CAV-S Mechanical constant volume ow controller, steel 1 Technical Documentation CAV-S • Date: 11/2012 • Subject to change without prior notice • www.schneider-elektronik.com Features Housing design available in round or rectangular Self-acting constant ow regulator made of galvanized steel Suitable for supply or exhaust air volume control Mountable in any position Externally accessible adjuster for adjustable volume ow rate setpoints Flow range > 7:1 Control spring stainless steel Low friction damping element Differential pressure range 50 .. 500 Pa High accuracy of the adjusted volume ow rates of ± 5 %, based on VNOM Operating temperature 10 to +50 °C Storage temperature -20 to +60 °C Without auxiliary power Product description Function description Features Product description The mechanical constant ow volumetric controller CAV-S is made of galvanized steel and works independently wi- thout requiring additional energy. The housing design is available in round or rectangular Functions description The central ball-bearing ap is moved by the air current. The control unit with control cam, spring and damper is at- tached to the outside of the galvanised sheet steel housing. The required volumetric ow is set in-factory. An adjustment of the volumetric ow at a later stage is possible (setting cam on housing). The control unit is protected with a cover. The controller can be assembled in any assembly position. For maintenance, service, retrotting, etc., inspection ope- nings in sufcient number and size must be provided on- site. Available connections are socket/socket, ange/ange or pipe/pipe. The constant volume ow controller CAV-S is suitable for supply and exhaust air ow control and the air volumes set- points are step adjustable (1...10 steps). To ensure accuracy, a sufcient ow route should be maintained. Attention: The CAV-S is an adjusted controller working by the mechanism of action principle. Tampering with the controller, whether manually or mechanically, is prohibited. When a high volumetric ow setting has been selected, the damper leaf must never be closed manually. Otherwise, the control mechanism will be changed, resulting in a loss of control accuracy. The range of application must always be complied with. If the CAV-S is used beyond its allowed range of application, this will result in mechanical overload and thus in a loss of control accuracy. We would like to point out that to clean the stainless steel design, only suitable corresponding cleaning materials must be used! CAV-S, rectangular CAV-S, round

CAV-S Mechanical constant volume fl ow controller, steel (galvanized... · CAV-S Mechanical constant volume fl ow controller, steel 2 Technical Documentation CAV-S • Date: 11/2012

  • Upload
    donhi

  • View
    220

  • Download
    0

Embed Size (px)

Citation preview

Page 1: CAV-S Mechanical constant volume fl ow controller, steel (galvanized... · CAV-S Mechanical constant volume fl ow controller, steel 2 Technical Documentation CAV-S • Date: 11/2012

CAV-SMechanical constant volume fl ow controller, steel

1 Technical Documentation CAV-S • Date: 11/2012 • Subject to change without prior notice • www.schneider-elektronik.com

Features Housing design available in round or rectangular Self-acting constant fl ow regulator made of galvanized

steel Suitable for supply or exhaust air volume control Mountable in any position Externally accessible adjuster for adjustable volume fl ow rate setpoints Flow range > 7:1 Control spring stainless steel Low friction damping element Differential pressure range 50 .. 500 Pa High accuracy of the adjusted volume fl ow rates

of ± 5 %, based on VNOM Operating temperature 10 to +50 °C Storage temperature -20 to +60 °C Without auxiliary power

Product description ● Function description ● Features

Product description

The mechanical constant fl ow volumetric controller CAV-S is made of galvanized steel and works independently wi-thout requiring additional energy. The housing design is available in round or rectangular

Functions description

The central ball-bearing fl ap is moved by the air current. The control unit with control cam, spring and damper is at-tached to the outside of the galvanised sheet steel housing.

The required volumetric fl ow is set in-factory. An adjustment of the volumetric fl ow at a later stage is possible (setting cam on housing). The control unit is protected with a cover. The controller can be assembled in any assembly position.

For maintenance, service, retrofi tting, etc., inspection ope-nings in suffi cient number and size must be provided on-site.

Available connections are socket/socket, fl ange/fl ange or pipe/pipe.

The constant volume fl ow controller CAV-S is suitable for supply and exhaust air fl ow control and the air volumes set-points are step adjustable (1...10 steps).

To ensure accuracy, a suffi cient fl ow route should be maintained.

Attention:

The CAV-S is an adjusted controller working by the mechanism of action principle. Tampering with the controller, whether manually or mechanically, is prohibited. When a high volumetric fl ow setting has been selected, the damper leaf must never be closed manually. Otherwise, the control mechanism will be changed, resulting in a loss of control accuracy.

The range of application must always be complied with. If the CAV-S is used beyond its allowed range of application, this will result in mechanical overload and thus in a loss of control accuracy.

We would like to point out that to clean the stainless steel design, only suitable corresponding cleaning materials must be used!

CAV-S, rectangular

CAV-S, round

Page 2: CAV-S Mechanical constant volume fl ow controller, steel (galvanized... · CAV-S Mechanical constant volume fl ow controller, steel 2 Technical Documentation CAV-S • Date: 11/2012

CAV-SMechanical constant volume fl ow controller, steel

2 Technical Documentation CAV-S • Date: 11/2012 • Subject to change without prior notice • www.schneider-elektronik.com

Diameter 250, galvanized steel, without rubber lip seal, without DD-coating, without insulation shell, pipe/pipe.

Make: SCHNEIDER Type: CAV-250-S-0-0-0-RR

Ordering example: Mechanical constant volume fl ow controller, round

CAV 250 - S RR - -

Material caseGalvanized steel SStainless steel 1.4301 V2Stainless steel 1.4571 V4

Type

Diameter DN [mm]80, 100, 125, 160, 200, 250, 315, 400 80

...400

0

Acoustic cladding0 withoutD with

-

Order code: Mechanical constant volume fl ow controller - round

Pipe connectionsIn- Outfl ow Remarks

RR Pipe Pipe Steel and stainless steelFF Flange Flange Steel and stainless steel

DD-coating0 without

DD with

0 -

Rubber lip seal0 withoutG with

0 -

CAV 400 - S -

Type

Width B [mm]200, 300, 400, 500, 600 200

...600

0

Acoustic cladding0 withoutD with

-

Order code: Mechanical constant volume fl ow controller - rectangular

DD-coating0 without

DD with

0 -200 -

Height H [mm]100, 150, 200, 250, 300, 400 100

...400

Material caseS Galvanized steel

Width=400 mm, Height=200 mm, Galvanized steel, without DD-coating, without insulation shell.

Make: SCHNEIDER Type: CAV-400-200-S-0-0

Ordering example: Mechanical constant volume fl ow controller, rectangular

Page 3: CAV-S Mechanical constant volume fl ow controller, steel (galvanized... · CAV-S Mechanical constant volume fl ow controller, steel 2 Technical Documentation CAV-S • Date: 11/2012

CAV-SMechanical constant volume fl ow controller, steel

3 Technical Documentation CAV-S • Date: 11/2012 • Subject to change without prior notice • www.schneider-elektronik.com

Nominal size V (m³/h) V [l/s]NW [mm] min. max. min. max.

80 31 210 9 58

100 48 383 13 106

125 81 558 23 155

160 112 902 31 251

200 177 1442 49 401

250 240 2280 67 633

315 326 3299 91 916

400 429 4571 119 1270

Volumetric fl ow range CAV-S-round

Distance to: round rectangularConnection piece with bend 1 x D 1 x diagonalOther connection pieces:branching or reducing piece, T-junction, etc.

2 x D 2 x diagonal

Fire damper 2 x D 2 x diagonalSilencer 2 x D 2 x diagonal

Installation information

To avoid unnecessary controller errors, the min. distances according to the following table / drawings must be observed. For combinations of several connection pieces or pieces with fi re dampers or silencers, the larger minimum distances must be observed.

The volumetric fl ow controllers round and rectangular can be assembled with horizontal or vertical damper axis.

V (m³/h) V [l/s] Width x Height min. max. min. max.

B[mm]

H[mm]

200 100 50 820 14 228

300 100 48 1161 13 323

300 150 213 1484 59 412

300 200 224 1830 62 508

400 446 2924 124 812

500 723 3188 201 886

600 656 3517 182 977

400 250 571 3180 159 883

500 712 4219 198 1172

600 767 4690 213 1303

400 300 661 4441 184 1234

500 871 5020 242 1701

600 395 5784 110 1607

400 400 276 5630 77 1564

500 806 6125 224 1701

Volumetric fl ow range CAV-S-rectangular

Installation information CAV-S-roundDistance to a connection piece with bend

Installation information CAV-S-rectangularDistance to a connection piece with bend

Distance to other connection pieces ( e.g. branching or reducing piece, T-junction, etc.) , fi re damper or silencer

Distance to other connection pieces ( e.g. branching or reducing piece, T-junction, etc.) , fi re damper or silencer

Page 4: CAV-S Mechanical constant volume fl ow controller, steel (galvanized... · CAV-S Mechanical constant volume fl ow controller, steel 2 Technical Documentation CAV-S • Date: 11/2012

CAV-SMechanical constant volume fl ow controller, steel

4 Technical Documentation CAV-S • Date: 11/2012 • Subject to change without prior notice • www.schneider-elektronik.com

Nominal size Constant air volume fl ow controller - roundStep adjustable volume fl ow setpoints [m³/h]

NW [mm] Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step 9 Step 1080 31 37 47 89 127 160 186 204 209 210

100 48 64 128 195 248 302 332 352 379 383

125 81 95 199 277 355 411 470 506 526 558

160 112 144 233 352 501 624 733 823 871 902

200 177 262 440 577 843 952 1129 1250 1362 1442

250 240 346 541 844 1156 1498 1781 1990 2167 2280

315 326 555 957 1356 1882 2293 2661 2907 3128 3299

400 429 853 1545 2039 2672 3284 3660 4118 4365 4571

Constant air volume fl ow controller - rectangular Width x Height Step adjustable volume fl ow setpoints [m³/h]

B[mm]

H[mm]

Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step 9 Step 10

200 100 50 114 247 374 521 602 699 737 790 820

300 100 48 190 210 360 583 763 880 1041 1142 1161

300 150 213 259 432 620 853 986 1169 1290 1392 1484

300 200 224 319 400 729 958 1198 1333 1589 1731 1830

400 446 789 1128 1534 1819 2199 2406 2662 2813 2924

500 723 778 1270 1501 1988 2335 2730 2931 3078 3188

600 656 786 1170 1540 1976 2449 2733 3152 3307 3517

400 250 571 883 1200 1559 1963 2351 2752 2931 3075 3180

500 712 996 1368 1778 2334 2846 3233 3700 4005 4219

600 767 950 1344 1920 2531 3077 3668 4061 4408 4690

400 300 661 1013 1485 1994 2553 3141 3579 3954 4269 4441

500 871 1352 1766 2389 3070 3665 4255 4519 4826 5020

600 395 1159 1519 2255 2925 3779 4454 4933 5447 5784

400 400 276 1373 1813 2831 3523 4123 4717 5134 5405 5630

500 806 1539 2248 3151 3823 4436 4983 5405 5813 6125

Page 5: CAV-S Mechanical constant volume fl ow controller, steel (galvanized... · CAV-S Mechanical constant volume fl ow controller, steel 2 Technical Documentation CAV-S • Date: 11/2012

CAV-SMechanical constant volume fl ow controller, steel

5 Technical Documentation CAV-S • Date: 11/2012 • Subject to change without prior notice • www.schneider-elektronik.com

Flow generated noise CAV-S, round

Page 6: CAV-S Mechanical constant volume fl ow controller, steel (galvanized... · CAV-S Mechanical constant volume fl ow controller, steel 2 Technical Documentation CAV-S • Date: 11/2012

CAV-SMechanical constant volume fl ow controller, steel

6 Technical Documentation CAV-S • Date: 11/2012 • Subject to change without prior notice • www.schneider-elektronik.com

Radiaded noise CAV-S, round

Page 7: CAV-S Mechanical constant volume fl ow controller, steel (galvanized... · CAV-S Mechanical constant volume fl ow controller, steel 2 Technical Documentation CAV-S • Date: 11/2012

CAV-SMechanical constant volume fl ow controller, steel

7 Technical Documentation CAV-S • Date: 11/2012 • Subject to change without prior notice • www.schneider-elektronik.com

Radiaded noise CAV-S, round, with acoustic cladding

Page 8: CAV-S Mechanical constant volume fl ow controller, steel (galvanized... · CAV-S Mechanical constant volume fl ow controller, steel 2 Technical Documentation CAV-S • Date: 11/2012

CAV-SMechanical constant volume fl ow controller, steel

8 Technical Documentation CAV-S • Date: 11/2012 • Subject to change without prior notice • www.schneider-elektronik.com

Flow generated noise CAV-S, rectangular

Page 9: CAV-S Mechanical constant volume fl ow controller, steel (galvanized... · CAV-S Mechanical constant volume fl ow controller, steel 2 Technical Documentation CAV-S • Date: 11/2012

CAV-SMechanical constant volume fl ow controller, steel

9 Technical Documentation CAV-S • Date: 11/2012 • Subject to change without prior notice • www.schneider-elektronik.com

Flow generated noise CAV-S, rectangular

Page 10: CAV-S Mechanical constant volume fl ow controller, steel (galvanized... · CAV-S Mechanical constant volume fl ow controller, steel 2 Technical Documentation CAV-S • Date: 11/2012

CAV-SMechanical constant volume fl ow controller, steel

10 Technical Documentation CAV-S • Date: 11/2012 • Subject to change without prior notice • www.schneider-elektronik.com

Radiaded noise CAV-S, rectangular

Page 11: CAV-S Mechanical constant volume fl ow controller, steel (galvanized... · CAV-S Mechanical constant volume fl ow controller, steel 2 Technical Documentation CAV-S • Date: 11/2012

CAV-SMechanical constant volume fl ow controller, steel

11 Technical Documentation CAV-S • Date: 11/2012 • Subject to change without prior notice • www.schneider-elektronik.com

Radiaded noise CAV-S, rectangular

Page 12: CAV-S Mechanical constant volume fl ow controller, steel (galvanized... · CAV-S Mechanical constant volume fl ow controller, steel 2 Technical Documentation CAV-S • Date: 11/2012

CAV-SMechanical constant volume fl ow controller, steel

12 Technical Documentation CAV-S • Date: 11/2012 • Subject to change without prior notice • www.schneider-elektronik.com

Radiaded noise CAV-S, rectangular, with acoustic cladding

Page 13: CAV-S Mechanical constant volume fl ow controller, steel (galvanized... · CAV-S Mechanical constant volume fl ow controller, steel 2 Technical Documentation CAV-S • Date: 11/2012

CAV-SMechanical constant volume fl ow controller, steel

13 Technical Documentation CAV-S • Date: 11/2012 • Subject to change without prior notice • www.schneider-elektronik.com

Radiaded noise CAV-S, rectangular, with acoustic cladding

Page 14: CAV-S Mechanical constant volume fl ow controller, steel (galvanized... · CAV-S Mechanical constant volume fl ow controller, steel 2 Technical Documentation CAV-S • Date: 11/2012

CAV-SMechanical constant volume fl ow controller, steel

14 Technical Documentation CAV-S • Date: 11/2012 • Subject to change without prior notice • www.schneider-elektronik.com

SCHNEIDER Elektronik GmbH Phone: +49 (0) 6171 / 88 479 - 0 Industriestraße 4 Fax: +49 (0) 6171 / 88 479 - 9961449 Steinbach • Germany e-mail: [email protected]

No

liabi

lity

for m

ispr

int o

r mod

ifi ca

tions

• A

ll rig

hts

rese

rved

© S

CH

NE

IDE

R

Models and dimensions

The CAV-S, rectangle is only delivered in right-hand design. If the control unit is required on the left-hand side, the CAV-S must be rotated by 180°.

Available sizes CAV-S, roundNominal size

NW[mm]

ØD[mm]

L[mm]

80 78 290100 98 290125 123 290160 158 290200 198 290250 248 390315 313 390400 398 490

Available sizes CAV-S, rectangleHeight H Width B

200 300 400 500 600100 x x - - -150 - x - - -200 - x x x x250 - - x x x300 - - x x x400 - - x x -

x = available- = not availableLR = Air fl ow direction

Tender specifi cation CAV-S, roundMechanical volumetric fl ow controller type CAV-S, in rounddesign, right-hand model, for constant volumetric fl ow re-gulation for duct connection to DIN EN 12237. Housing and control damper made of galvanised sheet steel, control housing made of plastic. Externally accessible adjusting for step adjustable fl ow rate setpoints. Differential pressure range 50 to 500 Pa, tolerance range typically ± 5 %, opera-ting temperature 10 to +50 °C.

Product: SCHNEIDER Type: CAV-S Size:

Tender specifi cation CAV-S, rectangleMechanical volumetric fl ow controller type CAV-S, in rectan-gle design, right-hand model, for constant volumetric fl ow regulation for duct connection to DIN EN 12237. Housing and control damper made of galvanised sheet steel, con-trol housing made of plastic. Externally accessible adjusting for step adjustable fl ow rate setpoints. Differential pressure range 50 to 500 Pa, tolerance range typically ± 5 %, opera-ting temperature 10 to +50 °C.

Product: SCHNEIDER Type: CAV-S Size: