68
USER GUIDE Model: IQ Variable Speed Drive Three Phase

Vada Three Phase Manual | Reece Plumbing you for choosing Vada high performance IQ Drive series. ... Resistance 120%, 1 minute Torque Boost Manual Torque Boost (0~10%) Opera-tion

Embed Size (px)

Citation preview

User GUideModel: IQ Variable Speed Drive

Three Phase

BLANK PAGE

│ 3

SAFETY PRECAUTIONS

PrefaceThank you for choosing Vada high performance IQ Drive series.

The IQ Drive is a dedicated pump drive designed for variable speed pumping systems.

The IQ Drive is manufactured with high quality components and materials and incorporates the

latest microprocessor technology.

Before installation and operation please read the instruction manual thoroughly.

Note: The information contained in this manual is subject to change without prior notice.

Safety PrecautionsThis manual contains two kinds of marks: “WARNING” and “CAUTION”.

• These marks are designed to prevent the health and safety hazard and damage to the pump unit and drive.

• In order to prevent misuse of the drive, please ensure that you read the manual through to the end before use.

• Please keep this manual where the user can read it at any time.

Warning:Indicates a potential dangerous situation which may result in serious injury or

death if instruction is not observed.

Caution:Indicates a potential dangerous situation which may result damage to the drive

or loss of property if instruction is not observed.

4 │

SAFETY PRECAUTIONS

• Do not open cover whilst drive is in a powered state or operation.(Exposed terminals may result in electric shock)

• Do not open cover when power is off except for wiring or electrical inspection. (When power is off, residual charge may still result in electrical shock)

• During wiring or inspection work cut power, wait 10 minutes and check with electrical tester that there is no residual charge before commencing work. (When power is off, residual charge may still result in electrical shock. Do not commence work until residual charge is 30V or less)

• Do not operate the switch or drive with wet hands. (It may cause electric shock.)

• If any part of drive input or cable jacket is damaged, do not apply electricity or operate the equipment. (It may cause electric shock.)

• Do not put any stress on the input/output power or signal cables (It may damage on the cable jacket to cause electric shock.)

• Do not turn on power if drive is damaged or if any part is damaged (It may cause electric shock.)

• Do not touch the drive during powered state or several minutes after power is turned off. (Drive can generate high temperatures during operation, body contact may cause burn.)

• Do not install the equipment near the inflammable materials.

(Installation on or near the inflammable materials may cause fire.)

• When drive has any fault, cut off the input power.

(Failure to cut power may result in a fire hazard.)

• Do not leave any objects inside of drive. eg. screw, metal, water, oil, etc.

(May result in fire hazard.)

│ 5

SAFETY PRECAUTIONS

Cautions for UseA. Transportation and Installation• Transport the product using the correct method for its weight

• Do not stack the product with more than specified layers.

• Install the drive as per the instructions in the User’s Manual.

• Do not open during transportation

• Do not place any heavy objects on top of drive.

• Do not drop the drive or subject it to sudden impacts.

• Do not operate drive in conditions outside of those specified below.

Installation Location Keep away from corrosive or inflammable gases, liquids or dust

Temperature/Humidity -10 ~ 40°C / Not more than 90% relative humidity

Storage Temperature -20 ~ 65°C

Elevation Altitude 1000m or lower

Vibration <5.9m/sec2 (0.6G)

Ambient Air Pressure 70 ~ 106kpa

B. Wiring• Wiring and inspection to be completed by a qualified electrician

• After Installing the drive body, begin wiring.

• Do not install a static capacitor, radio noise filter or any other device on the output terminals of the drive.

• Confirm that the power input and motor output wires are installed correctly as per the user’s manual.

• Use a circuit breaker between the power supply and the drive.

• Do not install earth leakage breaker (RCD) at the power input.

• If there are any problems or issues contact your local Reece branch.

6 │

SAFETY PRECAUTIONS

C. Startup Checks• Check setup parameters before operating.

• Check to ensure that terminal block main power and control circuits are wired correctly as per the user manual.

• Use pressure sensors and low water level sensors specified by Vada.

D. Operation• Take care when turning on power as drive has automatic restart and recovery function and may

start immediately when power is applied.

• Do not modify or make changes to drive.

• Do not start or stop drive with electrical contactor installed at the power input.

• Install EMC filters when required to reduce impact from electromagnetic interference and protect nearby electrical equipment.

• Install input reactor when input voltage is unbalanced.

• Only use the drive on electric motors designed for use with variable frequency drives (motors of this type are protected against voltage spikes from the output of the drive.)

• If initialising parameters, setup is required as values will be reset to factory settings

E. Drive Failure or Malfunction• In order to prevent downtime of pump units, it is recommended that an auxiliary unit is installed.

• If drive fails or malfunctions, refer to Chapter 7.

│ 7

CONTENTS

Chapter 1. Basic Information 9

1.1 Nameplate Information 9

1.2 Drive Identification 9

Chapter 2. Specifications 10

2.1 Drive Specifications 10

Chapter 3. Dimensions 12

3.1 IQ-0075T ~ IQ-0220T 12

3.2 IQ-0400T 13

3.3 IQ-0550T ~ IQ-0750T 14

3.4 IQ-1100T ~ IQ-1500T 15

3.5 IQ-1850T ~ IQ-2200T 16

Chapter 4. Installation 17

4.1 Installation Precautions 17

4.2 Terminal Wiring Diagram 18

4.3 Main Power Supply Circuit Wiring 19

4.4 Control Circuit Wiring 21

Chapter 5. Operation 26

5.1 FND 26

5.2 Function Setup 29

5.3 Basic Operation 32

8 │

CONTENTS

Chapter 6. Function Table & Description 39

6.1 Present Status Display 39

6.2 Pump Control Group 40

6.3 Drive Control Group 42

6.4 Pump Control Group Parameter Functions 44

6.5 Drive Control Group Parameter Functions 52

Chapter 7. Troubleshooting 60

7.1 Fault History Table 60

7.2 Reset of Fault and Alarm 60

7.3 Troubleshooting Guide 61

│ 9

CHAPTER 1. BASIC INFORMATION

1.1 Nameplate Information

After taking drive out of package box, check the namesplate on the side to verify that the Model,

Input Specification and Output Specification match the ordered product.

Check that the drive has not sustained any damage during transportation.

If the drive is damaged in anyway or the specifications do not match the ordered product contact

your local Reece branch.

Type of DriveInput Specification

Output Specification

1.2 Drive Identification

Indicates the multi-drive control type. (Omitted for single type)

T: Three phase input.

Indicates capacity in 00.00kW.

• Product model name is indicated as above. Initial 4 digits indicate driving capacity of the drive in 00.00kW format. Decimal point is not indicated.

• ‘T’ refers to Three phase

• ‘D’ means CAN Driver indicating multi-drive control system. If it is a single type, D will be omitted.

I

Protection Class : IP55

IQ-0075-T3Ø 50-60Hz380-415V3Ø 0-60Hz380V - 460V 16A

DOOXX0074

10 │

CHAPTER 2. SPECIFICATIONS

2.1 Drive Specifications

Model IQ-_____S, T(D) 0075 0150 0220 0400 0550 0750 1100 1500 1850 2200

Standard Motor [kW] 0.75 1.5 2.2 4 5.5 7.5 11 15 18.5 22

Standard Motor [HP] 1 2 3 5.5 7.5 10 15 20 25 30

Rated Output

Output Capacity [kVA]

2 2.6 4 5.9 7.9 10.5 15.8 19.7 25.7 29.6

Rated OutputCurrent [A]

3 4 6 9 12 16 24 30 39 45

Output Voltage [V] 380-415

Output Frequency [Hz]

0.05 ~ 50 / 60

Rated Input

Rated Input Voltage [V]

3φ 380V (-15% ~ +10%)

Input Frequency [Hz]

50 / 60 (±5%)

Protection Class IP55

Switching Frequency [kHz] 2 ~ 15

Cooling Natural Cooling Forced Fan Cooling

Control

Controlling Method

V/F Control, Slip Compensation Control

Frequency Stability

1% of Rated Frequency

Overload Resistance

120%, 1 minute

Torque Boost Manual Torque Boost (0~10%)

Opera-tion

Operation Method FND / Terminal / Communication (CAN) Operation

Frequency Setting

FND / Terminal (0~10V or 4~20mA)

Acceleration/ Deceleration Time

1 ~ 600 Sec.

Abnormal Reset Automatic Reset upon Automatic Restart Setting

Output Signal

Abnormal Output Output Contact (FLT-AT,CT,BT), LED Output

Operation Status Output Contact (RUN-AT,CT,BT), LED Output

Other Functions

Freezing Protection for Pump, Auto Recovery after Power Fail, High/Low Pressure Alarm, Low Water Level Detection, Multi-Drive Control,

Failure History Storage, Forced Alternative Operation, PID Control, No Flow Detection, Dry running Protection

Protection FunctionsHigh Voltage, Low Voltage, Over Current, Surge, Overload, Inverter

Overheating, Output Wire Disconnection, Communication Error

│ 11

Display Code

Drive InformationOutput Frequency, Pump’s Current Pressure, Pump’s Setting

Pressure, DC Voltage, Output Current, Input/Output Pressure (on Differential Pressure Control)

Abnormality Information

Pressure Sensor Error, High/Low Pressure Alarm, Low Level Alarm, Drive Error

Use Condition

Installation Altitude 1,000M or lower

Location Keep from Corrosive Gases and Liquid, Dust

Ambient Temperature

-10°C ~ 40°C

Storage Temperature

-20°C ~ 60°C

Ambient Humidity Under 90% RH (No Due)

Vibration Below 5.8m/sec²(0.6g)

CHAPTER 2. SPECIFICATIONS

12 │

CHAPTER 3. DIMENSIONS

3.1 IQ-0075T ~ IQ-0220T

Model H (mm) W (mm) D (mm) W1 (mm) D1 (mm) Weight (kg)

IQ-0075T 143 151 229 133 217 2.9

IQ-0150T 143 151 229 133 217 2.9

IQ-0220T 143 151 229 133 217 3

│ 13

3.2 IQ-0400T

CHAPTER 3. DIMENSIONS

Model H (mm) W (mm) D (mm) W1 (mm) D1 (mm) Weight (kg)

IQ-0400T 162 151 229 133 217 3.3

14 │

3.3 IQ-0550T ~ IQ-0750T

CHAPTER 3. DIMENSIONS

Model H (mm) W (mm) D (mm) W1 (mm) D1 (mm) Weight (kg)

IQ-0550T 176 290 290 189 277 5.5

IQ-0750T 176 290 290 189 277 5.7

│ 15

3.4 IQ-1100T ~ IQ-1500T

CHAPTER 3. DIMENSIONS

Model H (mm) W (mm) D (mm) W1 (mm) D1 (mm) Weight (kg)

IQ-1100T 290 390 186 277 185 27

IQ-1500T 290 390 186 277 185 27

16 │

3.5 IQ-1850T ~ IQ-2200T

CHAPTER 3. DIMENSIONS

Model H (mm) W (mm) D (mm) W1 (mm) D1 (mm) Weight (kg)

IQ-1850T 290 440 186 277 210 30

IQ-2200T 290 440 186 277 210 30

│ 17

CHAPTER 4. INSTALLATION

4.1 Installation Precautions

A. Take care when handling

Drive consists of sensitive electric/electronic devices. Take care to prevent damage due to rough

handling during transportation and installation.

B. Minimize Vibration

Drive is susceptible to damage due to excessive vibration. If mounting drive directly onto motor or

piping, take measures to prevent damage due to excessive vibration.

C. Caution: Ambient Temperature

The drive has an allowable ambient temperature range of between -10 ~ 40ºC. If ambient

temperature exceeds these limits, reduce the output rating of the drive before use.

D. Install on non-flammable/ incombustible materials

The drive will generate heat and become hot during operation. To minimise fire hazards, mount the

drive on non-flammable/ incombustible materials.

E. Allow sufficient space for effective cooling

Install drive ensuring that air flow to the cooling fins is not obstructed

F. If the drive is installed off the motor, install the drive securely in upright position.

18 │

4.2 Terminal Wiring Diagram

CHAPTER 4. INSTALLATION

MCCB

3 � 380 VAC Input 50/60 Hz

Main Power Circuit

S

T

U

V

W

FG

Motor

S1P

S1N

S2P

S2N

PressureSensor1(4~20mA)

Pressure Sensor2 (4~20mA)

LV1

LV2Low Level Sensor (Pulse)

CANH

CG

CANL

1

BT

Control Circuit

R

CAN Communication Terminal

Running CnditionOutput

V1

VGND

I1

4~20mA

0~10V

AT

CT

BT

AT

CT

RUN

FAULT

Command of (RUN

CG

ESTOP

RUN

CG

24V

Emergency STOP)

Setting Frequency Input

Setting Frequency Input

Drive Fault OutputAC250V(DC30V), 5A

485_TX

CG

485_RX

RS 485 CommunicationTerminal(Option)

RS 485 (Option))

NPN CONNECTION

NPNPNP

SHORTOPEN

(Differential Pressure Control Only)

(P1)

│ 19

CHAPTER 4. INSTALLATION

4.3 Main Power Supply Circuit Wiring

Main Power Supply Terminals

Terminal Name Description

R, S, T AC Input Connect to commercial AC input

FG Earth Connect to earth

U, V, W Drive Output Connect to Motor

Precautions on Main Power Supply Wiring

• Ensure power supply is disconnected and there is no residual charge in drive (<30V)

• Install circuit breaker (MCCB) between AC input power and drive input power terminals (R, S, T). Use a circuit breaker with a capacity 1.5 ~ 2 times larger than the rated current.

• EMI can occur due to the high speed switching of the drive and can cause radio interference on nearby electrical equipment. In order to minimise radio interference, install EMC filters between

• AC power input and the drive where required.

• AC input terminals (R, S, T) can be connected regardless of phase sequence of input power.

• When connecting output terminals of the drive to the input terminals of the motor, consider the rotation direction of the motor. In order to reverse the direction of the motor swap any two of the drive terminals (U, V, W). May also be altered through programming.

• In order to prevent damage to the drive, take care not to short circuit or earth the drive output terminals (U, V ,W).

• Do not connect static condenser or noise filter at the output of the drive as it may cause the drive to frequently trip. This may result in damage to the devices due to overheating.

• Use wires of the specified size for the drive input/output. Failure to use wires of appropriate size may result in a reduction in voltage and may result in a fire hazard due to overheating.

• Maintain wiring distance between motor and drive less than 50 metres. If drive is installed further away than this, use a motor with reinforced insulation or micro-surge filter.

Precautions on Earth Wiring

• A leak current is produced from the high speed switching of the drive so an earth connection is required to prevent electric shock.

• Maintain earth resistance within 10Ω during earthing work.

• Use wire tas shown in the table below for the earth connection.

20 │

CHAPTER 4. INSTALLATION

Wire and Terminal Screw Recommended Specifications

Drive Capacity

Size of Terminal Screw

Fastening Torque for Screw (N.m)

Thickness of Wires

mm² (AWG)

R,S,T U,V,W FG

0.75 kW M4 1.2~1.5 2.5(14) 2.5(14) 2.5(14)

1.5 kW M4 1.2~1.5 2.5(14) 2.5(14) 2.5(14)

2.2 kW M4 1.2~1.5 4.0(12) 4.0(12) 4.0(12)

4 kW M4 1.2~1.5 4.0(12) 4.0(12) 4.0(12)

5.5 kW M5 2.5 6.0(10) 6.0(10) 6.0(10)

7.5 kW M5 2.5 6.0(10) 6.0(10) 6.0(10)

11 kW M6 4~5 10(8) 10(8) 10(8)

15 kW M6 4~5 10(8) 10(8) 10(8)

18.5 kW M6 4~5 16(6) 16(6) 16(6)

22 kW M6 4~5 25(4) 25(4) 25(4)

• Apply specified torque for fastening the terminal screws.

• Use 600V class wire.

│ 21

4.4 Control Circuit Wiring

Control Terminal Block Arrangement

Power Range: 0.75 ~ 4kW

CHAPTER 4. INSTALLATION

22 │

Power Range: 5.5 ~ 22kW

CHAPTER 4. INSTALLATION

│ 23

CHAPTER 4. INSTALLATION

Control Terminal Block Functions

Classification Terminal Sign Terminal Name Description

Input Signal

Pump Control

S1P, S1N Pressure Sensor 1Connection terminal for Pressure Sensor 1

S2P, S2N Pressure Sensor 2Connection terminal for Pressure Sensor 2 (used for differential pressure control)

LV1, LV2 Low Level SensorConnection terminal for low level sensor

Contact Operation

P1Operation Command

Run/Stop Terminal

EST Emergency StopWhen EST signal is ON, it turns off drive output.

24VContact Operation Common Terminal

Common terminal of input terminal for PNP contact.

CGContact Operation Common Terminal

Common terminal of input terminal for NPN contact.

Analog Frequency

Setup

V1Frequency Setup

(Voltage)If entering DC 0~10V, it makes setup frequency.

I1Frequency Setup

(Current)If entering DC 4~20mA it makes setup frequency.

GNDFrequency Setup

(Common Terminal)

Common terminal for Analog frequency setup terminal

Output Signal

Relay Contact

RUN (AT,CT,BT)

Normal Signal Output

It outputs signal when drive is running. (≤AC250V 5A, ≤ DC30V 5A)

FAULT (AT,CT,BT)

Multi-function Output

Outputs signal on drive fault or protection function. (≤AC250V 5A, ≤DC30V 5A)

Com. Signal

CAN

CANH, CANL CAN Signal CAN signal line terminal

CGCAN Common

TerminalCommon terminal of power ground for CAN

RS485 (Option)

TX, RX (AUX1, AUX2)

RS485 SignalRS485 Signal Terminal

CG (AUXG)RS485 Common

Terminal

Common terminal of power ground for RS485 communication

24 │

CHAPTER 4. INSTALLATION

Control Circuit Wiring Precautions

• Maintain wiring distance between pressure sensor and drive within 10 metres.

• If using a remote control with analogue signals, maintain distance between remote and drive within 50 metres.

• Separate sensor and analogue signal wires away from power wires.

• Use shielded twisted wires for signal lines of control circuit.

• GND and CG are insulated from each other. Do not connect them together.

Pressure Sensor and Low water Sensor connection

• Use pressure sensors and low water sensors approved by Vada.

Category Pressure Sensor Low Water Level Sensor

Excited Voltage DC 12V DC ±12V Pulse

Sensor Output 4~20mA Connection

• Ensure pressure sensor is installed with the correct polarity.

• Ensure that pressure sensor complies with the requirements of the table above.

(Optional)

(Optional)

│ 25

Sink Mode and Source Mode

The Vada IQ Drive allows application of both sink mode (NPN: Using CG common terminal) and

source mode (PNP: Using 24V common terminal) to the input terminal logic of the control circuit.

It is possible to switch between sink mode and source mode using the selection switch within the

control board.

Communication Line Wiring

The IQ Drive supports CAN communication which is used for multiple pump control. When using

CAN communication, connect CANH (High of CAN) and CANL (Low of CAN) on the terminal block

and wire to CG using shielded and twisted wire.

When using termination resistor for connecting multiple CANs, change the switch from OPEN to SHORT.

When Using RS 485 communication, please contact Vada.

CHAPTER 4. INSTALLATION

SinkMode (NPN)

SourceMode (PNP)

26 │

CHAPTER 5. OPERATION

5.1 Function Display (FND)

Appearance and Description of Function DisplayThe function display has five digits, four LEDs to display drive status and four buttons to operate drive and enter settings.

LED Display

The LEDs are labelled Run, Stop, Alarm1 and Alarm2.

Run Turned on for standby. Flickering when drive operating

Stop Turned on during stop.

Alarm1 Turned on for High Pressure/Low Pressure/Sensor Error/ Low Level Alarms

Alarm2 Turned on for drive error

• Run and Stop LEDs indicate drive status.

• Alarm1 indicates problem with pump system. Alarm2 indicates drive error.

Indicator LEDs

Function Display

Buttons

│ 27

Digital Display

The digital display consists of five digits and displays parameter setting and status values of the

drive and pump. Displays are divided in St group (Status Group), Pr group (Pump Control Group)

and dr group (Drive Group).

Buttons

The function display has four buttons which are used for changing parameter settings.

CHAPTER 5. OPERATION

Used for setting up pressure settings, parameters or resetting alarms.

Runs or stops the drive.

Used for changing parameter items or settings. button increases the value,

while the button reduces value. After changing settings, press button to

save the value. Press and hold both and buttons for 3 seconds to change

parameter group.

Changing Parameter Settings

• Any changes to the parameter settings will directly affect how the pumping system operates.

• Setting must not be changed except by a trained operator or professional engineer.

• Some settings cannot be changed whilst pump is operating. (Refer to Chapter 6. Functions & Descriptions.)

1) Parameter Group Movement

When power is first applied, the drive will enter into the St group. In order to move parameter

group press and hold and buttons for 3 seconds.

2) Parameter Item Movement

Use the and buttons to move to desired parameter within the parameter group.

28 │

CHAPTER 5. OPERATION

3) Changing Parameter Settings

Press the button at the desired parameter item to enter into Setting Change Mode.

Use the and buttons to change parameter setting to the desired value.

Press the button to apply and save setting. The message will be displayed.

Press the button to discard changes and exit Setting Change Mode.

dr

│ 29

CHAPTER 5. OPERATION

5.2 Function Setup

Basic Function Setup

Any parameter that is not set by the user will be set to the factory default setting.

1) Common Setup

These parameters are used to setup drive when controlling pump regardless of type of control.

Setup ItemParameter

CodeDescription

Input Location of Run Command dr-01To select a method to issue Run command (FND, Terminal Block)

Input Method of Target Frequency dr-02To select a method to control target operation frequency (Own PID, FND, V1, I1)

Capacity of Motor dr-10 To set up Capacity of Motor

No. of Poles of Motor dr-11 To set up No. of Poles of Motor

Rated Current of Motor dr-12 To set up Rated Current of Motor

Rated Rotations of Motor dr-13 To set up Rated Rotations of Motor

Rated Voltage of Motor dr-14 To set up Rated Voltage of Motor

No-load Current of Motor dr-15 To set up No-load Current of Motor

Rated Slip Frequency of Motor dr-16 To set up Rated Slip Frequency of Motor

Rated Frequency of Motor dr-17 To set up Rated Frequency of Motor

Efficiency of Motor dr-18 To set up Efficiency of Motor

Rotation Direction Selection of Motor dr-20To set up Rotation Direction Selection of Motor Properly

Stopping Method of Motor dr-21To set up Stopping Method of Motor to stop the motor

30 │

CHAPTER 5. OPERATION

2) Pump Control Function Setup

These parameters are used to setup pump system when controlling pump using drive.

Setup ItemParameter

CodeDescription

Pump Capacity Pr-01 To set up Pump Capacity

Pump Control Mode Pr-02 To set up Pump Control Mode

Sensor Capacity and Correction Pr-03~06

To set up capacity of pressure sensor and correct variation between actual pressure and pressure sensor (On constant pressure control, Sensor2 is not used.)

To Use Low Water Level Sensor Pr-76To decide whether to use low water level sensor

3) Drive Control Function Upon External Command

These parameters are used to set up pump system when controlling pump using external controller.

Setup ItemParameter

CodeDescription

Frequency Setup upon V1 Voltage dr-60~63To set up output frequency range against voltage when controlling drive using V1 voltage

Frequency Setup upon I1 Voltage dr-64~67To set up output frequency range against current when controlling drive using I1 current

4) CAN Communication Function Setup

These parameters are used when CAN communication is to be used on interoperation or connecting

FND/LCD Monitor.

Setup ItemParameter

CodeDescription

CAN Comm. Mode Pr-50 To set up CAN Comm. Mode

CAN Comm. ID Pr-51To set up CAN Comm. ID (If ID is ‘0’, CAN Comm. is disabled.)

CAN Comm. Speed Pr-52 To set up CAN Comm. Speed

│ 31

CHAPTER 5. OPERATION

Expansion Function Setup

These parameters are used to optimise the performance of the drive and finetune the operation of

the drive.

1) Pump Control Parameters

Setup ItemParameter

CodeDescription

PID Controller Gain Setup Pr-07~09To set up gain to adjust response characteristics of PID controller

Control Cycle of PID Controller Pr-10 To set up Control Cycle of PID Controller

Start Pressure Variation Pr-12Minimum pressure variance to allow drive to start

Initial Output Ratio on Starting Pr-15To set up initial starting output frequency of PID controller in order to speed up response against initial starting

Lead Pump Alternation Pr-53~54To operate pump alternatively in force during multi-drive operation

2) Pump System Protection Parameters

Setup ItemParameter

CodeDescription

High Pressure AlarmPr-70Pr-72

To set up high pressure alarm level and time in order to protect discharge pipe from high pressure

Low Pressure AlarmPr-71Pr-73

To set up low pressure alarm level and time in order to protect the pump from damaged pump

Low Water Level Alarm Pr-74~77There are two detection methods using low level sensor or software in order to protect the pump by detecting existence of water within suction pipe.

3) Setup Parameter for Fault History Storage

Setup ItemParameter

CodeDescription

Fault History Storage and Deletion

Pr-80~86To store or delete fault or alarm generated from

pump system or drive.

32 │

5.3 Basic Operation

Constant Pressure Control Mode

1) Single Drive Operation

When using a single drive to control constant pressure, use the following method.

A. Wiring Diagram

• Connect drive wiring so that power input and motor output lines are not interchanged.

• Install a wiring breaker at the power input of the drive.

• Check polarity of pressure sensor.

• Connect low level sensor if necessary. If not using a low water level sensor, change setup to usE Low Water Level Detection method of software (Pr-76 Low Water Level Detection Method ‘0’.)

CHAPTER 5. OPERATION

│ 33

B. Setup and Operation

• ● Apply power, check if Stop LED on FND is turned on and FND displays pressure.

• ● If is displayed , check wiring of the pressure sensor.

C. Operation Parameters

Setup Sequence

Setup ItemParameter

CodeDescription

1Run Command Input

Location Setupdr-01 To set up Run command with FND.

2Target Frequency Input

Method Setupdr-02

To set up Target Frequency Input Method of drive with own PID.

3 Pump Control Mode Setup Pr-02To set up Pump Control Mode to Constant Pressure Mode.

4 Sensor 1 Capacity Setup Pr-03To set up rated capacity of pressure sensor used.

5Sensor 1 Pressure

Variation CorrectionPr-04

To correct variation between value of used pressure sensor and real pressure value.

6 Comm. ID Setup Pr-51To set up CAN Comm. ID to ‘0’ in order to make CAN Comm. Disabled.

7 Target Pressure Setup St Group To set up target pressure of pump system.

8Motor Rotation Direction

Selectiondr-20

To make rotation direction of motor same as pump operation direction

9 Operation Press key, them pump operates with target pressure.

D. Target Pressure Setup

• Before attempting setup, ensure that you know the correct pressure setting.

• Select the St Group and the S Parameter. Press and hold the button for 3 seconds to enter the Pressure Setting Screen

• Use the or button to change value to desired setting.

• Press the button to apply and save setting.

• The setting will be changed and will be displayed.

• The High Pressure Alarm (Pr-70) will automatically be set to 2 bar higher than the applied pressure setting.

• Press the button before applying settings to exit from the Pressure Setting Screen.

CHAPTER 5. OPERATION

34 │

E. Pump Rotation Direction

• The default rotation direction is counter clockwise.

• In order to change rotation direction use one of the following methods:

1. Switch two of the three motor power input wires.

2. Change the value of the Motor Rotation Direction parameter (dr-20).

CHAPTER 5. OPERATION

│ 35

CHAPTER 5. OPERATION

2) Multi-Drive Operation

When using multiple drives to control constant pressure, use the following method.

A. Wiring Diagram

• Connect drive wiring so that power input and motor output lines are not interchanged.

• Install a wiring breaker at the power input of the drive.

• Check polarity of pressure sensor. Connect auxillary pressure sensor to each drive depending on the system.

• Connect low level sensor if necessary. If not using a low water level sensor, change setup to use Low Water Level Detection method of software (Pr-76 Low Water Level Detection Method ‘0’.)

• If using the centralised control method of PID control, set Pr61 to ’0’.

B. Setup and Operation

• Apply power, check if Stop LED on FND is turned on and FND displays pressure.

• If is displayed , check wiring of the pressure sensor.

36 │

CHAPTER 5. OPERATION

C. Operation Parameters

Setup Sequence

Setup ItemParameter

CodeDescription

1Run Command Input

Location Setupdr-01 To set up Run command with FND.

2Target Frequency Input

Method Setupdr-02

To set up Target Frequency Input Method of drive with own PID.

3 Pump Control Mode Setup Pr-02To set up Pump Control Mode to Constant Pressure Mode.

4 Sensor 1 Capacity Setup Pr-03To set up rated capacity of pressure sensor used.

5Sensor 1 Pressure

Variation CorrectionPr-04

To correct variation between value of used pressure sensor and real pressure value.

6 Comm. ID Setup Pr-51To set up CAN Comm. ID to 1~6 so that it should not be duplicated with other drive.

7 Target Pressure Setup St Group To set up target pressure of pump system.

8Motor Rotation Direction

Selectiondr-20

To make rotation direction of motor same as pump operation direction

9 OperationPress key, the pump operates with target pressure.

10 PID Setup Pr-61 Set to Master Control (0)

11 Fred. Ratio to Stop Pr-14Set minimum frequency to initiate shutoff.√(set pressure/shutoff pressure) x 100

│ 37

CHAPTER 5. OPERATION

D. Pump Rotation Direction

• The default rotation direction is counter clockwise.

• In order to change rotation direction use one of the following methods:

1. Switch two of the three power input wires.

2. Change the value of the Motor Rotation Direction parameter (dr-20).

D. Target Pressure Setup

• Before attempting setup, ensure that you know the correct pressure setting.

• If using linked drive operation, setup pressure on one drive will be automatically set on all drives through CAN communication.

• Select the St Group and the S Parameter. Press and hold the button for 3 seconds to enter the Pressure Setting Screen

• Use the or button to change value to desired setting.

• Press the button to apply and save setting.

• The setting will be changed and will be displayed.

• The High Pressure Alarm (Pr-70) will automatically be set to 2 bar higher than the applied pressure setting.

• If you press the button before pressing the button the setting will not be changed.

38 │

CHAPTER 6. FUNCTION TABLE & DESCRIPTION

6.1 Status Group

Display Name Description Note

P Pressure Measured pressureWhen using difference

pressure control - Shows difference pressure

S Setting PressurePressure set in drive (can be

changed by operator)

Press and hold Setting button for 2 seconds to enter

pressure input mode.

HOutput Frequency

(Hz)Measured drive output frequency

o Output Ratio Measured drive output (%) % of FLS

U Voltage Measured voltage of DC Link(Input voltage x √2) = DC Link

voltage (V)

A Current Measured output current Unit (A)

O Discharge PressureWhen using difference pressure

control - Shows discharge pressure

Differential pressure

I Suction PressureWhen using difference pressure

control - Shows suction pressureDifferential pressure

│ 39

6.2 Pump Control Group

Para. Link - Linked or related to other parameters

O - yes X - No

Display Name RangeFactory Setting

Para. Link

Diff. Pressure

Use

Change While in

Operation

Ref. Page

Pr-00 Jump Code 1~92 1 X O O 43

Pr-01 Pump Capacity Setup0.75 ~

25.00[kW]- X O X 43

Pr-02 Pump Control Mode 0~1 1 O O X 43

Pr-03Capacity Setup of Sensor 1

1.0~25.0[bar] 16 X ● X 44

Pr-04Correction Value of Sensor 1

-1.0~1.0[bar] 0 X ● O 44

Pr-05Capacity Setup of Sensor 2

1.0~25.0[bar] 16 ● ● X 44

Pr-06Correction Value of Sensor 2

-1.0~1.0[bar] 0 ● ● O 44

Pr-07 P Gain of PID Controller 0~100[%] 10 ● ● O 44

Pr-08 I Gain of PID Controller 0~100[sec] 1 ● ● O 44

Pr-09 D Gain of PID Controller 0~100[ms] 0 ● ● O 45

Pr-10Control Cycle of PID Controller

10~200[ms] 200 ● ● X 45

Pr-11Selection of Freezing Prevention

0~1 0 ● ● O 45

Pr-12Starting pressure Variation

0~2.0[bar] 0.3 ● ● O 45

Pr-13Stopping Time after reaching Setup Pressure

5~200[sec] 30 ● ● O 45

Pr-14

Ratio of Min Output Freq. of Stop Mode after reaching Setup Pressure

0~100[%] 100 ● ● O 46

Pr-15Ratio of Initial Output on Starting

5~100[%] 50 ● ● X 46

Pr-40RS485 Communication Mode

0-1 0 ● ● ● 46

Pr-41RS485 Communication ID

0-250[bps] 0 ● ● ● 46

Pr-42RS485 Communication Speed

1-5 4 ● ● ● 46

CHAPTER 6. FUNCTION TABLE & DESCRIPTION

40 │

Display Name RangeFactory Setting

Para. Link

Diff. Pressure

Use

Change While in

Operation

Ref. Page

Pr-43RS485 Communication Delay Time

0-999[ms] 5 ● ● ● 47

Pr-50 Lead Pump Alternation 0~1 0 X ● X 47

Pr-51 CAN Comm. ID 0~6 0 X ● X 47

Pr-52 CAN Comm. Speed 1~5 1 X O X 48

Pr-54Lead pump alternation time

0~24(hour) 12 O O O 48

Pr-55Standby Pump waiting time

0~100[sec] 5 ● ● O 48

Pr-61 PID control Type Setup 0~1 0 O O X 48

Pr-64Output Ratio of Starting AllPID Increase

70~100[%] 100 O O O 49

Pr-70High Pressure Alarm Level

0~Sen1 Capacity

[bar]16.0 ● ● O 49

Pr-71Low Pressure Alarm Level

0~10.0[bar] 0.5 ● ● O 49

Pr-72High Pressure Alarm Time

0~100[sec] 5 ● ● O 49

Pr-73Low Pressure Alarm Time

0~200[sec] 20 ● ● O 49

Pr-74Low Level Trip Time of Pressure Sensor

0~250[sec] 20 ● ● O 49

Pr-75Low Level Trip Pressure Level

0~1.0[bar] 0.3 ● ● O 50

Pr-76Low Level Detection Method Selection

0~1 0 X ● X 50

Pr-77Low Level Trip Time of Low Level Sensor

0~250[sec] 2 ● ● O 50

Pr-80 Fault History - - X O X 50

Pr-81 Fault History 1 - - X O X 50

Pr-82 Fault History 2 - - X O X 50

Pr-83 Fault History 3 - - X O X 50

Pr-84 Fault History 4 - - X O X 50

Pr-85 Fault History 5 - - X O X 50

Pr-86 Fault History Delete 0~1 0 X O O 51

Pr-87 Sensor percentage 0~200 100 X X O 51

Pr-90 Initialisation Code 0~1 0 X O X 51

Pr-92 S/W Version - - X O X

CHAPTER 6. FUNCTION TABLE & DESCRIPTION

│ 41

6.3 Drive Control Group

Display Name RangeFactory Setting

Change While in

Operation

Ref. Page

dr-00 Jump Code 1~90 1 O 52

dr-01Command Input Location

Setup0~1 0 X 52

dr-02Target Freq. Input Method

Setup0~3 0 X 52

dr-03 Target Freq. Value Setup Min Freq. (dr-42)~Max Freq. 30.0 O 52

dr-10 Motor Capacity Selection 0.10~75.00[kW] X 52

dr-11 No. of Motor Poles Selection 1~2 1 X 52

dr-12 Rated Current of Motor 1.0~100.0[Arms] X 53

dr-13 Rated Rotations of Motor 1~9999[rpm] X 53

dr-14 Rated Voltage of Motor 200.0~500.0[Vrms] X 53

dr-15 Non-load Current of Motor 0.5~100.0[Arms] X 53

dr-16Rated Slip Frequency of

Motor0.10~10.00[Hz] X 53

dr-17 Rated Frequency of Motor 0~1 1 X 53

dr-18 Efficiency of Motor 50~100[%] X 54

dr-20Rotation Direction Selection

of Motor0~1 0 X 54

dr-21 Stopping Method of Motor 0~1 0 X 5

dr-22 Increase Time 1.0~600.0 3.0 O 54

dr-23 Decrease Time 1.0~600.0 6.0 O 54

dr-30Motor Overload Trip

Selection0~1 0 O 54

dr-31 Motor Overload Trip Level 100~200[%] 120 O 55

dr-32 Motor Overload Trip Time 5~200[sec] 60 O 55

dr-33 Stall Prevention Setup 0~1 0 X 55

dr-34 Stall Prevention Level 100~200[%] 150 X 55

dr-35 Motor Overheat Selection 0~1 0 O 55

dr-36 Ground Detection 0~1 0 O 55

dr-37 No. of Restart after Trip 0~50 3 O 56

dr-38Waiting Time of Automatic

Restart after Trip1~250[sec] 10 O 56

dr-40 Drive Control Mode 0~1 0 X 56

dr-41 Torque Boost Amount 0~10.0[%] 2.0 X 56

dr-42 Start Frequency. 0.10~40.00[Hz] 0.50 X 56

dr-43 Max Operation Freq.40.0~Rated Freq. of Motor

[Hz]60.00 X 57

CHAPTER 6. FUNCTION TABLE & DESCRIPTION

42 │

Display Name RangeFactory Setting

Change While in

Operation

Ref. Page

dr-44 Switching Frequency. 1.0~15.0[kHz] 5.0 O 57

dr-50 Fan Operation Type 0~2 1 O 57

dr-51Power Consumption

Correction0.0~1000.0 100.0 O 57

dr-52 Output Power Indication 0.0~100.0[kW] - 57

dr-53Indicating Accumulated

Mega Wh0~9999[MWh] 57

dr-54Indicating Accumulated Kilo

Wh0~9999[kWh] 57

dr-55Temp. of Power Semiconductor

0~200ºC - 57

dr-56 Ambient Temp. Display 0~200ºC - 58

dr-57 Output Power Display 0.0~500.0[V] - 58

dr-60 V1 Min Input Voltage 0.0~5.0[V] 0.0 O 58

dr-61Corresponding Freq. to V1

Min Input Voltage0.00~30.00[Hz] 0.00 O 58

dr-62 V1 Max Input Voltage 5.1~10.0[V] 10.0 O 58

dr-63Corresponding Freq. to V1

Max Input Voltage30.01~ Rated Freq. of Motor

[Hz]

Rated Freq. of Motor

O 58

dr-64 I1 Min Input Current 0~10[mA] 4 O 58

dr-65Corresponding Freq. to I1

Min Input Current0.00~30.00[Hz] 0.00 O 58

dr-66 I1 Max Input Current 11~20[mA] 20 O 58

dr-67Corresponding Freq. to I1

Max Input Current30.01~ Rated Freq. of Motor

[Hz]

Rated Freq. of Motor

O 58

dr-70 Year Display 0~9999 - 59

dr-71 Month/Date Display 01.01~12.31 - 59

dr-72 Hour/Minute Display 00.00~23.59 - 59

dr-90 Initialisation Code 0~1 0 X 59

CHAPTER 6. FUNCTION TABLE & DESCRIPTION

│ 43

CHAPTER 6. FUNCTION TABLE & DESCRIPTION

6.4 Pump Control Group Parameter Functions

Pr-00 Jump Code

• Allows moving to desired code directly.

• It is also possible to move to other codes using keys after moving.

Pr-01 Pump Capacity

• To setup and confirm pump capacity.

• Initial value is automatically set by drive capacity.

Related Functions

dr-10 Capacity of Motor

dr-11 No. of Poles of Motor

dr-12 Rated Current of Motor

dr-13 Rated Rotations of Motor

dr-14 Rated Voltage of Motor

dr-15 No-load Current of Motor

dr-16 Rated Slip Frequency of Motor

dr-17 Rated Frequency of Motor

dr-18 Efficiency of Motor

Pr-02 Pump Control Mode

• To set up pump control method.

Setup DataFunctional Description

Related Functions

0Differential Pressure

Control Method

Pr-03, Capacity of Sensor 1Pump Discharge

Pr-04 Correction of Sensor 1

Pr-05 Capacity of Sensor 2Pump Suction

Pr-06 Correction of Sensor 2

1Constant Pressure

Control Method (Factory Setting)

Pr-03 Capacity of Sensor 1

Pr-04 Correction of Sensor 1

44 │

CHAPTER 6. FUNCTION TABLE & DESCRIPTION

Pr-03 Sensor 1 Capacity Setup

• Enter the maximum value the pressure sensor 1 can measure. Example: If maximum value of 10 bar, enter 10.0.

Factory Setting Input Range

16.0 bar 0.0 ~ 25.0 bar

Pr-04 Sensor 1 Correction Setup

• Corrects the pressure variation between analogue or digital pressure meter and the one displayed on the drive FIND.

Factory Setting Input Range

0.0 bar -1.0 ~ 1.0 bar

Pr-04 Sensor 1 Correction Setup

• Corrects the pressure variation between analogue or digital pressure meter and the one displayed on the drive FIND.

Pr-05 Sensor 2 Capacity Setup

• Enter the maximum value the pressure sensor 2 can measure. (Setup method same as Pr-03)

Pr-06 Sensor 2 Correction Setup

• Corrects the pressure variation between analogue or digital pressure meter and the one displayed on the drive FIND. (Setup method same as Pr-04)

Pr-07 P Gain of PID Controller

• Changes the Proportional Constant (P) of the PID Controller This parameter is factory set. Do not change without reference to Vada.

Factory Setting Input Range

10% 0 ~ 100%

Pr-08 I Gain of PID Controller

• Changes the Integral Constant (I) of the PID controller.

• This parameter is factory set. Do not change without reference to Vada.

Factory Setting Input Range

1 sec 0 ~ 100 sec

│ 45

CHAPTER 6. FUNCTION TABLE & DESCRIPTION

Pr-09 D Gain of PID Controller

• Changes the Differential Constant (D) of the PID controller.

• This parameter is factory set. Do not change without reference to Vada.

Factory Setting Input Range

0ms 0 ~ 100ms

Pr-10 PID Control Cycle

• Sets up the PID control cycle

• This parameter is factory set. Do not change without reference to Vada.

Factory Setting Input Range

10ms 10 ~ 200ms

Pr-11 Freezing Prevention Function

• Sets up freezing prevention mode of pump which prevents pump damage by detecting when the temperature drops below freezing and running pump for 0 ~ 10 seconds to create frictional heat and prevent water from freezing.

Setup Value Input Range

0 (Factory Setting) Off

1 On

Pr-12 Start Variation

• Sets start variation pressure.

• Does not start when alarm occurs

Factory Setting Input Range

0.3 bar 0.0 ~ 2.0 bar

Pr-13 Stopping Time After Setup Pressure Reached

• Set the time that the pump will continue to run before slowing down once setup pressure has been reached.

Factory Setting Input Range

30 sec 5 ~ 200 sec

46 │

CHAPTER 6. FUNCTION TABLE & DESCRIPTION

Pr-14 Minimum Output Frequency Ratio to Stop After Reaching Setup Pressure

• Sets the output frequency ratio which is required before pump can stop after reaching setup pressure.

Factory Setting Input Range

100% 0 ~ 100%

Pr-15 Minimum Initial Output Ratio

• Sets the minimum output on starting the drive

• Example: If setting 50% with a 50Hz motor, it can start at 25Hz.

• Insert RS485 settings as per attached sheet Pr40 to 43.

Factory Setting Input Range

50% 5 ~ 100%

Pr-40 RS485 Communication Mode

• Sets RS485 communication mode.

Setup Value Input Range

0 (Factory Setting) RS485 Communication OFF

1 RS485 Communication ON

Pr-41 RS485 Communication ID

• Sets ID for device on RS485 communication network.

Setup Value Input Range

0 (Factory Setting) 0-250

Pr-42 RS485 Communication Speed

• Sets data rate for RS485 communication.

• Long cable runs may require lower speeds.

Setup Data Functional Description

1 1200bps

2 2400bps

3 4800bps

4 9600bps

5 19200bps

│ 47

Pr-43 RS485 Communication Delay Time

• Sets the delay time between data packets for RS485 communications.

Factory Setting Input Range

5[ms] 0-999

Pr-50 CAN Communication Mode

• Sets multi-drive mode for multiple pump operation.

Setup Value Input Range

0 (Factory Setting) Single Pump

1 Multiple Pumps

Pr-51 CAN Communication ID Setup

• Sets CAN communication ID on multi-drive control mode

• Do not duplicate ID for setup.

Setup Value Functional Description

0 (Factory Setting) Single Pump Mode

1 ~ 6Multi-Drive Control

Communication ID No.

Related Functions

dr-02 Target Frequency Input Method

Pr-52 CAN Communication Speed

Pr-53 Lead Pump Alternation Method

Pr-54 Lead Pump Alternation Time

Pr-55 Standby Pump Waiting Time

Pr-61 PID Type on Multi-Drive Control

CHAPTER 6. FUNCTION TABLE & DESCRIPTION

48 │

Pr-52 CAN Communication Speed

• Sets CAN communication speed

• In the event of long connection distances, reduce communication speed.

Setup Value Functional Description

1 (Factory Setting) 40kbps

2 50kbps

3 100kbps

4 200kbps

5 250kbps

Pr-54 Lead Pump Alternation Time

• Sets the operation time that lead pump will operate continually before switching to standby pump.

• This parameter is factory set. Do not change without reference to Vada.

Setup Value Functional Description

0 Off

1 ~ 24 hours (Factory Setting 12 hour)

Alternation Time

Pr-55 Standby Pump Waiting Time

• Sets the delay time before standby pump starts on a multiple pump control.

• Setting time to 0 may cause pressure to increase suddenly when standby pump starts.

Factory Setting Input Range

5 seconds 0 ~ 100 seconds

Pr-61 PID Setup on Multi-Drive Control Mode

• Sets control on multi-drive pumpset to Master Control or Centralised Control

• Master Control

Setup Value Functional Description

0 (Factory Setting) Master Control

1 Centralised Control

Related Function

Pr-64Output Ratio on Starting

Increase of AIIPID

CHAPTER 6. FUNCTION TABLE & DESCRIPTION

│ 49

CHAPTER 6. FUNCTION TABLE & DESCRIPTION

Pr-64 Output Ratio on Starting AIIPID

• Sets the drive output ratio required to start the next drive in a mult-pump set.

Factory Setting Input Range

100% 70 ~ 100%

Pr-70 High Pressure Alarm Level

• Sets the pressure required to trip the high pressure alarm

• The high pressure alarm is automatically set at +2 bar above the setup pressure.

Factory Setting Input Range Related Function

20.0 bar 0.0 ~ 20 bar Pr-72 High Pressure Trip Time

Pr-71 Low Pressure Alarm Level

• Sets the pressure required to trip the low pressure alarm.

Factory Setting Input Range Related Function

20.0 bar 0.0 ~ 20 bar Pr-73 Low Pressure Trip Time

Pr-72 High Pressure Alarm Time

• Sets the time that pressure can be maintained at a level above the high pressure setting before tripping the high pressure alarm.

Factory Setting Input Range Related Function

5 sec 0 ~ 100 sec Pr-70 High Pressure Alarm Level

Pr-73 Low Pressure Alarm Time

• Sets the time that pressure can be maintained at a level below the low pressure setting before tripping the low pressure alarm.

Factory Setting Input Range Related Function

20 sec 0 ~ 200 sec Pr-71 Low Pressure Alarm Level

Pr-74 Low Water Level Alarm Time

• Sets the time that the low water level measurement value can be maintained before tripping the low water level alarm.

Factory Setting Input Range Related Function

30 sec 0 ~ 250 secPr-71 Low Pressure Alarm Level

Pr-76 Low Water Level Alarm Detection Method

50 │

CHAPTER 6. FUNCTION TABLE & DESCRIPTION

Pr-75 Low Water Level Alarm Pressure Level

• Sets the pressure required to trip the low water level alarm

Factory Setting Input Range Related Function

0.3 bar 0.0 ~ 1.0 bar

Pr-74Low Water Level Alarm

Time of Pressure Sensor

Pr-76Low Water Level Alarm

Detection Method

Pr-76 Low Water Level Alarm Detection Method

• Sets the method used to detect low water level.

• Outside electrode connections required if setting up low water level sensor.

• Connect low water level sensor to lowest ID drive in multi-drive pump sets.

Setup Value Functional Description Related Function

0 (Factory Setting)Software Detection Using

Pressure Sensor

Pr-74Low Water Level Alarm

Time of Pressure Sensor

Pr-75Pressure Level for Low

Water Level Alarm

1 ~ 24 hours (Factory Setting 12 hour)

Alternation Time Pr-77Low Water Level Sensor

Trip Time

Pr-77 Low Water Level Sensor Trip Time

• Sets the time that the low water level sensor signal can be maintained before tripping the low water level alarm

Setup Value Functional Description

0 Off

1 ~ 250 sec Time Setup (Factory Setting 2 sec)

Pr-80 ~85 Fault History List

• Pr-80 displays most recent error code

• Pr-81 ~ Pr-85 displays memorised error codes in reverse order.

FND Display Description

tSF, tOP, tUP, tUL,tASH etc. Error Content (Refer to Chapter 8 Fault History Table

H xx.x Frequency with Error

A xx.x Current with Error

t xx No. of Errors Occurred

Stdy, stOP, AdOFS, wdOG Operation Status with Error

│ 51

CHAPTER 6. FUNCTION TABLE & DESCRIPTION

Pr-86 Deletion of Fault History

• Deletes all content of fault history

Setup Value Functional Description

0 Maintain Fault History (Factory Setting)

1 Delete Fault History

Pr-87 Sensor Percentage

• Sets sensor correction percentage.

Factory Setting Input Value

100 1 ~ 200

Pr-90 Reset Factory Defaults

• Resets all pump control group parameters back to factory default settings.

Setup Value Functional Description

0 (Factory Setting) Keep Setup

1 Restore Factory Default Settings

52 │

CHAPTER 6. FUNCTION TABLE & DESCRIPTION

6.5 Drive Control Group Parameter Functions

dr-00 Jump Code

• Allows moving to desired code directly.

• It is also possible to move to other codes using keys after moving.

dr-01 Command Input Location Setup

• Sets command input location. (Run/Stop Operation)

Setup Value Functional Description

0 (Factory Setting) Operation Command with FND

1 Operation Command with Terminal Block (P1)

dr-02 Target Frequency Input Method Setup

• Sets up target frequency input method.

Setup Data Functional Description

0 Setup with Own PID Operation

1Setup when Using Fixed Frequency

on the Main Body of FND Drive

Related Function

dr-03Target Frequency Value

Setup

2 Setup with External Voltage V1(0 ~10V)

3 Setup with External Current I1 (4 ~20mA)

dr-03 Target Frequency Setup

• Sets the target frequency when using target frequency input method.

Factory Setting Input Range

30.0Hz 0.1 ~ 60Hz

dr-10 Motor Capacity

• Sets the capacity of the motor.

Factory Setting Input Range

Initial value set upon drive capacity 0.1 ~ 75.00kW

dr-11 Motor Pole Selection

• Sets the number of motor poles

Setup Value Functional Description

1 2 Pole Motor

2 4 Pole Motor

│ 53

CHAPTER 6. FUNCTION TABLE & DESCRIPTION

dr-12 Motor Rated Current

• Sets the rated current (RMS) of the motor

Factory Setting Input Range

Initial Value Set Upon Drive Capacity 1.00 ~ 100.0 Arms

dr-13 Motor RPM rating

• Sets the rated RPM of the motor.

Factory Setting Input Range

Initial Value Set Upon Drive Capacity 1 ~ 9999 rpm

dr-14 Motor Rated Voltage

• Sets the rated voltage of the motor

Factory Setting Input Range

Initial Value Set Upon Drive Capacity 200.0 ~ 500.0 Vrms

dr-15 Motor Non-Load Current

• Sets the Non-Load Current of the Motor.

Factory Setting Input Range

Initial Value Set Upon Drive Capacity 0.5 ~ 100 Arms

dr-16 Motor Rated Slip Frequency

• Displays rated slip frequency of motor based on previously entered parameters: number of poles, rated number of rotations and rated frequency.

Factory Setting Input Range Related Function

Automatic Setup 0.10 ~ 10Hz

dr-11 Motor Pole Selection

dr-12 Motor Rated Current

dr-17 Motor Rated Frequency

dr-17 Motor Rated Frequency

• Sets the rated frequency of the motor

Setup Value Functional Description Related Function

0 50Hzdr-43

Max Operation Frequency1 (Factory Setting) 60Hz

54 │

CHAPTER 6. FUNCTION TABLE & DESCRIPTION

dr-18 Motor Efficiency

• Sets the rated efficiency of the motor

Factory Setting Input Range

Initial Value Set Upon Drive Capacity 70 ~ 100 %

dr-20 Motor Rotation Direction

• Sets the motor rotation direction

Setup Value Functional Description

0 (Factory Setting) Clock Wise (From Fan End)

1 Counter Clockwise (From Fan End)

dr-21 Motor Stopping Method

• Sets the motor stopping method

Setup Data Functional Description

0 (Factory Setting) Decelerated StopRelated Function

dr-23 Falling Time

1 Cut Drive Output Voltage

dr-22 Rising Time

• Sets the time taken for the motor to reach maximum frequency from 0Hz.

Factory Setting Input Range

3.0 sec 1 ~ 600 sec

dr-23 Falling Time

• Sets the time taken for the motor to reach 0Hz from maximum frequency.

Factory Setting Input Range

6.0 sec 1 ~ 600 sec

dr-30 Overload Trip Selection

• Sets whether the drive will trip the motor in the event of an overload to prevent motor damage.

Setup Value Functional Description

0 Off

1 (Factory Setting) Setting

Related Function

dr-12 Motor Rated Current

dr-31 Overload Trip Level

dr-32 Overload Trip Time

│ 55

CHAPTER 6. FUNCTION TABLE & DESCRIPTION

dr-31 Overload Trip Level

• Sets the percentage of rated current required to trip the motor.

Factory Setting Input Range Related Function

120% 100 ~ 200%dr-12 Motor Rated Current

dr-32 Overload Trip Time

dr-32 Overload Trip Time

• Sets the time which the overload trip level must be maintained in order to trip the motor

Factory Setting Input Range

90 sec 5 ~ 200 sec

dr-33 Stall Prevention

• Sets whether to enable stall protection. In the event of the motor stalling, the drive will decelerate the motor.

Setup Data Functional Description

0 (Factory Setting) Off

1 Setup

Related Function

dr-12 Motor Rated Current

dr-34 Stall Prevention Level

dr-34 Stall Prevention Level

• Sets the percentage of the rated motor current required to activate stall prevention.

Factory Setting Input Range Related Function

150% 100 ~ 200% dr-12 Motor Rated Current

dr-35 Motor Overheat Selection

• Sets the overheating function on or off.

Setup Value Functional Description

0 (Factory Setting) Off

1 On

dr-36 Ground Detection

• Sets the ground detection function on or off.

Setup Value Functional Description

0 (Factory Setting) Off

1 On

56 │

CHAPTER 6. FUNCTION TABLE & DESCRIPTION

dr-37 Autostart Occurrances After Trip

• Sets the number of times which the drive will automatically start after trips.

• If the drive trips more than the specified setting, the drive will not automatically restart.

Factory Setting Input Range

3 0 ~ 50

dr-38 Automatic Restart Waiting Time

• Sets the time between a trip occurring and the drive automatically restarting.

Factory Setting Input Range

10 sec 0 ~ 250 sec

dr-40 Drive Control Mode

• Sets whether the drive will operate using V/F Control or Slip Compensation Control

●In the event of the motor stalling, the drive will decelerate the motor.

Setup Data Functional Description Related Function

0 (Factory Setting) V/F Control dr-41 Torque Boost

1 Slip Compensation Control

dr-10 Motor Capacity

dr-12 Motor Rated Current

dr-15 Motor Non-Load Current

dr-16 Motor Rated Slip

dr-18 Motor Efficiency

dr-41 Torque Boost

• Sets the torque applied when drive starts.

Factory Setting Input Range

2% 0.0 ~ 10%

dr-42 Start Frequency

• Sets the frequency output when drive starts.

Factory Setting Input Range

0.50Hz 0.1 ~ 40.00Hz

│ 57

CHAPTER 6. FUNCTION TABLE & DESCRIPTION

dr-43 Maximum Operating Frequency

• Sets the Maximum Operating Frequency of the drive.

Factory Setting Input Range

60.00Hz 40.00 ~ Rated Frequency of Motor [Hz]

dr-44 Switching Frequency

• Sets the switching frequency of the drive.

• Decreasing the switching frequency reduces noise and leak current.

Factory Setting Input Range

5 kHz 1.0 ~ 15 kHz

dr-50 Fan Operation Method

• Sets the fan operation method

Setup Data Functional Description

0 Operate Upon Application of Drive Power

1 (Factory Setting) Operate Upon Output of Drive Frequency

2Operate Upon Abnormal State of Internal Setup

Temperature

dr-51 Power Consumption Correction

• Sets power consumption correction.

dr-52 Power Consumption Display

• Displays power consumption.

Range 0.0 ~ 100 kW

dr-53 ~ dr-54 Accumulated Power Consumption Display

• Displays accumulated power consumption.

Parameter Functional Description

dr-53 Power Consumption MWh

dr-54 Power Consumption kWh

dr-55 Power Semiconductor Temperature

• Displays power consumption.

Range 0 ~ 200ºC

58 │

dr-56 Ambient Temperature Display

• Displays ambient temperature of the drive.

Range 0 ~ 200ºC

dr-57 Output Voltage Display

• Displays the effective output voltage of the drive.

Range 0.0 ~ 500.0V

dr-60 ~ dr-67 Command Frequency Setup Upon External Analogue Input

Parameter Function Name Functional Description

dr-60 V1 Min Input Voltage To set up min voltage to be input from external.

dr-61Corresponding Freq. to V1

Min Input VoltageTo set up frequency corresponding V1 min input

voltage

dr-62 V1 Max Input Voltage To set up max voltage to be input from external.

dr-63Corresponding Freq. to V1

Max Input VoltageTo set up frequency corresponding V1 max input

voltage.

dr-64 I1 Min Input Current To set up min current to be input from external.

dr-65Corresponding Freq. to I1

Min Input CurrentTo set up frequency corresponding I1 min input current

dr-66 I1 Max Input Current To set up max current to be input from external.

dr-67Corresponding Freq. to I1

Max Input CurrentTo set up frequency corresponding I1 max input

current.

Parameter Function Setting Input Range

dr-60 0.0 0.0 ~ 5.0 V

dr-61 0.0 0.00 ~ 30.00Hz

dr-62 10.0 5.1 ~ 10.0 V

dr-63 Rated Freq. of Motor 30.10 ~ Rated Freq. of Motor

dr-64 4 0 ~ 10mA

dr-65 0.0 0.00 ~ 30.00Hz

dr-66 20 11 ~ 20mA

dr-67 Rated Freq. of Motor 30.10 ~ Rated Freq. of Motor

CHAPTER 6. FUNCTION TABLE & DESCRIPTION

│ 59

dr-70 ~ dr-72 Time Display

Parameter Functional Description

dr-70 Displays Year

dr-71 Displays Month and Day

dr-72 Diplays Hours and Minutes

dr-90 Restore Factory Defaults

Setup Value Functional Description

0 (Factory Setting) Keep Settings

1 Restore Factory Default Settings

CHAPTER 6. FUNCTION TABLE & DESCRIPTION

60 │

CHAPTER 7. TROUBLESHOOTING

7.1 Fault History Table

FND Display

Content Description Restarting Reference

Er-01 tSF Pressure Sensor Error O 61

Er-02 tOP High Pressure Alarm O 61

Er-03 tLP Low Pressure Alarm O 62

Er-04 tUL Low Level Alarm O 62

Er-05 tASH Drive Arm Short Trip X 63

Er-06 tOC Drive H/W Over Current Trip O 63

Er-07 SOCDrive H/W Over Current Restriction

TripO 64

Er-08 tMOH Motor Overheat (TMOH) O 64

Er-09 tOH Drive Overheat Trip O 65

Er-10 tLv DC-Link Low Voltage Trip O 65

Er-11 tOv DC-Link High Voltage Trip O 65

Er-12 tOL Overload Operation Trip O 66

Er-13 tdOL Drive Overload Operation Trip O 66

Er-14 tGF Ground Trip X 66

Er-15 tIdE Communication ID Duplication Trip X 66

Er-16 tCE Communication Error X 67

Er-17 tIO The Defects of Input X 67

Er-18 tOO The Defects of Output X 67

Er-20 tES External Fault Input X 67

Er-21 tLt Allowable Time Elapsed X 67

7.2 Fault/Alarm Reset Procedure• Fault/alarm displayed on FND Pr-80.

• Press twice to reset in Pr-group

• Press once to reset in St-group

• In event of Er-01, Er-02, Er-04 (Low Level Sensor Alarm), drive will reset and restart automatically once cause has been resolved.

│ 61

CHAPTER 7. TROUBLESHOOTING

7.3 Fault Identification and Reaction

Er-01 Pressure Sensor Error - tSF

Cause

• Sensor error.

• Drive error.

• Sensor Terminal Wiring.

• Comm. ID not setup (Multi-drive pumpset).

Reaction

• Replace sensor.

• Replace drive.

• Check sensor terminal wiring.

• Check Comm. ID setup.

Related Function Function Name Reference

Pr-50 CAN Communication Mode 45

Pr-51 Communication ID 45

Pr-52 CAN Communication Speed 46

Er-02 High Pressure Alarm - tOP

Cause

• In the event of the pressure rising above the High Pressure Alarm Level (Pr-70) for a period exceeding the High Pressure Alarm Time (Pr-72), the drive will stop and the alarm LED will turn on.

Reaction

• Check setup pressure and high pressure alarm level.

• When pressure drops below the high pressure alarm level, the drive will automatically restart.

Related Function Function Name Reference

Pr-70 High Pressure Alarm Level 47

Pr-72 High Pressure Alarm Time 47

62 │

CHAPTER 7. TROUBLESHOOTING

Er-03 Low Pressure Alarm - tLP

Cause

• Pressure dropping below the Low Pressure Alarm Level (Pr-71) for a period exceeding the Low Pressure Alarm Time (Pr-73).

• The drive will automatically restart after the Automatic Restart Time (dr-38). If the drive trips the number of times specified by Autostart Occurrences After Trip (dr-37) it will not restart.

Reaction

• Check water tank (reservoir) is full.

• Check pump for air.

• Check pump for water by opening air cock.

• Press to release error and to start the pump.

Related Function Function Name Reference

Pr-71 Low Pressure Alarm Level 47

Pr-73 Low Pressure Alarm Time 47

dr-37 No. of Automatic Restart after Trip 54

dr-38 Waiting Time for Automatic Restart after Trip 54

Er-04 Low Water Level Alarm - tUL

Cause

• When using a low water level sensor, the alarm will be generated when the electrode detects no water on the suction side of the pump.

• When using a low water level sensor, the drive will automatically restart when water is detected in the suction side of the pump.

• When using software low water level detection, the alarm will be generated when the pressure is maintained below the Low Pressure Alarm Level (Pr-75) for a period of time exceeding the Low Pressure Alarm Time (Pr-74).

Reaction

• Check water tank (reservoir) is full.

●Check pump for water by opening air cock.

• Press to release error and to start the pump.

│ 63

CHAPTER 7. TROUBLESHOOTING

Related Function Function Name Reference

Pr-74 Low Pressure Level Alarm Time 47

Pr-75 Low Pressure Level Alarm Level 48

Pr-76 Low Water Level Alarm Detection Method 48

Pr-77 Low Water Level Sensor Trip Time 48

Er-05 Arm Short Trip - tASH

Cause

• The motor acceleration/deceleration time is excessively short compared to load inertia.

• Up/Down short circuit of IGBT.

• Output short circuit.

• Motor damage due to fire or insulation defect.

Reaction

• Increase Rising Time (dr-22).

• Check for motor damage from fire or insulation faults.

• Disconnect motor from drive and run drive. Alarm indicates an up/down short circuit of the IGBT.

Related Function Function Name Reference

dr-22 Rising Time 52

Er-06 H/W Over Current Trip - tOC

Cause

• The motor acceleration/deceleration time is excessively short compared to load inertia.

• Drive restarts during free run of motor

• Drive damage

64 │

Reaction

• Adjust the Rising Time (dr-22) or Falling Time (dr-23).

• Check the drive capacity matches the motor capacity.

• Start pump after the motor has stopped.

• Check load, motor and output wiring.

Related Function Function Name Reference

dr-21 Motor Stopping Method 52

dr-22 Rising Time 52

dr-23 Falling Time 52

Er-07 H/W Over Current Restriction Trip - SOC

Cause

• The motor acceleration/deceleration time is excessively short compared to load inertia.

• Drive restarts during free run of motor.

• Generation of over current due to sudden overload.

Reaction

• Adjust the Rising Time (dr-22) or Falling Time (dr-23).

• Check the drive capacity matches the motor capacity.

• Start pump after the motor has stopped.

• Adjust Torque Boost (dr-41).

Related Function Function Name Reference

dr-10 Motor Capacity 50

dr-21 Motor Stopping Method 52

dr-22 Rising Time 52

dr-23 Falling Time 52

dr-41 Torque Boost Amount 54

Er-08 Motor Overheat - tMOH

Cause

• Motor overheating.

• Load in excess of drive rating.

• Incorrect selection of drive capacity.

• Excessive low speed operation.

CHAPTER 7. TROUBLESHOOTING

│ 65

Reaction

• Check load capacity is suitable for drive rating.

• Reduce load or number of operations.

Related Function Function Name Reference

dr-10 Motor Capacity 50

dr-35 Motor Overheat Selection 53

Er-09 Overheat Trip - tOH

Cause

• Cooling fan interruption or fault.

• Excessively high ambient temperature.

Reaction

• Check cooling fan for faults or obstructions.

• Check that the ambient temperature does not exceed 40ºC.

Er-10 Low Voltage Trip - tLv

Cause

• Power supply voltage too low.

• Load in excess of the power capacity.

Reaction

• Check drive input voltage.

• Check power capacity.

Er-11 High Voltage Trip - tOv

Cause

• Falling time is too short compared to load inertia.

• Excessive drive input voltage.

Reaction

• Increase Falling Time (dr-23).

• Check driver power supply voltage.

Related Function Function Name Reference

dr-23 Falling Time 52

CHAPTER 7. TROUBLESHOOTING

66 │

Er-12 Motor Overload Operation - tOL

Cause

• In the event that load exceeds the Motor Rated Current (dr-31) for a period exceeding the Overload Trip Time.

Reaction

• Check that the Rated Current setting (dr-12) matches the rated current of the motor.

Related Function Function Name Reference

dr-10 Motor Capacity 50

dr-12 Rated Current of Motor 51

dr-30 Motor Overload Trip Selection 52

dr-31 Motor Overload Trip Level 53

dr-32 Motor Overload Trip Time 53

Er-13 Drive Overload Operation - tdOL

Cause

• The load exceeds the rated drive capacity.

Reaction

• Check that the drive capacity is sufficient for the load.

Er-14 Ground Trip - tGF

Cause

• Drive output line makes a short circuit with the earth line.

• Defective motor insulation.

Reaction

• Check drive output wiring.

• Replace motor.

Er-15 Comm. ID Duplication - tldE

Cause

• Duplication of drive ID on multi-drive pumpset.

Reaction

• Check drive IDs for duplication.

Related Function Function Name Reference

Pr-51 Communication ID 45

CHAPTER 7. TROUBLESHOOTING

│ 67

CHAPTER 7. TROUBLESHOOTING

Er-16 Communication Error - tCE

Cause

• Defective connection of CAN communication lines.

• Defective CAN communication IC.

Reaction

• Check connections of CAN communication lines.

Er-17 Input Defect - tIO

Cause

• Defective input wiring

• Defective input terminal contacts.

Reaction

• Check input wiring.

• Check input terminals.

Er-18 Output Defect - tOO

Cause

• Defective output wiring

• Defective output terminal contacts.

Reaction

• Check output wiring.

• Check output terminals.

Er-20 External Fault - tES

Cause

• External signal error

Reaction

• Check input of external signals.

Er-21 Allowable Time Elapsed

Reaction

• Contact your local Reece branch.

WARRANTY

You have purchased a quality product from Reece Australia. This product is covered by a 24 month warranty. This warranty covers faults in the product construction, material and assembly. Faulty products will be repaired or exchanged free of charge. Faulty items become our property.

This warranty does not include faults caused by:

• Unsuitable or improper use

• Incorrect installation

• Normal wear and tear

• Inadequate or complete lack of maintenance

• Chemical, electrochemical or electrical influences

To the maximum extent permitted by law, Reece excludes all warranties other than those set out above. In the event of a warranty claim, we will replace or repair defective products, or pay for the cost of having defective products repaired or replaced, but will not be liable for any injury to any person, damage to any property, any indirect or consequential loss, or in any other respect.

Disclaimer:

Products in this specification manual must by regulation be installed by licensed and registered trade people. The manufacturer/distributor reserves the right to vary specifications or delete models from their range without prior notification. Dimensions and set-outs listed are correct at time of publication however the manufacturer/distributor takes no responsibility for printing errors.

October 2013

L100

233

A10

13