 32 48 40 66 64 57 50 49 46 46 47 55 47 66 68 61 55 55 53 53 51 61 53

250

3 529 45 40 30 27 28 30 32 31 35 27 49 43 36 33 33 35 37 37 42 34 55 48 40 38 39 41 41 41 48 406 1065 54 54 42 37 34 33 35 32 41 33 55 57 47 42 40 41 43 42 49 41 59 61 51 48 47 49 47 46 54 469 1604 57 55 44 37 34 34 35 33 45 37 60 63 52 49 45 45 46 45 52 44 67 69 59 53 51 51 51 50 58 50

12 2144 63 56 48 43 39 37 37 33 48 40 70 67 56 50 47 46 47 48 55 47 70 71 60 55 53 53 54 52 61 53

280

3 666 46 41 33 31 33 32 32 29 37 29 50 44 39 37 38 37 37 37 44 36 56 49 43 42 44 43 41 41 50 426 1339 55 55 45 41 39 35 35 32 43 35 56 58 50 46 45 43 43 42 51 43 60 62 54 52 52 51 47 46 56 489 2014 58 56 47 41 39 36 35 32 47 39 61 64 55 53 50 47 46 45 54 46 68 70 62 57 56 53 51 50 60 42

12 2690 64 57 51 47 44 39 37 33 50 42 71 68 59 54 52 48 47 48 57 49 71 72 63 59 58 55 54 52 63 55

315

3 843 47 42 32 29 30 33 34 31 37 29 42 32 27 28 31 37 32 37 44 36 58 50 42 40 41 44 43 43 50 426 1692 55 56 44 39 36 36 37 33 43 35 48 46 38 37 38 43 38 42 51 43 62 63 53 50 49 52 49 48 56 489 2543 59 57 46 39 36 37 37 34 47 39 53 52 49 45 44 46 46 45 54 46 70 71 61 55 53 54 53 52 60 52

12 3394 65 58 50 45 41 40 39 34 50 42 63 56 47 44 44 47 48 48 57 49 73 73 62 57 55 56 56 54 63 55

355

3 1073 48 43 35 31 35 38 36 34 40 32 53 46 41 37 40 43 41 41 47 39 59 51 45 42 46 49 45 45 53 456 2160 56 57 47 41 41 41 39 34 46 38 59 60 52 46 47 49 47 46 54 46 63 64 56 52 54 57 51 50 59 519 3252 60 58 49 41 41 42 39 35 50 42 64 66 57 53 52 53 50 49 57 49 71 72 64 57 58 59 55 54 63 55

12 4347 66 59 53 47 46 45 41 36 53 45 74 70 61 54 54 54 51 50 60 52 74 74 65 59 60 61 58 56 66 58

400

3 1364 47 42 37 33 36 33 37 35 40 32 54 45 43 39 41 38 42 42 47 39 59 50 47 44 47 44 46 46 53 456 2736 55 56 49 43 42 36 40 36 46 38 60 59 54 48 48 44 48 47 54 46 63 63 58 54 55 52 52 51 59 519 4111 59 57 51 43 42 37 40 37 50 42 65 65 59 55 53 48 51 50 57 49 71 71 66 59 59 54 56 55 63 55

12 5488 65 58 55 49 47 40 42 37 53 45 75 69 63 56 55 49 52 53 60 52 74 73 67 61 61 56 59 57 66 58

Table 7: Case-radiated noise

Defi nitions:fm in Hz: mid-band frequency of the octave bandLW in dB/octave: sound power level determined in the echo chamberLWA in dB(A): overall noise level, A-ratedL in dB(A): noise level, A-rated, room attenuation of 8 dB/octave considered∆pg in Pa: total pressure difference (measured in front of and behind the volume fl ow controller)V in m3/h: volume fl owv in m/s: fl ow velocity

VAV700Multi-functional air volume fl ow controller with integrated web server

35 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

Sound values ● PPs-volume fl ow controller with measuring cross, rectangular version

WidthB [mm]

Height H [mm]100 160 200 250 300 400

200 0,020 0,032 0,040 0,050 0,060 0,080300 0,030 0,048 0,060 0,075 0,090 0,120400 0,040 0,064 0,080 0,100 0,120 0,160500 0,050 0,080 0,100 0,125 0,150 0,200600 0,060 0,096 0,120 0,150 0,180 0,240700 0,070 0,112 0,140 0,175 0,210 0,280800 0,080 0,128 0,160 0,200 0,240 0,320900 0,090 0,144 0,180 0,225 0,270 0,360

1000 0,100 0,160 0,200 0,250 0,300 0,400

Table 8: Airfl ow surface

Are

a A

in m

2

v in

m/s

∆pg = 250 Pa ∆pg = 500 Pa ∆pg = 1000 PaLW in dB/octave

L WA in

dB

(A)

L in

dB

(A)

LW in dB/octaveL W

A in

dB

(A)

L in

dB

(A)

LW in dB/octave

L WA in

dB

(A)

L in

dB

(A)

fm in Hz fm in Hz fm in Hz

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

1

3 68 68 67 67 65 63 72 64 74 74 73 73 71 69 78 70 81 82 81 81 80 77 86 786 73 73 72 71 69 67 76 68 78 79 78 77 76 74 82 74 84 85 84 84 84 82 90 829 79 78 78 76 75 73 82 74 79 80 81 80 80 78 86 78 86 88 87 86 86 85 92 84

12 81 81 80 79 78 76 85 77 85 85 84 84 82 81 89 81 87 89 89 90 89 88 95 87

Table 10: Case-radiated noise

Table 9: Flow noise

Are

a A

in m

2

v in

m/s

∆pg = 250 Pa ∆pg = 500 Pa ∆pg = 1000 PaLW in dB/octave

L WA in

dB

(A)

L in

dB

(A)

LW in dB/octave

L WA in

dB

(A)

L in

dB

(A)

LW in dB/octave

L WA in

dB

(A)

L in

dB

(A)

fm in Hz fm in Hz fm in Hz

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

1

3 75 68 62 56 51 50 65 57 82 74 68 63 58 53 72 64 90 82 77 72 67 60 80 726 80 72 66 58 54 50 69 61 85 80 73 66 62 57 76 68 95 85 79 75 70 66 83 759 85 75 70 61 58 54 73 65 85 79 75 67 65 61 77 69 95 87 82 75 71 69 85 77

12 86 77 71 63 60 57 74 66 90 83 78 70 66 64 80 72 94 87 84 78 73 71 86 78

Table 11: Correction factor for fl ow noise and case-radiated noise

Defi nitions:fm in Hz: mid-band frequency of the octave bandLW in dB/Oktave: sound power level determined in the echo chamberLWA in dB(A): overall noise level, A-ratedL in dB(A): noise level, A-rated, room attenuation of 8 dB/octave considered∆pg in Pa: total pressure difference (measured in front of and behind the volume fl ow controller)V in m3/h: volume fl owv in m/s: fl ow velocityA in m2: airfl ow surface (W x H)CF correction factor

A [m²] 0,04 0,06 0,08 0,10 0,12 0,16 0,2 0,25 0,3 0,4 0,5 0,6 0,8 1

CF [-] - 14 - 12 - 11 - 10 - 9 - 8 - 7 - 6 - 5 - 4 - 3 - 2 - 1 0

36 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

VAV700Multi-functional air volume fl ow controller with integrated web serverSound values ● Steel volume fl ow controller with measuring cross, rectangular version

WidthB [mm]

Height H [mm]100 160 200 250 300 400

200 0,020 0,032 0,040 0,050 0,060 0,080300 0,030 0,048 0,060 0,075 0,090 0,120400 0,040 0,064 0,080 0,100 0,120 0,160500 0,050 0,080 0,100 0,125 0,150 0,200600 0,060 0,096 0,120 0,150 0,180 0,240700 0,070 0,112 0,140 0,175 0,210 0,280800 0,080 0,128 0,160 0,200 0,240 0,320900 0,090 0,144 0,180 0,225 0,270 0,360

1000 0,100 0,160 0,200 0,250 0,300 0,400

Table 12: Airfl ow surface

Are

a A

in m

2

v in

m/s

∆pg = 250 Pa ∆pg = 500 Pa ∆pg = 1000 PaLW in dB/octave

L WA in

dB

(A)

L in

dB

(A)

LW in dB/octaveL W

A in

dB

(A)

L in

dB

(A)

LW in dB/octave

L WA in

dB

(A)

L in

dB

(A)

fm in Hz fm in Hz fm in Hz

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

1

3 68 68 67 67 65 63 72 64 74 74 73 73 71 69 78 70 81 82 81 81 80 77 86 786 73 73 72 71 69 67 76 68 78 79 78 77 76 74 82 74 84 85 84 84 84 82 90 829 79 78 78 76 75 73 82 74 79 80 81 80 80 78 86 78 86 88 87 86 86 85 92 84

12 81 81 80 79 78 76 85 77 85 85 84 84 82 81 89 81 87 89 89 90 89 88 95 87

Table 14: Case-radiated noise

Table 13: Flow noise

Are

a A

in m

2

v in

m/s

∆pg = 250 Pa ∆pg = 500 Pa ∆pg = 1000 PaLW in dB/octave

L WA in

dB

(A)

L in

dB

(A)

LW in dB/octave

L WA in

dB

(A)

L in

dB

(A)

LW in dB/octave

L WA in

dB

(A)

L in

dB

(A)

fm in Hz fm in Hz fm in Hz

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

1

3 75 68 62 56 51 50 65 57 82 74 68 63 58 53 72 64 90 82 77 72 67 60 80 726 80 72 66 58 54 50 69 61 85 80 73 66 62 57 76 68 95 85 79 75 70 66 83 759 85 75 70 61 58 54 73 65 85 79 75 67 65 61 77 69 95 87 82 75 71 69 85 77

12 86 77 71 63 60 57 74 66 90 83 78 70 66 64 80 72 94 87 84 78 73 71 86 78

Table 15: Correction factor for fl ow noise and case-radiated noise

A [m²] 0,04 0,06 0,08 0,10 0,12 0,16 0,2 0,25 0,3 0,4 0,5 0,6 0,8 1

CF [-] - 14 - 12 - 11 - 10 - 9 - 8 - 7 - 6 - 5 - 4 - 3 - 2 - 1 0

Defi nitions:fm in Hz: mid-band frequency of the octave bandLW in dB/Oktave: sound power level determined in the echo chamberLWA in dB(A): overall noise level, A-ratedL in dB(A): noise level, A-rated, room attenuation of 8 dB/octave considered∆pg in Pa: total pressure difference (measured in front of and behind the volume fl ow controller)V in m3/h: volume fl owv in m/s: fl ow velocityA in m2: airfl ow surface (W x H)CF correction factor

VAV700Multi-functional air volume fl ow controller with integrated web server

37 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

Connection diagram

1, 2, 3 Max. 3 static differential pressure sensorsOptional, up to 3 position-independent static differential pressure sensors with measuring ranges (-100 to +300 Pa), (-50 to +50 Pa) and / or (-100 to +1000 Pa) for vari-ous measuring tasks. The functionality for the static differential pressure sensor, like exhaust air / supply air, auxilary air, room pressure and / or duct pressure is freely confi gurable.

Lay out air hose kink-free in a loop against ingress of condensation

Check assignment of function to the air connec-tions!

Air hosing of static differential pressure sensors - Housing, right side

View: housing, right sideAir connection

(Example)Function Description

1 Exhaust air static differential pressure sensor -100 bis +300 Pa (connect plus and Minus hose)2 Auxilary air static differential pressure sensor -100 bis +300 Pa3 Room pressure static differential pressure sensor -50 bis +50 Pax Duct pressure static differential pressure sensor -100 bis +1000 Pa

Overview wiring and sensor hosing

i

i

1 2 3

X6VAV-

controller

VAV700

Actuator

Measuring system

Feedback Potentiometer

M

+ -

230 VAC Power lineX41

Temperature sensor, passive

Laptop

Optional Functional display

FA-2.0

BACnet/IP

OK

LOW

ECO

485 m³/h

Tag

X1 X8X9

X7

Digital In-/Output

X4

Analogue InputX3

Lay out air hose kink-free in a loop against ingress of

condensation

38 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

VAV700Multi-functional air volume fl ow controller with integrated web serverConnection overview

X41 Power Input 230 VAC The power supply is done via the plug at the left case-side.

Optional prewired cabling can be done with WAGO con-nectors / sockets or with IEC connectors. This simplifi es installation and prevents errors.

Attention! Always disconnect the mains input X41 power input light when working on the device.

- Ensure that the controller is power-free

Only after controller is power-free installation work must be carried out.

Power Input / Output - Plugs - Housing, left side

View: housing, left sidePlug /

SocketFunction Description

X41 Power supply Optional: WAGO socket for Power supply 230 VAC

!

X41 L

Power Supply

N

L1230 VAC

N

VAV700Multi-functional air volume fl ow controller with integrated web server

39 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

X1 X2 X3 X4 X5 X6 X7

X21

X22

FA-2.0 not applica-ble for VAV700

Analog Input PT100/PT1000

not appli-cable for VAV700

High speed actuator linear 0...10 VDC

Digital I/O2 x Opto-In

2 x Relay-Out

FA-2.0

FA-1.0

X23

High speed actuatorNMQ-12

Direct Drive

JP6

X20

CAN-Bus

JP7JP8

JP9JP1 JP2

JP3

JP4 JP5

Power Supply

SW1 SW2

SW3

Motherboard - Top view

Front

Outside connections housing, back side

40 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

VAV700Multi-functional air volume fl ow controller with integrated web server

Plug / Socket

Jumper External connections - Housing, back side

X1 FA-2.0, Functional display, 6-pole socket RJ45X2 Not applicable for VAV700X3 Analogue Input

JP9 Universal Analogue Input (special equipment)X4 PT100/PT1000, passive Temperature sensor

JP1, JP2, JP3 PT100/PT1000-AdaptionX5 Not applicable for VAV700X6 NMQ-12, High speed Actuator Direct DriveX7 Digital I/O, 2 x Opto In, 2 x Relay Out

SW1, SW2 Optocoupler Input via external voltage or dry contactJP4, JP5 RC-element (time delay)

In use of 24 VAC JP4 and/or JP5 plugged. In use of 24 VDC JP4 and/or JP5 not plugged.

Plug / Socket

Jumper Internal connections - Motherboard

X20 CAN-Bus plug for extension purposesSW3 Terminator 120 Ohm for CAN-Bus

X21 Second FA-2.0, Functional display, 6-pole socket RJ45JP7, JP8 Plug in jumper JP7 and JP8 if you use one FA-2.0. In case of two FA-2.0 jumper JP7 and

JP8 are not plugged = open.X22 Second FA-1.0, Functional display, 8-pole socket RJ45X23 Actuator, linear, 0...10 VDC

JP6 Signal swap X23, Pin 4 and 6 Signal GND/Power GNDNETZ Internal connection to power supply boardCPU CPU-Board with Ethernet-connection X8 and X9 (external connection at the back side).

CPU-Bord must always be plugged here.EMDP DP-Board with 1, 2 or 3 free confi gurable differential sensors assembled.

Extension module EMDP must always be plugged here.EM1 Extension module e. g. EM10, EM50, EMSC etc. optional plug-inEM2 Extension module e. g. EM10, EM50, EMSC etc. optional plug-inEM3 Extension module e. g. EM10, EM50, EMSC etc. optional plug-inEM4 Extension module e. g. EM10, EM50, EMSC etc. optional plug-in

Connection description - Motherboard - Top view

For terminal connections please refer to the VAV700 Wiring and connection diagram!!

VAV700Multi-functional air volume fl ow controller with integrated web server

41 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

Connection diagram

External connections - Housing, back side

X1 X2 X3 X4 X5 X6 X7

X1 Functional display 2. Generation (FA-2.0)The functional display has to be mounted visible for the operator (e.g. in the room).

Plug-in only the new functional display (FA-2.0 in X1 with 6-pin plug).

A second plug for the respective functional display generation (FA-2.0 = X21) is located on the inside on the motherboard.

ATTENTION on functional displays from the second generation! In use of one functional display FA-2.0 jumpers JP7 and JP8 must be plugged-in. In case of two functional dis-plays FA-2.0 jumpers JP7 and JP8 must be unplugged (=open).

These jumpers are located on the inside on the mother-board near the connector X21.

FA-2.0

i

X9 X8Grounding Cover

Grounding cable cover

X Function DescriptionX1 FA-2.0 Functional display 2. Generation,

FAZ0700 with graphic display, 6-pole plug

X2 FA-1.0 Not applicable for VAV700X3 A-In Analog InputX4 PT100 or

PT1000Temperature sensor input PT100 or PT1000

X Function DescriptionX5 AFS100 Not applicable for VAV700

X6 Actuator High speed damper actuatorNMQ-12, Direct-Drive-Mode

X7 Digital IN/OUT 2 x Optocoupler Input, 2 x Relay Output 2 x changeover 24 VAC/3 A

X8 ETHERNET Channel-IN-Dual-Port-SwitchX9 ETHERNET Channel-OUT-Dual-Port-Switch

42 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

VAV700Multi-functional air volume fl ow controller with integrated web serverConnection overview

Motherboard - Case open

Frontwith internal connections

Left sidefor Power Supply, Light and Auxilary

air

Right sidefor differential

presssure sensor connection

Back sidewith external connections

Plug / Socket

Minimum confi guration required for FC700, VAV700, DPC700

CPU CPU-Board with Ethernet-connection X8 and X9 (external connection at the back side). CPU-Bord must always be plugged here.

EMDP DP-Board with 1, 2 or 3 free confi gurable differential sensors assembled. Extension module EMDP must always be plugged here.

EM1 Extension module e. g. EM10, EM50 etc. optional plug-inEM2 Extension module e. g. EM10, EM50 etc. optional plug-inEM3 Extension module e. g. EM10, EM50 etc. optional plug-inEM4 Extension module e. g. EM10, EM50 etc. optional plug-in

CPU-Borad with Ethernet-sockets

X8, X9

EMDPwith 1, 2 or 3 static

differential pressure sensors

EM1 till EM4 forExtension modules, e. g. EM10, EM50, EMSC etc.

VAV700Multi-functional air volume fl ow controller with integrated web server

43 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

Technical data

GeneralNominal voltage 230 V AC/50/60 Hz/+-15 %Max. charging rate 200 mAMax. power input 35 V ARecovery time 600 msOperational temperature 0 OC to +55 OCHumidity max. 80 % relative, non-

condensingExternal supply 24 V AC/50/60 Hz/+-10 %Power input 20 V A

HousingProtection class IP 20Material steel plateColour white, RAL 9002Dimensions (LxWxH) (290 x 208 x 100) mmWeight approx. 2,8 kgAppliances terminals screw-type terminal 1,5

mm2

Relay outputsNumber 1 light relayOperating principle make contactMax. switching voltage 24 V ACMax. steady current 3 A

Digital inputs (galvanically isolated)Number 2 optocouplerMax. input voltage 24 V DC +-15 %Max. input circuit 10 mA (per input)

Analogue input1 input 0(2) - 10 V DC, 1 mA

Differential pressure transmitterNumber 3Measuring principle staticPressure range -100 - 300 Pascal

8 - 800 Pascal optionalResponse time < 10 msSensor burst pressure 500 mbar

Maintenance-free measuring system MD with damper

Material polypropylene (PPs)Measuring system integrated measuring

system with two ring chambers

Optional instead of MD: Venturi measuring device VD with damper Material PPs, PPs-el, PVCMeasuring system integrated Venturi

measuring nozzle

Optional instead of MD, VD: Measuring nozzle DD with damper Material galvanised steel, stainless

steel 1.4301 (V2A)Measuring system integrated measuring

nozzle

Optional instead of MD, VD, DD: Measuring cross KD with damper Material galvanised steel, stainless

steel1.4301 (V2A)Measuring system integrated measuring cross

ActuatorFull load 3 NmRegulating time 3 s for 90 °Activation direct with integrated fl ow

monitoringResolution < 0,5 °Feedback delay angle < 0,5 ° via potentiometer

ETHERNET specifi cation Amount 1 dual port switchVelocity 100 MBitCable CAT 6

BACnet® specifi cationInterface Ethernet, TCP/IPoptional RS 485, MS/TP

Modbus® specifi cation (optional)Interface Ethernet, TCP/IPoptional RS 485, MS/TP

44 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com

VAV700Multi-functional air volume fl ow controller with integrated web serverDimensions ● Scale drawings

Housing VAV700: top view

Housing VAV700: side view

325

200

180

315

300

10

20

95

200

Static differential pressure sensor (max. 3)

+ Connection = positive pressure- Connection = negative pressure

+ -

+ -

+ -

Cha

nges

rese

rved

• A

ll rig

hts

rese

rved

© S

CH

NE

IDE

R

Tender specifi cation VAV700For the complete tender specifi cation please visit our websitewww.schneider-elektronik.com

SCHNEIDER Elektronik GmbH Phone: +49 (0) 6171 / 88 479 - 0 Industriestraße 4 Fax: +49 (0) 6171 / 88 479 - 9961449 Steinbach • Germany e-mail: [email protected]