60
THE GLOBAL SPECIALIST IN ELECTRAL AND DIGITAL BUILDING INFRASTRUCTURES ENERGY GUARANTEED EFFICIENCY ABSOLUTE UPS UNINTERRUPTIBLE POWER SUPPLY

UNINTERRUPTIBLE POWER SUPPLY UPS · of the uninterruptible power supplies. 10 p12 MODULAR p32 CONVENTIONAL UPS up to 120kVA with the maximum degree of redundancy (power and control)

  • Upload
    others

  • View
    20

  • Download
    0

Embed Size (px)

Citation preview

THE GLOBAL SPECIALIST IN ELECTRAL AND DIGITAL BUILDING INFRASTRUCTURES

ENERGY GUARANTEED

EFFICIENCYABSOLUTE

UPSUNINTERRUPTIBLE POWER SUPPLY

WWW.UPS.LEGRAND.COM

3UPSINDEX

®

INDEX

• General Features page 4

• Modular UPS page 12

• Conventional UPS page 32

• Line Interactive UPS page 44

• Accessories Communication page 50

• Services page 56

VDI STRUCTURED CABLES ELECTRICAL PROTECTION LIGHTING MANAGEMENT HOSPITAL SIGNALLING ENERGY MANAGEMENT

4

®

5

WWW.UPS.LEGRAND.COM

UPSGENERAL FEATURES

®

A guarantee of the highest level

in “BusinessContinuity”

LEGRAND, worldwide leader in manufacturing electrical equipment, offers a wide range of solutions for the tertiary sector fit to satisfy system requirements: from data network cable systems, and conduit and distribution systems, to system control and management.

TODAY, with an eye on technological development that respects the environment and responds to a continuously evolving market, LEGRAND proposes a new range of UPS. A complementary range of technological functions to guarantee maximum protection in all systems.

MEASUREMENT SYSTEMS ENERGY DISTRIBUTION SYSTEM SUPERVISION FIRE ALARM SYSTEMSUPS UNINTERRUPTABLE POWER SUPPLY

TERTIARY A PROPOSAL FOR THE BUILDING IN CONTINUOUS EVOLUTION

6

Energy efficiency and savings

®

7UPS

WWW.UPS.LEGRAND.COM

GENERAL FEATURES

maximum quality of energy output

High efficiency

UPS with cutting-edgemanufacturing characteristicsthat make it possible to obtainefficiency up to 95% fora significant energyand economic savings.

Evolved technology

Products with double conversionONLINE technologycapable of re-phasingthe power supply systemand guaranteeing maximumquality of usable energy.

Environmentally friendly products

Efficient UPS manufactured giving them maximum attention.In a development view that is environmentally friendly, LEGRAND developed an innovative test system that drastically reduces energy consumption for each machine produced.

8

®

9UPS

WWW.UPS.LEGRAND.COM

GENERAL FEATURES

Reliable electronics

Optimum sizing for power stages and extensive, in-depth tests guarantee a notable level of reliability.

Components of latest generation

Careful research for the best electronic components present on the market, combined with the most modern production methods, make Legrand UPS extremely reliable machines and in step with the times.

High performance Batteries

Batteries supplied with Legrand UPS are the best available on the market. An innovative charging system significantly extends battery life, even by 50%

reliability and safetyTechnological excellence of the uninterruptible power supplies

10

CONVENTIONALMODULARp12 p32

UPS up to 120kVAwith the maximum degree of redundancy (power and control) suitable for applications where expansion flexibility and quick maintenance are required.

UPS up to 10kVA guarantee a power supplysystem that is safe and reliable.

THE RANGE OF

UPS

®

11UPS

WWW.UPS.LEGRAND.COM

THE RANGE OF UPS

COMMUNICATION ACCESSORIESLINE INTERACTIVE p50p44

A complete range of communication devices allows you to remotely manage, configure and control the UPS.

UPS up to 3 kVAentry level, they areideal protectionfor work station, telephone switchboards, home automation applications and small tertiary.

Calibrated solutionsfor every context

LEGRAND proposes a range of UPSdivided into 3 different types. An offering for all application environments with solutions that guarantee maximum protection in terms of power and uptime. With LEGRAND UPS it is possible to obtain the correct solution for every need.

12

®

13

WWW.UPS.LEGRAND.COM

UPSMODULAR UPS

®

TRIMOD ARCHIMODMEGALINE

UPS

MODULAR

Allows to size the UPS on a needs-basis and allows for future implementations.

They are made of «STANDARD» modules that can be added to existing machines in order to expand both power and uptime.

They guarantee maximum levels of redundancy thanks to the innovative three-phase system made of individual single-phase modules.

Flexible, expandable and redundant solutions

ARCHIMOD AND TRIMOD

DYNAMIC THREE-PHASE SYSTEMSUPS with exclusive technology capable of adapting to all types of systems in the best possible way.

These machines have an innovative modularity concept that optimizes the availability of power, increases system flexibility and reduces the total cost of operation (TCO).

Highly standardised structures, made of individual single-phase modules, guarantee the highest levels of granularity on the market.

1414

®

15UPS

WWW.UPS.LEGRAND.COM

MODULAR UPS

®

ARCHIMOD and TRIMOD have received

from FROST & SULLIVANthe prestigious prize

Product DifferentiationExcellence award 2011

for the EMEA area.

FLEXIBILITY MODULARITY SCALABILITY

Granularity of power

Three-phase UPS are composed of redundant and self-configuring individual single-phase modules for fast and safe power increases.

Optimisation of interventions

Transport, installation and maintenance interventions are easier to manage with UPS power modules given their reduced dimensions and weight (only 8.5 kg).

ARCHIMOD AND TRIMOD

16

EXCLUSIVE FEATURES

ARCHIMOD AND TRIMOD

Power scalability

Power expansion, for both product families, can always be obtained within the same cabinet in an extremely simple and immediate manner, without the need to re-configure the system and UPS.

Scalability uptime

Based on UPS power and the request for uptime, expansion may take place both in the same cabinet, adding battery slots or in additional battery cabinets. Compact non modular battery cabinets that further extend uptime reaching a level of hours, are also available.

TRIMOD10 to 60 kVA

ARCHIMOD20 to 120 kVA

®

17

WWW.UPS.LEGRAND.COM

UPSMODULAR UPS

MODULAR

THREE-PHASEMaximum levels

of redundancy

Thanks to modular UPS construction technology, various redundancy levels can be set to always guarantee maximum service continuity.

Redundancy on the phases

In a system with three independent outputs, redundancy can be set on individual phases.If one of the power modules breaks down, modules of the same phase make up for the absence of the faulty module.

Redundancy on control

In UPS composed of several control modules, if one of them breaks down, only the modules controlled by it will shut-down. Lost power, however, is automatically redistributed to other modules to guarantee service continuity.

Redundancy on the single-phase load

In a system with three-phase power supply and single-phase load, if one of the power modules breaks down, there is no power loss since it is supplied by the other operating modules.

R

LOAD

S T

KO

R

LOAD

S T

R

L1 L1L2 L2L3 L3

RS ST T

KO

R RS ST T

R RS ST T

KO

18

ARCHIMOD is the UPS with a modular and expandable architecture with power from 20 to 120kVA, in 19 inch rack cabinet.

The system is made from a set of standard and pre-assembled components that allow simplifying and speeding up the design and completion process for infrastructures.

Efficiency up to 95% when in ON LINE MODE

Standard modules with self-configurable Plug&Play system

Power factor close to 1 at input

Multi IN/OUT to obtain different three-phase or single-phase configurations ON SITE

ARCHIMOD MODULAR THREE-PHASE

®

WWW.UPS.LEGRAND.COM

19UPS

MODULAR ARCHITECTURE

1 Control logicsEquipped with microprocessor, it manages 3 power modules.If combined with a power expansion module, it can manage up to 6 power modules, thus increasing power from 20 to 40kVA.It comes equipped with a multifunction display and keyboard to monitor UPS operating parameters, and to configure numerous functions.It can be connected in parallel to other control modules and with power modules. On the front side, there is a backlit status indicator to immediately identify the system’s operation status, and an RS232 communication port for maintenance.

2 Power modulesPower modules, with power equal to 6.7 kVA, are extremely compact and easy to move.Equipped with a plug-in and real hot-swap system, installation and maintenance is quick.They work in parallel with all modules to guarantee maximum system performance.

3 Power expansion moduleIt must be combined with a control module. Power can be increased from 20 to 40 kVA, and redundancy on single-phase can be set.

4 Battery moduleEach module has batteries that can be connected to others in series, creating independent strings.The compactness and functionality of individual modules (plug-in) means they can be easily moved and expanded without changing the installed solution (flexibility and scalability).

5 DistributionUPS can be configured directly on site into different distribution systems (three-three, three-single, single-single and single-three). Inside there are terminal blocks for in-out connection, movement and protection components, and the predisposition for additional battery cabinets.Power supply can be configured on two separate input networks (primary and emergency by-pass).

6 Input cableInput cable compartments allow inserting in-out connection cables at both the top and bottom.

6

5

4

3

2

1

6

MODULAR UPS

20

TRIMOD MODULAR

THREE-PHASEModular and upgradable with power from

10 to 60kVA in compact structures with a reduced

footprint.

The completely modular structure enables programming eachindividual power module in order to obtain the desired input/outputconfiguration.

It is possible to manage three-phase or single-phase output and input voltage in order to choose, 3-3 phases, 3-1 phases, 1-3 phases and 1-1 phase.Furthermore, it is possible to obtain single-phase and three-phase output lines simultaneously or two or more single-phase lines, even of different power levels (upon request).

Control display

The TRIMOD system is completely managed by a microprocessor and using the keyboard on the LCD display it is possible to:- set and view operational data in real time- configure and control parameters for each

power module- access event logs- complete functional tests

Compact and reduced footprint versions The compact dimensions, the vertical build of the structure and 2 small wheels located in the rear help with positioning and transporting the UPS, even in rooms that are not easy to access.

®

21

WWW.UPS.LEGRAND.COM

MODULAR UPS

MEGALINE MODULAR

SINGLE-PHASE

THEY ARE AVAILABLE IN THREE FORMATS:- SINGLE CABINET;

- DOUBLE CABINET;- 19 INCH RACK.

All models have a microprocessor control card that can be configured on

the display, by modules powered by 1250 VA each, and by battery kits that contain no. 3x9Ah batteries.

Modular UPS redundant and upgradable up to

10kVA with perfomance and functions at the top

of their category

The single cabinet and 19 inch rack models issue a power from 1250 to 5000 VA, they can house a maximum of 4 power boards and 4 battery kits. Additional batteries can be stored in specific cabinets, which can be easily connected thanks to an uptime upgrading pre-setting.

The range is completed with products made of two cabinets; the first cabinet can house up to 8 power modules, each up to 1250 VA, reaching a maximum power of 10kVA. In the second cabinet it is possible to insert up to 10 battery kits and an additional battery charger.Other battery cabinets identical to the one supplied canbe added in order to further upgrade uptime.

UPS

22

ARCHIMODModular three-phase UPS with double conversion VFI

Pack. Item CONFIGURABLE CABINETS

The cabinets are supplied empty and are pre-set for power and uptime as indicated in the table

NOMINAL

POWER KVA

NO. BATTERY

MODULES

NO. MODULES

FOR CONTROL

NO. MODULES

FOR POWER

EXPANSION

NO. PHASES

3 104 51 * 20 12 1 - 3-1/3-3

3 104 52 20 30 1 - 3-1/3-3

3 104 53 40 24 2 - 3-3/3-3

3 104 54 60 18 3 - 3-3

3 104 55 80 - 3 1 3-3

3 104 56 100 - 3 2 3-3

3 104 57 120 - 3 3 3-3

* cabinet with 18 rack units available

ADDITIONAL CABINETS FOR BATTERIESDESCRIPTION

3 108 18 Empty modular battery cabinet

3 108 21 Battery cabinet for 20kVA UPS with 21 94 Ah long life batteries

3 108 22 Battery cabinet for 40-60kVA UPS with 21 94 Ah long life batteries

3 108 23 Battery cabinet for 80kVA UPS with 21 94 Ah long life batteries

3 108 24 Battery cabinet for 100-120kVA UPS with 21 94 Ah long life batteries

3 108 65 Cover for closing empty battery slots

3 108 66 Cover for closing empty power module slots

ACCESSORIESDESCRIPTION

3 108 40 6.7kVA power module

3 108 64 Front/rear closing door

3 108 55 Kit of 3x9Ah battery slots

3 108 56 Kit of 3 empty battery slots

3 108 40

3 108 55

20Power: 20 kVAUptime (80% of the load): 1h1 Cabinet1 Control module3 Power modules30 Battery modules1 Distribution modules

40Power: 40 kVAAutonomy (80% of the load): 20 min1 Cabinet2 Control modules6 Power modules24 Battery modules1 Distribution modules

CONFIGURATIONS

100Power: 100 kVAAutonomy (80% of the load): 10 min2 Cabinets3 Control modules2 Power expansion modules15 Power modules36 Battery modules1 Distribution modules

120Power: 120 kVAAutonomy (80% of the load): 6 min2 Cabinets3 Control modules3 Power expansion modules18 Power modules36 Battery modules1 Distribution modules

60Power: 60 kVAUptime (80% of the load): 6 min1 Cabinet3 Control modules9 Power modules18 Battery modules1 Distribution modules

80Power: 80 kVAAutonomy (80% of the load): 12 min2 Cabinets3 Control modules1 Power expansion module12 Power modules36 Battery modules1 Distribution modules

3 104 54

NOTE: autonomy values, expressed in minutes, are measured during optimal

operating conditions.

23UPS

WWW.UPS.LEGRAND.COM

MODULAR UPS

ARCHIMODModular three-phase UPS with double conversion VFI

Idem3 104 513 104 52

3 104 53 3 104 54 3 104 55 3 104 56 3 104 57

General features

Nominal Power (kVA) 20 40 60 80 100 120

Active power (kW) 18 36 54 72 90 108

Module Power (kVA) 6.7 for the Power Module (20kVA with 3 Modules), power factor 0.9

Technology On-Line Double Conversion VFI-SS-111

System Modular, expandable and redundant UPS system in just one 19’’ rack cabinet

Hot Swap capacity Possibility of replacing the power modules and/or battery without turning off the UPS

Input features

Input voltage 230V 1F+N, 400V 3F+N 400V 3F+N

Input frequency 50-60 Hz ±2% Autosensing

Input Voltage Range230V +15%/-20% 1F 400V +15%/-20% 3F

400V +15%/-20% 3F

THD Input Current ‹ 3%

Compatibility with Power-Supply UnitsConfigurable in order to achieve synchronism between input

and output frequencies, even for wider frequency ranges, ±14%

Input Power Factor › 0,99

Output features

Output voltage 230V 1F, 400V 3F 400V 3F

Performance at Full Load 95%

Nominal output frequency 50/60 Hz ±0.1

Crest Factor 3,5:1

Output Voltage Tolerance ±1%

Allowed Overload 10 minutes at 125% and 1 minute at 150%

Performance in Eco Mode 99%

Bypass Automatic and maintenance bypass

Batteries

Battery ModuleThe battery modules are designed to easily be fitted inside the cabinet.

No particular operation is necessary to connect them

Battery Series Type/Voltage VRLA - AGM / 252 Vdc

Uptime Configurable and expandable both internally and with additional battery cabinets

Battery Charge Smart Charge technology. 3-stage advanced cycle

Configuration and management

Display and Signals4 lines/20 characteristics, 4 buttons for menu navigation,

multi-colour LED status indicator

Communication Ports2 RS232 serial ports, 1 Logical gate, 5 ports with dry contacts,

2 slots for SNMP interfaces (optional)

Emergency Power Off (EPO) Yes

Remote Management Available

Physical features

Dimensions (H x W x D) (mm) 2080 x 570 x 912 (42U)

Installed Power Modules 3 6 9 12 15 18

Installable Battery Slots Up to 30 Up to 24 Up to 18 - - -

Net Weight (kg) 205 240 276 272 318 364

Environmental conditions

Operating Temperature/Humidity 0 - 40 °C / 20 - 80% non-condensing

Degree of protection IP21

Maximum Audible Noise at 1 m from the Unit (dBA) 50÷65

Heat Loss (BTU/h) 2730 5460 8190 10920 13650 16380

Conformity

Certifications EN 62040-1, EN 62040-2, EN 62040-3

Standard Warranty 2-year warranty

Services

InstallationCan be performed by the user, modular architecture with "plug and play"

power and battery modules for easy installation and configuration

Maintenance Can be performed by the user, optional services available from the manufacturer

24

3 103 99

TRIMODModular three-phase UPS with double conversion VFI

Pack. Item POWER CABINETSNOMINAL

POWER

KVA

ACTIVE

POWER

KW

UPTIME

(MIN.) 80%

OF THE LOAD

NO.

CABINET

WEIGHT

(kg)

3 103 98 10 9 0' 1 120

3 104 04 15 13,5 0' 1 120

3 104 10 20 18 0' 1 120

3 104 16 30 27 0' 1 146

3 104 21 40 36 0' 1 146

3 104 28 60 54 0' 1 165

POWER CABINETS (EMPTY)NO. POWER

MODULES

NO. BATTERY

MODULES

POWER MODULE

TYPES

NO. PHASES

3 104 36 3 12 3 x 3,4 kVA 1-1 / 3-3 / 3-1 / 1-3

3 104 37 3 12 3 x 5 o 6,7 kVA 1-1 / 3-3 / 3-1 / 1-3

3 104 38 6 - 6 x 3,4 kVA 3-3

3 104 39 6 - 6 x 5kVA 1-1/3-3/3-1/1-3

3 104 40 6 - 6 x 6,7kVA 3-3

3 104 41 9 - 9 x 6,7kVA 3-3

ACCESSORIESDESCRIPTION

3 108 36 Power module 3.4 kVA

3 108 38 Power module 5 kVA

3 108 40 Power module 6.7 kVA

3 108 51 Additional 5kVA battery charge module for expansions

ACCESSORIES FOR BATTERIESDESCRIPTION

3 108 54 Kit of 4 empty battery slots

3 108 43 Single slot with 5x7,2Ah batteries (installable in multiples of 4)

3 108 45 Single slot with 5x9Ah batteries (installable in multiples of 4)

ADDITIONAL BATTERY CABINETSDESCRIPTION

3 108 05 Modular battery cabinet (empty) with 16 trays

3 108 06 Modular battery cabinet (empty) with 20 trays

3 107 55 Modular battery cabinet with 4 battery trays (7.2 Ah)

3 107 56 Modular battery cabinet with 8 battery trays (7.2 Ah)

3 107 57 Modular battery cabinet with 12 battery trays (7.2 Ah)

3 107 58 Modular battery cabinet with 16 battery trays (7.2 Ah)

3 107 59 Modular battery cabinet with 20 battery trays (7.2 Ah)

3 107 60 Modular battery cabinet with 4 battery trays (9 Ah)

3 107 61 Modular battery cabinet with 8 battery trays (9 Ah)

3 107 62 Modular battery cabinet with 12 battery trays (9 Ah)

3 107 63 Modular battery cabinet with 16 battery trays (9 Ah)

3 107 64 Modular battery cabinet with 20 battery trays (9 Ah)

3 108 07 10kVA battery cabinet for UPS with 20, 94 Ah long life batteries

3 108 08 20kVA battery cabinet for UPS with 20, 94 Ah long life batteries

3 108 09 30kVA battery cabinet for UPS with 20, 94 Ah long life batteries

3 108 10 40kVA battery cabinet for UPS with 20, 94 Ah long life batteries

3 108 11 60kVA battery cabinet for UPS with 20, 94 Ah long life batteries

Pack. Item UPSNOMINAL

POWER

KVA

UPTIME

(MIN.) 80%

OF THE LOAD

NO.

CABINET

WEIGHT

(kg)

3 103 99 10 11' 1 167

3 104 00 10 17' 1 223

3 104 01 10 35' 1 279

3 104 00 + 3 107 57 10 54' 2 471

3 104 00 + 3 107 58 10 68' 2 527

3 104 05 15 13' 1 220

3 104 06 15 21' 1 279

3 104 06 + 3 107 60 15 33' 2 413

3 104 06 + 3 107 63 15 57' 2 550

3 104 04 + 3 108 08 15 109' * 2 865

3 104 11 20 9' 1 220

3 104 12 20 14' 1 279

3 104 12 + 3 107 58 20 35' 2 572

3 104 12 + 3 108 08 20 81' * 2 865

3 104 12 + 2 x 3 107 58 20 59' 3 574

3 104 16 + 3 107 57 30 6' 2 378

3 104 16 + 3 107 58 30 12' 2 434

3 104 16 + 3 108 09 30 50' * 2 890

3 104 16 + 2 x 3 108 09 30 109' * 3 1645

3 104 21 + 3 107 63 40 8' 2 564

3 104 21 + 2 x 3 107 58 40 16' 3 801

3 104 21 + 3 108 10 40 33' * 2 925

3 104 21 + 3 x 3 107 59 40 38' 4 439

3 104 21 + 4 x 3 107 64 40 60' 5 1663

3 104 21 + 3 x 3 108 10 40 120' * 4 2430

3 104 28 + 2 x 3 107 58 60 9' 3 830

3 104 28 + 2 x 3 107 64 60 15' 3 942

3 104 28 + 3 108 11 60 17' * 2 952

3 104 28 + 3 x 3 107 64 + 3 107 60

60 32' 5 1579

3 104 28 + 2 x 3 108 11 60 50' * 3 1715

3 104 28 + 3 x 3 108 11 60 80' * 4 2474

3 104 28 + 4 x 3 108 11 60 110' * 5 3234

* Configurations with battery cabinets (20 x 94 Ah). Battery cabinet dimensions and weight: A x L x P 1635 x 600 x 800 (mm), 785 kg

3 108 43

3 108 40

NOTE: autonomy values, expressed in minutes, are measured during optimal operating conditions.

25UPS

WWW.UPS.LEGRAND.COM

MODULAR UPS

TRIMODModular three-phase UPS with double conversion VFI

Item 3 103 98 3 104 04 3 104 10 3 104 16 3 104 21 3 104 28

General Features

Nominal Power (kVA) 10 15 20 30 40 60

Active power (kW) 9 13,5 18 27 36 54

Module Power (kVA) 3,4 5 6,7 5 6,7 6,7

Technology On-Line Double Conversion VFI-SS-111

SystemModular, expandable and redundant

UPS in a single cabinetModular, expandable and redundant UPS system

Input features

Input voltage 230V 1F+N, 400V 3F+N 400V 3F + Neutral

Input frequency 50-60 Hz ±2% Autosensing

Input Voltage Range 400V +15%/-20% - 230V +15%/-20% 400V +15%/-20%

THD Input Current ‹ 3%

Compatibility with Power-Supply UnitsConfigurable in order to achieve synchronism between input

and output frequencies, even for wider frequency ranges, ±14%

Input Power Factor › 0,99

Output features

Output voltage 230V, 400V 3F +N 400V 3F + Neutral

Performance at Full Load 95%

Nominal output frequency 50/60 Hz can be selected by the user ±1 Hz

Crest Factor 1:3,5

Output Voltage Tolerance ±1%

Allowed Overload 100 seconds at 125%, 30 seconds at 150%

Performance in Eco Mode 98%

Bypass Automatic and maintenance bypass

Batteries

Battery ModuleThe battery modules are designed to easily be fitted inside the cabinet.

No particular operation is necessary to connect them

Battery Series Type/Voltage VRLA - AGM / 240 Vdc (internal redundant series)

Uptime Configurable and expandable both internally and with additional battery cabinets

Battery Charge Smart Charge technology. 3-stage advanced cycle

Configuration and management

Display and Signals4 rows/20 characters, 4 menu browsing buttons, multi-colour LED status indicator,

alarms and audio signals

Communication Ports 2 RS232 serial ports, 1 Logical gate, 4 ports with dry contacts, 1 slots for interfaces

Emergency Power Off (EPO) Yes

Remote Management Available

Physical features

Dimensions (H x W x D) (mm) 1345 x 414 x 628

Installed Power Modules 3 6 6 9

Installable Battery Slots Up to 12 - - -

Net Weight (kg) 120 130 130 150

Environmental conditions

Operating Temperature/Humidity 0 - 40 °C / 20 - 80%

Degree of protection IP21

Maximum Audible Noise at 1 m from the Unit (dBA) 46

Heat Loss (BTU/h) 1436 2155 2873 4310 5746 8619

Conformity

Certifications EN 62040-2, EN 62040-3, EN 62040-1

Standard Warranty 2-year warranty

Services

Installation Can be performed by the user, modular architecture with "plug and play" power and battery modules

Maintenance Can be performed by the user, optional services available from the manufacturer

Easy to Manage Advanced diagnostics functions via the display

26

3 108 35

MEGALINEModular single-phase UPS with double conversion VFI

Pack. Item SINGLE CABINET (German Standard)NOMINAL

POWER

VA

ACTIVE

POWER

W

UPTIME

(MIN.) 80%

OF THE LOAD

NO.

CABINET

WEIGHT

(kg)

3 103 50 1250 875 11 1 23,5

3 103 52 2500 1750 11 1 34

3 103 54 3750 2625 11 1 43

3 103 56 5000 3500 11 1 53

DOUBLE CABINETNOMINAL

POWER

VA

ACTIVE

POWER

W

UPTIME

(MIN.) 80%

OF THE LOAD

NO.

CABINET

WEIGHT

(kg)

3 103 60 + 3 107 78 5000 3500 11 2 24+50

3 103 63 + 3 107 79 6250 4375 11 2 27+58

3 103 66 + 3 107 80 7500 5250 11 2 29+65

3 103 69 + 3 107 81 8250 6125 11 2 32+73

3 103 72 + 3 107 82 10000 3500 11 2 34+80

SINGLE CABINET (French standard)NOMINAL

POWER

VA

ACTIVE

POWER

W

UPTIME

(MIN.) 80%

OF THE LOAD

NO.

CABINET

WEIGHT

(kg)

3 103 42 1250 875 11 1 23,5

3 103 43 2500 1750 11 1 34

3 103 44 3750 2625 11 1 43

3 103 45 5000 3500 11 1 53

SINGLE CABINET (British standard)NOMINAL

POWER

VA

ACTIVE

POWER

W

UPTIME

(MIN.) 80%

OF THE LOAD

NO.

CABINET

WEIGHT

(kg)

3 103 46 1250 875 11 1 23,5

3 103 47 2500 1750 11 1 34

3 103 48 3750 2625 11 1 43

3 103 49 5000 3500 11 1 53

Pack. Item SINGLE CABINET - WITHOUT BATTERIESNOMINAL

POWER

VA

ACTIVE

POWER

W

UPTIME

(MIN.) 80%

OF THE LOAD

NO.

CABINET

3 103 51 1250 875 - 1

3 103 53 2500 1750 - 1

3 103 55 3750 2625 - 1

3 103 57 5000 3500 - 1

DOUBLE CABINET - WITHOUT BATTERIESNOMINAL

POWER

VA

ACTIVE

POWER

W

UPTIME

(MIN.) 80%

OF THE LOAD

NO.

CABINET

3 103 60 + 3 108 59 5000 3500 - 2

3 103 63 + 3 108 59 6250 4375 - 2

3 103 66 + 3 108 59 7500 5250 - 2

3 103 69 + 3 108 59 8250 6125 - 2

3 103 72 + 3 108 59 10000 3500 - 2

BATTERY EXPANSIONSDESCRIPTION

3 107 75 Cabinet with 1 kb

3 107 76 Cabinet with 2 kb

3 107 77 Cabinet with 3 kb

3 107 78 Cabinet with 4 kb

3 107 79 Cabinet with 5 kb

3 107 80 Cabinet with 6 kb

3 107 81 Cabinet with 7 kb

3 107 82 Cabinet with 8 kb

3 107 83 Cabinet with 9 kb

3 107 84 Cabinet with 10 kb

BATTERY EXPANSION WITH BATTERY CHARGERDESCRIPTION

3 107 86 Cabinet with 1 kb with battery charger

3 107 87 Cabinet with 2 kb with battery charger

3 107 88 Cabinet with 3 kb with battery charger

3 107 89 Cabinet with 4 kb with battery charger

3 107 90 Cabinet with 5 kb with battery charger

3 107 91 Cabinet with 6 kb with battery charger

3 107 92 Cabinet with 7 kb with battery charger

3 107 93 Cabinet with 8 kb with battery charger

3 107 94 Cabinet with 9 kb with battery charger

3 107 95 Cabinet with 10 kb with battery charger

ACCESSORIESDESCRIPTION

3 108 35 Power module (PW 1250)

3 108 57 Uptime up-grade single cabinet (kb MegaLine/1)

3 108 58 Uptime up-grade double cabinet (kb MegaLine/2)

3 108 59 Empty battery cabinets

3 108 60 Y cable for connecting second additional battery cabinet (MegaLine SPLITTER)

3 108 61 Kit with battery cabinet extension for tower configuration (PL MegaLine cable)

3 108 62 Manual bypass for single cabinet (BP/1)

3 108 63 Manual bypass for double cabinet (BP/2)

3 107 85 Additional battery charger (CB 36)

3 109 72 Relay interface kit

3 103 60 + 3 107 78

3 108 57

3 108 63

3 108 62

NOTE: autonomy values, expressed in minutes, are measured during optimal operating conditions.

27UPS

WWW.UPS.LEGRAND.COM

MODULAR UPS

MEGALINEModular single-phase UPS with double conversion VFI

Item3 103 42 3 103 463 103 50

3 103 43 3 103 473 103 52

3 103 443 103 483 103 54

3 103 45 3 103 493 103 56

3 103 60 + 3 107 78

3 103 63 + 3 107 79

3 103 66 + 3 107 80

3 103 69 + 3 107 81

3 103 72 + 3 107 82

Single CABINET Double CABINET

General Features

Nominal power (VA) 1250 2500 3750 5000 5000 6250 7500 8750 10000

Active power (W) 875 1750 2625 3500 3500 4375 5250 6125 7000

Max expandability (VA) 5000 10000

Max expandability (W) 3500 7000

Technology On-line double conversion (VFI-111)

UPS architecture Modular, Expandable, N+X Redundant with 1250 VA power boards in a single cabinet

Input

Input nominal voltage 230 V

Input voltage range 184 V ÷ 264 V at 100% of the load

Minimum network operating voltage 100 V at 50% of the load

THD Input current ‹ 3%

Input Power Factor › 0.99 from 20% of the load

Input frequency 50 Hz / 60 Hz ± 2% autosensing

Output

Output voltage 230 V ± 1%

Output frequency 50 Hz / 60 Hz synchronised

THD Output voltage ‹ 1% with non-linear load

Waveform Sinusoidal

Crest Factor 3,5 : 1

Performance when connected to the mains 92% at 100% of the load

Allowed overload 300% for 1 sec. – 200% for 5 sec. – 150% for 30 sec.

Uptime

Uptime with 50% load (min) 20

Uptime with 80% load (min) 11

Uptime expandability Yes

Equipment

Bypass Static and Electromechanical, automatic and internally synchronised (due to overload or operating fault).

Signals and Alarms Large 4-line alphanumeric display, multi-colour status indicator, audio signal

Communication Ports no.1 RS 232 port, no.2 logical gates

UPS Communicator Software Can be downloaded free of charge (after requesting the activation code)

Protections

Electronic protections against overloads, short-circuits and excessive battery discharge. Operation stops when the uptime ends. In-rush current limiter at start-up.

Sensor to connect the neutral cable correctly. Back-feed protection (electrical safety insulation of the input plug during battery-based operation). EPO contact

(complete shutdown in the event of an emergency)

IN/OUT mains connection Standard German / Clamp connector with universal multiple socket outlet (Italian/German standard)

Mechanical features

Net weight (kg) 23,5 34 43 53 24 + 50 26,5+57,5 29 + 65 31,5+72,5 34 + 80

Dimensions (H x W x D) (mm) 475 x 270 x 570 2 x 475 x 270 x 570

Installed power boards 1 2 3 4 4 5 6 7 8

Free power expansion slots 3 2 1 - 4 3 2 1 -

Installed battery kits 1 2 3 4 4 5 6 7 8

Free uptime expansion slots 3 2 1 - 6 5 4 3 2

Environmental conditions

Operating temperature (°C) 0÷40

Degree of protection IP21

Relative humidity (%) 20÷80 non-condensing

Noise level at 1 m (dBA) ‹ 40

Certifications

Standards EN 62040-1, EN 62040-2, EN 62040-3

Certifications

Standard Warranty 2-year warranty

28

MEGALINE RACKModular single-phase UPS with double conversion VFI

- Wide input voltage and frequency range- Operational frequency at 50 or 60 Hz with auto-recognition- Frequency conversion 50 in - 60 out or vice versa- Extension of the input frequency range for operation with power-supply units- Operation in eco mode (energy savings)- Operation in load waiting mode (on demand protection)- Adjustable output voltage in 1 volt steps from the front panel- Low noise level- Internal and external temperature measurement- Fan control based on temperature and load- Pre-set for emergency remote shut-off

Pack. Item RACK (German standard)NOMINAL

POWER

VA

ACTIVE

POWER

W

UPTIME

(MIN.) 80%

OF THE LOAD

NO.

CABINET

WEIGHT

(kg)

3 103 79 1250 875 11 1 23,5

3 103 81 2500 1750 11 1 34

3 103 83 3750 2625 11 1 43

3 103 85 5000 3500 11 1 53

RACK (French standard)NOMINAL

POWER

VA

ACTIVE

POWER

W

UPTIME

(MIN.) 80%

OF THE LOAD

NO.

CABINET

WEIGHT

(kg)

3 103 34 1250 875 11 1 23,5

3 103 35 2500 1750 11 1 34

3 103 36 3750 2625 11 1 43

3 103 37 5000 3500 11 1 53

RACK (British standard)NOMINAL

POWER

VA

ACTIVE

POWER

W

UPTIME

(MIN.) 80%

OF THE LOAD

NO.

CABINET

WEIGHT

(kg)

3 103 38 1250 875 11 1 23,5

3 103 39 2500 1750 11 1 34

3 103 40 3750 2625 11 1 43

3 103 41 5000 3500 11 1 53

Pack. Item UPTIME EXPANSIONNOMINAL POWER

VA

KB

ADDITIONAL

EXPANSION (MIN.)

80% OF THE LOAD

3 103 87 1250 1 15

3 103 88 1250 2 30

3 103 89 1250 3 45

3 103 90 2500 1 15

3 103 91 2500 2 17

3 103 92 3750 1 15

BATTERY EXPANSIONS FOR UPS RACKDESCRIPTION

3 107 96 Rack with 1 kb

3 107 97 Rack with 2 kb

3 107 98 Rack with 3 kb

3 107 99 Rack with 4 kb

3 108 00 Rack with 1 kb with battery charger

3 108 01 Rack with 2 kb with battery charger

3 108 02 Rack with 3 kb with battery charger

3 108 03 Rack with 4 kb with battery charger

ACCESSORIESDESCRIPTION

3 108 35 Power module (PW 1250)

3 108 04 Empty battery rack cabinets

3 108 62 Manual bypass for single cabinet (BP/1)

3 107 85 Additional battery charger (CB 36)

3 109 72 Relay interface kit

3 109 73 Extendable Rack Guides Kit 6U

3 107 963 103 85

3 107 853 108 62 3 109 73

NOTE: autonomy values, expressed in minutes, are measured during optimal operating conditions.

29UPS

WWW.UPS.LEGRAND.COM

MODULAR UPS

Item3 103 343 103 383 103 79

3 103 353 103 393 103 81

3 103 363 103 403 103 83

3 103 373 103 413 103 85

General Features

Nominal power (VA) 1250 2500 3750 5000

Active power (W) 875 1750 2625 3500

Max expandability (VA) 5000

Max expandability (W) 3500

Technology On-line double conversion (VFI-111)

UPS architectureModular, Expandable, N+X Redundant with 1250 VA power boards

in a single cabinet

Input

Input nominal voltage 230 V

Input voltage range 184 V ÷ 264 V at 100% of the load

Minimum network operating voltage 100 V at 50% of the load

THD Input current ‹ 3%

Input Power Factor › 0.99 from 20% of the load

Input frequency 50 Hz / 60 Hz ± 2% autosensing

Output

Output voltage 230 V ± 1%

Output frequency 50 Hz / 60 Hz synchronised

THD Output voltage ‹ 1% with non-linear load

Waveform Sinusoidal

Crest Factor 3,5 : 1

Performance when connected to the mains 92% at 100% of the load

Allowed overload 300% for 1 sec. – 200% for 5 sec. – 150% for 30 sec.

Uptime

Uptime with 50% load (min) 20

Uptime with 80% load (min) 11

Uptime expandability Yes

Equipment

BypassStatic and Electromechanical, automatic and internally synchronised

(due to overload or operating fault)

Signals and Alarms Large 4-line alphanumeric display, multi-colour status indicator, acoustic signal

Communication Ports no.1 RS 232 port, no.2 logical gates

UPS Communicator Software Can be downloaded free of charge (after requesting the activation code)

Protections

Electronic protections against overloads, short-circuits and excessive battery discharge. Operation stops when the uptime ends. In-rush current limiter at start-up. Sensor to

connect the neutral cable correctly. Back-feed protection (electrical safety insulation of the input plug during battery-based operation).

EPO contact (complete shutdown in the event of an emergency)

IN/OUT mains connectionStandard German / Clamp connector with universal multiple socket outlet

(Italian/German standard)

Mechanical features

Net weight (kg) 23,5 34 43 53

Dimensions (H x W x D) (mm) 266 x 483 x 582

Installed power boards 1 2 3 4

Free power expansion slots 3 2 1 -

Installed battery kits 1 2 3 4

Free uptime expansion slots 3 2 1 -

Environmental conditions

Operating temperature (°C) 0÷40

Degree of protection IP21

Relative humidity (%) 20÷80 non-condensing

Noise level at 1 m (dBA) ‹ 40

Certifications

Standards EN 62040-1, EN 62040-2, EN 62040-3

Warranty

Standard Warranty 2-year warranty

MEGALINE RACKModular single-phase UPS with double conversion VFI

30

MEGALINETable of long uptimes single and double cabinet version

1 cabinetW 270mm

2 cabinetW 540mm

3 cabinetW 810mm

4 cabinetW 1080mm

5 cabinetW 1350mm

Model Power:Uptime 80% of the load

no. cabinet and dimensions W x H x D (mm)

Codes

Single Cabinet

1,250 VA 15’ 1x (270 x 475 x 570) 3 103 73

1,250 VA 30’ 1x (270 x 475 x 570) 3 103 74

1,250 VA 45’ 1x (270 x 475 x 570) 3 103 75

1,250 VA 60’ 2x (270 x 475 x 570) 3 103 50 + 3 107 76

2,500 VA 15’ 1x (270 x 475 x 570) 3 103 76

2,500 VA 30’ 2x (270 x 475 x 570) 3 103 52 + 3 107 78

2,500 VA 45’ 2x (270 x 475 x 570) 3 103 52 + 3 107 79

2,500 VA 60’ 2x (270 x 475 x 570) 3 103 52 + 3 107 81

3,750 VA 15’ 1x (270 x 475 x 570) 3 103 77

3,750 VA 30’ 2x (270 x 475 x 570) 3 103 54 + 3 107 79

3,750 VA 45’ 2x (270 x 475 x 570) 3 103 54 + 3 107 82

3,750 VA 60’ 2x (270 x 475 x 570) 3 103 54 + 3 107 84

5,000 VA 15’ 2x (270 x 475 x 570) 3 103 56 + 3 107 76

5,000 VA 30’ 2x (270 x 475 x 570) 3 103 56 + 3 107 80

5,000 VA 45’ 2x (270 x 475 x 570) 3 103 56 + 3 107 84

5,000 VA 60’ 3x (270 x 475 x 570) 3 103 56 + 3 107 84+ 3 107 77

Double Cabinet

5,000 VA 15’ 2x (270 x 475 x 570) 3 103 60 + 3 107 80

5,000 VA 30’ 2x (270 x 475 x 570) 3 103 60 + 3 107 84

5,000 VA 45’ 3x (270 x 475 x 570) 3 103 60 + 3 107 84 + 3 107 78

5,000 VA 60’ 3x (270 x 475 x 570) 3 103 60 + 3 107 84 + 3 107 81

6,250 VA 15’ 2x (270 x 475 x 570) 3 103 63 + 3 107 81

6,250 VA 30’ 3x (270 x 475 x 570) 3 103 63 + 3 107 84 + 3 107 76

6,250 VA 45’ 3x (270 x 475 x 570) 3 103 63 + 3 107 84 + 3 107 81

6,250 VA 60’ 4x (270 x 475 x 570) 3 103 63 + 3 107 84 (x2) + 3 107 76

7,500 VA 15’ 2x (270 x 475 x 570) 3 103 66 + 3 107 82

7,500 VA 30’ 3x (270 x 475 x 570) 3 103 66 + 3 107 84 + 3 107 79

7,500 VA 45’ 3x (270 x 475 x 570) 3 103 66 + 3 107 84 (x2)

7,500 VA 60’ 4x (270 x 475 x 570) 3 103 66 + 3 107 84 (x2) + 3 107 80

8,750 VA 15’ 2x (270 x 475 x 570) 3 103 69 + 3 107 84

8,750 VA 30’ 3x (270 x 475 x 570) 3 103 69 + 3 107 84 + 3 107 81

8,750 VA 45’ 4x (270 x 475 x 570) 3 103 69 + 3 107 84 (x2) + 3 107 78

8,750 VA 60’ 4x (270 x 475 x 570) 3 103 69 + 3 107 84 (x3)

10,000 VA 15’ 3x (270 x 475 x 570) 3 103 72 + 3 107 84 + 3 107 76

10,000 VA 30’ 3x (270 x 475 x 570) 3 103 72 + 3 107 84 (x2)

10,000 VA 45’ 4x (270 x 475 x 570) 3 103 72 + 3 107 84 (x2) + 3 107 81

10,000 VA 60’ 5x (270 x 475 x 570) 3 103 72 + 3 107 84 (x3) + 3 107 78

NOTE: autonomy values, expressed in minutes, are measured during optimal operating conditions.

31

WWW.UPS.LEGRAND.COM

UPSMODULAR UPS

MEGALINE RACKTable of long uptimes

Model Power:Uptime 80% of the load

no. cabinet and dimensions W x H x D (mm)

Codes

Rack

1,250 VA 15’ 1 (6U) 3 103 87

1,250 VA 30’ 1 (6U) 3 103 88

1,250 VA 45’ 1 (6U) 3 103 89

1,250 VA 60’ 2 (6U + 3U) 3 103 79 + 3 107 99

2,500 VA 15’ 1 (6U) 3 103 90

2,500 VA 30’ 2 (6U + 3U) 3 103 81 + 3 107 98

2,500 VA 45’ 2 (6U + 3U) 3 103 91 + 3 107 98

2,500 VA 60’ 3 (6U + 2x3U) 3 103 81 + 3 107 98 + 3 107 99

3,750 VA 15’ 1 (6U) 3 103 92

3,750 VA 30’ 2 (6U + 3U) 3 103 92 + 3 107 99

3,750 VA 45’ 3 (6U + 2x3U) 3 103 83 + 3 107 99 (x2)

3,750 VA 60’ 4 (6U + 3x3U) 3 103 83 + 3 107 99 (x2) + 3 107 97

5,000 VA 15’ 2 (6U + 3U) 3 103 85 + 3 107 97

5,000 VA 30’ 3 (6U + 2x3U) 3 103 85 + 3 107 97 + 3 107 99

5,000 VA 45’ 4 (6U + 3x3U) 3 103 85 + 3 107 97 + 3 107 99 (x2)

5,000 VA 60’ 5 (6U + 4x3U) 3 103 85 + 3 107 97 + 3 107 99 (x3)

6U= 483 x 266 x 582 3U= 483 x 133x 584

NOTE: autonomy values, expressed in minutes, are measured during optimal operating conditions.

1 cabinetH 266mm (6U)

2 cabinetH 532mm (9U)

3 cabinetH 798mm (12U)

4 cabinetH 1064mm (15U)

5 cabinetH 1330mm (18U)

32

®

WWW.UPS.LEGRAND.COM

CONVENTIONAL UPS 33UPS

®

UPS

CONVENTIONAL

Double conversion online UPS equipped with DSP microprocessor for precise and constant control of all the measurements and the power factor correction circuit (PFC).

Professional solutions with power that can achieve up to 10 kVA.

Electronics with no-transformer technology for high quality energy output with a yield of up to 93%.

Safe, powerful and technological solutions

WHADDaker DK DHEA

34

Daker DKCONVENTIONAL

SINGLE PHASEUPS online double conversion can be used in both tower and rack

configurations. Using the display it is possible to control all the main system parameters and the state of the UPS, including the load level, remaining battery life and failures.

Additional battery cabinets increase the autonomy of group continuity. A battery charger can be added to each battery cabinet for fast and secure charging.

tower version with additional battery cabinet

®

35

WWW.UPS.LEGRAND.COM

UPS and battery cabinet for 2 units

Three standard dimensions for power up to 10kVA Based on requested power and uptime there are UPS and additional battery cabinets available with dimensions for 2 to 4 units.

Reversible display UPS Daker DK can be used in both tower and 19 inch rack versions thanks to its reversible display.

UPS and battery cabinet for 3 units

UPS and battery cabinet for 4 units

CONVENTIONAL UPS UPS

36

WHAD CONVENTIONAL

SINGLE PHASEUPS on linedouble conversion

for application ofsmall and

medium power.

The issued power, 800 VA to 6,000 VA, allows for high level electrical protection for equipment whose power consumption is not too high.

The UPS are made of a single board that integrates control power and logic, control and diagnostics.

Thanks to the reduced footprint and the extended and tight shape, the WHAD UPS occupy very little space, even if placed on top of a work station.

Models up to 2500 VA can extend uptime by adding battery cabinets.

In the most performing version there is a slot for inserting internal versions of the SNMP communication interfaces.

®

37

WWW.UPS.LEGRAND.COM

DHEA ENERGY STATION CONVENTIONAL

SINGLE PHASEThe double conversion

on line UPS designed with overlapping

components with quick connections.

The system is made of an inverter section and battery modules (battery pack) equipped with a PLUG-IN connection and hot swap system.

Reduces overall dimensions, depth of 185 mm, allows positioning the uninterruptible power supply in extremely small spaces.

The special hermetically sealed batteries, that do not release any gas fumes, make it possible to use within home environments.

Load management

The 1500 VA model is equipped with 3 outputs, 2 of them are times for inverter

operation, since they deactivate after a pre-set interval, they make it possible to safeguard the power supply of the most

important loads based on available uptime.

Plug-in connection with hot swap system “Standard” components and quick connections make it possible for the less expert to transport and install every element of the system easily and, thanks to the hot swap system, it is possible to add or replace battery packs at any time, without shutting off the inverter.

CONVENTIONAL UPS UPS

38

3 109 53

Daker DKConventional UPS - Single-phase On-line double conversion VFI

3 100 54

The display shows the main system parameters and their status, including the battery charge level and malfunctions. The integrated communication software allows not only controlling the uninterruptable power supply and stopping in case of equipment malfunction, it also allows the user to remotely test the main functions of the uninterruptable power supply, communicating through SNMP/Internet/network adaptor, accessing uninterruptable power supply unit functions by way of Internet and also sending the user an SMS if specific events occur. The optional slot provides additional flexibility for network configuration. There is also a WEB/SNMP board and a relay interface available that are capable of supplying isolated contacts for application on industrial control panel or remote alarm panels. The automatic and manual bypass (optional) guarantees continual electrical power supply to critical loads, in case of electronic malfunction, overload, overheating or programmed maintenance. A maintenance bypass switch box is available.

Pack. Item CONVERTIBLE UPS WITH BATTERIESNOMINAL

POWER

VA

POWER

ACTIVE

W

UPTIME

(MIN.) 80%

OF THE LOAD

WEIGHT

(kg)

3 100 50 1000 800 8 16

3 100 51 2000 1600 8 29,5

3 100 52 3000 2400 6,3 30

3 100 53 4500 4050 6 60

3 100 54 6000 5400 4 60

CONVERTIBLE UPS - WITHOUT BATTERIESNOMINAL

POWER

VA

POWER:

ACTIVE

W

UPTIME

(MIN.) 80%

OF THE LOAD

WEIGHT

(kg)

3 100 56 4500 4050 - 25

3 100 57 6000 5400 - 25

3 100 58 10000 9000 - 26

BATTERY CABINET (WITH BATTERIES)DESCRIPTION

3 107 69 Battery cabinet for 3 100 50 (12 batteries 12V, 7.2 Ah)

3 107 70 Battery cabinet for 3 100 51 (12 batteries 12V, 7.2 Ah)

3 107 71 Battery cabinet for 3 100 52 (12 batteries 12V, 9 Ah)

3 107 72 Battery cabinet for 3 100 56 and 3 100 57 (20 batteries 12V, 7.2 Ah)

3 107 66 Battery cabinet for 3 100 58 (20 batteries 12V, 9 Ah)

BATTERY CABINETS (EMPTY)DESCRIPTION

3 107 50 Battery cabinet for 3 100 50 (for 12 batteries 12V, 7.2 Ah)

3 107 51 Battery cabinet for 3 100 51 (for 12 batteries 12V, 7.2 Ah)

3 107 52 Battery cabinet for 3 100 52 (for 12 batteries 12V, 9 Ah)

3 107 53 Battery cabinet for 3 100 56 and 3 100 57 (for 20 batteries 12V, 7.2 Ah)

3 107 54 Battery cabinet for 3 100 58 (for 20 batteries 12V, 9 Ah)

Pack. Item VARIOUS ACCESSORIESDESCRIPTION

3 109 50 Additional 200W battery charger

3 109 51 Additional 500W battery charger

3 109 54 Additional 1000W battery charger

3 109 52 Kit of Rack support brackets

3 109 53 External manual bypass

3 100 50 3 107 71

NOTE: autonomy values, expressed in minutes, are measured during optimal operating conditions.

39

WWW.UPS.LEGRAND.COM

Daker DKConventional UPS - Single-phase On-line double conversion VFI

Item 3 100 50 3 100 51 3 100 52 3 100 53 3 100 56 3 100 54 3 100 57 3 100 58

General Features

Nominal power (VA) 1000 2000 3000 4500 6000 10000

Active power (W) 800 1600 2400 4050 5400 9000

Technology On-Line Double Conversion VFI-SS-111

Waveform Sinusoidal

UPS architecture convertible tower and 19 rack

Input

Input voltage 230 V

Input frequency 50-60 Hz ±5% Autosensing

Input Voltage Range 160V - 288V with full load

THD Input current ‹ 3%

Input power factor › 0,99

Compatibility with Power-Supply Units

Configurable in order to achieve synchronism between input and output frequencies, even for wider frequency ranges, ±14%

Output

Output voltage 230V ± 1%

Output frequency (nominal) 50/60 Hz (can be set from the LCD panel) +/- 0.1%

Crest Factor 1:3

THD Output voltage 97%

Output Voltage Tolerance ±1%

Bypass Automatic and maintenance bypass (OPTIONAL)

Batteries

Uptime Expansion yes

Number of batteries 3 6 6 20 - 20 - -

Battery series Type/Voltage 12V 7.2Ah 12V 7.2Ah 12V 9Ah 12V 5Ah - 12V 5Ah - -

Uptime with 80% load (min) 8 8 6,3 6 - 4 - -

Configuration and management

Display and Signals Four buttons and four LEDs to monitor the status of the UPS in real time

Communication Ports RS232, USB serial ports

Remote Management available

Network interface slot SNMP

Mechanical features

Dimensions H x W x D (mm)440x88 (2U)

x405440x88 (2U)

x650440x88 (2U)

x650440x176 (4U)

x680440x88 (2U)

x680440x176 (4U)

x680440x88 (2U)

x680440x132 (3U)

x680

Battery Cabinet Dimensions H x W x D (mm)

440x176 (4U) x405

440x88 (2U) x650

440x88 (2U) x650

440x132 (3U) x680

440x132 (3U) x680

440x132 (3U) x680

440x132 (3U) x680

440x132 (3U) x680

Net Weight (kg) 16 29,5 30 52 25 52 25 26

Environmental conditions

Operating temperature (°C) 0 ÷ 40

Degree of protection IP21

Relative humidity (%) 20÷80 % non-condensing

Noise level at 1 m (dBA) ‹ 50

Heat Loss (BTU/h) 490 654 818 982 1310 1636

Certifications

Standards EN 62040-1, EN 62040-2, EN 62040-3

Warranty

Standard Warranty repair or replacement for 2 years

CONVENTIONAL UPS UPS

NOTE: autonomy values, expressed in minutes, are measured during optimal operating conditions.

40

Daker DKTable of long uptimes

1000 VA 2 cabinetW 2U + 4U

3000 VA 3 cabinetW 2U +2 U + 2U

6000 VA 2 cabinetW 2U + 3U

10000 VA 2 cabinetW 3U + 3U

TOWER version

1000 VA 2 cabinetH 6U (264mm)

4500 VA 3 cabinetH 6U (264mm)

6000 VA 2 cabinetH 5U (320mm)

10000 VA 2 cabinetH 6U (264mm)

RACK version

Model Power:Uptime 80% of the load

no. Cabinet and dimensions H x W x D (mm)

Item

Daker DK

1000 VA

8' 440 x 88 x 405 3 100 50

75' 440 x 88 x 405 + 440 x176 x 405 3 100 50 + 3 107 69

140' 440 x 88 x 405 + 440x176 x 405 (x2) 3 100 50 + 3 107 69 (x2)

205' 440 x 88 x 405 + 440 x176 x 405 (x3) 3 100 50 + 3 107 69 (x3)

265' 440 x 88 x 405 + 440 x 176 x 405 (x4) 3 100 50 + 3 107 69 (x4)

2000 VA

8' 440 x 88 x 650 3 100 51

45' 440 x 88 x 650 (x2) 3 100 51 + 3 107 70

75' 440 x 88 x 650 (x3) 3 100 51 + 3 107 70 (x2)

120’ 440 x 88 x 650 (x4) 3 100 51 + 3 107 70 (x3)

145’' 440 x 88 x 650 (x5) 3 100 51 + 3 107 70 (x4)

3000 VA

6'30" 440 x 88 x 650 3 100 52

30' 440 x 88 x 650 (x2) 3 100 52 + 3 107 71

65' 440 x 88 x 650 (x3) 3 100 52 + 3 107 71 (x2)

100' 440 x 88 x 650 (x4) 3 100 52 + 3 107 71 (x3)

120’ 440 x 88 x 650 (x5) 3 100 52 + 3 107 71 (x4)

4500 VA

9' 440 x 88 x 650 + 440 x 132 x 680 3 100 56 + 3 107 72

27' 440 x 88 x 650 + 440 x 132 x 680 (x2) 3 100 56 + 3 107 72 (x2)

50' 440 x 88 x 650 + 440 x 132 x 680 (x3) 3 100 56 + 3 107 72 (x3)

65' 440 x 88 x 650 + 440 x 132 x 680 (x4) 3 100 56 + 3 107 72 (x4)

90' 440 x 88 x 650 + 440 x132 x 680 (x5) 3 100 56 + 3 107 72 (x5)

110' 440 x 88 x 650 + 440 x 132 x 680 (x6) 3 100 56 + 3 107 72 (x6)

130' 440 x 88 x 650 + 440 x 132 x 680 (x7) 3 100 56 + 3 107 72 (x7)

6000 VA

8'30" 440 x 88 x 650 + 440 x 132 x 680 3 100 57 + 3 107 72

25' 440 x 88 x 650 + 440 x 132 x 680 (x2) 3 100 57 + 3 107 72 (x2)

45' 440 x 88 x 650 + 440 x 132 x 680 (x3) 3 100 57 + 3 107 72 (x3)

60' 440 x 88 x 650 + 440x132x680 (x4) 3 100 57 + 3 107 72 (x4)

10000 VA

5'30" 440 x 132 x 650 + 440 x 132 x 680 3 100 58 + 3 107 66

15'30" 440 x132x650 + 440 x 132 x 680 (x2) 3 100 58 + 3 107 66 (x2)

30' 440 x132x650 + 440 x 132 x 680 (x3) 3 100 58 + 3 107 66 (x3)

50' 440 x 132 x 650 + 440 x 132 x 680 (x4) 3 100 58 + 3 107 66 (x4)

NOTE: autonomy values, expressed in minutes, are measured during optimal operating conditions.

41UPS

WWW.UPS.LEGRAND.COM

3 101 08

- System that can be combined with a power supply unit to increase uptime in case of extended black out.

- Battery modules with batteries and related integrated PLUG-IN connections.- Possibility of adding up to 10 Battery pack.- Power supply voltage of the inverter only present once the module is connected.

DHEAConventional UPS - Single-phase On-line double conversion VFI

Pack. Item ENERGY STATIONSNOMINAL POWER

VA

POWER ACTIVE

W

3 101 07 1000 700

3 101 08 1500 1050

BATTERYDESCRIPTION

3 107 73 Battery module

no. battery pack

Uptime at 100% of the load

1000 VA 1500 VA

1 20’ 15’

2 48’ 32’

3 1 h 20’ 50’

4 2 h 1 h 15’

5 2 h 40’ 1 h 35’

6 3 h 20’ 2 h

7 4 h 2 h 30’

8 5 h 3 h

9 6 h 3 h 30’

10 7 h 4 h

3 107 73

CONVENTIONAL UPS

Idem 3 101 07 3 101 08

General Features

Nominal Power (VA) 1000 1500

Active Power (W) 700 1050

Technology on-line double conversion

Waveform sinusoidal

Input nominal voltage 230 V

Input Voltage Range

184 V ÷ 265 V at 100% of the load

Minimum network operating voltage

184V with nominal load / 100V at 50% of the nominal load

Input frequency 50/60 Hz ± 2% (± 14% in extended range)

Power factor on input

› 0.99 from 80% of the nominal load

Output voltage 230 V ± 1%

Distortion of output voltage ‹ 1%

Output frequency (battery operation)

50/60 Hz ± 1%

Batteries 2 x 36 V 7.2 Ah in overlapping Battery Packs

Acoustic noise at 1 m (dBA) ‹ 40

Net weight (kg) 4 (inverter) + 16 (battery pack)

Dimensions (H x W x D) (mm)

309 x 450 x 170 (inverter) - 125 x 450 x 170 (battery pack)

Standards EN 62040-1, EN 50091-2, EN 62040-3

External Connections 1 RS 232 + 3 contact outputs (2 poles) + EPO

Degree of protection IP21

Output socket 1 line3 lines

(2 of them with timer)

NOTE: autonomy values, expressed in minutes, are measured during optimal operating conditions.

42

3 100 96 3 101 013 100 87

All models are equipped with: - logical level port that can be connected to a Relay interface Kit.- slot for inserting internal versions of the SNMP, CS121 SK and CS121B SK communication interfaces.- possibility of connecting to an external maintenance bypass device, designed to be connected to the input/output connector present on the back of the UPS.

WHADConventional UPS - Single-phase On-line double conversion VFI

Pack. Item UPS WITH STANDARD GERMAN SOCKETSNOMINAL

POWER

VA

POWER:

ACTIVE

W

UPTIME

(MIN.) 80%

OF THE LOAD

WEIGHT

(kg)

3 100 87 800 560 20 12

3 100 90 1000 700 15 12

3 100 93 1500 1050 10 12

3 100 96 2000 1400 12 23

3 100 97 2500 1750 8 23

3 100 98 3000 2100 18 55

3 100 99 4000 2800 12 55

3 101 00 5000 3500 13 65

3 101 01 6000 4200 10 65

UPS WITH STANDARD FRENCH SOCKETSNOMINAL

POWER

VA

POWER:

ACTIVE

W

UPTIME

(MIN.) 80%

OF THE LOAD

WEIGHT

(kg)

3 100 88 800 560 17 12

3 100 91 1000 700 13 12

3 100 94 1500 1050 8 12

3 101 09 2000 1400 12 23

3 101 11 2500 1750 8 23

UPS WITH STANDARD ENGLISH SOCKETSNOMINAL

POWER

VA

POWER:

ACTIVE

W

UPTIME

(MIN.) 80%

OF THE LOAD

WEIGHT

(kg)

3 100 89 800 560 17 12

3 100 92 1000 700 13 12

3 100 95 1500 1050 8 12

3 101 10 2000 1400 12 23

3 101 12 2500 1750 8 23

VARIOUS ACCESSORIESDESCRIPTION

3 107 74 Additional battery cabinet for 800 - 1000 - 1500

3 108 20 Additional battery cabinet for 2000 - 2500

3 109 71 Y cable for connecting two battery cabinets

3 108 62 Manual bypass for 2000VA / 3000VA UPS

3 109 77 Manual bypass for 5000VA / 6000VA UPS

Model Power:Uptime

(80% of the load):

Cabinet no. and dimensions H X W X D (mm)

Codes

Whad

800 VA

90’88 x 355 x 390 + 160 x 319 x 390

3 100 87 + 3 107 74

170’88 x 355 x 390 +

160 x 319 x 390 (x2)3 100 87 + 3 107 74 (x2)

1000 VA

60’88 x 355 x 390 + 160 x 319 x 390

3 100 90 + 3 107 74

130’88 x 355 x 390 +

160 x 319 x 390 (x2)3 100 90 + 3 107 74 (x2)

1500 VA

35’88 x 355 x 390 + 160 x 319 x 390

3 100 93 + 3 107 74

75’88 x 355 x 390 +

160 x 319 x 390 (x2)3 100 93 + 3 107 74 (x2)

2000 VA

45’460 x 160 x 425 + 160 x 319 x 390

3 100 96 + 3 108 20

75’460 x 160 x 425 +

2x(160 x 319 x 390)3 100 96 + 3 108 20 (x2)

2500 VA

32’460 x 160 x 425 + 160 x 319 x 390

3 100 97 + 3 108 20

50’460 x 160 x 425+

2x(160 x 319 x 390)3 100 97 + 3 108 20 (x2)

NOTE: autonomy values, expressed in minutes, are measured during optimal operating conditions.

43UPS

WWW.UPS.LEGRAND.COM

WHADConventional UPS - Single-phase On-line double conversion VFI

Item3 100 873 100 88 3 100 89

3 100 903 100 91 3 100 92

3 100 933 100 94 3 100 95

3 100 963 101 09 3 101 10

3 100 973 101 11 3 101 12

3 100 98 3 100 99 3 101 00 3 101 01

General Features

Nominal power (VA) 800 1000 1500 2000 2500 3000 4000 5000 6000

Active power (W) 560 700 1050 1400 1750 2100 2800 3500 4200

Technology On-Line Double Conversion VFI-SS-111

Waveform Sinusoidal

UPS architecture Conventional UPS systems with expandable uptime

Input

Input voltage 230 V

Input frequency 50-60 Hz ±2% Autosensing

Input Voltage Range 184V÷265V at 100% of the load

THD Input current 3%

Input power factor › 0,99

Output

Output voltage 230V ± 1%

Output frequency (nominal) 50/60 Hz synchronised

Crest Factor 3,5 : 1

THD Output voltage 1%

Allowed Overload 300% for 1 sec., 200% for 5 sec., 150% for 30 sec.

Bypass Electromechanical, automatic and internally synchronised (due to overload or operating fault)

Batteries

Uptime Expansion Sì

Battery series Type/Voltage VRLA - AGM 48Vdc VRLA - AGM 36Vdc VRLA - AGM 144Vdc VRLA - AGM 192Vdc

Uptime with 80% load (min) 20 15 10 12 8 18 12 13 10

Configuration and management

Display and Signals Indicatore di stato multicolore a LED, allarmi e segnalazioni acustiche

Communication Ports 1 RS232 serial port1 RS232 serial port 1 logical level port

1 RS232 serial port, 1 logical level port, 1 slot for network interface connection

(CS121)

Remote Management UPS Communicator free to download software

Mechanical features

Dimensions (H x W x D) (mm) 355 x 88 x 390 460 x 160 x 425 475 x 270 x 570

Battery Cabinet Dimensions (H x W x D) (mm) 319 x 160 x 402 319 x 160 x 402 319 x 160 x 402

Net Weight (kg) 12 23 55 65

Environmental conditions

Operating temperature (°C) 0÷40

Relative humidity (%) 20÷80 non-condensing

Degree of protection IP21

Noise level at 1 m (dBA) ‹ 40 ‹ 42 ‹ 40

Heat Loss (BTU/h) 150 190 287 380 478 570 760 952 1140

Environmental conditions

Standards EN 62040-1, EN 62040-2, EN 62040-3

Warranty

Standard Warranty 2 years

CONVENTIONAL UPS

NOTE: autonomy values, expressed in minutes, are measured during optimal operating conditions.

44

®

45

WWW.UPS.LEGRAND.COM

UPSUPS LINE INTERACTIVE

®

Niky SNiky

UPS

LINE INTERACTIVE

Small dimensions, easy to install and configure.

Equipped with electronic stabiliser, signal LED and telephone protection ensure total and reliable system protection.

Offering a high quality/price ratio guaranteeinga safe investmentover time.

Simple, reliable and economical solutions

46

Niky line interactive

Ideal protectionfor all applications

such asSmall-Office

Home-Office.

They represent the offer with the best quality/price ratio for the safety of data within the office, your own business and the home PC.Equipped with CPU control, integrated AVR and interfacefor intelligent communication, ensuring optimal protection management.

Advanced management of battery dischargeAVR stabiliser Integrated self-diagnostic functionCold start-up functionIntelligent microprocessor controlRS232 or USB interface for managing the UPSMODEM/LAN telephone protection

®

WWW.UPS.LEGRAND.COM

47

Niky S line interactive

Sinusoidal outputControl using intelligent microprocessorMODEM/LAN telephone protectionRS-232 and USB interface for managing the UPSCold start-up functionProtection from voltage peaksSelf-test function for the Uninterruptable power unitIntelligent battery managementProtection from overload and short-circuitExcellent voltage adjustment

UPSUPS LINE INTERACTIVE

48

3 100 133 100 00

NikyUPS Line Interactive - Single-phase VI

Pack. Item UPS WITH STANDARD GERMAN OUTPUT SOCKETSNOMINAL

POWER

VA

POWER:

ACTIVE

W

UPTIME

(MIN.)

NO. OF

SOCKETS

IEC

NO. OF SOCKETS

STANDARD

GERMAN

PORTS

FOR

COMMUNICATION

3 100 00 600 300 5÷30 1 1 USB

3 100 01 800 400 5÷30 1 1 USB

UPS WITH STANDARD GERMAN OUTPUT SOCKETS + IEC SOCKET

NOMINAL

POWER

VA

POWER:

ACTIVE

W

UPTIME

(MIN.)

NO. OF

SOCKETS

IEC

NO. OF SOCKETS

STANDARD

GERMAN

PORTS

FOR

COMMUNICATION

3 100 09 600 300 5÷30 1 1 USB

3 100 10 800 400 5÷30 1 1 USB

3 100 13 1000 600 5÷30 2 2 RS232

3 100 14 1500 900 5÷30 2 2 RS232

UPS WITH MULTIPLE IEC OUTPUT SOCKETSNOMINAL

POWER

VA

POWER:

ACTIVE

W

UPTIME

(MIN.)

NO. OF

SOCKETS

IEC

NO. OF SOCKETS

STANDARD

GERMAN

PORTS

FOR

COMMUNICATION

3 100 02 600 300 5÷30 3 - USB

3 100 03 800 400 5÷30 3 - USB

3 100 04 1000 600 5÷30 6 - USB

3 100 05 1500 900 5÷30 6 - USB

Item3 100 003 100 023 100 09

3 100 013 100 033 100 10

3 100 013 100 043 100 13

3 100 053 100 14

General Features

Nominal power (VA) 600 800 1000 1500

Active power (W) 300 400 600 900

Technology Line-interactive VI

Waveform Pseudo-Sinusoidal

Input

Input voltage 230 V

Input frequency 50-60 Hz

Input Voltage Range 160V-290V

Output

Output voltage 230V ± 10%

Output frequency (nominal)

50/60 Hz +/-1%

THD Output voltage ‹ 3% with linear load

Batteries

Number of batteries 1 1 2 2

Battery series Type/Voltage

12V, 7Ah 12V, 9Ah 12V, 7Ah 12V, 9Ah

Configuration and Management

Display and SignalsOne push button and 2 LED to monitor UPS

status in real-time.

One push button and 4 LED to monitor UPS

status in real-time

Telephone protection RJ11/RJ45

Remote Management available

Mechanical Features

Dimensions H x W x D (mm)

171x95x349 239x147x354

Net Weight (kg) 7 7,5 13 16

Environmental Conditions

Operating temperature (°C)

0 ÷ 40°C

Relative humidity (%) 0÷95 % non-condensing

Noise level at 1 m (dBA) ‹40

Certifications

Standards EN62040-1, EN62040-2, EN62040-3

Warranty

Standard Warranty 2 years

600-800 VA 1000-1500 VA

SITE WIRING FAULT

AC INPUT AC OUTPUT

SITE WIRING FAULT

AC INPUT AC OUTPUT

IN OUTSITE WIRING

FAULT RS232USB

IN OUT

SITE WIRING

FAULT RS232USB

IN OUT

NOTE: autonomy values, expressed in minutes, are measured during optimal operating conditions.

49UPS

WWW.UPS.LEGRAND.COM

Niky SUPS Line Interactive - Single-phase VI-SS

Pack. Item UPSNOMINAL

POWER

VA

POWER:

ACTIVE

W

UPTIME

(MIN.) 80%

OF THE LOAD

PORTS

FOR

COMMUNICATION

3 100 06 1000 600 9 USB-RS232

3 100 20 1500 900 9 USB-RS232

3 100 07 2000 1200 9 USB-RS232

3 100 08 3000 1800 9 USB-RS232

3 100 06

1000-1500-2000 VA 3000 VA

IN OUT USB RS232 IN OUT USB RS232

UPS LINE INTERACTIVE

Item 3 100 06 3 100 20 3 100 07 3 100 08

General Features

Nominal power (VA) 1000 1500 2000 3000

Active power (W) 600 900 1200 1800

Technology Line-interactive VI-SS

Waveform Sinusoidal

Input

Input voltage 230 V ± 12% on network ± 5% on battery

Input frequency 50-60 Hz

Input Voltage Range 160V-290V

Output

Output voltage 230V ± 10%

Output frequency (nominal)

50/60 Hz +/-0.2%

THD Output voltage ‹ 3% with linear load

Batteries

Uptime Expansion Yes

Number of batteries 2 2 4 4

Type/Voltage battery series

12V, 7Ah 12V, 9Ah 12V, 7Ah 12V, 9Ah

Configuration and Management

Display and SignalsThree buttons and three LEDs to monitor

the status of the UPS in real time

Telephone protection RJ11/RJ45

Remote Management available

Mechanical Features

Dimensions H x W x D (mm)

242x169x361 242x169x464

Net Weight (kg) 13 15 22 24

Environmental Conditions

Operating temperature (°C)

0 ÷ 40°C

Relative humidity (%) 0÷95 % non-condensing

Noise level at 1 m (dBA) ‹40

Certifications

Standards EN62040-1, EN62040-2, EN62040-3

Warranty

Standard Warranty 2 years

NOTE: autonomy values, expressed in minutes, are measured during optimal operating conditions.

50

®

51

WWW.UPS.LEGRAND.COM

®

ACCESSORIES

COMMUNICATION

Network interface, enables remote control of the UPS which can be connected to the network.

Sensors for monitoring temperature and humidityof the environment.

Communication and supervisionsoftware that allowsaccessing UPS operational data, executing completediagnostics and configuringspecial functions.

UPS management and control systems

UPSACCESSORIES COMMUNICATION

The network interface for UPS management does not require external software. There is a a 32 bit internal processor with a proprietary operating system that can continously monitor UPS operation and handle multiple events (no power, overload, bypass, anomaly, ...); as a result, it executes the following actions:• Saving log files complete with date and time• Saving the trend of the main operational data complete with date and time• Sending e-mail• Executing scheduled actions• Displaying pop-up messages, carrying out a shutdown and customised commands

on remote computers (it is necessary for these computers to have the RCCMD software)

• Shutting off and turning on the UPS• Sending “Wake on LAN (WOL) Magic Packet” signals• Support for the SNMP protocol and the main management software (HP OpenView,

IBM Tivoli, etc…)• Sending SNMP trap messages• Displaying data and configuration through internet browser (Internet Explorer,

Mozilla Firefox, Opera, etc…) or Telnet• Firmware can be updated through specific software package that can be downloaded

from the Internet for free• Ethernet connection 10/100Mbit Base-T (half-duplex and full-duplex) with auto-

recognition function• DHCP Function• 1 RCCMD license included

Available in the internal and external versions, the internal version is housed in a dedicated UPS slot.Power supply voltage 9 - 30 V d.c. (power supply included in the external versions).Professional and industrial versions include programmable digital contacts and additional RS232 / RS485 communication ports.

ACCESSORIESNetwork interface

*only modbus over RS485.

Model A B C

CS121B X

CS121B X

CS121B SK X

CS121 X X X

CS121 SK X X X

CS121M X X* X

CS121M SK X X* X

SHUTDOWN / COMMANDS /MESSAGES

- Unix / Linux + RCCMD agent- Windows + RCCMD agent- MAC OS X + RCCMD agent- AS/400 + RCCMD agent- Novell NetWare + RCCMD agent- VMware + RCCMD agent- Citrix + RCCMD agent

MODBUS over IP

HTTP / java / UPSMON

Execution of remote programs

SNMP management, SNMP Trap

Sending e-mail (SMTP)

Telnet, FTP, setup / update

Log File, Historical Data File

Terminal Configuration

Pipe-Through RS232

MODBUS over RS232 / RS485

Temperature Sensors

Sensor Manager

Fire alarm systems

Air-conditioning units

Smoke sensors

Relay IN

Relay OUT

<<<>

>

<><><><><>

A B C

RS232

UPS

3 108 84

3 108 82

3 109 06

3 109 07

52

Model Items NETWORK INTERFACEDESCRIPTION

CS121 SK 3 108 81 PROFESSIONAL network interface internal version (slot)

CS121B SK 3 108 82 STANDARD network interface internal version (slot)

CS121 3 108 83 PROFESSIONAL network interface external version

CS121B 3 108 84 STANDARD network interface external version

CS121M 3 109 06 INDUSTRIAL network interface external version

CS121M SK 3 109 07 INDUSTRIAL network interface internal version (slot)

ACCESSORIESSensors and various accessories

Smoke sensors

Fire alarm system command

Temperature and/or humidity sensors

Conditioning system malfunctioning sensor

“Custom” analogue and digital sensors

Intrusion sensors

COM 2 COM 1

LAN/WANTCP/IP

UPS

3 109 033 109 023 108 99

3 109 00 3 108 98

53

WWW.UPS.LEGRAND.COM

UPSACCESSORIES COMMUNICATION

Model Items SENSORSDESCRIPTION

SM_T_COM 3 108 97 Temperature sensor for direct connection to COM2 of the CS121, CS121 SK and SiteSwitch 4 interfaces (only the SS4 model). It cannot be used with the SensorManager.

SM_T_H_COM 3 108 98 Combined temperature and humidity sensor for direct connection to COM2 for CS121, CS121 SK and SiteSwitch 4 interfaces (only the SS4 model). Cannot be used with the SensorManager.

SensorManager 3 108 99 Manager for environmental sensors: it connects to COM2 of CS121, CS121 SK and SiteSwitch 4 interfaces (only the SS4 model) and manages up to 8 analogue inputs, 4 digital inputs and 4 digital outputs. Configuration is managed directly from CS121 interfaces (PROFESSIONAL and INDUSTRIAL versions) previously described.“Scale Divisor” and “Off set” configuration functions allow using the SensorManager with any analogue apparatus (see features).Includes 1 temperature sensor “SM_T”.

SM_T 3 109 00 Temperature sensor can be used exclusively with SensorManager.Allows connecting another “SM_T” sensor using the specific connector.

SM_T_H 3 109 01 Combined temperature and humidity sensor can be used exclusively with SensorManager.

Door sensor 3 109 02 It is made of a reed tube switch and a magnet.Compatible with CS121, CS121 SK, CS121 M, CS121M SK, and SensorManager.

SM_flash 3 109 03 Flashing light signal. Exclusively compatible with SensorManager. 15 V D.C.

SENSOR MANAGER TECHNICAL FEATURES

Power supply voltage (Vd.c.) 9-24

Temperature (°C) 0 ÷ 40

Humidity % non condensing 10 ÷ 80

Analogue Inputs (V) 0 ÷ 10

Digital inputs (V) 9 ÷ 24

Digital outputs V (10mA) 9 ÷ 24

Dimensions (WxDxH) (mm) 70 X 126 X 30

* directed by network interface** directed by SensorManager

SENSOR TECHNICAL FEATURES

PAI0018 PAI0032 PAI0021 PAI0020

Power supply voltage Vd.c.

9÷15* 9÷15* 9÷24** 9÷24**

Temperaturerange (°C)

-25÷+100 -25÷+100 0 ÷ +100 0 ÷ +100

Relative humidity % (+- 5%)

0 ÷ 100 0 ÷ 100

Connection cable m (included)

1,8 1,8 5 5

Dimensions H x W x D (mm)

27 X 70 X 70

It is a device used to control energy distribution and it allows shutting down and turning on devices connected to it individually thanks to the four independent power supply.When without power, for example, a UPS can send a command to shut off less important loads (such as laser printers) in order to ensure the greatest possible uptime to the most critical systems. Once network power has been restored, the same UPS can send the command to turn on these loads.In the front part there are 5 LEDs that allow verifying the status of the main power supply and every output.Brackets that allow installation inside the 19” rack cabinet are included.SiteSwitch 4 is available in two versions: SS4 and SS4 AUX.

ACCESSORIESLoad management control unit (SiteSwitch)

3 109 04

SS4It is the most performing version, inside there is a network card installed that receives, through TCP/IP, the controls sent by the CS121 network interface (any model) that manages the UPS.This allows installing SiteSwitch near the loads to be powered and allows a UPS to control a potentially infinite number of control units.The presence of a CS121 SK network interface inside the SS4 also guarantees autonomous operation, i.e. withoutreceiving commands from a UPS: from the WEB interface it is possible to send commands to the computer (through the RCCMD software),program switch on and shut off, sending e-mail and managing environmental sensors.It is compatible with the SNMP protocol.

Any network interface

RS232 LAN

SS4 AUXIt represents the standard solution, it must be guided by a professional, or INDUSTRIAL, type interface installed in the UPS. The ideal solution if installed near the UPS (for example inside the same rack cabinet) a however within 15 metres.

RS232 control cable

Professional or industrial network interface

54

Model Items SITESWITCH 4DESCRIPTION

SS4 3 109 04 High performance load management control unit

SS4 AUX 3 109 05 STANDARD load management control unit

TECHNICAL FEATURES

Type SS4 SS4 AUX

Power supply voltage 230 V / 16 A 230 V / 16 A

Output socket 4 x (230 V / 8A max) 4 x (230 V / 8A max)

Management of output sockets

Internal / CS121(all models)

CS121 (PROFESSIONAL and INDUSTRIAL

versions)

Type of connection for management of output sockets

Ethernet 10/100 Mbit/s

RJ111 Cable approximately 5 m

(included)

Dimensions H x W x D (mm)

60 x 260 x 180 60 x 260 x 180

* after requesting the activation code.

ACCESSORIESManagement software

Example of types of management and communication achieved through software and hardware

LOCAL PROTECTIONAllows protecting a single user (pc or server) that must be positioned at a distance of less than 12 metres.

RS232

USB

UPS Communicatoror UPS management

software

EXTENDED LOCAL PROTECTIONAllows protecting a greater number of users (pc or server) but all depending on the COMPUTER controlling the UPS.

UPS Comunicatoror

UPS management software

RS system agentor

RCCMD agent

LAN

USB

CENTRALISED PROTECTIONThrough the UNMS monitoring software it is possible to control all UPS connected to a TCP/IP network.

RS232

RS232

UNMS

LAN/WAN

Any networkinterface

Any network interface

PROTECTION THROUGH TCP/IP NETWORKAllows controlling multiple users that can interact with the network card. Management of the entire system can be monitoring and controlled by each user.

RS232

RCCMD agent

RCCMD agent

RCCMD agent

LAN

Any networkinterface

55

WWW.UPS.LEGRAND.COM

UPSACCESSORIES COMMUNICATION

Model Items SOFTWAREDESCRIPTION

UPS Communicator

downloadable*. Software made of a system of applications designed to continually control UPS operation and guarantee the integrity of the operating systems of the computers powered by the actual UPS. Complete of agent for executing commands on remote computers (RS System)

UPS management software

3 108 79 Software made of a system of applications designed to continually control UPS operation and guarantee the integrity of the operating systems of the computers powered by the actual UPS. To be completed with agent for executing commands on remote computers (RCCMD).

UPS management software

3 108 80 Software made of a system of applications designed to continually control UPS operation and guarantee the integrity of the operating systems of the computers powered by the actual UPS. To be completed with agent for executing commands on remote computers (RCCMD), includes RS232/USB converter.

AS/400 3 109 08 Kit for connecting with AS/400 systems.Kit made of a connection cable and a cd-rom with instruction manual.

RCCMD Software that enables a computer to receive and execute, using the TCP/IP protocol, all remote commands sent by the UPS management system.A RCCMD license is necessary for each computer to be controlled.Only the licenses are supplied: the software can be downloaded from the internet (after requesting the activation code).

RCCMD 3 108 85 Multi OS RCCMD License

RCCMD 3 108 86 Packet with 5 multi OS RCCMD licenses

RCCMD 3 108 87 Packet with 10 multi OS RCCMD licenses

RCCMD 3 108 88 Packet with 25 multi OS RCCMD licenses

RCCMD 3 108 89 Packet with 50 multi OS RCCMD licenses

RCCMD 3 108 90 RCCMD license for AS/400 (minimum release: V5R3M0)

UNMS It is a “WEB based” application capable of continually monitoring, through the UPS management systems and the TCP/IP protocol, the state of all UPS.

UNMS 3 108 91 UNMS license for 25 UPS

UNMS 3 108 92 UNMS license for 50 UPS

UNMS 3 108 93 UNMS license for 150 UPS

UNMS 3 108 94 UNMS license for 250 UPS

UNMS 3 108 95 UNMS license for 500 UPS

UNMS 3 108 96 UNMS license for 1000 UPS

56

Reliability

LEGRAND guarantees their customers the highest levels of product and service reliability. Quality, efficiency and innovation are the strong points of the entire LEGRAND UPS Services range.

Excellence

A team of competent and professional specialists are available to satisfy diverse technical and sales requirements of the customer, in a quick and efficient manner in order to reduce machine down time.

Specificity

The needs of each individual customer are at the centre of the UPS Services offer. LEGRAND offers customised “Programmed Maintenance” support, with customised service plans, with predefined license fees.

Services for the

customer

57UPS

WWW.UPS.LEGRAND.COM

SERVIZI FOR THE CUSTOMER

UPS PowerCall is a monitoring and remote diagnostics system that guarantees continual UPS checking, thanks to a 24 / 7, 365 days a year connection with the operating control room.The PowerCall service ensures daily support, real time remote diagnostics and quick on-site intervention, in case of anomalies.During normal operation:

The UPS sends data to the operating control room, information is gathered, recorded and evaluated by a team of experts. Operational data is made available in a report that is periodically sent to customers.

In case of anomaly, there are 3 different solutions, according to the seriousness level:Event recording.Remote problem resolution.Sending a technician on-site.In case of emergency:

The technical department is responsible for the customer request in real time. The customer is immediately contacted to verify the conditions of the UPS.A specialised technician goes on-site to repair the breakdown.

UPS PowerCall

DESIGN CONSULTING

Support for designing systems with UPS, conforming to current regulations. Definition of the most suitable solution based on customer needs.

CONFIGURATION AND SIZING

Verification of application requirements in order to protect and identify the most appropriate UPS.

SYSTEM ANALYSIS

Detection of total system consumption trends and applications to be protected.

WARRANTY MANAGEMENT

Dedicated technical personnel and specialised services for standard products and warranty hotline.

INSTALLATIONS

Installation and commissioning on-site.

PREVENTIVE MAINTENANCE

Periodical maintenance in order to safeguard UPS reliability over time and to prevent possible malfunctions or anomalies.

REMOTE MANAGEMENT

Remote management, real time diagnostics and automatic activation of repair services.

BATTERY REPLACEMENT

“Turn-key” replacement of battery packs.

HW UPGRADES

Upgrade of hardware power and uptime, for modular UPS.

Pre and Post Sales Services

There are two warranty formulas available to satisfy customer needs.

EXCHANGE FORMULA

Includes complete product replacement in case of breakdown or malfunction. After the anomaly has been discovered, the technical department sends the customer a module with the instructions necessary to replace the uninterruptable power supply.

ON-SITE FORMULA

Includes technician assistance and repair at the site where the product has been installed.In the standard on-site Formula, the intervention is foreseen within three work days after the call, two for MT series UPS.The customer can choose a customised Formula if wanting to reduce intervention time even further.

Warranty Formulas

58

NOTES

AD

-EX

LG/U

PS

12

C/G

B -

06

/20

12

World Headquarters and

International Department

87045 Limoges Cedex - France

☎ : + 33 (0) 5 55 06 87 87 Fax : + 33 (0) 5 55 06 74 55